LECTROTEK-Product Operation Manual

Universal Input Scanner/Data Logger

Model-UniSCAN NX/H/V
1.

INTRODUCTIONS
1.1. Introduction
1.2. Features
1.3. Specifications

2.

I N S TAL L ATI O N / W I R I N G

3.

O P E R ATI O N / P R O G R AM M I N G
3.1.
3.2.
3.2.1
3.2.2
3.2.3
3.2.4
3.2.5

Size 96 x 96 x 110
Cutout 92 x 92

HMI Interface
Programming/Operation
Display Interval / Sl.No.& Auto/Manual Operation
Alarms Viewing / Programming
Calibration mode
Configuration / Setup mode
Auto Calibration Facility

APPENDIX A:
1. Wiring Diagram for Inputs (Extension Board)
2. Wiring Diagram for PS/Relays (Main Unit)
3. Back Connection for UniScan NX
4. Back Connection for UniScan H
5. Dimensions/Panel cutout details

Size 192 x 96 x 110


Cutout 92 x 92
1.1 INTORDUCTION
UNISCAN NX/H/V is a Universal Input Scanner are intended for continuous
monitors of process parameters and optionally generating alarm/trip outputs .
It incorporates advanced software features and micro controller based design
to provide complete user flexibility and can cater to almost all monitoring and
data acquisition needs of the user. It can be user programmed to cover
different application needs thus reducing time, inventory and spares cost. It
accepts direct signals from thermocouples, RTDs and linear voltage and
current inputs, either as fixed type or programmable universal input. Each
channel is sequentially scanned and active channels are displayed, Individual
channels can be locked for monitoring using the E key. Flexible alarm logic
and grouping is provided to energize alarm relay outputs as per the process
parameter values and programmed set points.
Serial communication is provided to enable the scanner to communicate with
PC (RS 232/RS 485 optional.

1. 2 F E A T U R E S
Site programmable mixed inputs, ranges, decimals, alarm/trip values.
Upto 32 relays (8 internal and 24 external in 8-relay modules wired to main
unit with external 24VDCpower supplies, as per schematic/wiring diagram.
All functions: operation, input/relayconfiguration, calibration from keyboard.
Programmable inputs 4-20 mA, RTD, J,K,R,S,T thermocouples.
RS-232 Serial Communication port or RS485 port OPTIONAL.
16 inputs and 8 relay outputs standard (additional inputs/relays on order)
2 nos 4-digit 7-segment LEDs for Process Values, Channel Numbers,
alarms etc.
LED matrix on option / as per order.

LECTROTEK SYSTEMS

Size 96 x 192 x 110


Cutout 92 x 92
All dimensions mm
Note: Photos are representative only, product front
fascia may vary as per ordered options (e.g. LED
matrix ordered, number of channels etc.)

OPERATION MANUAL UniScan Series

Page 1 of 6

LECTROTEK

Product

SYSTEMS

OPERATION MANUAL

www.lectrtek.com

1. 3 S P E C I F I C A T I O N S
1.3.1
1.3.2

Power Supply : 90-270 V AC, 50 Hz +/- 3 Hz


Input/Ranges : Site programmable as per following Input/range table:

Input

Ranges (default)

Resolution

Pt-100 RTD (3 wire)

-199.9 to +400.0 C

0.1 C

Fe-Const. Thermocouples (ANSI J)

0 to 800 C

1 C

Cu-Const. Thermocouples (ANSI T)

0 to 400 C

1 C

Cr-Al Thermocouples (ANSI K)

0 to 1200 C

1 C

Pt-PtRh13% Thermocouples (ANSI R)

0 to 1600 C

1 C

Pt-PtRh10% Thermocouples (ANSI S)

0 to 1600 C

1 C

0/4-20 mA DC (linear/square root)

