Sie sind auf Seite 1von 22

TCE CONSULTING ENGINEERS LIMITED

TCE.M2-CV-RC-D-005

ANCHOR BOLT SCHEDULE


USER INSTRUCTIONS

SECTION: TITLE

SHEET

i OF ii

ANCHOR BOLT SCHEDULE


USER INSTRUCTIONS

TCE CONSULTING ENGINEERS LIMITED


73/1, ST. MARKS ROAD
BANGALORE 560 001

REVALIDATED UP TO : 2003-06-08

File Name

: M2-CV-RC-D-005 (R1).DOC
R1

ISSUE

REV.NO
INITIALS

SIGN

PPD.BY

PVN

Sd/-

CKD.BY

AD

Sd/-

APP.BY

RDD

Sd/-

DATE

INITIALS

SIGN

INITIALS

SIGN

INITIALS

SIGN

R1

1992-09-11
FORM NO. 020R2

TCE CONSULTING ENGINEERS LIMITED


TCE.M2-CV-RC-D-005

ANCHOR BOLT SCHEDULE


USER INSTRUCTIONS

SECTION: : REV. STATUS

SHEET

ii OF ii

REVISION STATUS SHEET

REV. NO.

DATE

DESCRIPTION

R1

92.08.25

Allowable stresses on anchor bolts and plates


have been revised as per IS : 800-1984. SI units
have been used.

FORM NO. 120 R1

TCE CONSULTING ENGINEERS LIMITED


TCE.M2-CV-RC-D-005

1.0

SECTION: CIVIL

ANCHOR BOLT SCHEDULE


USER INSTRUCTIONS

SHEET 1 OF 17

SCOPE
Six types of anchor bolts are shown in the anchor bolt schedule
TCE.M2-CV-RC-I-019 R1. The table in this schedule is to be filled in
to provide fabrication details for each anchor bolt.
For a particular diameter of anchor bolt, the permissible axial force
and corresponding allowable shear force, recommended types of
anchor bolt and their details such as embedment length, anchor plate
size etc., are listed in Tables-I, II and III for the guidance of the user.
Design assumptions, use of this table and a typical design for the six
types of bolts are included in this guide.
Design tables are prepared based on working stress method for
concrete grades M15 and M20 only. Where concrete grades higher
than M20 are used, the details of anchor bolt given in the table for
M20 shall be adopted. On overseas projects wherever designs are
insisted by ultimate load theory / limit state theory, these tables shall
not be used. In such cases anchor bolts shall be redesigned using
that theory.

2.0

PERMISSIBLE STRESSES
(i)

(ii)

The following allowable stresses in concrete as per IS : 456


(1978) are adopted :
Concrete Grade
M15

Concrete Grade
M20

Average bond stress

0.6 N/mm2

0.8 N/mm2

Bearing stress

4.0 N/mm2

5.0 N/mm2

Shear stress

0.22 N/mm2

0.22 N/mm2

Permissible stresses as per IS:800-1984 in bolts of mild steel


conforming to IS:226-1975 St 42-S and IS:2062-1984 Fe 410W are as follows :
(a)

Tension (on net area of bolt) N/mm2

120

(b)

Shear (on nominal area of bolt) N/mm2 -

80

FORM NO. 120 R1

TCE CONSULTING ENGINEERS LIMITED


TCE.M2-CV-RC-D-005

(iii)

ANCHOR BOLT SCHEDULE


USER INSTRUCTIONS

SECTION: CIVIL

SHEET 2 OF 17

Permissible bending stress (as per IS:800) in plates of mild steel


conforming to IS : 226 St 42-S or IS:2062 Fe 410-W are as
follows :
Fy
N/mm2

Bending stress
N/mm2

(a)

Plates over 40 mm thick

230

151.8

(b)

Plates 20 mm & up to 40
mm thick

240

158.4

(c)

Plates less than 20 mm


thick

250

165.0

(iv) Fillet welds are designed for the following permissible stresses
as per IS:816-1969.
Shear stress at throat of fillet 110 N/mm2
(v)
3.0

Permissible axial compressive stress in sleeve (for type F) is


governed by Table-II, IS:806-1968 for grade YSt 22.

