ONSHORE FACILITIES
ELECTRICAL CABLES
I
I
. I".fJ../L'A+-,4-A--.
.
{57"1t
p-+-;y.-.t-,+----l
-/_-~---I--~----.--+".,..'.'Ifr'jMLfl'o
......
03
:---~I~----~~
S,ghods
M...R_.R
......-+~_A
__,-=G__
h_-1_S:;:''r/r-,=~lm+ ~--l
L.Zahedi
M,R,R
F.Ebadi
$i,Kim
F,Momeni
M.R.R
F,Ebadi
S,H,Kim
F,Momeni
M.R.R
F.Ebadi
12" Sep.,201 0
02
01
DO
REV
DATE
~--+-~-
PURPOSE OF ISSUE
PREPARED
CHECKED
JV LEAD
r~~~--/
S.H.Kim
JV PEM
AUTHORIZED
ThJ$ Document IS the property of N.1.0.C. Any unauthorized a.ttempt 10 reproduce It, In any fQfm. IS strictly prohIbited.
PPL
ROVED
Electrical Cables
Document No
SP12-2YY-EL-SP-999-007-D3
Date
Page
2 of 13
SHEET
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
REVISIONS D
00 01 02 03 04 05 06 07
SHEET
REVISIONS D
00 01 02 03 04 05 06 07
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
This Document is the property of N.I.O.C. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.
Electrical Cables
Document No
SP12-2YY-EL-SP-999-007-D3
Date
Page
3 of 13
TABLE OF CONTENTS
1.
SCOPE ................................................................................................................. 4
2.
3.
4.
5.
6.
7.
8.
9.
10.
SHIPPING ........................................................................................................... 12
11.
Additional requirements................................................................................... 13
12.
Inspection .......................................................................................................... 13
13.
Guarantees ........................................................................................................ 13
14.
Accessories ....................................................................................................... 13
This Document is the property of N.I.O.C. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.
Electrical Cables
Document No
SP12-2YY-EL-SP-999-007-D3
Date
Page
4 of 13
1. SCOPE
This specification covers the minimum requirements for design, manufacture and testing of
high and low voltage power cables, control and earthing cables for the SOUTH PARS GAS
FIELD DEVELOPMENT PHASE 12, ONSHORE FACILITIES PROJECT.
2.2 Definitions
Within this specification the following definitions shall apply:
COMPANY
CONTRACT
CONTRACTOR
CONSULTANT
ENGINEERING CONTRACTOR
INSPECTION AGENCY
OWNER
PLANT
This Document is the property of N.I.O.C. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.
Electrical Cables
2.3
Document No
SP12-2YY-EL-SP-999-007-D3
Date
Page
5 of 13
SITE
SUPPLIER
VENDOR or MANUFACTURER
WORK
Abbreviations
EPR
PDCS
PVC
XLPE
This Document is the property of N.I.O.C. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.
Electrical Cables
Document No
SP12-2YY-EL-SP-999-007-D3
Date
Page
6 of 13
NFC 13200
This specification
Drawings and documents relevant to the project
IEC standards
CENELEC publications
UTE, BS, when IEC publications have not been yet issued
Any deviation from the above mentioned standards and this specification shall be clearly
mentioned in the Vendors proposal.
When there are discrepancies among various contract documents on some requirement,
the most sever specification shall have precedence.
This Document is the property of N.I.O.C. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.
Electrical Cables
Document No
SP12-2YY-EL-SP-999-007-D3
Date
Page
7 of 13
50
Hz
50
Hz
50
Hz
50
Hz
50
Hz
50
Hz
3 phases
transformer
3 phases
3 phases
3 phases
solidly earthed
1 phase
1 phase
A.C. UPS
110 VDC
4.2
D.C UPS
Service conditions
Cables shall be designed to operate in continuous service at full load. Permissive
current shall be calculated according to IEC 60287.
4.3
Environmental conditions
Environmental conditions shall be as per SP12-2YY-PE-DB-999-004 Basic Engineering
design Data.
