Document Title:

Functional Design Specification


of
Class I & II Equipment Performance Calculations

Customer:

National Thermal Power Corporation Ltd.


(AGovernmentofIndiaEnterprise)

Project:

Ramagundam Super Thermal Power Station


Stage-I, (3 X 200 MW Units)
Renovation & Modernisation of DAS Package

2
1
Rev. :

2004/06/18
2004/06/07
2004/02/26

Revised as per NTPC comments


Revised as per NTPC comments
First Issue

Date :

Description :

STS
STS
SP
Prepared :

VV
VV
VV
Reviewed:

VV
VV
VV
Released :

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express
authority is strictly forbidden. ABB Ltd.

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

Page :

En

YN1G176789-D

Introduction:
This is the FDS (Functional Design Specification) document for the Plant performance calculation for
NALCO Angul. The document contains the design and calculation methodology to be used by the
performance calculation software. The calculation methodology employed here is based on the
approach adopted for performance calculation of TNEB Mettur. The performance calculation
application will be developed with a Visual Basic front end. MySQL will be used as the database for
the application. The interface to be used for reading and writing process data to the Fix32 database of
the DAS is Fix Real Time ODBC. This is a standard SQL ODBC interface available to Fix 32. A
schematic for the architecture of the performance calculation software is given below:

FIX32
OS

FIX32
Database

FIX ODBC
Product

ACCESS
ODBC
Driver

MySQL
DATABASE
(DBMS)

SQT
Block
SQD
Block
FIX 32

SQL
TASK

VB Front
End

Performance
Calculation
Application

Brief description of the solution:


The FIX ODBC product provides communication between MySQL and the FIX database. The FIX
database can be configured to communicate based on an event, a time, or a combination of both.
The FIX ODBC product consists of
SQL Task
SQL Trigger (SQT) block
SQL Data (SQD) database block.
The SQL task performs the following functions:
Executes the SQT blocks that trigger.
Retrieves process data from the SQD blocks and inserts the data into the relational database.
Selects data from the relational database and writes the data back to the FIX database.

Revision 1

Project :

Ramagundam STPS Stage-I DAS R&M

Language :

En

Page :

YN1G176789-D

The SQL Trigger block defines:


Which SQL commands in the SQL Library Table are used to manipulate data. (The SQL
commands to be executed shall be stored in the SQL library table in the MS ACCESS database)
The time or event that triggers the data transfer.
The SQL Data block defines:
The data that is collected and transferred.
The direction of the data transfer.
Communication Process:

The SQL Trigger block (SQT) triggers. The SQL task reads the SQL command name from the
SQT block.
The SQL task retrieves the associated command from the SQL Library Table.
The SQL task reads the tag names specified in the SQL command from the SQL Data block
(SQD) and reads the values associated with these tag names from the FIX database.
The SQL task executes the SQL command and inserts data into or selects data from the
relational database.
If the SQL command is a SELECT command, the retrieved data is written to the FIX tag names
defined in the SQD block

The MS ACCESS shall act as a temporary storage location. The calculations shall be performed in
the VB front end and can also be viewed. The important performance parameters shall be displayed
in the Operator stations.
Linking with the steam table routines:
Steam table routines are provided as a standard Visual Basic add-on module. The module contains
standard built-in functions that takes properties such as temperature and pressure as input
parameters and returns thermodynamic properties such as enthalpy, entropy, saturation temperature
etc.
Class II tags:
The performance calculation module uses an internal set of tags which is independent of the Fix32
process tags. An installation of the performance calculation software (signifying an instance of the
database) can handle the calculations for one unit. So each unit in the plant needs to have a separate
installation of the package. Where process tags are created in the Fix32 database for the purpose of
Class II calculations, the process tags (AVxxx) and performance tags (CVxxx) will have the
corresponding unit number as prefix.
Bad quality points: If an input value for the calculation is found to be invalid, based on the percentage
load at that time an interpolated value from the heat balance diagram will be substituted for the bad
point.
Data validity: If the calculated value is found to deviate from the nominal value by more than a
specified percentage, the calculated value shall be highlighted in red on the display screen.

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

YN1G176789-D

Analog tag list:


Analog tag list:
S.No
1.
2.

Parameter

Process tag

Class II tag

Feed water flow

(FF004 + FF007)/2

AV001

Stage I Pressure

TP005

3.

Condensate pump discharge press

4.

Ext. temperature heater 6

5.