DESIGN DETAILS
(i)

Maximum allowable axial force is given in table, I, II & III.


Maximum allowable shear force is limited to 40% of the shear
capacity of the bolt.

(ii)

Tensile stress area of bolt is given by the following formula


(IS :4218 (Part III)-1976 :
Tensile stress area =

d2 d3 2

If d is the nominal diameter of the bolt or nut, whichever is minimum


and P is the pitch, then.
d2
d3

=
=

d 0.650 P
d 1.227 P

For the information of the user, pitch & nut size considered are given
in tables I, II & III.

FORM NO. 120 R1

TCE CONSULTING ENGINEERS LIMITED


TCE.M2-CV-RC-D-005

(iii)

ANCHOR BOLT SCHEDULE


USER INSTRUCTIONS

SECTION: CIVIL

SHEET 3 OF 17

Combined Shear and Tension


Bolts subjected to shear and tension are so proportioned that the
stress ratio :
fs
ps

< 1.40

Subject to
fs
ps

<

1.0 &

f
p

< 1.0

Where fs = actual shear stress in bolt


ft = actual tensile stress in bolt
ps = permissible shear stress in bolt
pt = permissible tensile stress in bolt.
(iv) Threaded length for bolts T1/T2 is the thickness of nut
(single/double) + washer thickness + projection above nut + 6
mm.
(v)

4.0

The minimum embedment of an anchor bolt is fixed as 300 mm.


Thickness of stiffener plates for type E is given in
table II.
Depth of stiffener plate is 0.7 times width of plate washer.

TYPICAL DESIGNS
Concrete Grade

4.1

= M20

TYPE-A
Diameter of bolt

= 22 mm

Tensile stress area

= 303.4 mm2

Max. allowable axial force on bolt P

= 303.4 x 120
= 36408 N

FORM NO. 120 R1

TCE CONSULTING ENGINEERS LIMITED


TCE.M2-CV-RC-D-005

ANCHOR BOLT SCHEDULE


USER INSTRUCTIONS

SECTION: CIVIL

SHEET 4 OF 17

d lb f b = P = 36408 N
d

diameter of the bolt

lb

embedment length below the pipe sleeve

fb

allowable bond stress as per IS:456

x 22 x 0.8 x lb
lb
4.2

= 36408

= 658.5 mm.

TYPE-B
Diameter of bolt

= 56 mm

Tensile stress area

= 2030 mm2

Max. allowable axial force on bolt P

= 2030 x 120
= 243600 N

d (lb+ 8d) fb = P = 243600


lb = length below the pipe sleeve to the starting of curve for 90 0
bend
8d = anchorage value for 900bend.
lb = 1731 8 (56) = 1283 mm.
4.5

TYPE C
Diameter of bolt

= 56 mm

Max. allowable axial force on bolt P

= 243600 N

Let 1100 mm be the length of the anchor bolt below pipe sleeve
through which transfer of force to concrete is available through bond.
Tension transferred by bond through bolt

= x 56 x 1100 x 0.8
= 154818 N

Tension to be carried by washer plate

= 88782 N
FORM NO. 120 R1

TCE CONSULTING ENGINEERS LIMITED


TCE.M2-CV-RC-D-005

ANCHOR BOLT SCHEDULE


USER INSTRUCTIONS

SECTION: CIVIL

SHEET 5 OF 17

Assume plate size 180 x 180


Bolt size = 56 mm
Circumference

= x 56
= 176 mm

Circumference
4

= 44 mm

Area of hatched part =

180 44
2

90 28

= 6944 mm2
Average bearing pressure on concrete =

88782
4 x 6944

= 3.1967 N/mm2 < 5 N/ mm2


Bending Moment = 44 x 62 x 31 x 3.1967 + x 2

180 44

x 62 x 2/3 x 62 x 3.197

= 270339 + 557061 = 827400 N-mm


Z reqd. =

827400
158.4

= 5223 mm3

With 28 mm plate Z =

44 x 28
6

= 5749 mm 3 > 5223 mm 3

(180 x 180 x 28 mm plate)

