ABB LIMITED
YN1G176789-D
Segment :
Responsible Deptt :
Revision :
Language:
File Name :
Power technology
PTUA-PA
En
270611638.doc.doc
Prepared :
Reviewed :
Released :
Page
Pages
2004/02/22 SP
2004/02/26 VV
2004/02/26 VV
82
Contract No.:
Replaces :
Classify No:
CS-3120(R&M)-415-9 Vol II
Document Title:
Customer:
Project:
2
1
Rev. :
2004/06/18
2004/06/07
2004/02/26
Date :
Description :
STS
STS
SP
Prepared :
VV
VV
VV
Reviewed:
VV
VV
VV
Released :
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express
authority is strictly forbidden. ABB Ltd.
Revision 1
Project :
Language :
Page :
En
YN1G176789-D
Introduction:
This is the FDS (Functional Design Specification) document for the Plant performance calculation for
NALCO Angul. The document contains the design and calculation methodology to be used by the
performance calculation software. The calculation methodology employed here is based on the
approach adopted for performance calculation of TNEB Mettur. The performance calculation
application will be developed with a Visual Basic front end. MySQL will be used as the database for
the application. The interface to be used for reading and writing process data to the Fix32 database of
the DAS is Fix Real Time ODBC. This is a standard SQL ODBC interface available to Fix 32. A
schematic for the architecture of the performance calculation software is given below:
FIX32
OS
FIX32
Database
FIX ODBC
Product
ACCESS
ODBC
Driver
MySQL
DATABASE
(DBMS)
SQT
Block
SQD
Block
FIX 32
SQL
TASK
VB Front
End
Performance
Calculation
Application
Revision 1
Project :
Language :
En
Page :
YN1G176789-D
The SQL Trigger block (SQT) triggers. The SQL task reads the SQL command name from the
SQT block.
The SQL task retrieves the associated command from the SQL Library Table.
The SQL task reads the tag names specified in the SQL command from the SQL Data block
(SQD) and reads the values associated with these tag names from the FIX database.
The SQL task executes the SQL command and inserts data into or selects data from the
relational database.
If the SQL command is a SELECT command, the retrieved data is written to the FIX tag names
defined in the SQD block
The MS ACCESS shall act as a temporary storage location. The calculations shall be performed in
the VB front end and can also be viewed. The important performance parameters shall be displayed
in the Operator stations.
Linking with the steam table routines:
Steam table routines are provided as a standard Visual Basic add-on module. The module contains
standard built-in functions that takes properties such as temperature and pressure as input
parameters and returns thermodynamic properties such as enthalpy, entropy, saturation temperature
etc.
Class II tags:
The performance calculation module uses an internal set of tags which is independent of the Fix32
process tags. An installation of the performance calculation software (signifying an instance of the
database) can handle the calculations for one unit. So each unit in the plant needs to have a separate
installation of the package. Where process tags are created in the Fix32 database for the purpose of
Class II calculations, the process tags (AVxxx) and performance tags (CVxxx) will have the
corresponding unit number as prefix.
Bad quality points: If an input value for the calculation is found to be invalid, based on the percentage
load at that time an interpolated value from the heat balance diagram will be substituted for the bad
point.
Data validity: If the calculated value is found to deviate from the nominal value by more than a
specified percentage, the calculated value shall be highlighted in red on the display screen.
Revision 1
Project :
Language :
En
Page :
YN1G176789-D
Parameter
Process tag
Class II tag
(FF004 + FF007)/2
AV001
Stage I Pressure
TP005
3.
4.
5.
6.
HPH 6 FW temperature In
7.
8.
9.
Deaerator pressure
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
Gross generation
CP001
XT006
XP005
FT013
XT012
FF006
FP001
CT008
XT003
XP003
CT007
XT010
XT002
XP002
CT006
XT009
XP001
CT005
XT008
(RT007 + RT008)/2
(RP005 + RP006)/2
GE001
AV002
AV008
AV009
AV010
AV011
AV012
AV013
AV014
AV029
AV031
AV032
AV033
AV034
AV035
AV036
AV037
AV038
AV040
AV041
AV042
AV045
AV046
AV049
Revision 1
Project :
Language :
25.
Condenser vacuum mm Hg A
26.
27.
28.
AH A gas in temp
29.
30.
AH B gas in temp
31.
32.
33.
34.
35.
36.
37.
38.
39.
40.
41.
42.
43.
44.
Mill B PA flow
45.
Mill C PA flow
46.
Mill D PA flow
47.
Mill E PA flow
48.
Mill F PA flow
49.
Mill A PA flow
50.
51.
En
HP006
(WA001+WA002)/2
(ST050 + ST051 +
ST052) / 3
(ST044 + ST045 +
ST046) / 3
(ST053 + ST054 +
S0T55)/3
(ST047 + ST048 +
ST049) / 3
(ST020 + ST021 +
ST022)/3
(ST014 + ST015 +
ST016) / 3
ST024
(ST017 + ST018 +
ST019) / 3
XT005
XP004
XT011
FT012
(TT068 + TT069)/2
(TP003+TP004)/2
TT011
TP013
(FF005 + FF008)/2
SF002
SF003
SF004
SF005
SF006
SF001
SF011
SF012
Page :
YN1G176789-D
AV050
AV053
AV054
AV055
AV057
AV058
AV063
AV064
AV065
AV066
AV067
AV068
AV069
AV071
AV072
AV073
AV074
AV075
AV076
AV077
AV078
AV079
AV080
AV081
AV082
AV083
AV084
Revision 1
Project :
Language :
52.
53.
54.
55.
56.
57.
58.
59.
60.
61.
62.
63.
64.
65.
66.
67.
68.
69.
70.
71.
72.
73.
74.
75.
76.
77.
78.
Page :
En
(FF004 + FF007)/2 +
FFOO5 + FF008
FP005
FP005
FT009
(XF001)
CF001
HT002
HF002B
CT002
CT011
(TP003+TP004)/2
ST073
ST075
(SP001 + SP002)/2
RT013
RT016
RP002
SM001
SM002
SM003
SM004
SM005
SM006
SF007
SF008
(FT005+FT006+FT007)/
3
AF002
YN1G176789-D
AV085
AV086
AV087
AV088
AV090
AV091
AV092
AV093
AV094
AV096
AV097
AV098
AV099
AV100
AV101
AV102
AV103
AV104
AV105
AV106
AV107
AV108
AV109
AV110
AV111
AV114
AV115
Revision 1
Project :
79.
80.
81.
82.
83.
84.
85.
86.
87.
88.
89.
90.
91.
92.
93.
94.
95.
96.
97.
98.
99.
100.
101.
102.
103.
104.
Language :
Page :
En
AT003
MF003
CT007
CT004
HF001B
CT012
(RP001 + RP004)/2
SP014
FT010
FT011
(ST008 + ST009 +
ST010)/3
ST060
ST061
ST062
ST063
ST064
ST065
SP045
SP046
SP039
SP040
SP037
SP038
SP006
SP007
(ST011 + ST012 +
ST013)
(ST042 + ST043) / 2
YN1G176789-D
AV116
AV117
AV118
AV119
AV120
AV122
AV135
AV136
AV138
AV139
AV140
AV149
AV150
AV151
AV152
AV153
AV154
AV156
AV157
AV159
AV160
AV163
AV164
AV165
AV166
AV167
AV170
Revision 1
Project :
Language :
En
Page :
YN1G176789-D
Constants:
S No.
1.
Description
Process Tag
KN001
2.
KN002
3.
Atmospheric pressure
KN003
4.
KN006
5.
KN007
6.
KN008
7.
KN009
8.
KN010
9.
KN011
10.
KN013
11.
KN014
12.
KN015
13.
KN016
14.
KN018
15.
KN020
16.
KN021
17.
KN025
18.
KN035
19.
KN036
20.
KN037
21.
Design rated value of wet gas flow through each air heater
KN039
22.
KN040
23.
KN041
24.
KN042
Revision 1
Project :
Language :
En
Page :
YN1G176789-D
25.
KN043
26.
KN044
27.
KN045
28.
KN046
29.
KN047
30.
KN048
31.
KN049
32.
KN050
33.
KN051
34.
KN052
35.
KN053
36.
KN055
37.
KN056
38.
KN057
39.
KN058
40.
KN034
41.
KN038
42.
KN032
43.
KN026
44.
KN033
45.
Cost of coal
KN099
46.