Ext. pressure heater 6

6.

HPH 6 FW temperature In

7.

HPH 6 Drain Temperature

8.

Reheat spray flow

9.

Deaerator pressure

10.

Heater-3 Condensate outlet temperature

11.

Extraction temperature of heater 3

12.

Extraction pressure of heater 3

13.

Outlet temperature heater 2

14.

Drain temperature heater 3

15.

Heater 2 extraction temperature

16.

Heater 2 extraction pressure

17.

Outlet temperature heater 1

18.

Drain temperature heater 2

19.

LPH-1 extraction pressure

20.

Inlet temperature heater 1

21.

LPH -1 drain temp

22.

Hot reheat temperature IV inlet

23.

Hot reheat pressure IV inlet

24.

Gross generation

CP001
XT006
XP005
FT013
XT012
FF006
FP001
CT008
XT003
XP003
CT007
XT010
XT002
XP002
CT006
XT009
XP001
CT005
XT008
(RT007 + RT008)/2
(RP005 + RP006)/2
GE001

AV002
AV008
AV009
AV010
AV011
AV012
AV013
AV014
AV029
AV031
AV032
AV033
AV034
AV035
AV036
AV037
AV038
AV040
AV041
AV042
AV045
AV046
AV049

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

25.

Condenser vacuum mm Hg A

26.

Economiser outlet oxygen per cent

27.

AH A gas out temperature

28.

AH A gas in temp

29.

AH B gas out temperature

30.

AH B gas in temp

31.

AH A sec air out temp

32.

AH A secondary air in temperature

33.

AH B sec air out temp

34.

AH B secondary air in temperature

35.

HPH 5 extraction temp

36.

HPH 5 extraction pressure

37.

HPH 5 drain temp

38.

HPH 5 FW inlet temp.

39.

Main Steam Temperature after ESV

40.

Main Steam Pressure before ESV

41.

HPT exhaust temp

42.

HPT exhaust press

43.

Superheat Spray Flow

44.

Mill B PA flow

45.

Mill C PA flow

46.

Mill D PA flow

47.

Mill E PA flow

48.

Mill F PA flow

49.

Mill A PA flow

50.

Sec Air Flow Left

51.

Sec Air Flow Right

En

HP006
(WA001+WA002)/2
(ST050 + ST051 +
ST052) / 3
(ST044 + ST045 +
ST046) / 3
(ST053 + ST054 +
S0T55)/3
(ST047 + ST048 +
ST049) / 3
(ST020 + ST021 +
ST022)/3
(ST014 + ST015 +
ST016) / 3
ST024
(ST017 + ST018 +
ST019) / 3
XT005
XP004
XT011
FT012
(TT068 + TT069)/2
(TP003+TP004)/2
TT011
TP013
(FF005 + FF008)/2
SF002
SF003
SF004
SF005
SF006
SF001
SF011
SF012

Page :

YN1G176789-D
AV050
AV053
AV054
AV055
AV057
AV058
AV063
AV064
AV065
AV066
AV067
AV068
AV069
AV071
AV072
AV073
AV074
AV075
AV076
AV077
AV078
AV079
AV080
AV081
AV082
AV083
AV084

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

52.

Feedwater flow through heaters

53.

Feedwater pressure (at BFP suction)

54.

FW pressure at Econ inlet

55.

FW temperature at Econ inlet

56.

Deaerator extraction flow

57.

Condensate flow to D/A from LPH

58.

Condenser cooling water temperature

59.

Condensate flow right

60.

Condenser B outlet temp

61.

Condensate pump-A suction temp

62.

Main steam pressure after ESV

63.

SH Outlet Stm Temp (L)

64.

SH Outlet Stm Temp (R)

65.

SH Outlet Stm Pressure

66.

Reheater outlet steam temp left

67.

Reheater outlet steam temp right

68.

Reheater outlet steam pressure

69.

Mill A coal flow

70.

Mill B coal flow

71.

Mill C coal flow

72.

Mill D coal flow

73.

Mill E coal flow

74.

Mill F coal flow

75.

Heavy oil supply flow

76.

Heavy oil return flow

77.

BFP Disch to Desuperheater Temp

78.