FORM NO. 120 R1

TCE CONSULTING ENGINEERS LIMITED


TCE.M2-CV-RC-D-005

ANCHOR BOLT SCHEDULE


USER INSTRUCTIONS

SECTION: CIVIL

SHEET 6 OF 17

Shear force to be transferred through 44 mm fillet weld on one side of


the plate =

88782
4x 2

N = 11098 N

Compression / tension due to bending moment on 44 mm long


weld =

827400
28

= 29550 N

Equivalent force on weld =

29550 2 1.8 x11098 2 33089 N

Strength of 12 mm fillet weld = 44 x 0.707 x 12 x 110 N


= 41063 N > 33089 N
4.4

TYPE-D
Diameter of bolt

= 25 mm

Diameter of nearest available nut

= 24 mm

Tensile stress area

= 352.5 mm2

Max. allowable axial force on bolt P

= 352.5 x 120 = 42300 N`

d (lb + 16d) fb = P = 42300 N


lb = length below the pipe sleeve to the starting of curve for 180 0
bend.
16d = anchorage value for 1800 bend.
lb = 673 16 (25) = 273 mm.
4.5

TYPE-E
Diameter of bolt

= 56 mm

Max. allowable axial force on bolt P

= 243600 N

4 stiffener plates 8 mm thick are used. Depth of stiffener plate is 0.7 x


width of plate washer.

FORM NO. 120 R1

TCE CONSULTING ENGINEERS LIMITED


TCE.M2-CV-RC-D-005

ANCHOR BOLT SCHEDULE


USER INSTRUCTIONS

SECTION: CIVIL

SHEET 7 OF 17

Let 900 mm be the length of anchor bolt below pipe sleeve through
which transfer of force is available through bond.
Tension transferred by bond
through bolt

= x 56 x 900 x 0.8 = 126669 N

Tension to be carried by stiffened


washer plate

= 243600 126669

Plate size 250 x 250

= 116931 N

Net area transferring force by bearing on concrete


2
= 250 x 250 - x 56
4

= 60037 mm

Average bearing pressure on concrete = 116931


60037
= 1.948 N/mm2 < 5 N/mm2
Max. B.M per mm width of plate = 1.948 x 2502 = 15219 N- mm
8
Z reqd = 15219 = 96.08 mm3
158.4
With 25 mm plate Z available = 252 = 104.17 mm3
6
Load on each stiffener plate = 116931 = 29233 N
4
Length of each stiffener plate = 125 2 28 = 148.78 mm
Load distribution on stiffener plate per mm length of the
plate = b x 1.948 / 1.4142 = 1.377 x b
Load intensity at point P
= 1.377 x 250 = 344.3 N/mm

FORM NO. 120 R1

TCE CONSULTING ENGINEERS LIMITED


TCE.M2-CV-RC-D-005

ANCHOR BOLT SCHEDULE


USER INSTRUCTIONS

SECTION: CIVIL

SHEET 8 OF 17

Load intensity at point Q


= 1.377 x 39.6 = 54.53 N/mm
Cantilever B.M =
54.53 x 148.782 + (344.3-54.53) x x 148.78 x 2 148.78
2
3
= 2741591 N- mm
Z reqd. = 2741591
165