KN098
Tag
CV001
Description
CV002
Revision 1
Project :
CV003
CV004
CV005
CV006
CV007
CV008
CV011
10
CV012
11
CV014
12
CV024
13
CV025
14
CV026
15
CV027
16
CV028
17
CV029
18
CV034
19
CV035
20
CV036
21
CV037
22
CV040
23
CV042
24
CV044
25
CV048
26
CV049
27
CV050
28
CV051
29
CV052
Language :
En
Page :
10
YN1G176789-D
Revision 1
Project :
Language :
En
30
CV053
31
CV054
32
CV055
33
CV056
34
CV057
35
CV058
36
CV059
37
CV061
38
CV062
39
CV064
40
CV065
41
CV066
42
CV067
43
CV069
44
CV070
45
CV071
46
CV073
47
CV074
48
CV075
49
CV076
50
CV078
51
CV079
52
CV080
53
CV082
54
CV083
55
CV084
56
CV085
Page :
11
YN1G176789-D
Revision 1
Project :
57
CV087
58
CV088
59
CV089
60
CV090
61
CV091
62
CV092
63
CV093
HP turbine efficiency
64
CV094
65
CV095
66
CV096
67
CV097
IP turbine efficiency
68
CV098
69
CV099
70
CV108
Generator losses
71
CV109
72
CV110
73
CV111
74
CV112
LP turbine efficiency
75
CV117
76
CV118
77
CV119
78
CV120
79
CV121
80
CV122
81
CV123
Boiler efficiency
82
CV124
Net generation
83
CV125
Language :
En
Page :
12
YN1G176789-D
Revision 1
Project :
Language :
84
CV126
85
CV127
86
CV133
87
CV136
88
CV137
89
CV138
90
CV139
91
CV140
92
CV141
93
CV142
94
CV145
95
CV146
96
CV147
97
CV148
98
CV149
99
CV150
100
CV152
101
CV153
102
CV154
103
CV155
104
CV156
105
CV157
106
CV158
107
CV159
108
CV160
109
CV161
110
CV162
En
Page :
13
YN1G176789-D
Revision 1
Project :
Language :
En
111
CV163
112
CV164
113
CV166
114
CV169
115
CV170
116
CV171
117
CV172
118
CV173
119
CV174
120
CV175
121
CV176
122
CV177
123
CV178
HPT CV leakage
124
CV179
125
CV180
126
CV181
127
CV182
128
CV183
129
CV184
130
CV185
131
CV187
132
CV188
133
CV189
134
CV190
135
CV191
136
CV192
137
CV193
Page :
14
YN1G176789-D
Revision 1
Project :
Language :
En
Page :
15
YN1G176789-D
138
CV194
139
CV195
140
CV196
141
CV197
142
CV198
143
CV199
144
CV200
145
CV201
146
CV202
147
CV203
Ton of dry air leakage in AHA per the quantity of wet flue gas per ton of fuel fired entering
AH A
Tone of dry air leakage in AH B per the quantity of wet flue gas per ton of fuel fired
entering AH B
Ton of moisture per ton of dry air (I.e., specific humidity of dry air)
148
CV204
Ton of minimum air for complete combustion per ton of fuel fired
149
CV205
150
CV206
151
CV207
152
CV208
Ton of wet air leakage in AH A per the quantity of wet flue gas per ton of fuel fired entering
AH A
Tone of wet air leakage in AH B per the quantity of wet flue gas per ton of fuel fired
entering AH B
Ton of moisture in flue gas at AH inlet per ton of fuel fired
153
CV209
154
CV210
155
CV211
156
CV212
Fraction of the total air leakage of AH A coming from primary of air side
157
CV213
Fraction of the total air leakage of AH A coming from secondary air side
158
CV214
159
CV215
160
CV216
161
CV217
162
CV218
163
CV219
164
CV220
Revision 1
Project :
Language :
En
Page :
16
YN1G176789-D
165
CV221
166
CV222
167
CV223
168
CV224
169
CV225
170
CV226
171
CV229
Test X ratio AH A
172
CV230
Test X ratio AH B
173
CV231
174
CV232
175
CV233
Corrected percentage air leakage of AH A for deviation from design pressure differential
and from design air temperature
Corrected percentage air leakage of AH B for deviation from design pressure differential
and from design air temperature
Ton of coal fired per hour
176
CV234
Gas side pressure loss of AH A corrected for deviation from design flow and temperature
177
CV235
Gas side pressure loss of AH B corrected for deviation from design flow and temperature
178
CV236
179
CV237
180
CV238
Primary air side pressure loss of AH A corrected for deviation from design flow and
temperatures
Primary air side pressure loss of AH B corrected for deviation from design flow and
temperatures
PA flow through AH A
181
CV239
PA flow through AH B
182
CV240
183
CV241
184
CV242
Secondary air side pressure loss of AH A corrected for deviation from design flow and
temperatures
Secondary air side pressure loss of AH B corrected for deviation from design flow and
temperatures
Corrected gas temperature leaving AH A for deviation from design entering air temperature
185
CV243
186
CV244
187
CV245
188
CV246
Corrected gas temperature leaving AH B for deviation from design entering air
temperature
Corrected gas temperature leaving AH A for deviation from design entering gas
temperature
Corrected gas temperature leaving AH B for deviation from design entering gas
temperature
Corrected gas temp leaving air heater A for deviation from design X ratio
189
CV247
Corrected gas temp leaving air heater B for deviation from design X ratio
190
CV248
191
CV249
Revision 1
Project :
Language :
En
Page :
17
YN1G176789-D
192
CV250
193
CV251
Corrected gas temperature leaving air heater A for deviation from design entering flue gas
flow
Corrected gas temp leaving air heater B for deviation from design entering flue gas flow
194
CV252
Correction factor for gas temp of AH A for deviation from design entering flue gas flow
195
CV253
Correction factor for gas out temp of AH B for deviation from design entering flue gas flow
196
CV254
197
CV255
198
CV256
199
CV257
200
CV258
201
CV259
202
CV260
203
CV261
204
CV262
205
CV263
206
CV264
207
CV265
208
CV266
Deviation of corrected exit gas temperature at AH A from design value of exit gas
temperature
Deviation of corrected exit gas temperature at AH B from design value of exit gas
temperature
AH A gas side pressure loss (corrected for deviation from design flow and temp)
expressed as a percentage of design gas side press loss
AH B gas side pressure loss (corrected for deviation from design flow and temp)
expressed as a percentage of design gas side press loss
AH A PA side pressure loss (corrected for deviation from design flow and temperature0
expressed as a percentage of the design rated value of PA side pressure loss
AH B PA side pressure loss (corrected for deviation from design flow and temperature)
expressed as a percentage of the design rated value of PA side pressure loss
AH A sec air side pressure loss (corrected for deviation from design flow and temperature)
expressed as a percentage of the design pressure loss
AH B sec air side pressure loss (corrected for deviation from design flow and temperature)
expressed as a percentage of the design pressure loss
AH A sec air inlet pressure delete from
209
CV267
210
CV269
211
CV270
212
CV272
213
CV273
214
CV274
215
CV275
216
CV276
217
CV277
218
CV278
Revision 1
219
CV279
Project :
Language :
En
Page :
18
YN1G176789-D
Revision 1
Project :
Language :
Page :
En
19
YN1G176789-D
Calculation details:
CV199
=Fn((AV098+AV099)/2 , AV100+KN003)
KCAL/KG
where
AV098 SH Outlet Stm Temp (L)
AV099 SH Outlet Stm Temp (R)
AV100 SH Outlet Stm Pressure
KN003 Atmospheric Pressure
-----------------------------------------------------------------------------------------------------------------------CV139
-----------------------------------------------------------------------------------------------------------------------CV140
BFP Discharge to Desuperheater Enthalpy
= Fn(AV114)
- A function of temp compressed liquid KCAL/KG
Where
AV114 BFP Disch to Desuperheater Temp
-----------------------------------------------------------------------------------------------------------------------CV141
Aux Steam Enthalpy
=Fn(AV115+KN003, AV116)
SH steam A function of press and temp KCAL/KG
Where
AV115 Aux Steam Pressure
KN003 Atmospheric Pressure
AV116 Aux Steam Temp
-----------------------------------------------------------------------------------------------------------------------CV142
Aux Steam Supply Flow =AV117*(CV141-CV140) / (CV139-CV140)
T/Hr
Where
AV117 Aux Steam Flow
CV139 Main Steam to Aux Steam Enthalpy
CV140 BFP Discharge to Desuperheater Enthalpy
CV141 Aux Steam Enthalpy
-----------------------------------------------------------------------------------------------------------------------CV001
Revision 1
Project :
Language :
AV001
KN001
CV142
AV076
En
Page :
20
YN1G176789-D
-----------------------------------------------------------------------------------------------------------------------CV002
Calculated Throttle Steam Flow
=Fn(AV002 + KN003) * FACTOR
-Throttle steam flow is a function of first stage shell press, adjusted for temperature
and pressure T/Hr
Where
FACTOR = VOPER/VRATED
VOPER Specific volume of steam at operating
conditions
=Fn (AV072,AV073 + KN003)
Where
AV072 Main Steam Temperature after ESV
AV073 Main Steam Pressure after ESV
KN003 Atmospheric pressure
AV002 First stage pressure
Vrated
VRATED
-Specific volume of Steam at 530
deg c & 130 kg/cm2
=Fn(530,130+KN003)
-----------------------------------------------------------------------------------------------------------------------CV003
Per Cent Rated Load
=(CV001/611.635 )*100
-Ratio of Main steam flow to rated steam flow as a percentage. %
Where
CV001 Main Steam Flow
611.635 Rated Steam Flow
-----------------------------------------------------------------------------------------------------------------------CV004
Fraction of Air That is Primary Air
=(AV077+AV078+AV079+AV080+AV081+AV082) /
(AV077+AV078+AV079+AV080+AV081+AV082+AV083+AV084)
-PA flow divided by total air flow
Where
AV077
AV078
AV079
AV080
AV081
AV082
AV083
AV084
Mill B PA flow
Mill C PA flow
Mill D PA flow
Mill E PA flow
Mill F PA flow
Mill A PA flow
Sec Air Flow Left
Sec Air Flow Right
-----------------------------------------------------------------------------------------------------------------------CV005
Fraction of Air that is Secondary Air
= 1.0 - CV004
- One minus PA fraction
Where
CV004 PA fraction
Revision 1
Project :
Language :
Page :
En
21
YN1G176789-D
-----------------------------------------------------------------------------------------------------------------------CV006
Feedwater Saturation Temperature in the Deaerator
- A function of deaerator pressure
=Fn (AV014 + KN003)
Deg C
Where
AV014 Deaerator pressure
KN003 Atmospheric pressure
-----------------------------------------------------------------------------------------------------------------------CV007
Feedwater Enthalpy (at BFP Suction)
=Fn (CV006,AV086 + KN003)
- A function of saturation temperature and pressure
KCAL/KG
Where
CV006 Feedwater saturation temperature
AV086 Feedwater pressure (at BFP suction)
KN003 Atmospheric pressure
-----------------------------------------------------------------------------------------------------------------------CV008
Superheat Spray Water Enthalpy
=Fn(AV088, AV087 + KN003)
- Function of FW Temp & press at Eco inlet
KCAL/KG
Where
AV087 FW pressure at Econ inlet
AV088 FW temperature at Econ inlet
KN003 Atmospheric pressure
.
-----------------------------------------------------------------------------------------------------------------------CV011
HPH 6 Drain Cooler Approach = AV012 - AV011
Deg C
Where
AV012 HPH 6 Drain Temperature
AV011 HPH 6 FW inlet temperature
-----------------------------------------------------------------------------------------------------------------------CV176
HPT Front Seal Leakage
= Fn(CV001)
- HPT Front Seal leakage is a function of main steam flow.
T/Hr
Where
CV001 Main Steam Flow
-----------------------------------------------------------------------------------------------------------------------CV177
HPT Rear Seal Leakage
= Fn(CV001)
-HPT Rear seal leakage is a function of main steam flow. T/Hr
Where
CV001 Main Steam Flow
-----------------------------------------------------------------------------------------------------------------------CV178
HPT CV leakage
=Fn(CV001)
-HPT CV leakage is a function of main steam flow.
Where
T/Hr
Revision 1
Project :
Language :
En
Page :
22
YN1G176789-D
-----------------------------------------------------------------------------------------------------------------------CV024
Economiser performance of Heat Exchange
=(AV170-GASOUT)*100 / (AV170-AV088)
(%)
Where
AV170 Gas temp before Econ
AV088 Feedwater temp at Econ inlet
-----------------------------------------------------------------------------------------------------------------------CV025
Heater 6 extraction enthalpy
=Fn(AV009,AV010+KN003)
-A function of extraction steam temperature and pressure - SH steam
KCAL/KG
Where
AV009 Ext. temperature heater 6
AV010 Ext. pressure heater 6
KN003 Atmospheric pressure
-----------------------------------------------------------------------------------------------------------------------CV026
Enthalpy of FW into Heater 6
=Fn(AV011, AV087 + KN003)
- A function of FW temperature & pressure into heater 6 - compressed liquid
KCAL/KG
Where
AV011 Inlet temperature heater 6
Revision 1
Project :
Language :
Page :
En
23
YN1G176789-D
T/Hr
Where
CV035 Cold Reheat flow
AV013 Reheat spray flow
-----------------------------------------------------------------------------------------------------------------------CV145
-----------------------------------------------------------------------------------------------------------------------CV146
High pressure heater 5 drain enthalpy =Fn(AV069)
-A function of drain temp; saturated liquid.