-1999 to +9999

Up to 3 digits

Cr-Cn

0 to 600 C

1 C

ntyp

0 to 1200 C

1 C

btyp

0 to 1600 C

1 C

1.3.3
1.3.4
1.3.4
1.3.5
1.3.6
1.3.7
1.3.8

Channels
Accuracy
Alarms
Alarm outputs
Relay type
Relay hysteresis
Display

: 1 to 32 (as per requirement)


: +/- 0.25% FS +/- 1 digit (For CU-53 it is +/- 0.50% FS)
: High or Low type per channel, programmable
: 8 relays built-in (24 relays in separate relay box with cutout as 92x192)
: Potential-free, rating 7A, 240V or 10V, 110V resistive loads
: Programmable at site
: 7-segment LED, 14.2 mm height; 4 digits (Channel No.), 4 digits (Value)
Red LED lamps for A/M status
1.3.9 Auto-Manual Station: built-in, for manual/automatic display of channel-wise data.
1.3.10 Skip/Unskip mode: for skipping from display open/unconnected channels
1.3.11 Calibration
: From front keyboard, via 4-key keyboard.
1.3.12 Port
: OPTIONAL RS-232/RS-485 Isolated serial port.
1.3.13 Acknowledge Function: Manual Acknowledge function is provided on request. Ack Key is not used (dummy) if not specified in
order.
1.3.14 Supply/relay terminations: Via screwed connectors, suitable for 2.5 mm2 wire size. Power supply, Sensor and relay terminals are
on instrument rear.
1.3.15 Sensor Terminations: on surface-mounted Terminal Board, connects to UniScan through 2m Cable/Connector, supplied with
UniScan order.
1.3.16 Enclosure
: UniScan NX : 92 x 92 x 110 mm WHD, IP40.
ABS Enclosure
UniScan H : 192 x 92 x 110 mm WHD, IP40.
UniScan V
1.3.17 Mounting

92 x 192 x 110 mm WHD, IP40.

: UniScan NX :
UniScan H :
UniScan V
:

Panel Cutout 92 x 92 mm (W X H)
Panel Cutout 186 x 92 mm (W X H)
Panel Cutout 92 x 186 mm (W X H)

mounts with 2 nos. clamps supplied with unit.

1.3.18 Operating conditions: Temperature 50C max, Humidity 90% RH max, NC.

2.0 INSTALLATION / WIRING


Unpack the instrument and install it in a panel having specified cutout. Provide instrument power as per order. Provide an external
fuse/MCB of 250 mA rating for additional protection. Wire up the relays if ordered; these are with potential-free output, external
voltage has to be connected to drive the trip circuit (e.g. contactors coil).
Wire up the instruments inputs via its detachable external termination board and connect it to the main unit by the built-in
Male/Female connector pairs. Route the sensor cables and the extension cable away from electrical noise sources. Ensure correct
input polarity.
Important Note: Insure proper earthing connection of supply

3. 0 O P E R A T I O N / P R O G R A M M I N G
3.1

HMI I NTE RFACE

LECTROTEK SYSTEMS

OPERATION MANUAL UniScan Series

Page 2 of 6

LECTROTEK

Product

SYSTEMS

OPERATION MANUAL

www.lectrtek.com

The UNISCAN-NX/H/V has the following HMI-interface:


1. Top 4 digit 7-segment LED normally shows Process Value display of channel being shown (PV). This indicates the value of the
channels input being measured, in direct engineering units. The range can be programmed for mA/Sqrt inputs at site over any 4-digit
range (-1999 to 9999 units).
2.

Bottom 4 digit 7-segment LED normally shows Channel Number and Alarm Status of channel being shown.

3.

2 nos LEDs A & M for display of Auto-Manual status. The instrument can be operated in automatic mode, wherein the channel display
automatically scrolls through all channels as per user set display interval time. In Manual mode, user can select any channel and hold
the display to that channel.

4.