= 16616 mm3

Stiffener plates 8 mm thick


Depth = 0.7B = 0.7 x 250 = 175 mm
Z available = 1752 x 8 = 40833 mm3
6
Shear on the weld = 116931 = 167.04 N/mm
4x175
Tension / compression due to
Bending moment on weld = 2741591 = 537.13 N/mm
1752 / 6
Equivalent stress on weld = 537.13 2 1.8 x 167.04 2
= 582.0 N/mm
Strength of 5 mm fillet weld on both sides of stiffener
= 2x5x0.707x110 = 777.7 N/mm > 582.0 N/mm
Tension on weld at point P = 344.3 N/mm < 777.7 N/mm
4.6

Type-F
Dia of bolt
Max. allowable axial force on bolt P
Nominal sleeve dia
Thickness
Area of cross section
Radius of gyration

=
=
=
=
=
=

56 mm
243600 N
135 mm
4.85 mm
2250 mm2
52.2 mm

FORM NO. 120 R1

TCE CONSULTING ENGINEERS LIMITED


TCE.M2-CV-RC-D-005

ANCHOR BOLT SCHEDULE


USER INSTRUCTIONS

SECTION: CIVIL

SHEET 9 OF 17

Sleeve Length :
The axial force of the bolt is transferred to concrete by bond around
the sleeve. Length of sleeve required is governed by force to be
transferred and permissible average bond stress. At the top, a length
of sleeve embedded in concrete equal to the diameter of sleeve is
assumed ineffective.
D l fb = P
x 135 x 1x 0.8 = P = 243600 N
l = effective length of sleeve = 718 mm
D = nominal diameter of sleeve
Sleeve length required = l + D
Total sleeve length required = 718 + 135
= 853 mm
Check axial compressive stress in sleeve
Axial stress = 243600 = 108.27 N/mm2
2250
l = 718 = 13.75 = 14
r
52.2
Allowable compressive stress (axial) = 120 N/mm2
Check plate thickness :
Assumptions

(i)

The axial force in the bolt is


transferred to the plate
washer over a radius r
determined by the size of
the washer below the plate.

(ii)

The plate washer is simply


supported on the sleeve
diameter (2 a).

FORM NO. 120 R1

TCE CONSULTING ENGINEERS LIMITED


TCE.M2-CV-RC-D-005

SECTION: CIVIL

ANCHOR BOLT SCHEDULE


USER INSTRUCTIONS

(iii)

SHEET 10 OF 17

The bending stress in the plate is determined using the


value of Poissons ratio 0.3.

The maximum bending stress (at the centre) is given by


Sr

= St =

r2

2 mt 2

4a 2

3W

m (m l ) log e

(m l )

Where : w = total load applied (N)


Sr = radial stress at surface of plate (N/mm2)
St = tangential stress at surface of plate (N/mm 2)
m = reciprocal of Poissons ratio
t = thickness of plate (mm)
r = radius of washer over which the load is distributed
a = radius at which plate is supported (radius of sleeve)
w

= 243600 N

= 1 = 3.33
0.3

= 105 mm = 52.5 mm
2

= 135 mm = 67.5 mm
2

Sr t2 =

67.5

52.5 2

52.5

4 x 67.5 2

3 x 243600
2 x 3.33

3.33 4.33 log e

2.33 x

= 142011

FORM NO. 120 R1

TCE CONSULTING ENGINEERS LIMITED


TCE.M2-CV-RC-D-005

ANCHOR BOLT SCHEDULE


USER INSTRUCTIONS

SECTION: CIVIL

SHEET 11 OF 17

Since the max. permissible bending stress = 158.4 N/mm 2


t2 = 142011 = 896.5 mm2 ; t = 29.9 mm
158.4
Use 32 mm plate size
Dimension B = 190 mm
Plate washer size 190 x 190 x 32 mm
Weld size
Use 6 mm weld on outside of pipe sleeve
The force is transferred from plate to sleeve

4.7

(i)

by bearing

(ii)

through welds connecting the plate and sleeve

Combined Shear & Axial Load


Diameter of bolt 56.mm, Shear = 78816 N
Tensile stress area = 2030.0 mm2
Nominal area