KCAL/KG
Revision 1
Project :
Language :
En
Page :
24
YN1G176789-D
Where
AV069 HPH 5 drain temp
-----------------------------------------------------------------------------------------------------------------------CV147
-----------------------------------------------------------------------------------------------------------------------CV148
High pressure heater 5 FW outlet enthalpy
=Fn(AV011, AV087 + KN003)
-A function of temp & press compressed liquid KCAL/KG
Where
AV011 HPH 5 FW outlet temp.
AV087 FW press at Econ inlet
KN003 Atmospheric pressure
-----------------------------------------------------------------------------------------------------------------------CV042
Heater 5 extraction flow
=((AV085*(CV148-CV147) + CV029*(CV146-CV027)) / (CV145-CV146)
-Calculated by a heat balance around Heater 5
T/Hr
Where
AV085
CV148
CV147
CV029
CV146
CV027
CV145
Feedwater flow
HPH 5 FW outlet enthalpy
HPH 5 FW inlet enthalpy
HPH 6 drain Flow
HPH 5 drain enthalpy
HPH 6 drain enthalpy
HPH 5 extraction enthalpy
-----------------------------------------------------------------------------------------------------------------------CV037
Heater 5 drain flow
=CV029+CV042
T/Hr
-Heater 6 drain flow plus heater 5 ext. flow
Where
CV029 Heater 6 drain flow
CV042 Heater 5 ext. flow
---------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------CV040
Enthalpy of FW out of heater 5 =CV026
KCAL/KG
-Equal to heater-6 FW inlet enthalpy
Where
CV026 Heater 6 FW in Enthalpy
----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Revision 1
CV044
Project :
Language :
Page :
En
YN1G176789-D
25
-----------------------------------------------------------------------------------------------------------------------CV048
-----------------------------------------------------------------------------------------------------------------------CV049
Heater 2 condensate out enthalpy
=Fn(AV033)
-A function of condensate temperature. Compressed liquid.
KCAL/KG
Where
AV033 Outlet temperature heater 2
-----------------------------------------------------------------------------------------------------------------------CV050
Heater 3 drain enthalpy =Fn(AV034)
-A function of drain temperature, saturated liquid.
KCAL/KG
Where
AV034 Drain temperature heater 3
-----------------------------------------------------------------------------------------------------------------------CV149
KCAL/KG
Where
AV118 LPH 3 condensate inlet temp.
-----------------------------------------------------------------------------------------------------------------------CV053
-----------------------------------------------------------------------------------------------------------------------CV054
KCAL/KG
Revision 1
Project :
Language :
En
Page :
26
YN1G176789-D
Where
AV037 Outlet temperature heater 1.
-----------------------------------------------------------------------------------------------------------------------CV055
Heater 2 drain enthalpy
=Fn(AV038)
-A function of drain temperature. Saturated liquid.
KCAL/KG
Where
AV038 Drain temperature heater 2
---------------------------------------------------------------------------------------------------------------------CV150
----------------------------------------------------------------------------------------------------------------------CV051
Heater 3 extraction flow
= AV091*(CV044-CV149) / (CV048-CV05))
-Calculated by a heat balance around heater 3 T/Hr
Where
AV091
CV044
CV149
CV050
CV048
Condensate flow
Heater 3 Condensate out enthalpy
Heater 3 Condensate in enthalpy
Heater 3 drain enthalpy
Heater 3 extraction enthalpy
-----------------------------------------------------------------------------------------------------------------------CV052
-----------------------------------------------------------------------------------------------------------------------CV056
Condensate flow
Condensate flow
Heater 2 condensate out enthalpy
Heater 3 drain flow
Heater 2 drain enthalpy
Heater 3 drain enthalpy
Heater 2 extraction enthalpy
Heater 2 drain flow
Revision 1
Project :
Language :
En
Page :
YN1G176789-D
27
----------------------------------------------------------------------------------------------------------------------CV059
KCAL/KG
Where
AV041 Inlet temperature heater 1.
-----------------------------------------------------------------------------------------------------------------------CV061
Circulating water velocity in condenser A tubes M/S
=1/2 ((AV093)/ (KN021*KN020*3600) + (AV093) / (KN021*KN056*3600))
Where
AV093 Circulating water flow right
KN021 Condenser cross sectional area for tube
KN020 Number of tubes in condenser A first pass
3600 Conversion from m/hr to m/s
KN056 Number of tubes in condenser A second
pass
-----------------------------------------------------------------------------------------------------------------------CV062
-----------------------------------------------------------------------------------------------------------------------CV064
Revision 1
Project :
Language :
En
Page :
28
YN1G176789-D
----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------CV069
Heater 3 saturation temperature =Fn(AV032+KN003)
-A function of extraction pressure to the heater DEG C
Where
AV032 Heater 3 extraction pressure
KN003 Atmospheric pressure
-----------------------------------------------------------------------------------------------------------------------CV070
Revision 1
Project :
Language :
En
Page :
29
YN1G176789-D
-----------------------------------------------------------------------------------------------------------------------CV071
CV073
-----------------------------------------------------------------------------------------------------------------------CV074
DEG C
Where
CV065 Heater 6 saturation temperature
AV007 Heater 6 outlet temperature
----------------------------------------------------------------------------------------------------------------------CV075
=AV094-AV092
Where
AV094 Condenser B CW outlet temperature
AV092 Cooling water temperature
--------------------------------------------------------------------------------------------------------------------CV076
DEG C
Where
CV067 Heater 5 saturation temperature
AV011 FW inlet temperature heater 6
Note: When contact status of XZ503 OR FZ507 OR FZ506 are closed, CV076 = 0
-------------------------------------------------------------------------------------------------------------------CV078
Terminal temperature difference heater 3
=CV069-AV029
-The approach to saturation for the condensate leaving the heater.
DEG C
Where
Revision 1
Project :
Language :
Page :
En
YN1G176789-D
30
DEG C
Where
CV070 Heater 2 saturation temperature
AV033 Heater 2 outlet temperature
Note: When contact status of XZ501 closed, CV079 = 0
-----------------------------------------------------------------------------------------------------------------------CV080
-----------------------------------------------------------------------------------------------------------------------CV082
KCAL/KG
Where
AV096 Condensate pump suction temperature
--------------------------------------------------------------------------------------------------------------------CV269
Design temperature heater 6 outlet FW =Fn(AV049)
DEG C
Where
AV049 Gross generation
--------------------------------------------------------------------------------------------------------------------CV083
Where
CV269 Design temperature heater 6 FW outlet
AV007 Heater 6 outlet temperature
----------------------------------------------------------------------------------------------------------------------CV084
Revision 1
Project :
Language :
Page :
En
31
YN1G176789-D
-----------------------------------------------------------------------------------------------------------------------CV085
Temperature deviation from design heater 5
=CV270-AV011
Difference between design and actual outlet temperature DEG C
Where
CV270 Design temperature heater 5 FW outlet
AV011 Heater 6 inlet temperature
-----------------------------------------------------------------------------------------------------------------------CV272
Design temperature heater 3 condensate outlet =Fn(AV049)
DEG C
Where
AV049 Gross generation
----------------------------------------------------------------------------------------------------------------------CV087
Where
CV272 Design temperature heater 3 condensate
outlet
AV029 Heater 3 outlet temperature
-----------------------------------------------------------------------------------------------------------------------CV273
-----------------------------------------------------------------------------------------------------------------------CV088
---------------------------------------------------------------------------------------------------------------------
Revision 1
CV157
Project :
Language :
Page :
En
32
YN1G176789-D
KCAL/KG
Where
AV040 LPH-1 extraction pressure
KN003 Atmospheric pressure
Dryness fraction = The quality of extraction steam
will be from :BHEL curves based on load. Fn(AV049)
----------------------------------------------------------------------------------------------------------------------CV158
Where
AV042 LPH -1 drain temp
----------------------------------------------------------------------------------------------------------------------CV159
KCAL/KG
Where
AV121 Outlet temp heater 1B.
----------------------------------------------------------------------------------------------------------------------CV089
Note: When contact status of CZ512 & CZ513 are closed, CV089 = 0
-----------------------------------------------------------------------------------------------------------------------CV090
Where
AV072 Main steam temp after ESV
AV073 Main steam press after ESV
KN003 Atmospheric pressure
-----------------------------------------------------------------------------------------------------------------------CV091
Revision 1
Project :
Language :
En
Page :
33
YN1G176789-D
Where
AV074 HPT exhaust temp
AV075 HPT exhaust press
KN003 Atmospheric pressure
----------------------------------------------------------------------------------------------------------------------CV092
HP turbine exhaust ideal enthalpy
=Fn(AV072,AV073+KN003, AV075+KN003)
-The enthalpy of main steam after isentropic expansion through the HP turbine
KCAL/KG
Where
AV072 Main steam temp after ESV
AV073 Main steam pressure after ESV
AV075 HPT exhaust pressure
KN003 Atmospheric pressure
-----------------------------------------------------------------------------------------------------------------------CV093
HP turbine efficiency
=(CV090-CV091) / (CV090-CV092) *100
-The ratio of the actual change in enthalpy across the HP turbine compared to the
theoretical change (at constant entropy), expressed as a percentage)
%
Where
CV090 Enthalpy of main steam at CV inlet
CV091 HP turbine exhaust enthalpy
CV092 HP turbine exhaust enthalpy (Ideal)
-----------------------------------------------------------------------------------------------------------------------CV094
Where
AV045 Hot reheat temperature IV inlet
AV046 Hot reheat pressure IV inlet
KN003 Atmospheric pressure
-----------------------------------------------------------------------------------------------------------------------CV095
----------------------------------------------------------------------------------------------------------------------CV096
Revision 1
Project :
Language :
Page :
En
34
YN1G176789-D
IP turbine efficiency
=((CV094-CV095/CV094-CV096))*100
-The ratio of the actual change in enthalpy to the theoretical change in enthalpy if
expansion was isentropic, expressed as a percentage. %
Where
CV094 Enthalpy of hot reheat at IV inlet
CV095 IP turbine exhaust enthalpy
CV096 IP turbine exhaust enthalpy (Ideal)
Where
CV098 Condenser A actual heat transfer
coefficient
CV064 Condenser A basic heat transfer
coefficient corrected.
-----------------------------------------------------------------------------------------------------------------------CV183
----------------------------------------------------------------------------------------------------------------------CV184
T/Hr
Revision 1
Project :
Language :
En
Page :
35
YN1G176789-D
T/Hr
Where
CV001 Main steam flow
-----------------------------------------------------------------------------------------------------------------------CV187
Steam leakage into LPT =Fn(CV001)
-Steam leakage into LPT is a function of main steam flow
T/Hr
Where
CV001 Main steam flow
----------------------------------------------------------------------------------------------------------------------CV188
=CV183+CV184+CV185-CV187
Where
CV183 IPT leakoff thru control valves
CV184 IPT leakoff thru rear seals
CV185 IPT leakoff thru front seals
CV187 Steam leakage into LPT
--------------------------------------------------------------------------------------------------------------------CV108
Generator variable losses
=Fn(AV049
-A function of gross generation MW
Where
AV049 Gross generation
---------------------------------------------------------------------------------------------------------------------CV109
-----------------------------------------------------------------------------------------------------------------------CV189
=Fn(CV001)
Revision 1
Project :
Language :
Page :
En
36
YN1G176789-D
Where
CV001 Main steam flow
-----------------------------------------------------------------------------------------------------------------------CV192
----------------------------------------------------------------------------------------------------------------------CV193
--------------------------------------------------------------------------------------------------------------------CV194
IPT rear seal leakoff enthalpy =Fn(CV001)
-IPT rear seal leakoff enthalpy is a function of main steam flow.