5. GENERAL CHARACTERISTICS
5.1
5.2
Insulating material
Insulation for HV and LV power cables shall be cross-linked polyethylene (XLPE).
HV cables shall be of the following type:
Copper core conductor, cross linked poly ethylene primary insulation (XLPE) copper
wire screen PVC bedding, wire armoured with red low smoke and fume (LSF) over
sheath.
LV cables shall be of the following type:
Copper core conductor, cross linked polyethylene insulation (XLPE), PVC bedding, wire
armoured with black low smoke and fume (LSF) over sheath, The insulation thickness
shall be in accordance with IEC 60502.
This Document is the property of N.I.O.C. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.
Electrical Cables
Document No
SP12-2YY-EL-SP-999-007-D3
Date
Page
8 of 13
Control cables (multi-core cables) shall be PVC insulated in accordance with IEC 60502.
5.3
Cross sections
S 25
35
25
50
25
70
35
95
50
120
70
150
95
185
95
240
120
300
150
Cross section of phase cores (sqmm) Cross section of protective cores (sqmm)
S 16
16 < S 35
16
S 50
S/2
This Document is the property of N.I.O.C. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.
Electrical Cables
Document No
SP12-2YY-EL-SP-999-007-D3
Date
Page
9 of 13
This table is applicable when the protective conductor is made of the same material as
the phase conductor. If application of this table involves non-standard sizes, the nearest
larger standard size shall be used.
5.4
Conductors
Conductors shall be high conductivity, circular stranded or shaped stranded plain
annealed copper. Conductors shall be class 2 for cables for fixed installations and class
5 for flexible cables feeding mobile equipment, in accordance with IEC 60228. Tinned
conductors are also acceptable. Only LV conductors may be sector shaped.
5.5
Over sheath
Cable over sheath shall be UV stabilised or UV resistant to prevent colour fading due to
sunlight.
Over sheath of cables shall be PVC.
All cables shall be aliphatic hydrocarbon, sunlight resistant, flame retardant and low
density of smoke according to IEC 60332 and IEC 61034 (for earthing cables see
paragraph 6).
PVC over sheath shall be coloured according to its specified voltage, as indicated
below:
HV cable
: red
LV cable
: black
Fire resistant cable : orange
Earthing cable
: yellow and green stripes
The following information shall be indelibly marked or engraved on outer sheath of all
cables at intervals not exceeding 0.5m:
Type of cable
Number of conductors and cross-section
Specified voltage
Quality of PVC sheath
Fire-resistance class according to standard
Metric marking every meter
Manufacturer
Year of manufacture
5.6
5.7
Armour
Armour shall mechanically protect the cable and shall be single wire galvanized round
steel. Non magnetic armour shall be used for single core cables. The minimum
dimension of armour wires shall conform to IEC 60502.
5.8
This Document is the property of N.I.O.C. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.
Electrical Cables
Document No
SP12-2YY-EL-SP-999-007-D3
Date
Page
10 of 13
Cables shall incorporate sealed lead sheath when installed underground, in areas
subject to aromatic hydrocarbon contamination.
5.9
Conductor Screen
Cable 3.6/6 kV and above shall have a semi-conducting screen over the conductor.
Conductor screen shall be non-metallic and shall consist of extruded and or taped semiconducting material as per IEC 60502 recommendations.
5.10 Binder
The laid up cores together with the filler shall be lapped with a suitable binder tape.
5.11 Fire resistance
Only circuits for safety requirements (for example all F&G cables, fire alarm, PA/GA, fire
water pumps cable) shall be compulsorily fire resistant. Fire resisting cables shall
withstand to a 1000C temperature during 30 minutes (with test procedure requirement
of the IEC 60331) and shall continue to conduct electric power during this period. A test
procedure shall be issued (complying with IEC 60331):
5.12 Cable joints
Cable joints shall be prohibited except where cable length exceeds the normal
manufactured length.
Joints shall be achieved using specific underground boxes, restoring the integrity of the
insulation and continuity of service of the cable.
5.13 Fibre optic
Fibre optic cables shall be in accordance with operating system requirements (e.g.