= 2463.0 mm2

Actual shear stress = 32 N/mm2


The permissible axial stress is calculated thus :

ft

32

1 .4
80

120

ft = 1.4 - 0.4
120
ft

= 120 N/mm2

Allowable axial force = 2030.0 x 120 = 243600 N

FORM NO. 120 R1

TCE CONSULTING ENGINEERS LIMITED


TCE.M2-CV-RC-D-005

5.0

ANCHOR BOLT SCHEDULE


USER INSTRUCTIONS

SECTION: CIVIL

SHEET 12 OF 17

RECOMMENDATIONS ON SELECTION OF BOLT TYPE


(I)
(ii)
(iii)

Use 2 nuts on bolts subjected to tension, vibrations, seismic or


wind action. One nut is ordinary nut, while the other is a lock
nut.
Type A bolt should be used for minor foundation such as stairs,
ladders. Use this type only for bolts upto 25 mm dia.
Type B bolt is recommended for dia upto 56 mm for structural
foundations.

(iv) Type C, D, E may be used for structures subjected to


overturning e.g. portal columns subjected to heavy bending
moments at base. Type C is recommended for dia 25 mm to 56
mm. Type D is recommended for dia 20 mm to 32 mm and type
E is recommended for dia 40 mm to 72 mm.
(v)

Type A and C bolts without sleeves should be used for bolts in


pockets.

(vi) In case of foundations for equipment, anchor bolts are specified


by the vendor.
(vii) For anchor bolts not subjected to tension, select the diameter
according to shear requirement and use Type A or B. The
embedment length may be designed for bearing with a min.
length of 300 mm below pipe sleeve.
(viii) Anchor bolt Type-F shall be used where heavy towers and tower
like vessels, chimneys are to be erected on foundations. Where
there is a restraint on depth of embedment and type A to E
cannot be used, Type F is to be adopted.
6.0

USE OF DESIGN TABLE (Tables I, II & III)


It is desired to select a bolt to resist an axial force P and shear
force S.
(i)

If the force on the bolt includes those due to wind or earthquake


effects, multiply these by 0.8 before using the table.

FORM NO. 120 R1

TCE CONSULTING ENGINEERS LIMITED


TCE.M2-CV-RC-D-005

ANCHOR BOLT SCHEDULE


USER INSTRUCTIONS

SECTION: CIVIL

SHEET 13 OF 17

(ii)

From the appropriate table (Table I, II or III depending on


concrete grade) select the diameter necessary. In case of
structures in chemical plants and structures exposed to
corrosion environment, allowance shall be made by selection of
the next higher diameter than that necessary as per design.

(iii)

As per guidelines given 5.0 select type of bolt.

(iv) Pick up from this table the required embedment length ,


plate
sizes (Type C and E, F), sleeve dimensions, threaded lengths
and fill these in the schedule. If anchor bolts without sleeves are
used, select Type A or C and pick the lengths as indicated in the
design table.
(v)

The projection P is the threaded length T1 or T2 + thickness of


grout + thickness of base plate 6 mm.

(vi) The total length of the anchor bolt is the sum of the projection P
and lengths L2 and L3 (as applicable to the type).
(vii) If the embedment length worked out for Types C & E is not
available and hence found excessive, redesign with more load
carried by the plate washer. Follow the procedure for design as
indicated in the example.
7.0

USE OF STANDARD SCHEDULE


(i)

TCE-M2-CV-RC-D-005 R1 Anchor Bolt Schedule User


instructions.
These are meant for design office use only.

(ii)

TCE-M2-CV-RC-I-019 R1 Anchor Bolt Schedule. This is to be


filled in with fabrication details and released to site.