BHEL drg MS-0105-HW-03020.
Where
CV001 Main steam flow
---------------------------------------------------------------------------------------------------------------------CV195
----------------------------------------------------------------------------------------------------------------------CV196
Steam leakage into LPT enthalpy
=Fn(CV001)
-Steam leakage into LPT enthalpy is a function of main steam flow
Where
CV001 Main steam flow
**CV105
T/Hr
Revision 1
Project :
Language :
Page :
En
37
YN1G176789-D
Where
CV036 Hot reheat flow
CV042 Heater 5 extraction flow
CV051
CV056
CV089
AV090
CV188
Note :
1) The above equation is valid when the contact status of XZ505 is open
(contact status to be checked at site)
--------------------------------------------------------------------------------------------------------------------------------**CV111
Extract =
CV028*CV025 + CV042*CV145 + CV051*CV048 + CV056*CV053 + CV089*CV157
+ AV090*HXDEA
Where
CV028
CV025
CV042
CV145
CV051
CV048
CV056
CV053
CV089
CV157
AV090
Revision 1
Project :
Language :
En
Page :
38
YN1G176789-D
LP turbine efficiency
=((CV095-CV111) / (CV095-CV109))*100)
-The ratio of the energy used to the energy theoretically available expressed as a
percentage.
%
Where
CV095 IP turbine exhaust enthalpy
CV109 LP turbine exhaust enthalpy(Ideal)
CV111 LP turbine exhaust enthalpy(Actual)
Revision 1
Project :
Language :
En
Page :
39
YN1G176789-D
-----------------------------------------------------------------------------------------------------------------------CV181
Excess air percentage =(CV205/CV204)*100 %
Where
CV205 Ton of excess air per ton of fuel
CV204 Kg of minimum air required for complete
combustion per KG of fuel.
-----------------------------------------------------------------------------------------------------------------------CV182
Excess air percentage standard =Fn(AV049)
-Excess air percentage standard is a function of load.
%
Where
AV049 Gross generation
-----------------------------------------------------------------------------------------------------------------------CV034
Excess Air Deviation
=CV181-CV182 %
Where
CV181 Excess air percentage
CV182 Excess air % standard
-----------------------------------------------------------------------------------------------------------------------CV117
=WAEX+WGMA
Where
WAEX =t of excess air/t of fuel
=(54.88*KN006/100.+20.56*KN007/100. + 129.25 * KN008/100. - 16.29 *
KN009/100. + 4.90*KN010)/100.) * ((AV053/100)/(1-(4.78*AV053/100))
WGMA =T of dry gas/T of fuel in minimum air supply
for complete combustion condition.
=12.482xKN006/100. + 5.301*KN007/100. + 26.260*KN008/100. - 3.309*KN009/100.
+ KN010/100.
Where
KN006
KN007
KN008
KN009
KN010
Revision 1
Project :
Language :
Page :
En
40
YN1G176789-D
Where
CV117 Dry gas/ fuel fired
KN025 Specific heat of flue gas
AV054 AH A gas out temperature
AV057 AH B gas out temperature
AV060 AH A PA in temperature **
AV062 AH B PA in temperature **
CV004 Fraction of air that is primary air
CV005 Fraction of air that is secondary air
AV064 AH A secondary air in temperature**
AV066 AH B secondary air in temperature**
Note: a) when contact status of SZ517 OR SZ524 is closed the following equation are applicable
AHGOT = AV057, AHPAIT= AV062, AHSPAIT=AV066
b) When contact status of SZ519 OR SZ525 is closed the following equation are applicable
AHGOT = AV054, AHPAIT= AV060, AHSPAIT=AV064
c) When both above note are applicable, CV118=0
d) When none of above notes is applicable the following equations shall be used.
AHGOT = (AV054+AV057)/2, AHPAIT= (AV060+AV062)/2, AHSPAIT=(AV064+AV066)/2
**Process TAGS are not available in the database the same to be checked & incorporated at site
along with relevant calculation.
-----------------------------------------------------------------------------------------------------------------------CV119
Note: The above equation is valid when contact status of SZ524 AND SZ525 are open.
-------------------------------------------------------------------------------------------------------------------**CV120
= Fn(AV060 + AV062) / 2
= Fn(AV064 + AV066) / 2
Where
AV060
AV062
AV064
AV066
CV004
AH A PA inlet temperature**
AH B PA inlet temperature**
AH A SA inlet temperature
AH B SA inlet temperature
Fraction of air that is primary air
Revision 1
Project :
Language :
En
Page :
41
YN1G176789-D
**Process TAGS are not available in the database the same to be checked & incorporated at site
along with relevant calculation.
---------------------------------------------------------------------------------------------------------------------**CV122
-----------------------------------------------------------------------------------------------------------------------CV203
Ton of moisture per ton of dry air (i.e., specific humidity of dry air)
=(KN002* PSAT/100)/(1.608*(KN003-KN002 * PSAT/100))
-Specific humidity is a function of relative humidity, temperature and atmospheric
pressure
Where
KN002 Relative humidity per cent
KN003 Atmospheric pressure kg/sc
PSAT Saturation pressure of water vapor at
ambient temp
PSAT f ((AV140+AV167) / 2)
AV140 FD Fan A discharge temp
AV167 FD Fan B discharge temp
Note:
a) When contact status of SZ506 AND SZ507 are open the above equation is valid
b) When contact status of SZ506 is open AND SZ507 is close, CV203=Fn (KN002, AV140)
c) When contact status of SZ506 is close AND SZ507 is open, CV203=Fn (KN002, AV167)
----------------------------------------------------------------------------------------------------------------------CV164
Heat loss due to moisture in air
=(CV204+CV205)*(CV203*0.477*(TG -TEMP)
KCAL/KG
Where
Revision 1
Project :
Language :
En
Page :
42
YN1G176789-D
gas
---------------------------------------------------------------------------------------------------------------------CV123
Revision 1
Project :
Language :
Page :
En
43
YN1G176789-D
----------------------------------------------------------------------------------------------------------------------------CV127
Reference Gross turbine heat rate
=Fn(AV049)
-See curve
KCAL KWH
Where
AV049 Gross generation
----------------------------------------------------------------------------------------------------------------------CV166
---------------------------------------------------------------------------------------------------------------------CV133
Adjusted gross turbine heat rate
=CV166*(1-CV128/100.) * (1. + CV129/100.) * (1. + CV130/100.) * (1. +
CV131/100.)* (1+CV167/100)
KCAL/KWH
Where
CV128 Heat rate deviation main steam temperature
CV129 Heat rate deviation reheat steam temp
CV130 Heat rate deviation main steam press
CV131 Heat rate deviation condenser vacuum
CV167 Heat rate deviation Reheater press drop
CV166 Gross turbine heat rate
-----------------------------------------------------------------------------------------------------------------------CV200
=Fn((AV101+AV102),AV103+KN003)
Where
AV101 Reheater outlet steam temp left
AV102 Reheater outlet steam temp right
AV103 Reheater outlet steam pressure
KN003 Atmospheric pressure
Revision 1
Project :
Language :
Page :
En
YN1G176789-D
44
----------------------------------------------------------------------------------------------------------------------CV138
Where
AV001 Feedwater flow
KN001 Blowdown flow
CV199 Superheater outlet enthalpy
CV008 Superheater spray water enthalpy
Economiser inlet enthalpy
AV076 Superheat spray water flow
CV035 Cold reheat flow
CV200 Reheater outlet enthalpy
CV091 HP turbine exhaust enthalpy
AV013 Reheat spray flow
KN032 Blow down enthalpy
KN013 Heating value of coal
AV104 Mill A coal flow
AV105 Mill B coal flow
AV106 Mill C coal flow
AV107 Mill D coal flow
AV108 Mill E coal flow
AV109 Mill F coal flow
AV110 Heavy oil supply flow
AV111 Heavy oil return flow
KN026 Heating value of fuel oil
KN033 Heat added other than chemical
-----------------------------------------------------------------------------------------------------------------------CV137
=(CV123+CV138) / 2
Where
CV123 Boiler efficiency by heat loss method
CV138 Boiler efficiency by input/output method
-----------------------------------------------------------------------------------------------------------------------CV136
-----------------------------------------------------------------------------------------------------------------------CV169
Net unit heat rate
=CV136 * AV049/CV124
KCAL/KWH
Revision 1
Project :
Language :
En
Page :
45
YN1G176789-D
Where
CV136 Gross unit heat rate
AV049 Gross generation
CV124 Net generation
----------------------------------------------------------------------------------------------------------------------CV152
Circulating water velocity in condenser B tubes
=1/2((AV120/KN021*KN036*3600)+( AV120/KN021*KN058*3600)) M/S
Where
AV120 Condenser flow, left
KN021 Condenser cross section area per tube
KN036 Number of tubes condenser B first pass
3600 Conversion from m/hr to m/s
KN058 Number of tubes condenser B Second pass
-----------------------------------------------------------------------------------------------------------------------CV153
-----------------------------------------------------------------------------------------------------------------------CV154
-----------------------------------------------------------------------------------------------------------------------CV155
Condenser B terminal temperature difference
=CV066 - AV095
DEG C
Where
CV066 Condenser saturation temp
AV095 Condenser B outlet temp
Note: When HZ503 contact status closed, CV155=0.
-----------------------------------------------------------------------------------------------------------------------CV156
=AV095-AV092
Where
AV095 Condenser B outlet temp
AV092 Cooling water temp
Revision 1
Project :
Language :
Page :
En
46
YN1G176789-D
-----------------------------------------------------------------------------------------------------------------------CV160
Where
AV122 Condensate suction pump temp
----------------------------------------------------------------------------------------------------------------------CV161
-----------------------------------------------------------------------------------------------------------------------CV197
pass of
Revision 1
Project :
Language :
En
Page :
YN1G176789-D
47
Where
CV162 Condenser B actual heat transfer rate
CV154 Condenser B basic heat transfer rate
corrected.
----------------------------------------------------------------------------------------------------------------------CV170
Boiler efficiency deviation between heat loss and input/output method
=ABS (CV123-CV138)
-Percentage deviation of heat loss method and input/output method
%
Where
CV123 Boiler efficiency by heat loss method
CV138 Boiler efficiency by input/output method
ABS
Absolute value
-----------------------------------------------------------------------------------------------------------------------CV171
Where
AV040 Heater 1 extraction pressure
KN003 Atmospheric pressure
-----------------------------------------------------------------------------------------------------------------------CV172
Deg C
Where
CV171 Heater 1 saturation temp
AV037 Heater 1A condensate temp out
-----------------------------------------------------------------------------------------------------------------------CV173
Deg C
Where
CV171 Heater 1 saturation temp
AV121 Heater 1B condensate temp out
Note : When contact status of CZ512 and CZ513 are closed, CV162=0.