4 nos. keys for operating the instrument. Their normal functions are given below (keys from left to right)

1. S SCROLL: This key sequentially selects parameter being displayed or programmed.


2. Decrement: This key selects (decrements) channel numbers in Manual Mode
3. Increment: This key selects (increments) channel numbers in Manual Mode.
4. M Auto/Manual: This key toggles the instrument between Auto/Manual modes.
All keys are multi-function keys and used singly or in combination with other keys and this is described in the relevant sections.
Any unused channel should be terminated by minimum 100 resistor

3.2

P R O G R AM M I N G / O P E R ATI O N S

3.2.1

D i s p l a y I n t e r v a l / S e r i a l N u m b e r C h a n g e & Au t o / M a n u a l O p e r a t i o n

Press

Displays

Annunciates

S Key

DStn

Auto mode display time selectable 1-99 seconds by or keys

S Key

SLno

Serial number 1-99 for addressing in network selectable by or keys

S Key

AtrP

Alarm trip select by or keys


Continue pressing of or keys show yes or no If yes, trips at high Alarm and
keeps the relay in latched state until you ACKNOWLEDGE ( key)

S Key

Exits to normal mode of display

M Key
3.2.2

Toggles A or M LED

Toggles instrument between Auto Scroll and Manual Mode of display

A L AR M M O D E - P r o g r a m m i n g / V i e w i n g Al a r m s

Press

Displays

1. Press S + keys
Enters into Alarm View /
Change Mode.

Annunciates

2 0 0.1

2. Alarms can be set or


programmed per channel.

1A01

Press M key successively to


select on the Bottom Window:

- 0 0.

1A(Alarm 1)
1d(Relay Hysterisis 1A)
2A(Alarm 2) and
2d(Relay Hysterisis 2A)
This section describes the
relay hysterisis 1d and 2d,
used to select relay on-off
differential and relay state in
alarm condition.
Press S key to select Next
Channel, repeat procedure to
set Alarms.
Press S + keys to quit

1d01

Top display shows present alarm setting.


Change set value by using keys.
Bottom display shows the Channel No.(2 digits) and remaining two digits, it
sequentially shows: - 1A(Alarm 1), 1d (Relay Hysterisis of A1), 2A(Alarm 2)
and 2d (Relay Hysterisis of A2).
Top display shows hysterisis value & polarity of 1st alarm of selected channel.
Hysterisis: Respective alarms hysterisis can be adjusted for providing a deadband between alarm trip/reset, to avoid frequent trips/relay chattering. Relay
state in alarm condition is set by polarity of the value.
The table below shows polarity settings:

1 1 00
2A02

Hysterisis programmed

Relay ON condition

Relay OFF condition

Positive

PV Alarm Set

PV Alarm Set

Negative

PV Alarm Set

PV Alarm Set

Repeat above steps to set alarms for channel selected.


Press S + keys to quit Alarm Mode

Important Note: Programming a negative or positive sign to the Hysterisis enables user to make relays OFF or ON in alarm
condition, as desired. User caution and care is to be taken while programming this feature in this extremely universal
instrument.
3.2.3

C AL I B R ATI O N M O D E

LECTROTEK SYSTEMS

OPERATION MANUAL UniScan Series

Page 3 of 6

LECTROTEK

Product

SYSTEMS

OPERATION MANUAL

www.lectrtek.com

The instrument can be calibrated from the front panel keyboard by adjusting the Slope/Intercept of each channel by connecting a calibrated
source/standard at the input terminals of channel to be calibrated.
Enter the calibration mode by pressing S + M key combination as per table below:
Press

Displays

Annunciates
It asks for password. Enter correct password. Password is 70 Press E key to
enter Calibration Mode.

Skipping/Unskipping Channels
S + M keys Enters Calibration
Mode.

Top display shows current channels input value. Connect zero side input from
calibrator.