Aux Steam Pressure

Page :

En

(FF004 + FF007)/2 +
FFOO5 + FF008
FP005
FP005
FT009
(XF001)
CF001
HT002
HF002B
CT002
CT011

(TP003+TP004)/2
ST073
ST075
(SP001 + SP002)/2
RT013
RT016
RP002
SM001
SM002
SM003
SM004
SM005
SM006
SF007
SF008
(FT005+FT006+FT007)/
3
AF002

YN1G176789-D
AV085
AV086
AV087
AV088
AV090
AV091
AV092
AV093
AV094
AV096
AV097
AV098
AV099
AV100
AV101
AV102
AV103
AV104
AV105
AV106
AV107
AV108
AV109
AV110
AV111
AV114
AV115

Revision 1

Project :

Ramagundam STPS Stage-I DAS R&M

79.

Aux Steam Temp

80.

Aux Steam Flow

81.

LPH 3 condensate inlet temp.

82.

Gland cooler 2 condensate outlet temp.

83.

Condenser flow, left

84.

Condensate pump-B suction temp

85.

Reheater inlet press

86.
87.

Measured press drop in gas path across


economiser
Econ temp outlet left of feedwater

88.

Econ temp outlet right of feedwater

89.

FD Fan A discharge temp

90.

Mill A PA inlet temp

91.

Mill B PA inlet temp

92.

Mill C PA inlet temp

93.

Mill D PA inlet temp

94.

Mill E PA inlet temp

95.

Mill F PA inlet temp

96.

AH A gas out press

97.

AH B gas outlet press

98.

Gas pressure drop across AH A

99.

Gas pressure drop across AH B

100.
101.
102.
103.

AH A Sec air press drop


AH B Sec air press drop
FD fan A Disch pressure
FD fan B Disch pressure
FD Fan B discharge temp

104.

105. Gas temp before Econ

Language :

Page :

En

AT003
MF003
CT007
CT004
HF001B
CT012
(RP001 + RP004)/2
SP014
FT010
FT011
(ST008 + ST009 +
ST010)/3
ST060
ST061
ST062
ST063
ST064
ST065
SP045
SP046
SP039
SP040
SP037
SP038
SP006
SP007
(ST011 + ST012 +
ST013)
(ST042 + ST043) / 2

YN1G176789-D
AV116
AV117
AV118
AV119
AV120
AV122
AV135
AV136
AV138
AV139
AV140
AV149
AV150
AV151
AV152
AV153
AV154
AV156
AV157
AV159
AV160
AV163
AV164
AV165
AV166
AV167
AV170

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

YN1G176789-D

Constants:
S No.
1.

Blow down flow

Description

Process Tag
KN001

2.

Relative humidity per cent

KN002

3.

Atmospheric pressure

KN003

4.

Coal content carbon per cent

KN006

5.

Coal content sulfur per cent

KN007

6.

Coal content hydrogen per cent

KN008

7.

Coal content oxygen per cent

KN009

8.

Coal content nitrogen per cent

KN010

9.

Coal content moisture

KN011

10.

Heating value of coal

KN013

11.

Heat loss refuse

KN014

12.

Heat loss radiation

KN015

13.

Heat loss unmeasured

KN016

14.

Tube metal correction factor

KN018

15.

Number of tubes in condenser A first pass

KN020

16.

Condenser cross sectional area for tube

KN021

17.

Specific heat of flue gas

KN025

18.

Specific heat of circulating water for mean temp and salinity

KN035

19.

Number of tubes in first pass of condenser B

KN036

20.

Entered value = per cent oxygen by volume for gas at AH A outlet

KN037

21.

Design rated value of wet gas flow through each air heater

KN039

22.

Design pressure AH inlet PA

KN040

23.

Design temp AH inlet PA

KN041

24.

Design press AH outlet gas

KN042

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

YN1G176789-D

25.

Design press AH inlet sec air

KN043

26.

Design temp AH inlet sec air

KN044

27.

AH entering gas temp in design rated condition

KN045

28.

AH exit gas temp in design rated condition

KN046

29.

Design rated PA flow through each air heater

KN047

30.

Design PA out temp

KN048

31.

Design rated Sec air flow of each AH

KN049

32.

Design rated sec air outlet temp

KN050

33.

Design percent leakage of each air heater at rated condition

KN051

34.

Design gas side pressure loss of AH

KN052

35.

Design PA side press loss of AH

KN053

36.

Sec air flow at MCR through each air heater

KN055

37.

Number of tubes in condenser A second pass

KN056

38.

Condenser surface area per tube

KN057

39.

Number of tubes in second pass of condenser B

KN058

40.