----------------------------------------------------------------------------------------------------------------------CV278
Fn(AV049)
Where
AV049 Gross generation
----------------------------------------------------------------------------------------------------------------------CV174
-See curve
Revision 1
Project :
Language :
Page :
En
48
YN1G176789-D
=Fn(AV049)
Where
AV049 Gross generation
-----------------------------------------------------------------------------------------------------------------------CV175
----------------------------------------------------------------------------------------------------------------------CV198
=AV069-AV071
Where
AV069 HPH-5 drain temperature
AV071 HPH-5 CNDS in temp
Note: When contact status of XZ503 OR FZ507 OR FZ506 are closed, CV198 = 0
----------------------------------------------------------------------------------------------------------------------CV201
Ton of dry air leakage in AH A per the quantity of wet flue gas per ton of fuel fired
entering AH A = (54.88*KN006/100 + 20.56 * KN007/100 + 129.25 * KN008/10016.29 * KN009/100+4.90 * KN010/100) * (
KN037/100/((1-4.78*KN037/100)(AV053/100)*(1-4.78*AV053/100))
Where
KN037 Entered value = per cent oxygen by volume
for gas at AH A outlet
AV053 Per cent oxygen by volume for gas at AH
inlet
KN006 Coal content carbon per cent
KN007 Coal content sulper per cent
KN008 Coal content hydrogen per cent
KN009 Coal content oxygen per cent
KN010 Coal content nitrogen per cent
Revision 1
CV202
Project :
Language :
En
Page :
49
YN1G176789-D
Ton of dry air leakage in AH B per the quantity of wet flue gas per ton of fuel fired
entering AH B
= (( 54.88 * KN006/100 + 20.56 * KN007/100 + 129.25 * KN008/100 16.29 *
KN009/100 + 4.90 * KN010/100) * (KN038/100) / ((1-4.78 * KN038/100)
(AV053/100) * (1-.78 * AV053/100))
Where
KN038 Entered value = per cent oxygen by volume
for gas at AH B outlet
AV053 Percent oxygen by volume for gas at AH
inlet
KN006 Coal content carbon per cent
KN007 Coal content sulfur per cent
KN008 Coal content hydrogen per cent
KN009 Coal content oxygen per cent
KN010 Coal content nitrogen per cent
Ton of wet air leakage in AH A per the quantity of wet flue gas per ton of fuel fired
entering AH A =CV201*(1+CV203)
T
Where
CV201 Ton of dry air leakage in AH A per the
quantity of wet flue gas per ton of fuel fired entering
AH A
CV203 Ton of moisture per ton of dry air (i.e.,
specific humidity per ton)
-----------------------------------------------------------------------------------------------------------------------CV207
Ton of wet air leakage in AH B per the quantity of wet flue gas per ton of fuel fired
entering AH B =CV202*(1+CV203)
T
Where
CV202 Ton of dry air leakage in AH B per the
quantity of wet flue gas per ton of fuel fired entering
AH B
CV203 Ton of moisture per ton of dry air (I.e.,
specific humidity per ton)
-----------------------------------------------------------------------------------------------------------------------CV208
Revision 1
Project :
Language :
En
Page :
50
YN1G176789-D
-----------------------------------------------------------------------------------------------------------------------CV210
Where
CV206 Ton of wet air leakage in AH A per the
quantity of wet flue gas per ton of fuel fired entering
AH A
CV209 Ton of wet gas at AH inlet per ton of fuel
fired.
----------------------------------------------------------------------------------------------------------------------CV211
-----------------------------------------------------------------------------------------------------------------------CV266
Note :
1) The above equation is applicable when the contact status of SP573 or SS556 and SS558,
SP574are on and SZ506 and SZ507 are open.
2) When the contacts of SZ506, SZ507 are open and SP573or SS556 is on, & SP574 and SS558
off, use the following equation
CV266=AV165-37 * (AV083+AV084)2/(KN055)2 * (AV064+273.2)/(KN044+273.2)
Revision 1
Project :
Language :
En
Page :
51
YN1G176789-D
3) When the contacts of SZ506 is open and SP573 or SS556 and SP574 or SS558 are on, and
SZ507 is closed, use the following equation
CV266=AV165-37 * (AV083)2/(KN055)2 * (AV064+273.2)/(KN044+273.2)
4) When the contacts of SP573 or SS556 is on and SZ506 is open, and SP574 and SS558 are off
and SZ507 is closed, use the following equation
CV266=AV165-37 * (AV083+AV084)2/(KN055)2 * (AV064+273.2)/(KN044+273.2)
5) When the contacts of SZ507 is open, SP573 or SS556 and SP574 or SS558 are on, and SZ506 is
closed, use the following equation
CV266=AV166-37 * (AV083)2/(KN055)2 * (AV064+273.2)/(KN044+273.2)
6) When the contacts of SZ507 is open, and SP573 or SS556 is on, and SZ506 is closed & SP574
and SS558 are off, use the following equation
CV266=AV166-37 * (AV083+AV084)2/(KN055)2 * (AV064+273.2)/(KN044+273.2)
7) When the contact status of SP573 is closed, CV266=0.
-----------------------------------------------------------------------------------------------------------------------**CV212 Fraction of the total air leakage of AH A coming from primary of air side
= { ((( AV155 AV156) * (AV064 + 273.2)) / ((CV266 AV156) * (AV060 + 273.2))) 1/2 /
{ 1 + ((( AV155 AV156) * (AV064 + 273.2)) / ((CV266 AV156) * (AV060 + 273.2))) 1/2 }}
Where
AV060 AH A PA in temp**
AV064 AH A sec air in temp
AV155 AH A PA in press
AV156 AH A gas out press
CV266 AH A sec air in press
Note : When the contact status of SP573 and SS556 is off, CV212=0.
**Process TAGS are not available in the database the same to be checked & incorporated at site
along with relevant calculation.
-----------------------------------------------------------------------------------------------------------------------CV213
Fraction of the total air leakage of AH A coming from secondary air side
=1-CV212
Where
CV212 Fraction of AH A total air leakage coming
from primary air side
Revision 1
Project :
Language :
Page :
En
52
YN1G176789-D
-----------------------------------------------------------------------------------------------------------------------CV214
Fraction of the total air leakage of AH B coming from primary air side
= { ((( AV158 AV157) * (AV066 + 273.2)) / (( CV267 AV157) * (AV062 + 273.2))) 1/2 } / { 1 +
((( AV158 AV157) * (AV066 + 273.2)) / (( CV267 AV157) * (AV062 + 273.2))) 1/2 }}
Where
AV062
AV066
AV157
AV158
CV267
AHA B PA in temp**
AH B sec air in temp
AH B gas out press
AH B PA in press
AH B sec air in press
Fraction of the total air leakage of AH B coming from secondary air side
=1-CV214
Where
CV214 Fraction of the total air leakage of AH B
coming from primary air side
Revision 1
**CV217
Project :
Language :
En
Page :
53
YN1G176789-D
AH B gas out temperature corrected for no leakage =CV214*CV211*0.242*(AV057AV062)+/100*KN025 + CV215*CV211*0.242 (AV057-AV066)/(100*KN025) + AV057
DEG C
Where
CV214 Fraction of the total air leakage of AH B
coming from primary air side
CV215 Fraction of the total air leakage of AH B
coming from secondary air side
CV211 Percentage air leakage of AH A
0.242 Mean specific heat of air between design air
inlet and gas outlet temp
KN025 Sp heat of flue gas
AV057 AH B gas out temperature
AV062 AH B PA in temperature **
AV066 AH B sec air in temperature
Revision 1
Project :
Language :
En
Page :
54
YN1G176789-D
Notes :
1) The above equation is applicable when the contact status of SP573 or SS556 and SP574 or
SS558 are on.
2) When the contact status of SP573 SS556 is on and the contact status of SP574 and SS558 is of
use the following
equation for CV220.
CV220=(AV149-AV060)/(AV059-AV060)
3) When the contact status of SP573 and SS556 is off and the contact status of SP574 or SS558 is
on, use the following equation
CV220=(AV149-AV062)/(AV061-AV062)
4) When the contact status of SS576 is off, CV220=0.
**Process TAGS are not available in the database the same to be checked & incorporated at site
along with relevant calculation.
----------------------------------------------------------------------------------------------------------------------**CV221
Notes :
1) The above equation is applicable when the contact status of SP573 or SS556 and SP574 or
SS558 are on.
2) When the contact status of SP573 SS556 is on and the contact status of SP574 and SS558 is of
use the following
equation for CV220.
CV221=(AV150-AV060)/(AV059-AV060)
3) When the contact status of SP573 and SS556 is off and the contact status of SP574 or SS558 is
on, use the following equation
CV221=(AV150-AV062)/(AV061-AV062)
Revision 1
Project :
Language :
En
Page :
55
YN1G176789-D
Notes :
1) The above equation is applicable when the contact status of SP573 or SS556 and SP574 or
SS558 are on.
2) When the contact status of SP573 SS556 is on and the contact status of SP574 and SS558 is of
use the following
equation for CV220.
CV222=(AV151-AV060)/(AV059-AV060)
3) When the contact status of SP573 and SS556 is off and the contact status of SP574 or SS558 is
on, use the following equation
CV222=(AV151-AV062)/(AV061-AV062)
4) When the contact status of SS580 is off, CV222=0.
**Process TAGS are not available in the database the same to be checked & incorporated at site
along with relevant calculation.
-----------------------------------------------------------------------------------------------------------------------**CV223
Notes :
1) The above equation is applicable when the contact status of SP573 or SS556 and SP574 or
SS558 are on.
2) When the contact status of SP573 SS556 is on and the contact status of SP574 and SS558 is of
use the following
equation for CV223.
CV223=(AV152-AV060)/(AV059-AV060)
3) When the contact status of SP573 and SS556 is off and the contact status of SP574 or SS558 is
on, use the following equation
Revision 1
Project :
Language :
En
Page :
56
YN1G176789-D
CV223=(AV152-AV062)/(AV061-AV062)
4) When the contact status of SS582 is off, CV223=0.
**Process TAGS are not available in the database the same to be checked & incorporated at site
along with relevant calculation.
-----------------------------------------------------------------------------------------------------------------------**CV224
Notes :
1) The above equation is applicable when the contact status of SP573 or SS556 and SP574 or
SS558 are on.
2) When the contact status of SP573 SS556 is on and the contact status of SP574 and SS558 is of
use the following
equation for CV220.
CV224=(AV153-AV060)/(AV059-AV060)
3) When the contact status of SP573 and SS556 is off and the contact status of SP574 or SS558 is
on, use the following equation
CV224=(AV153-AV062)/(AV061-AV062)
4) When the contact status of SS584 is off, CV224=0.
**Process TAGS are not available in the database the same to be checked & incorporated at site
along with relevant calculation.