Power Distribution Control System PDCS).
5.14 Cable Core Identification
The following cable core identification will be used.
Cable voltage grade 600/1000V
Lighting cable 3 core (single phase): Red, Black and Green/Yellow
Lighting Cable 4 core (single phase with battery back-up): Red, Blue, Black and
Green/Yellow
1 core: Black, yellow/green for earthing
2 cores: Red, Black
3 cores: Red, Yellow, Blue (phase L1, L2, L3)
4 cores: Red, Yellow, Blue, Black (phase L1, L2, L3, NEUTRAL)
5 cores: Red, Yellow, Blue, Black and Green/Yellow
Cables exceeding 5 cores: number (black printed numbers on the core white insulation)
This Document is the property of N.I.O.C. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.
Electrical Cables
Document No
SP12-2YY-EL-SP-999-007-D3
Date
Page
11 of 13
7. CABLES DATA
A complete data sheet shall be provided for each type and size of cable. The data sheet
shall include the following information:
Type tests
Where certificates are not available, type tests shall be performed in accordance with
the IEC standards. The manufacturer shall supply three copies of certified test reports of
the specified tests.
Where necessary, type tests shall be performed by the manufacturer on samples from
each type of cable according to IEC 60502. The results of such test shall be submitted
to COMPANY.
This Document is the property of N.I.O.C. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.
Electrical Cables
9.2
Document No
SP12-2YY-EL-SP-999-007-D3
Date
Page
12 of 13
9.3
Field tests
The following tests shall be carried out before cables are placed in service:
Insulation check
Dielectric test for HV cables
10. SHIPPING
10.1 Drums
Maximum weight and minimum weight of cable drums shall be specified in the tender
documents.
Metallic cable drums shall be applied for heavy applications.
Cables shall be supplied in drums.
Every drum shall be made up of a single length.
Cable wound on drums shall be protected to prevent damage and tampering.
The inside diameter of the drum on which every cable is wound shall in general not be
less than twice the cable minimum permissible bending radius.
Following completion of all necessary tests and inspections, Supplier shall prepare the
goods in a suitable way for the type of shipment specified by the PURCHASER and in
accordance with COMPANY specification for Packing, Marking and Shipping DB-5561V999-P-332-407. The main shipping mark referred to in the Packing, Marking and
Shipping Specification shall be amended to show the PURCHASER, and current project
name South Pars Gas Field Development-Phase12
In order to facilitate loading, unloading and handling of cargo, Supplier shall stencil the
necessary cautionary symbols with red mark on the proper place on two opposite ends
of the packs. If the equipment is filled with nitrogen gas, N2 shall be indicated on the
face of the package. If it is acceptable to store the goods in an open area under a
Tarpaulin then the goods shall be marked with a red free from wet mark.
Pre shipment Inspection of the packing and marking shall be carried out before any
shipment by an approved third party. In case any export licenses and/or other necessary
permits, authorisation, etc., are required by authorities in the exporting country then the
Supplier shall obtain such export licenses, permits, authorisations, etc. prior to shipment
at own cost and risk.
This Document is the property of N.I.O.C. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.
Electrical Cables
Document No
SP12-2YY-EL-SP-999-007-D3
Date
Page
13 of 13
12. Inspection
COMPANY and/or appointed inspectors reserve the right for inspection at any stage of
manufacture, testing or preparation for shipment.
13. Guarantees
Suppliers of cables under this specification shall certify that such cables meet all
requirements of this specification. Any deviation from this specification shall be clearly
mentioned in the Suppliers proposal. Suppliers shall replace any length of cable which fails
under a voltage test performed before cable is placed in service.
14. Accessories
The Supplier shall include for the supply of the following accessories; (Note the numbers
and sizes will be finalised during detail engineering).
Cable gland
Nickel plated brass, double compression type, suitable for armoured cable, Ex certified for
use in hazardous areas, complete with shroud and earth tag
Splicing kits
Splicing kits shall be flame retardant
This Document is the property of N.I.O.C. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.