Press M key again


Enters Zero Calibration

0 0 1.2
Z

1. If small error is observed, adjust using & keys.


2. Lower display shows z->zero and 01-> channel no.
Top display shows current channels input value.
Connect full span input from calibrator.

01

1. If small error is observed, adjust using & keys.


Lower display shows S->Span and 01-> channel no.

Press M key again


Enters Span Calibration

Press S + M keys

Top display shows Channel Unskipped (n S t P ) or Skipped (S L I P ) positions.


Skipped channels are not viewable by user. Key toggles between Skip and
Unskip mode.

n
StP
01

Then press M key to enter


calibration mode.

1199

2. If channel is being calibrated for newly setup input, use


QuickCal keys (S + ) to come quickly to span side calibration.

01

Quits Calibration Mode

Important Note:
i) Whenever dual key press functions are discussed, the keys have to be pressed as follows: Press first key in the combination,
keeping it pressed, press second, release first and then release second. In above case, press S first, keep it pressed and press M,
then release S, then release M.
ii) After last channel, it shows Ambient. Adjust it by or keys. For thermocouple inputs apply absolute mV between terminal R
AND B and short terminals B and G and follow same procedure for calibration.
iii) If user will change any thing, he has to save the changes first.
3.2.4

CONFIGURATION/SETUP MODE

In this mode, the UNISCAN-NX/H/V can be configured for its channel-wise inputs, ranges, alarm/relay grouping/assignment from the front
panel keyboard.
Enter the Configuration mode by pressing first S + M key combination. This enters instrument into Calibration Mode. Continuing further in
the same mode, next press S + key. Configure step-wise as per the table below:
Press
1. S + M keys
Enters Calibration Mode
2. S + key.
Enters Configuration Mode
Press M key to enter configuration mode.

Press or keys
Selects desired input for the channel A I P

Displays

Annunciates

r t d

Top display shows Input selected.

in 0 1

Bottom display shows the Input Selection Mode of selected channel


(in- input; 01- Channel No.)

nAI P
in 01

Use keys to toggle top display between:


rtd
Pt-100 RTD
CU53 Copper 53 type
nAIP Linear dc current input (0/4-20mA)
V_5 voltage difference(5V)
V_10 voltage difference(10V)
nASq Square root current input (0/4-20mA)
V_Sq square root voltage input
Pt10 Pt-PtRh10% thermocouple input(S)
Pt13 Pt-PtRh13% thermocouple input (R )
CUCn Cu-Const. Thermocouple input (T)
btype btyp thermpcouple input
ntyp ntyp thermocouple input
FECn Fe-Const. Thermocouple input (J)
CrAl Cr-Al thermocouple input (K)
CrCn CrCn thermocouple input
Back to rtd input.

LECTROTEK SYSTEMS

OPERATION MANUAL UniScan Series

Page 4 of 6

LECTROTEK

Product

SYSTEMS

OPERATION MANUAL
Press M key again
Enters Range High for the selected
channel (e.g. 100.0 for 0-100.0 range)
Press M key again
Enters Range Low for the selected
channel (e.g. 000.0 for 0-100.0 range)
Press M key again
Enters Decimal Mode for the selected
channel.
This selection is valid for mA dc inputs
(linear and square root).
Press E key to select sequentially
following conditions for channel:
Alarm1 (1A).
Alarm2 (2A).
Open Input (Pn)
Press S + M keys

www.lectrtek.com
1 0 0. 0
rH01
0 0 0. 0
rL01

Top display shows channels span side range value (Range High).
Use keys to change if required.
Note: Ranges are limited by respective sensor types see Section 1.2
Top display shows channels zero side range value (Range Low).
Use keys to change if required.

0 0 0. 0

Top display shows channels Range Low with previous decimal point.

dP01

Use keys to change.


Note: Decimals are fixed as 0.1 for RTD and 1 digit for thermocouple inputs.

rL01

Top display shows relay number assignable to channel selected. Use


keys to assign relay number. If no relay is to be assigned to selected
channel, choose nORL by toggling beyond rL32 Any relay no. upto 32 can
be selected, using keys.