-----------------------------------------------------------------------------------------------------------------------**CV225
Notes :
1) The above equation is applicable when the contact status of SP573 or SS556 and SP574 or
SS558 are on.
2) When the contact status of SP573 SS556 is on and the contact status of SP574 and SS558 is of
use the following
equation for CV220.
CV225=(AV154-AV060)/(AV059-AV060)
Revision 1
Project :
Language :
En
Page :
57
YN1G176789-D
3) When the contact status of SP573 and SS556 is off and the contact status of SP574 or SS558 is
on, use the following equation
CV225=(AV154-AV062)/(AV061-AV062)
4) When the contact status of SS586 is off, CV225=0.
**Process TAGS are not available in the database the same to be checked & incorporated at site
along with relevant calculation.
-----------------------------------------------------------------------------------------------------------------------CV226
Where
CV220 Fraction of mill A primary air which
in AH
CV221 Fraction of mill B primary air which
in AH
CV222 Fraction of mill C primary air
heated in AH
CV223 Fraction of mill D primary air
heated in AH
CV224 Fraction of mill E primary air
heated in AH
CV225 Fraction of mill F primary air which
in AH
AV082 Mill A PA flow
AV077 Mill B PA flow
AV078 Mill C PA flow
AV079 Mill D PA flow
AV080 Mill E PA flow
AV081 Mill F PA flow
----------------------------------------------------------------------------------------------------------------------**CV229
is heated
is heated
which is
which is
which is
is heated
Test X ratio AH A
=(AV055-CV216) * (1-CV004*CV228) / (CV004*CV226 * (AV059-AV060) + CV005 *
(AV063-AV064))
-This is found as the ratio of heat capacity of the total air passing through the air
heater to the heat capacity of the gas passing through the heater.
Where
AV055 AH A gas in temp
CV216 AH A gas out temp corrected for no
leakage
CV004 Fraction of air that is primary air
CV228 Fraction of total PA which is cold
PA=1-CV266
CV226 Fraction of total PA which is hot PA
CV005 Fraction of air that is secondary air
AV059 AH A PA out temp**
AV060 AH A PA in temp**
AV063 AH A sec air out temp
Revision 1
Project :
Language :
En
Page :
58
YN1G176789-D
Test X ratio AH B
=(AV058-CV217) * (1-CV004*CV228) / (CV004*CV226 * (AV061-AV062) + CV005 *
(AV065-AV066))
Where
AV058 AH B gas in temp
CV217 AH B gas out temp corrected for no leakage
CV004
CV228
CV226
CV226
CV005
AV061
AV062
AV065
AV066
**Process TAGS are not available in the database the same to be checked & incorporated at site
along with relevant calculation.
-----------------------------------------------------------------------------------------------------------------------CV233
T/HR
-----------------------------------------------------------------------------------------------------------------------*CV231
Revision 1
Project :
Language :
En
Page :
59
YN1G176789-D
Revision 1
Project :
Language :
KN040
KN041
KN042
KN043
KN044
AV062
AV066
AV157
AV158
CV267
En
Page :
60
YN1G176789-D
Notes :
1) The above equation is applicable when the contact status of SP573 SS556 and SP574 or SS558
are on
2) When the contact status of SP573 or SS556 is on and the contact status of SP574 and SS558 is
off use the following equation
CV232 = ( CV214 * CV211 * CV209 * CV233 / (KN039)) * ((( KN040 KN042) /
(AV158 AV157)) * ((AV062 + 273.2) + (KN041 + 273.2))) 1/2
+ ( CV215 * CV211 * CV209 * CV233 / (KN039)) * ((( KN043 KN042) /
(( CV267 AV157 )) * (( AV066 + 273.2) + ( KN044 + 273.2 ))) 1/2
* To be checked at site
-----------------------------------------------------------------------------------------------------------------------CV234
Gas side pressure loss of AH A corrected for deviation from design flow and
temperature
CV234 = AV159*(KN039)2 * ((KN045+273.2) + (KN046 + 273.2)) / ((CV209 *
CV233/2)2 * ((AV055 + 273.2) + (AV054 + 273.2)))
MMWCL
Where
AV159 Gas pressure drop across AH A
KN039 Design rated value of wet gas flow through
each air heater
KN045 AH entering gas temp in design rated
condition
KN046 AH exit gas temp in design rated
condition
CV209 Ton of wet gas at AH inlet per ton of fuel
fired
CV233 Ton of coal fired per hour
AV055 AH A gas in temp
AV054 AH A gas out temp
Note :
1) The above equation is applicable when the contact status of SP573 SS556 and SP574 or SS558
are on
2) When the contact status of SP573 or SS556 is on and the contact status of SP574 and SS558 is
off use the following equation
Revision 1
Project :
Language :
En
Page :
61
YN1G176789-D
Gas side pressure loss of AH B corrected for deviation from design flow and
temperature
CV235 = AV160*(KN039)2 * ((KN045+273.2) + (KN046 + 273.2)) / ((CV209 *
CV233/2)2 * ((AV058 + 273.2) + (AV057 + 273.2)))
MMWCL
Where
AV160 Gas pressure drop across AH B
KN039 Design rated value of wet gas flow through
each air heater
KN045 AH entering gas temp in design rated
condition
KN046 AH exit gas temp in design rated condition
CV209
fired
CV233
AV057
AV058
Note :
1) The above equation is applicable when the contact status of SP573 SS556 and SP574 or SS558
are on
2) When the contact status of SP573 or SS556 is on and the contact status of SP574 and SS558 is
off use the following equation
CV235 = AV160 * (KN045)2 * ((KN045+273.2) + (KN046 + 273.2)) / ((CV209 *
CV233/2)2 * ((AV058 + 273.2) + (AV057 + 273.2)))
MMWCL
-----------------------------------------------------------------------------------------------------------------------CV238
PA flow through AH A
T/HR
=(AV077+AV078 + AV079 + AV080+ AV081+AV082) * CV226/2
Where
AV077
AV078
AV079
AV080
AV081
AV082
CV226
Mill B PA flow
Mill C PA flow
Mill D PA flow
Mill E A flow
Mill F PA flow
Mill A PA flow
Fraction of total PA which is hot PA
Note :
1) The above equation is applicable when the contact status of SP573 & SS556 and SP574 & SS558
are on
2) When the contact status of SP573 & SS556 are on and the contact status of SP574 or SS558 are
off, use the following equation
(AV077+AV078 + AV079 + AV080+ AV081+AV082) * CV226
3) When the contact status of SP573 or SS556 is off, CV238=0.
Revision 1
Project :
Language :
Page :
En
62
YN1G176789-D
----------------------------------------------------------------------------------------------------------------------**CV236
Primary air side pressure loss of AH A corrected for deviation from design flow and
temperatures =AV161* (KN047)2 * ((KN041 + 273.2) + ( KN038 + 273.2)) /
((CV238)2 * ((AV060 + 273.2) + (AV059 + 273.21)))
MMWCL
Where
AV161
KN047
heater
KN041
KN048
CV238
AV060
AV059
**Process TAGS are not available in the database the same to be checked & incorporated at site
along with relevant calculation.
-----------------------------------------------------------------------------------------------------------------------CV239
PA flow through AH B
T/HR
=(AV077+AV078 + AV079 + AV080+ AV081+AV082) * CV226/2
Where
AV077
AV078
AV079
AV080
AV081
AV082
CV226
Mill B PA flow
Mill C PA flow
Mill D PA flow
Mill E PA flow
Mill F PA flow
Mill A PA flow
Fraction of total PA which is hot PA
Note :
1) The above equation is applicable when the contact status of SP573 & SS556 and SP574 & SS558
are on
2) When the contact status of SP573 & SS556 are on and the contact status of SP574 or SS558 are
off, use the following equation
(AV077+AV078 + AV079 + AV080+ AV081+AV082) * CV226
3) When the contact status of SS598 or SS555 is off, CV239=0.
----------------------------------------------------------------------------------------------------------------------**CV237
Primary air side pressure loss of AH B corrected for deviation from design flow and
temperatures =AV162* (KN047)2 * ((KN041 + 273.2) + KN048 + 273.2)) /
(CV239)2 * ((AV062 + 273.2) + (AV061 + 273.21)
MMWCL
Where
AV162
KN047
heater
KN041
KN048
CV239
AV062
Revision 1
Project :
Language :
En
Page :
63
YN1G176789-D
Secondary air side pressure loss of AH A corrected for deviation from design flow and
temperatures =AV163* (KN049)2 * ((KN044 + 273.2) + ( KN050 + 273.2)) /
((AV083)2 * ((AV064 + 273.2) + (AV063 + 273.21)))
MMWCL
Where
AV163
KN049
KN044
KN050
AV083
AV084
AV064
AV063
Notes :
1) The above equation is applicable when the contact status of SP573 & SS556 and SP574 & SS558
are on
2) When the contact status of SP573 & SS556 are on, and the contact status of SP574 or SS558 are
off, use the following equation
AV163* (KN049)2 * ((KN044 + 273.2) + (KN050 + 273.2)) / (AV083) 2 * ((AV064 + 273.2) + (AV063 +
273.21))
3) When the contact status of SP573 or SS556 is off, CV240=0.
**Process TAGS are not available in the database the same to be checked & incorporated at site
along with relevant calculation.
-----------------------------------------------------------------------------------------------------------------------**CV241
Secondary air side pressure loss of AH B corrected for deviation from design flow
and temperatures
=AV164* (KN049)2 * ((KN044 + 273.2) + (KN050 + 273.2)) /
2
((AV084) * ((AV066 + 273.2) + (AV065 + 273.21)))
MMWCL
Where
AV164
KN049
KN044
KN050
AV083
AV084
AV066
AV065
Notes:
1) The above equation is applicable when the contact status of SP573 & SS556 and SP574 & SS558
are on
2) When the contact status of SP573 or SS556 is off and the contact status of SP574 & SS558 is on,
use the following equation
AV164* (KN049)2 * ((KN044 + 273.2) + (KN050 + 273.2)) / ((AV084) 2 * ((AV066 + 273.2) + (AV065 +
273.21)))
Revision 1
Project :
Language :
En
Page :
64
YN1G176789-D
Corrected gas temperature leaving AH A for deviation from design entering air
temperature
=KN044 * (AV055 - AV054) + AV055 * ((AV054-(CV004 * AV060 +
CV005 * AV064)) / (AV055- (CV004 * AV060 + CV005 * AV064))
DEG C
Where
KN044
AV055
AV054
AV060
AV064
CV004
CV005
Corrected gas temperature leaving AH B for deviation from design entering air
temperature
=KN044 * (AV058 - AV057) + AV058 * ((AV057-(CV004 * AV062+
CV005 * AV066)) / (AV058- (CV004 * AV062 + CV005 * AV066))
DEG C
Where
KN044
AV058
AV057
AV062
AV066
CV004
CV005
---------------------------------------------------------------------------------------------------------------------CV244
Corrected gas temperature leaving AH A for deviation from design entering gas
temperature
=(KN045*((AV054-(CV004*AV060 + CV005 * AV064)) + (CV004 *
AV060 + CV005 * AV064) * (AV055 - AV054))) / (AV055-(CV004 * AV060 + CV005 *
AV064))
DEG C
Where
KN045
AV054
AV055
AV060
AV064
CV004
Revision 1
Project :
Language :
En
Page :
65
YN1G176789-D
Corrected gas temperature leaving AH B for deviation from design entering gas
temperature
=(KN045*((AV057-(CV004*AV062 + CV005 * AV066)) + (CV004 *
AV062 + CV005 * AV066) * (AV058 - AV057)) )/ (AV058-(CV004 * AV062 + CV005 *
AV066))
DEG C
Where
KN045
AV057
AV058
AV062
AV066
CV004
CV005
Corrected gas temp leaving air heater A for deviation from design X ratio
=AV054 * CV248
Deg C
Where
AV054 AH A gas out temperature
CV248 Correction factor for gas out temp of AH A as
a function of the test X ratio
Revision 1
Project :
Language :
En
Page :
66
YN1G176789-D
----------------------------------------------------------------------------------------------------------------------CV247
Corrected gas temp leaving air heater B for deviation from design X ratio
=AV057 * CV249
Deg C
Where
AV057 AH B gas out temperature
CV248 Correction factor for gas out temp of AH B
as a function of the test X ratio
Note : When contact status of SP574 or SS558 is
off, CV247=0.