FORM NO. 120 R1

2.5

2.5

3.0

3.0

3.5

M22

M24

M27

M30

2.0

M20

M16

NUT
(mm) MAX. PITCH
SIZE

560.5

459.4

352.5

303.4

244.8

156.7

AREA (sq.mm) TENSILE STRESS

67.27

55.12

42.30

36.41

29.38

18.80

ALLOWABLE
AXIAL FORCE
(kN)
(kN)

25.74

19.70

15.71

12.16

10.05

6.43

LIMITED SHEAR
FORCE

60

50

45

40

40

30

NUT 1

85

75

65

60

55

40

NUTS 2

L3

700 160

550 130

L2

300
-

80
-

--

--

1100

800

1000

700

100*100*16

100*100*16

100*100*16

B*B*T

PLATE WASHER

TYPE -C

Tw
(mm)

ANCHOR BOLT SCHEDULE


USER INSTRUCTIONS

100 300

300 1250 1050 200 900

750 175

80

950

250 1200 1000 175


950 750 200 600

L2

65
-

850

700

L2

TYPE - B

250 1100 950 160

50

L1

D1

PIPE SLEEVE TYPE TYPE A, B, C


A

TCE.M2-CV-RC-D-005

T / T2

(All dimension are in millimetres) TABLE I : ANCHOR BOLT DETAILS FOR CONCRETE GRADE M15
TATA CONSULTING ENGINEERS
SECTION: CIVIL

SHEET 14 OF 17

FORM NO. 120 R1

TATA CONSULTING ENGINEERS

32

SHEET 15 OF 17

28

25

22

20

16

ANCHOR BOLT SCHEDULE


USER INSTRUCTIONS
BOLT
DIA
(mm)

TCE.M2-CV-RC-D-005

SECTION: CIVIL

FORM NO. 120 R1

(kN) FORCE SHEAR

40

45

50

60

12.16

15.71

19.70

25.74

40.21

65

60

40

10..05

100

90

85

75

65

60

55

40

110

350

350

100

300

100

300

80

300

80

250

65

250

50

L1

D1

1050

750

950

700

900

650

550

L2

290

255

255

225

225

200

200

175

175

160

160

130

L3

700

900

600

850

550

800

500

L2

320
1250 320

900

1150

800

1200 290 1050

850

950

650

900

600

850

550

800

550

750

500

425

L2

TYPE- B

120x120x20

120X120X20

100X100X16

100X100X16

100X100X16

PLATE
WASHER
BxBxT

TYPE C

Tw
(mm)
L3

750 480

750 420

700 375

650 330

600 300

L2

TYPE-D

950

600

L2

200x200x20

PLATE
WASHER
BxBxT

TYPE-E

Tw
Ts
(mm) (mm)

ANCHOR BOLT SCHEDULE


USER INSTRUCTIONS

32.57

30

NUT 1 2 NUTS

PIPE SLEEVE TYPE TYPE-A


A TO E

TCE.M2-CV-RC-D-005

6.43

LIMITED

T1 / T2

TABLE II : ANCHOR BOLT DETAILS FOR CONCRETE GRADE M20 (TYPE A TO E)

TATA CONSULTING ENGINEERS


SECTION: CIVIL

SHEET 16 OF 17

FORM NO. 120 R1

M22

M24

M27

M30

M36

22

25

28

32

36

M39

M20

20

4.5

4.0

3.5

3.0

3.0

2.5

2.5

949.9

816.7

560.5

459.4

352.5

303.4

244.8

156.7

114.00

98.00

67.27

55.12

42.30

36.41

29.38

18.80

FORCE (kN) ALLOWABLE AXIAL

ANCHOR BOLT SCHEDULE


USER INSTRUCTIONS

40

M16

16

TENSILE
STRESS
AREA
(sq.mm)

TCE.M2-CV-RC-D-005

2.0

NUT MAX. PITCH


SIZE
(mm)

BOLT
DIA
(mm)

(All dimension are in millimetres)