Bottom display shows Channel Number and the Alarm type (changeable by
A/M key between A1, A2 and Pn conditions).
Save and quits Configuration Mode, gets back to normal display mode.

1A01

I mportant Note 1: The UNISCANs standard software enables user to select up to 32 relays for assigning them
for alarms of any desired channel. The software allows selection of maximum number of relays (32), obviously, if
lesser number of relays are ordered, user must select relay numbers less than or equal to the relays ordered. (For
example, if 8 relays are ordered, you can assign alarms of desired channels among these 8 relays only, if an alarm
is allocated to relay number higher than 8, it will not function).
Important Note 2: The user must satisfy himself that relays have been correctly assigned/grouped. This is especially important for critical
applications like alarm/trips of safety devices. Standard suggested method is to make a table of desired alarm assignments, so that alarm
type conflicts are avoided while programming the UNICSAN-NX. (For example, the same relay can be assigned for High or Low Alarm
conditions to different channels.
Important Note 3: When alarm condition H (TRIP) for any channel occurs and if instrument is in auto mode then It stops scanning and
holds the temperature value of that channel. It will be remains in that state unless and until the condition get acknowledged. Press key to
acknowledge that condition, it will run in auto mode till next H alarm condition occurs.
3.2.5

A U T O C AL I B R ATI O N M O D E

Calibrate all input types to Channel no. 1. And just setting the respective input type, that particular channel will gets calibrated
1.
2.

Suppose User wants to calibrate RTD to ch-2. Go in configuration mode. Recall that input type and then save it by pressing S+M
key.
Suppose input type (e.g. RTD) is there then also user has to change it and set to RTD. Save it by pressing S+M key.
Important Note: User can calibrate the instruments without auto calibration. It needs individual calibration for each channel
(Procedure is given in calibration mode). By this way these instruments can be use for any input type as mentioned above.

LECTROTEK SYSTEMS

OPERATION MANUAL UniScan Series

Page 5 of 6

LECTROTEK

Product

SYSTEMS

OPERATION MANUAL

www.lectrtek.com

APPENDIX
THERMOCOUPLE INPTS

APPLY BETWEEN R&B AND SHORT B&G

SHORTLINKS

J19-J34

Pt100

APPLY BETWEEN R&B AND G

SHORTLINKS

J19-J34

mA INPUT

APPLY BETWEEN R&B AND SHORT B&G

SHORTLINKS

J1-J34

Shortlinks are already placed on boards as per specification. If mixed inputs are to be used put only required shortlinks as per
table.

1 . W I R I N G D I AG R AM
For Inputs - extensions
CHANNEL 9

CHANNEL 16

FR C C ABLE

+ - TC
CHANNEL 1

LECTROTEK SYSTEMS

CHANNEL 8

OPERATION MANUAL UniScan Series

Page 6 of 6

LECTROTEK

Product

SYSTEMS

OPERATION MANUAL

www.lectrtek.com

Connection details of main unit

90V~
to
264V~

N C

P5

N O

NC

P6

NO

NC

P7

NO

NC

D1 CM N D2 D3

P8

NO

G B A
D IG IT A L
IN P U T S

P R IN T E R

RS
485

IN P U T S
1 7 -3 2

U N IS C A N _B A K 3
NO

P1

NC

NO

P2

NC

NO

P3

NC

NO

IN P U T S
1 -1 6
P4

4 -2 0 m A O P

NC

U N IS C A N V

SN

R ELAY

R ELAY

RL26RL27RL28R L 2 9R L30R L31R L 3 2-

R L25

R L19R L20R L 2 1R L22R L23R L 2 4-

RL17

R L18

R ELAY

-+
RL6

RL13R L12R L 11 R L10R L9 RL15

RL14

- +

WARRANTY