Circulating water density

KN034

41.

Entered value = per cent oxygen by volume for gas at AH B outlet

KN038

42.

Blow down enthalpy

KN032

43.

Heating value of fuel oil

KN026

44.

Heat added other than chemical

KN033

45.

Cost of coal

KN099

46.

Number of hours in a shoft

KN098

Class II tag list:


S No.
1
2

Tag
CV001

Main Steam Flow

Description

CV002

Calculated Throttle Steam Flow

Revision 1

Project :

Ramagundam STPS Stage-I DAS R&M

CV003

Per Cent Rated Load

CV004

Fraction of Air That is Primary Air

CV005

Fraction of Air that is Secondary Air-

CV006

Feedwater Saturation Temperature in the Deaerator

CV007

Feedwater Enthalpy (at BFP Suction)

CV008

Superheat Spray Water Enthalpy

CV011

HPH 6 Drain Cooler Approach

10

CV012

HP Turbine Exhaust Flow

11

CV014

Enthalpy of Feedwater Out of Heater 6

12

CV024

Economiser performance of Heat Exchange

13

CV025

Heater 6 extraction enthalpy

14

CV026

Enthalpy of FW into Heater 6

15

CV027

Enthalpy of heater 6 drain

16

CV028

HPH 6 extraction flow

17

CV029

HPH 6 drain Flow

18

CV034

Excess Air Deviation

19

CV035

Cold Reheat Flow

20

CV036

Hot reheat flow

21

CV037

Heater 5 drain flow

22

CV040

Enthalpy of FW out of heater 5

23

CV042

Heater 5 extraction flow

24

CV044

Heater 3 condensate out enthalpy

25

CV048

Low pressure heater 3 extraction enthalpy

26

CV049

Heater 2 condensate out enthalpy

27

CV050

Heater 3 drain enthalpy

28

CV051

Heater 3 extraction flow

29

CV052

Heater 3 drain flow

Language :

En

Page :

10

YN1G176789-D

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

30

CV053

Heater 2 extraction enthalpy

31

CV054

Heater 1A condensate out enthalpy

32

CV055

Heater 2 drain enthalpy

33

CV056

Heater 2 extraction flow

34

CV057

Heater 2 drain flow

35

CV058

Temperature correction factor for circulating water in temperature

36

CV059

Heater 1 condensate in enthalpy (Ideal)

37

CV061

Circulating water velocity in condenser A tubes

38

CV062

Condenser A basic heat transfer coefficient uncorrected

39

CV064

Condenser A basic heat transfer coefficient corrected.

40

CV065

High pressure heater 6 saturation temperature

41

CV066

Condenser saturation temperature

42

CV067

Heater 5 saturation temperature

43

CV069

Heater 3 saturation temperature

44

CV070

Heater 2 saturation temperature

45

CV071

Condenser A terminal temperature difference

46

CV073

Condenser cooling water

47

CV074

Terminal temperature difference heater 6

48

CV075

Condenser A temperature rise

49

CV076

Terminal temperature difference heater 5

50

CV078

Terminal temperature difference heater 3

51

CV079

Terminal temperature difference heater 2

52

CV080

Logarithmic mean temperature difference for condenser A

53

CV082

Condensate enthalpy leaving condenser A

54

CV083

Temperature deviation from design heater 6

55

CV084

Steam energy removed in condenser A

56

CV085

Temperature deviation from design heater 5

Page :

11

YN1G176789-D

Revision 1

Project :

Ramagundam STPS Stage-I DAS R&M

57

CV087

Temperature deviation from design heater 3

58

CV088

Temperature deviation from design heater 2

59

CV089

Low pressure heater 1 extraction flow

60

CV090

Enthalpy of main steam at HP turbine

61

CV091

HP turbine exhaust enthalpy

62

CV092

HP turbine exhaust ideal enthalpy

63

CV093

HP turbine efficiency

64

CV094

Enthalpy of hot reheat

65

CV095

Enthalpy of IP turbine exhaust

66

CV096

IP turbine exhaust enthalpy (Ideal)

67

CV097

IP turbine efficiency

68

CV098

Condenser A actual heat transfer coefficient

69

CV099

Condenser A cleanliness factor

70

CV108

Generator losses

71

CV109

LP turbine exhaust enthalpy (Ideal)

72

CV110

Condenser vacuum (Absolute)

73

CV111

LP turbine exhaust enthalpy (Actual)