-----------------------------------------------------------------------------------------------------------------------CV252
Correction factor for gas temp of AH A for deviation from design entering flue gas
flow
=Fn(CV209 * CV233/2)
-This is found as function of flue gas flow through AH A
Where
CV209 Ton of wet gas at AH inlet per ton of fuel
fired
CV233 Ton of fuel fired per hour
Notes :
1) The above equation is applicable when the contact status of SP573 or SS556 and SP574 or
SS558 are on.
2) When the contact status of SP573 or SS556 is on and the contact status of SP574 or SS558 is off
use the following equation
CV252=Fn(CV209*CV233)
3) When the contact status of SP573 or SS556 is off, CV252=0.
----------------------------------------------------------------------------------------------------------------------CV250
Corrected gas temperature leaving air heater A for deviation from design entering flue
gas flow
=AV054 * CV252
Deg C
Where
AV054 AH A gas out temp
CV252 Correction factor for gas out temp of AH A
for deviation from design entering flue gas flow
Correction factor for gas out temp of AH B for deviation from design entering flue gas
flow
=Fn(CV209 * CV233/2)
-This is found as a function of flue gas flow through AH B
Where
CV209 Ton of wet gas at AH inlet per ton of fuel
fired
CV233 Ton of fuel fired per hour
Notes :
Revision 1
Project :
Language :
En
Page :
67
YN1G176789-D
1) The above equation is applicable when the contact status of SP573 or SS556 and SP574 or
SS558 are on
2) When the contact status of SP573 or SS556 is off and the contact status of SP574 or SS558 is on
use the following equation
CV253=Fn(CV209*CV233)
3) When the contact status of SP574 or SS558 is off, CV253=0.
---------------------------------------------------------------------------------------------------------------------CV251
Corrected gas temp leaving air heater B for deviation from design entering flue gas
flow
=AV057 * CV253
DEG C
Where
AV057 AH B gas out temp
CV253 Correction factor for gas out temp of AH B
for deviation from design entering flue gas flow
Note : When the contact status of SP574 or SS558
is off, CV251=0.
-----------------------------------------------------------------------------------------------------------------------CV254
DEG C
Where
CV242 Corrected gas temp leaving
deviation from design entering air temp
CV244 Corrected gas temp leaving
deviation from design entering gas temp
CV246 Corrected gas temp leaving
deviation from design X ratio
CV250 Corrected gas temp leaving
deviation from entering flue gas flow
AV054 AH A gas out temp
AH A for
AH A for
AH A for
AH A for
DEG C
Where
CV243 Corrected gas temp leaving
deviation from design entering air temp
CV245 Corrected gas temp leaving
deviation from design entering gas temp
CV247 Corrected gas temp leaving
deviation from design X ratio
CV251 Corrected gas temp leaving
deviation from entering flue gas flow
AV057 AH B gas out temp
Note: When the contact status of SP574 or SS558 is off, CV255=0.
-----------------------------------------------------------------------------------------------------------------------
AH B for
AH B for
AH B for
AH B for
Revision 1
CV256
Project :
Language :
En
Page :
68
YN1G176789-D
Where
CV231 Corrected percent air leakage of AH A for
deviation from design pressure differential and from
design air temperature
KN051 Design percent leakage of each air heater at
rated condition
-----------------------------------------------------------------------------------------------------------------------CV257
Where
CV232 Corrected percent air leakage of AH Bfor
deviation from design pressure differential and from
design air temperature
KN051 Design percent leakage of each air heater at
rated condition
-----------------------------------------------------------------------------------------------------------------------CV258
Deviation of corrected exit gas temperature of AH A from design value of exit gas
temperature
=CV254-KN046
Where
CV254 Totally corrected gas temperature leaving
AH A
KN046 AH exit gas temp in design condition
Deviation of corrected exit gas temperature of AH B from design value of exit gas
temperature
=CV255-KN046
Where
CV255 Totally corrected gas temperature leaving
AH B
KN046 AH exit gas temp in design condition
AH A gas side pressure loss (corrected for deviation from design flow and temp)
expressed as a percentage of design gas side press loss
=(CV234/KN052) * 100%
Where
CV234 Gas side press loss of AH A corrected for
deviation from design flow and temperatures
KN052 Design gas side pressure loss of AH
Revision 1
Project :
Language :
En
Page :
69
YN1G176789-D
-----------------------------------------------------------------------------------------------------------------------CV261
AH B gas side pressure loss (corrected for deviation from design flow and temp)
expressed as a percentage of design gas side press loss
=(CV235/KN052) * 100 %
Where
CV235 Gas side press loss of AH B corrected for
deviation from design flow and temperatures
KN052 Design gas side pressure loss of AH A
----------------------------------------------------------------------------------------------------------------------CV262
AH A PA side pressure loss (corrected for deviation from design flow and
temperature) expressed as a percentage of the design rated value of PA side
pressure loss =(CV236/KN053) *100 %
Where
CV236 Corrected PA side press loss of AH A
KN053 Design PA side press loss of AH
-----------------------------------------------------------------------------------------------------------------------CV263
AH B PA side pressure loss (corrected for deviation from design flow and
temperature) expressed as a percentage of the design rated value of PA side
pressure loss =(CV237/KN053) *100 %
Where
CV237 Corrected PA side press loss of AH A
KN053 Design PA side press loss of AH
---------------------------------------------------------------------------------------------------------------------CV264
AH A sec air side pressure loss (corrected for deviation from design flow and
temperature) expressed as a percentage of the design pressure loss
=(CV240/KN053 *100 %
Where
CV240 Corrected sec air side press loss of AH A
KN053 Design sec air side press loss of AH
---------------------------------------------------------------------------------------------------------------------CV265
AH B sec air side pressure loss (corrected for deviation from design flow and
temperature) expressed as a percentage of the design pressure loss
=(CV241/KN054) *100 %
Where
CV241 Corrected sec air side press loss of AH B
KN054 Design sec air side press loss of AH
---------------------------------------------------------------------------------------------------------------------CV274
Revision 1
Project :
Language :
En
Page :
70
YN1G176789-D
-----------------------------------------------------------------------------------------------------------------------CV276
---------------------------------------------------------------------------------------------------------------------CV277
Temperature deviation from design heater 1B
=CV275-AV121 DEG C
Where
CV275 Design temperature heater 1B condensate
outlet
AV121 LPH 1B CNDS temp out
---------------------------------------------------------------------------------------------------------------------
Revision 1
Project :
Language :
En
Page :
71
YN1G176789-D
Class I calculations:
Class I calculations will be carried out in the FIX process database. Appropriate calculation blocks will be
employed in the database for Class I calculations. Calculation results will be displayed on the operator
console. Calculation methodology adopted for Class I calculations is as below:
S.No.
PID
Description
Variable
name
Engg.
Unit
Calculation equation
1.
RC401
TSAT8
Deg C
F(RP001+ KN003)
2.
RC402
CRHAL
Deg C
RC401- RT011
3.
RC403
TSAT9
Deg C
F(RP004+ KN003)
4.
RC404
CRHPAL
Deg C
RC403- RT012
5.
SC401
TSAT1
Deg C
SP003+ KN003
6.
SC402
SHAPL
Deg C
F(SP026+KN003)-ST079
7.
SC403
SHAPR
Deg C
F(SP027+KN003)-ST078
8.
TC401
HPDT1
Deg C
TT012-TT013
9.
TC402
HPDT2
Deg C
TT026-TT027
10.
TC404
HPDT4
Deg C
TT024-TT029
11.
TC405
HPDT5
Deg C
TT030-TT031
12.
TC406
HPDT6
Deg C
TT032-TT033
13.
TC500
HPDT7
Deg C
TT018-TT034
14.
TC501
HPDT8
Deg C
TT042-TT043
15.
TC502
HPDT9
Deg C
TT044-TT045
16.
TC503
HPDT10
Deg C
TT062-TT063
17.
TC504
HPDT11
Deg C
TT064-TT065
Revision 1
18.
TC416
19.
TC417
20.
TC418
21.
TC419
22.
TC420
23.
TC421
24.
TC422
25.
TC423
26.
TC424
27.
TC425
28.
TC426
29.
TC427
30.
TC428
31.
TC429
32.
TC430
33.
TC431
34.
TC432
35.
TC433
Project :
Language :
Difference
Rate of change of UPR HT
TURB EXHT IN SUR MTL
TEMP.
Rate of change of HPT
EXHT LWR INR MTL
TEMP.
Rate of change of HPT
EXHT UPR RH BOWL INR
SUR MTL TEMP.
Rate of change of UPR RH
BOWL INLT INR SUR
MTL TEMP.
Rate of change of LWR RH
BOWL INLT INR SUR
MTL TEMP.
Rate of change of UPR 3rd
STG MP EXT INR MTL
TEMP.
Rate of change of LOWR
3rd STG MP EXT INR
MTL TEMP.
Rate of change of UPR 6th
STG MP EXT INR MTL
TEMP.
Rate of change of LOW 6th
STG MP EXT INR MTL
TEMP.
Rate of change of HPT
STM ADM PIPE MTL
TEMP. LEFT A
Rate of change of HPT
STM ADM PIPE MTL
TEMP. RIGHT
En
Page :
72
YN1G176789-D
RCMT3
Deg
C/Min
R(TT018)
RCMT4
Deg
C/Min
R(TT026)
RCMT5
Deg
C/Min
R(TT027)
RCMT6
Deg
C/Min
R(TT024)
RCMT7
Deg
C/Min
R(TT029)
RCMT8
Deg
C/Min
R(TT030)
RCMT10
Deg
C/Min
R(TT031)
RCMT10
Deg
C/Min
R(TT032)
RCMT11
Deg
C/Min
R(TT033)
RCMT12
Deg
C/Min
R(TT042)
RCMT13
Deg
C/Min
R(TT043)
RCMT14
Deg
C/Min
R(TT042)
RCMT15
Deg
C/Min
R(TT043)
RCMT16
Deg
C/Min
R(TT044)
RCMT17
Deg
C/Min
R(TT045)
RCMT18
Deg
C/Min
R(TT062)
RCMT19
Deg
C/Min
R(TT063)
RCMT20
Deg
R(TT064)
Revision 1
36.