TATA CONSULTING ENGINEERS


SECTION: CIVIL

SHEET 17 OF 17

FORM NO. 120 R1

78.82

90.48

130.29

160.85

243.59

283.43

415.15

521.26

251.33

62.83

176.77

150

130

110

95

90

80

75

230

195

170

140

135

120

110

2 NUTS

800

200

650

175
-

600

150
-

500

135
-

450

135
-

400

125
-

400

125
-

L1

D1

PIPE SLEEVE
TYPE A TO E
-A

L2

TYPE

L3

PLATE
WASHER
BXBXT

TYPE-C

900 25150x 150x

L2

1800 450 1600

1350 450 1150 28180x 180x

1500 400 1400

1100 400 1000 25150x 150x

1500 360 1300

1100 360

L2

TYPE-B

12

10

10

Tw
(MM)

L2

L3

TYPE - D

360x 360x
36

360x 360x
32

300x300x 28

250x250x 25

200x200x 20

200x200x 20

PLATE
WASHER
BXBXT

400x 400x
50
2500

1700

2100

1450

1800

1200

1500

1000

1400

950

1250

850

1150

750

L2

10

20

12

12

Tw
Ts (mm)
(mm)

TYPE - E

ANCHOR BOLT SCHEDULE


USER INSTRUCTIONS

839.32

50.89

NUT

T1 / T2

TCE.M2-CV-RC-D-005

156.71

ALLOWAB
LE AXIAL LIMITED SHEAR
FORCE
FORCE (kN)
(kN)

(All dimension are in millimetres)TABLE II : ANCHOR BOLT DETAILS FOR CONCRETE GRADE M20 (TYPE A TO E)

TATA CONSULTING ENGINEERS


SECTION: CIVIL

SHEET 18 OF 17

FORM NO. 120 R1

M48

M56

M60

M72

M80

50

56

60

72

80

6.0

6.0

6.0

5.5

5.5

5.0

4.5

6994.6

4343.8

3459.6

2362.0

2030.0

1473.0

1306.0

TENSILE
STRESS AREA
(sq.mm)

ANCHOR BOLT SCHEDULE


USER INSTRUCTIONS

M100

M45

45

MAX. PITCH
(mm)

TCE.M2-CV-RC-D-005

100

NUT
SIZE

BOLT
DIA
(mm)

TATA CONSULTING ENGINEERS


SECTION: CIVIL

SHEET 19 OF 17

FORM NO. 120 R1

M39

M45

M48

M56

M60

M72

40

45

50

56

60

72

NUT
SIZE

6.0

5.5

5.5

5.0

4.5

4.5

MAX.
PITCH
(mm)

3459.6

2362.0

2030.0

1473.0

1306.0

949.9

TENSILE
STRESS
AREA
(sq.mm)

415.15

283.43

243.59

176.77

156.71

114.00

130.29

90.48

78.82

62.83

50.89

40.21

(kN) ALLOWABLE LIMITED


AXIAL FORCE SHEAR
FORCE (kN)

110

95

90

80

75

65

NUT1

170

140

135

120

110

100

2 NUTS

T1 / T2

200

175

135

125

125

110

D1

1100

900

900

750

700

600

L1

PIPE SLEEVE

140

115

110

100

90

80

T3

1285

1055

1040

880

815

705

L2

150 x 25

120 x 20

110 x 20

100 x 20

90 x 16

80 x 16

270 x 270 x 45

240 x 240 x 40

190 x 190 x 32

180 x 180 x 32

180 x 180 x 28

150 x 150 x 25

DXTWASHER PLATE BXBXTPLATE WASHER

TYPE-F

TCE.M2-CV-RC-D-005

BOLT
DIA
(mm)

(All dimension are in millimetres)TABLE III : ANCHOR BOLT DETAILS FOR CONCRETE GRADE M20 (TYPE F)
TATA CONSULTING ENGINEERS
SECTION: CIVIL

ANCHOR BOLT SCHEDULE


USER INSTRUCTIONS
SHEET 20 OF 17

FORM NO. 120 R1