74

CV112

LP turbine efficiency

75

CV117

Dry gas per ton of fuel fired

76

CV118

Heat loss due to dry gas

77

CV119

Enthalpy of water vapor at exhaust gas temperature

78

CV120

Enthalpy of water at ambient temperature

79

CV121

Heat loss due to moisture in fuel

80

CV122

Heat loss due to water combined from hydrogen

81

CV123

Boiler efficiency

82

CV124

Net generation

83

CV125

Auxiliary power per cent

Language :

En

Page :

12

YN1G176789-D

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

84

CV126

Net turbine heat rate

85

CV127

Reference Gross turbine heat rate

86

CV133

Adjusted test gross turbine heat rate

87

CV136

Gross unit heat rate

88

CV137

Average boiler efficiency

89

CV138

Boiler efficiency by input-output method

90

CV139

Main Steam to Aux Steam Enthalpy

91

CV140

BFP Discharge to Desuperheater Enthalpy

92

CV141

Aux. Steam Enthalpy

93

CV142

Aux. Steam Supply Flow

94

CV145

High pressure heater 5 extraction enthalpy

95

CV146

High pressure heater 5 drain enthalpy

96

CV147

High pressure heater 5 FW inlet enthalpy

97

CV148

High pressure heater 5 FW outlet enthalpy

98

CV149

Heater 3 condensate inlet enthalpy

99

CV150

Gland cooler 2 condensate outlet enthalpy

100

CV152

Circulating water velocity in condenser B tubes

101

CV153

Condenser B basic heat transfer coefficient uncorrected

102

CV154

Condenser B basic heat transfer coefficient corrected

103

CV155

Condenser B terminal temperature difference

104

CV156

Condenser B temperature rise

105

CV157

Low pressure heater 1 extraction enthalpy

106

CV158

Low pressure heater 1 drain enthalpy

107

CV159

Heater 1B condensate outlet enthalpy

108

CV160

Condensate enthalpy leaving condenser B

109

CV161

Steam energy removed in condenser B

110

CV162

Condenser B actual heat transfer coefficient

En

Page :

13

YN1G176789-D

Revision 1

Project :

Ramagundam STPS Stage-I DAS R&M

Language :

En

111

CV163

Condenser B cleanliness factor

112

CV164

Heat loss due to moisture in air

113

CV166

Gross turbine heat rate

114

CV169

Net unit heat rate

115

CV170

Boiler efficiency deviation

116

CV171

Heater 1 saturation temperature

117

CV172

Heater 1A terminal temp different

118

CV173

Heater 1B terminal temp different

119

CV174

Economizer press drop performance deviation

120

CV175

Economizer temp rise performance deviation

121

CV176

HPT Front Seal Leakage

122

CV177

HPT Rear Seal Leakage

123

CV178

HPT CV leakage

124

CV179

Steam supplied from Front sealing of HPT to HPT exhaust

125

CV180

Total HPT leakage

126

CV181

Excess air percentage

127

CV182

Excess air percentage standard

128

CV183

IPT leak off thru control valve

129

CV184

IPT leak off thru rear seals

130

CV185

IPT leak off thru front seals

131

CV187

Steam leakage into LPT

132

CV188

IPT and LPT leakage

133

CV189

HPT front seal leak off enthalpy

134

CV190

HPT rear seal leak off enthalpy

135

CV191

HPT CV seal leak off enthalpy

136

CV192

HPT front seal to HPT exhaust steam enthalpy

137

CV193

IPT front seal leak off enthalpy

Page :

14

YN1G176789-D

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

15

YN1G176789-D

138

CV194

IPT rear seal leak off enthalpy

139

CV195

IPT CV seal leak off enthalpy

140

CV196

Steam leakage into LPT enthalpy

141

CV197

LMTD for condenser B

142

CV198

HPH-5 drain cooler approach

143

CV199

Super heater Outlet Enthalpy

144

CV200

Reheater outlet enthalpy

145

CV201

146

CV202

147

CV203

Ton of dry air leakage in AHA per the quantity of wet flue gas per ton of fuel fired entering
AH A
Tone of dry air leakage in AH B per the quantity of wet flue gas per ton of fuel fired
entering AH B
Ton of moisture per ton of dry air (I.e., specific humidity of dry air)