TC434
37.
FC401
38.
FC402
39.
FC403
40.
FC407
41.
FC408
42.
FC409
43.
CC401
44.
CC402
45.
CC403
46.
CC404
47.
CC405
48.
CC406
49.
CC407
50.
CC408
51.
CC409
52.
SC404
53.
SC413
Project :
Language :
En
Page :
73
YN1G176789-D
C/Min
RCMT21
Deg
C/Min
R(TT065)
TSAT6
Deg C
XP005 + KN003
HP heater 6 terminal
temperature difference
HP heater 6 drain cooler
approach temperature
HP heater 5 saturation
temperature
HP heater 5 terminal
temperature difference
HP heater 5 drain cooler
approach temperature
LP heater 3 saturation
temperature
LP heater 3 terminal
temperature difference
LP heater 3 drain cooler
approach temperature
LP heater 2 saturation
temperature
LP heater 2 terminal
temperature difference
LP heater 2 drain cooler
approach temperature
TTD6A
Deg C
FC401-FT001
DCA6A
Deg C
XT012 - FT013
TSAT16
Deg C
F(XP004 + KN003)
TTD5A
Deg C
F407-FT013
DCA5A
Deg C
XT011-FT012
TSAT24
Deg C
F(XP003 + KN003)
TTD3
Deg C
CC401-CT008
DCA3
Deg C
XT010-CT007
TSAT26
Deg C
F(XP002 + KN003)
TTD2
Deg C
CC404-CT007
DCA2
Deg C
XT009-CT006
LP heater 1 saturation
temperature
LP heater 1 terminal
temperature difference
LP heater 1 drain cooler
approach temperature
Rate of change of drum
water saturation
temperature
Deviation in feed water at
HPH 6 outlet
TSAT28
Deg C
F(XP001 + KN003)
TTD1
Deg C
CC407-CT006
DCA1
Deg C
XT008-CT005
Rcdwt
Deg C
R(F(SP003+KN003))
DVFWT1
Deg C
F(GE001)-FT001
F = Function of
R= rate of change of
Revision 1
Project :
Language :
En
Page :
74
YN1G176789-D
Using the deviation of the above parameters from the design value, heat rate deviation is calculated using the
heat rate deviation curves provided by the manufacture. Summation of these deviations will give the total heat
rate deviation for the unit. Monetary loss due to heat rate deviation for each shift is then computed as follows:
Loss (in rupees) = (Net generation in MW X 1000) X (Number of hours in shift) X (Heat rate deviation in kCal /
kWh) X (Cost of coal in rupees / Kg) / (Heating value of coal in kCal / kg)
Heat rate deviation will be handled as a separate module outside of the performance calculation package.
Actual values of the process parameters will be made available to the external module. Design values for
each of the parameters as well as the heat rate deviation curves will be provided as static data in the external
module (this can be modified by users, as and when required). Using the heat rate deviation values, loss in
rupees will be computed using the above equation. Results will be made available as a separate report
through the module.
Heat rate deviation Class II tag list:
S No.
1
2
3
4
5
6
7
8
10
11
12
13
14
Tag
HD001
KD001
KD002
KD003
KD004
KD005
HD003
HD004
HD005
HD006
HD007
HD002
HD008
Description
Average power generation (in MW) for the shift
Design value of main steam temperature
Design value of main steam pressure
Design value of hot reheat temperature
Design value of hot reheat pressure
Design value of condenser vacuum
Heat rate deviation due to deviation in main steam temperature
Heat rate deviation due to deviation in main steam pressure
Heat rate deviation due to deviation in hot reheat temperature
Heat rate deviation due to deviation in hot reheat pressure
Heat rate deviation due to deviation in condenser vacuum
Net heat rate deviation
Total loss in rupees due to heat rate deviation
Calculation details:
-------------------------------------------------------------------------------------------------------------------------------------------HD001 = Avg.(GE001)
Where
HD001: Average power generation (in MW) for the shift
GE001: Gross generation
-------------------------------------------------------------------------------------------------------------------------------------------KD001 = Fn(AV049)
Revision 1
Project :
Language :
En
Page :
75
YN1G176789-D
Where
KD001: Design value of main steam temperature (obtained from manufacturers curve as a function of gross
generation)
AV049: Gross generation
-------------------------------------------------------------------------------------------------------------------------------------------KD002 = Fn(AV049)
Where
KD002: Design value of main steam pressure (obtained from manufacturers curve as a function of gross
generation)
AV049: Gross generation
-------------------------------------------------------------------------------------------------------------------------------------------KD003 = Fn(AV049)
Where
KD003: Design value of hot reheat temperature (obtained from manufacturers curve as a function of gross
generation)
AV049: Gross generation
-------------------------------------------------------------------------------------------------------------------------------------------KD004 = Fn(AV049)
Where
KD004: Design value of hot reheat pressure (obtained from manufacturers curve as a function of gross
generation)
AV049: Gross generation
-------------------------------------------------------------------------------------------------------------------------------------------KD005 = Fn(AV049)
Where
KD005: Design value of condenser vacuum (obtained from manufacturers curve as a function of gross
generation)
AV049: Gross generation
-------------------------------------------------------------------------------------------------------------------------------------------HD003 = Fn(KD001 AV072)
Where
HD003: Heat rate deviation due to deviation in main steam temperature (obtained from heat rate deviation
curve)
KD001: Design value of main steam temperature
AV072: Actual main steam temperature (process value obtained from DAS)
-------------------------------------------------------------------------------------------------------------------------------------------HD004 = Fn(KD002 AV073)
Where
HD004: Heat rate deviation due to deviation in main steam pressure (obtained from heat rate deviation curve)
KD002: Design value of main steam pressure
AV073: Actual main steam pressure (process value obtained from DAS)
--------------------------------------------------------------------------------------------------------------------------------------------
Revision 1
Project :
Language :
En
Page :
76
YN1G176789-D
Revision 1
Project :
Language :
En
Page :
77
YN1G176789-D
Frequency
Turbine speed
HPT inlet steam temperature
IPT inlet steam temperature
In addition to these, power generation will also be accumulated over one hour and one day.
All time accounting calculations will be handled in the FIX database. A combination of calculation block and
totalizer block will used for the same purpose. Results of the time accounting calculations will be made
available through the operator console (similar to Class I calculation results).
Sno
1
2
3
4
5
Tag id
TA001
TA002
TA003
TA004
TA005
TA006
TA007
TA008
Description
Generation frequency high time accumulation
Generation frequency low time accumulation
Turbine high speed running time accumulation
Turbine low speed running time accumulation
Time duration for which HP turbine
temperature is high
Time duration for which HP turbine
temperature is low
Time duration for which IP turbine
temperature is high
Time duration for which IP turbine
temperature is low
metal
Calculation
TA(GC001 > 50)
TA(GC001 < 50)
TA(TM007 > 3150)
TA(TM007 < 2850)
TA((TT068 + TT069)/2) > 552
metal
metal
metal
Notes:
1. TA() indicates the time accumulation function. This will be a database tag that will calculate the time in
seconds when the process tag is in the state specified
2. Turbine metal high and low temperature calculation will be done only when the generation is greater than
30% of the rated capacity. Else the time accumulation function will be fed a constant value of 0,
irrespective of the value of the process tag
Revision 1
Project :
Language :
En
Page :
78
YN1G176789-D
Description
Calculation
Remarks
Process
tag
MC001
Avg(CT009)
MC002
Max(CT009)
MC003
TAA(CT009)
-do-
MC004
Avg(BAD2)
MC005
Max(BAD2)
MC006
TAA(BAD2)
-do-
MC007
CEP
B
winding
temperature
is
being
indicated as a BAD point
in IO list presently.
Alternate tag will have to
be provided or the
calculation will need to be
omitted
-do-
Avg(FT017)
MC008
Max(FT017)
MC009
TAA(FT017)
-do-
10
MC010
Avg(FT018)
11
MC011
Max(FT018)
12
MC012
TAA(FT018)
-do-
13
MC013
Avg(FP019)
14
MC014
Max(FP019)
15
MC015
TAA(FP019)
-do-
16
MC016
Avg(ST080)
Revision 1
17
MC017
18
MC018
19
MC019
20
MC020
21
MC021
22
MC022
23
MC023
24
MC024
25
MC025
26
MC026
27
MC027
28
MC028
29
MC029
30
MC030
31
MC031
32
MC032
33
MC033
34
MC034
35
Project :
Language :
En
Page :
79
YN1G176789-D
Max(ST080)
-do-
TAA(ST080)
-do-
Avg(ST081)
Max(ST081)
TAA(ST081)
-do-
Avg(ST084)
Max(ST084)
TAA(ST084)
-do-
Avg(ST085)
Max(ST085)
TAA(ST085)
-do-
Avg(ST082)
Max(ST082)
TAA(ST082)
-do-
Avg(ST083)
Max(ST083)
TAA(ST083)
-do-
Avg(GE001)
MC035
36
MC036
37
MC037
Revision 1
Project :
Language :
En
range
480)
TAA(520
>
(TT068+TT069)/2
>
500)
TAA(535
>
(TT068+TT069)/2
>
520)
TAA(545
>
(TT068+TT069)/2
>
535)
TAA(565
>
(TT068+TT069)/2
>
545)
TAA((TT068+TT069)/2
> 565)
TAA(500
>
(RT013+RT016)/2
>
480)
TAA(520
>
(RT013+RT016)/2
>
500)
TAA(535
>
(RT013+RT016)/2
>
520)
TAA(545
>
(RT013+RT016)/2
>
535)
TAA(565
>
(RT013+RT016)/2
>
545)
TAA((RT013+RT016)/2
> 565)
COUNT(TZ001>2% is
SET AND TT026>350
deg c)
COUNT(TZ001>2% is
SET AND TT026<350
but > 250 deg c)
COUNT(TZ001>2% is
SET AND TT026< 250
deg c)
Time
count
from
startup to setting of
GS550
38
MC038
39
MC039
40
MC040
41
MC041
42
MC042
43
MC043
44
MC044
45
MC045
46
MC046
47
MC047
48
MC048
49
MC050
50
MC051
51
MC052
51
MC053
Page :
80
YN1G176789-D
for
main
temperature
-do-
steam
Note: The sample calculations shown above are indicated how min, max, average and time duration
calculations will be carried out. Similar calculations shall be carried out for the following tags:
T001 to GT011 (Gen wdg. Temp)
GT014 to GT016 (Gen hot gas temp)
GT017 to GT020 (Gen cold gas temp)
H2 purity GP001
Revision 1
Project :
Language :
En
Page :
81
YN1G176789-D
Revision 1
Project :
Language :
En
Page :
82
YN1G176789-D