DEIF A/S
DEIF A/S
Tel: (+45) 9614 9614
Frisenborgvej 33, DK-7800 Skive Fax: (+45) 9614 9615
Denmark
E-mail: deif@deif.com
4189340225C
Page 2/26
4189340225C
Page 3/26
Dynamic synchronisation
o Frequency matching
o Voltage check
o Breaker delay time compensation
o Check phase sequence
Fixed load (base load) running of the generator
Fixed frequency running of a stand-alone generator
Load sharing between generators with power and frequency control
Relay outputs for speed governor
Relay outputs to close / open generator breaker
Adjustable ramp up/down of generator load
Relay outputs for start / stop of next generator (high / low load)
4189340225C
Page 4/26
Reverse power
Overcurrent (2 levels)
Option A and option B cannot be chosen at the same time as some functions are common for
both.
Option A, mains failure supervision
-
Vector jump
Df/dt (ROCOF)
Overvoltage (2 levels)
Undervoltage (2 levels)
Overfrequency (2 levels)
Underfrequency (2 levels)
Overvoltage (2 levels)
Undervoltage (2 levels)
Overfrequency (2 levels)
Underfrequency (2 levels)
4189340225C
Page 5/26
Option K, IP 54 display
Rubber gasket for display.
4189340225C
Page 6/26
Hardware
The GPC unit housing is divided into board slot positions, some of which are standard (nonchangeable) and some intended for options. The unit is divided like this:
Slot #1: Standard
Slot #2:
Slot #3:
Slot #4:
Slot #5: Standard
Slot #6:
Slot #7: Not used
Slot #8:
Terminal 1-28
Terminal 29-36
Terminal 37-64
Terminal 65-72
Terminal 73-89
Terminal 90-97
Terminal 98-125
Terminal 126-133
In the standard GPC, the only slots used are as standard slot #1, #3, #5 and #8. Slots #2, #4 and
#6 are used for options, slot # 7 is not used.
Besides the slots, there is an additional board where the communication (RS 232 PC service port
for programming of set-points and timers etc. and display) is placed.
NOTE:
For slots #1, 3 and 5, only specific boards can be mounted.
For slots #2, 4, 6 and 8, the boards are interchangeable.
An overview of the terminals can be seen on the next page.
4189340225C
Page 7/26
SLOT #5
SLOT #7
5 6
8 9 10 11 12 13 14
98
112 113 114 115 116 117 118 119 120 121 122 123 124 125
85 86 87 88 89
DISPLAY
90 91 92 93 94 95 96 97
65 66 67 68 69 70 71 72
51 52 53 54 55 56 57 58 59 60 61 62 63 64
Service port
29 30 31 32 33 34 35 36
15 16 17 18 19 20 21 22 23 24 25 26 27 28
79 80 81 82 83 84
99 100 101 102 103 104 105 106 107 108 109 110 111
73 74 75 76 77 78
37 38 39 40 41 42 43 44 45 46 47 48 49 50
er
Po
w
ok
ch
ec
k
Se
lf
SLOT #1
SLOT #3
Al
ar
inh
ibi
t
1 2
SLOT #6
SLOT #8
SLOT #2
SLOT #4
The slots are positioned in the unit as follows (seen from the top of the unit):
4189340225C
Page 8/26
4189340225C
Page 9/26
4189340225C
Page 10/26
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
NO
Com.
NC
NO
Com.
NC
NO
Com.
NC
NO
Com.
NC
NO
Com.
NC
Open collector 1
Open collector 2
Com.
Transistor out
Transistor out
Common
23
24
25
26
27
Digital input 1
Digital input 2
Digital input 3
Digital input 4
Digital input 5
Optocoupler
Optocoupler
Optocoupler
Optocoupler
Optocoupler
28
Com
Common
Description
Power supply.
Normally closed relay,
processor power supply status
supervision
Configurable
Relay 2,
250V AC / 8A
Configurable
Relay 3,
250V AC / 8A
Configurable
Relay 4,
250V AC / 8A
Relay 5,
250V AC / 8A
NOTE: If the input terminal 25 (start sync. / control) is not activated, all control functions are
disabled. This includes the terminal 43 de-load function.
4189340225C
Page 11/26
< 100 kW
100-1000 kW
> 1000 kW
1 pulse/kW
1 pulse/10 kW
1 pulse/100 kW
Function
CAN-H
GND
CAN-L
CAN-H
GND
CAN-L
Not used
Not used
Description
The CAN-bus is based on CAN 2.0 B passive.
The protocol is adapted for Deif use and can
be provided. Contact Deif for further details.
4189340225C
Page 12/26
Function
Technical
data
-505V DC
Analogue I/O
Com
Common
-505V DC
Analogue I/O
-10010V DC Analogue
input
Com
Common
-10010V DC Analogue
input
43
44
Binary input 6
Binary input 7
Optocoupler
Optocoupler
45
Binary input 8
Optocoupler
46
Binary input 9
Optocoupler
47
Binary input 10
Optocoupler
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
Binary input 11
Binary input 12
Binary input 13
Binary input 14
Binary input 15
Binary input 16
Binary input 17
Binary input 18
Com
NO
Com
NO
Com
NO
Com
NO
Com
Optocoupler
Optocoupler
Optocoupler
Optocoupler
Optocoupler
Optocoupler
Optocoupler
Optocoupler
Common
Relay no. 6
250V AC 8A
Relay no. 7
250V AC 8A
Relay no. 8
250V AC 8A
Relay no. 9
250V AC 8A
Description
Active load sharing line
Common for load sharing lines
Reactive load sharing
Frequency / Active load set-point. Passive
(requires external power supply)
Common for terminals 40 and 42
Voltage /var/Power factor/Reactive load
set-point. Passive (requires external power
supply)
De-load (not possible in freq-control mode)
Manual raise speed (only active when start
sync. /reg. is OFF)
Manual lower speed (only active when
start sync. /reg. is OFF)
Manual raise voltage (only active when
start sync. /reg. is OFF)
Manual lower voltage (only active when
start sync. /reg. is OFF)
Mode 1
Mode 2
Mode 3
Mode 4
Mode 5
Mode 6
Generator breaker open
Generator breaker closed
Common for terminals 43 to 55
Engine speed governor: Raise speed
Engine speed governor: Lower speed
Start next generator (high load)
Stop next generator (low load)
NOTE: The terminal 43 de-load function will ramp down the generator and open the breaker. If
the input is left ON after opening of the breaker, it will prevent re-synchronisation.
Mode 1-6: These controls are only active when the breaker is closed and the "activate controls"
input is ON.
Control selections with mode 1-6 inputs: See next page
4189340225C
Page 13/26
Mode 1
Mode 2
OFF
ON
OFF
ON
OFF
OFF
ON
ON
Value
- 50+5 Hz related to nominal frequency
0100% load related to nominal power
- 50+5 Hz related to nominal frequency
- 50+ 5Hz related to nominal frequency
Mode 4
Mode 5
OFF
ON
OFF
OFF
OFF
ON
ON
ON
Mode 3 OFF
Mode 3 ON
0+10V DC
-100+10V DC
Mode 6 OFF
Mode 6 ON
Value
- 100+10 % related to nominal voltage
0100% reactive load related to nominal
power
Cos 10.6 inductive
- 100+10 % voltage setting related to
nominal voltage
External set-point inputs are passive and require an external power source (+/- 10V DC)
4189340225C
Page 14/26
Function
Not used
+/- 20 mA out
0
Not used
Not used
+/- 20 mA out
0
Not used
Description
Speed governor set-point output.
4189340225C
Page 15/26
Note:
Function
I L1 s1
I L1 s2
I L2 s1
I L2 s2
I L3 s1
I L3 s2
U L1
U L2
U L3
U Neutral
U L1
U L2
U L3
Technical description
Generator current L1
Description
1/5A AC input.
Generator current L2
1/5A AC input.
Generator current L3
1/5A AC input.
Generator voltage L1
Not used
Generator voltage L2
Not used
Generator voltage L3
Generator voltage
neutral
BUS voltage L1
Not used
BUS voltage L2
Not used
BUS voltage L3
4189340225C
Page 16/26
Function
Not used
0
0(4) - 20 mA out
Not used
Not used
0
(4) - 20 mA out
Not used
Description
Analogue output, selectable.
Function
Technical data
Description
NO
Com
NO
Com
Not used
Not used
Not used
Not used
Relay 10
250V AC, 8A
Relay 101
250V AC, 8A
4189340225C
Page 17/26
BU SBA R
L2
L3
L1
PPU
8 9 U L3
8 7 U L2
BU SBA R
V O LTA G E
8 5 U L1
18
19
BR EA KER
ON
15
16
BR EA KER
O FF
84 N
8 3 U L3
8 1 U L2
s2
s1
s2
7 9 U L1
78
I3
77
76
s1
I2
75
s2
74
s1
G EN ER A TO R
V O LTA G E
G EN ER A TO R
C U RR EN T
I1
73
G EN ER A TO R
Notes:
The neutral line (N) connection is not necessary for correct measurement. 3phase without neutral is also possible.
The current transformers ground connection can be on s1 or s2 connection,
whichever is preferred.
Fuses: 2A slow-blow.
4189340225C
Page 18/26
Binary inputs
All binary inputs are 24 VDC bi-directional optocoupler. Typical input is:
4189340225C
Page 19/26
4189340225C
Page 20/26
PPU
2 0 (kW h)
2 2 (C O M M O N )
O VD C
4189340225C
Page 21/26
PC interface cable
A standard computer null-modem cable can be used (9-pole SUB-D female / female plugs) or a
cable can be tailored:
4189340225C
Page 22/26
General data
Technical specifications
Accuracy:
Operating temp.:
-2070 oC
Aux. supply:
Measuring voltage:
100690V AC
Frequency:
3070 Hz
Measuring current:
From current transformers ../1 A or ../5A. Load max. 0.3 VA per phase.
Binary inputs:
+/- 5V DC
Analog inputs:
Relay outputs:
Safety:
Galvanic separation:
EMC / CE:
Material:
Climate:
Connections:
4 mm2 multi stranded for AC currents, all others 2.5 mm2 multi stranded.
Response times:
4189340225C
Page 23/26
Case: IP40.
Terminals: IP20.
Operator panel: IP 52 (IP54 when mounted with gasket).
To IEC 529 and EN 60529.
Mounting:
4189340225C
Page 24/26
Display dimensions
4189340225C
Page 25/26
4189340225C
Page 26/26