148

CV204

Ton of minimum air for complete combustion per ton of fuel fired

149

CV205

Ton of Excess Air at AH Inlet Per Ton of Fuel Fired

150

CV206

151

CV207

152

CV208

Ton of wet air leakage in AH A per the quantity of wet flue gas per ton of fuel fired entering
AH A
Tone of wet air leakage in AH B per the quantity of wet flue gas per ton of fuel fired
entering AH B
Ton of moisture in flue gas at AH inlet per ton of fuel fired

153

CV209

Ton f wet gas at AH inlet per ton of fuel fired

154

CV210

Percentage air leakage of AH A

155

CV211

Percentage air leakage of AH B

156

CV212

Fraction of the total air leakage of AH A coming from primary of air side

157

CV213

Fraction of the total air leakage of AH A coming from secondary air side

158

CV214

159

CV215

Fraction of the total air leakage of AH B coming from


Side
Fraction of the total air leakage of AH B coming from secondary air side

160

CV216

AH A gas out temperature corrected for no leakage

161

CV217

AH B gas out temperature corrected for no leakage

162

CV218

Gas side efficiency-AH A

163

CV219

Gas side efficiency-AH B

164

CV220

Fraction of mill A primary air which is heated in air heater

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

16

YN1G176789-D

165

CV221

Fraction of mill B primary air which is heated in air heater

166

CV222

Fraction of mill C primary air which is heated in air heater

167

CV223

Fraction of mill D primary air which is heated in air heater

168

CV224

Fraction of mill E primary air which is heated in air heater

169

CV225

Fraction of mill F primary air which is heated in air heater

170

CV226

Fraction of total PA which is hot PA

171

CV229

Test X ratio AH A

172

CV230

Test X ratio AH B

173

CV231

174

CV232

175

CV233

Corrected percentage air leakage of AH A for deviation from design pressure differential
and from design air temperature
Corrected percentage air leakage of AH B for deviation from design pressure differential
and from design air temperature
Ton of coal fired per hour

176

CV234

Gas side pressure loss of AH A corrected for deviation from design flow and temperature

177

CV235

Gas side pressure loss of AH B corrected for deviation from design flow and temperature

178

CV236

179

CV237

180

CV238

Primary air side pressure loss of AH A corrected for deviation from design flow and
temperatures
Primary air side pressure loss of AH B corrected for deviation from design flow and
temperatures
PA flow through AH A

181

CV239

PA flow through AH B

182

CV240

183

CV241

184

CV242

Secondary air side pressure loss of AH A corrected for deviation from design flow and
temperatures
Secondary air side pressure loss of AH B corrected for deviation from design flow and
temperatures
Corrected gas temperature leaving AH A for deviation from design entering air temperature

185

CV243

186

CV244

187

CV245

188

CV246

Corrected gas temperature leaving AH B for deviation from design entering air
temperature
Corrected gas temperature leaving AH A for deviation from design entering gas
temperature
Corrected gas temperature leaving AH B for deviation from design entering gas
temperature
Corrected gas temp leaving air heater A for deviation from design X ratio

189

CV247

Corrected gas temp leaving air heater B for deviation from design X ratio

190

CV248

Correction factor for gas out temp of AH A as a function of test X ratio

191

CV249

Correction factor for gas out temp of AH B as a function of test X ratio

Revision 1

Project :

Ramagundam STPS Stage-I DAS R&M

Language :

En

Page :

17

YN1G176789-D

192

CV250

193

CV251

Corrected gas temperature leaving air heater A for deviation from design entering flue gas
flow
Corrected gas temp leaving air heater B for deviation from design entering flue gas flow

194

CV252

Correction factor for gas temp of AH A for deviation from design entering flue gas flow

195

CV253

Correction factor for gas out temp of AH B for deviation from design entering flue gas flow

196

CV254

Totally corrected gas temp leaving AH A

197

CV255

Totally corrected gas temp leaving AH B

198

CV256

AH A air leakage expressed as a percentage of design leakage

199

CV257

AH B air leakage expressed as a percentage of design leakage

200

CV258

201

CV259

202

CV260

203

CV261

204

CV262

205

CV263

206

CV264

207

CV265

208

CV266

Deviation of corrected exit gas temperature at AH A from design value of exit gas
temperature
Deviation of corrected exit gas temperature at AH B from design value of exit gas
temperature
AH A gas side pressure loss (corrected for deviation from design flow and temp)
expressed as a percentage of design gas side press loss
AH B gas side pressure loss (corrected for deviation from design flow and temp)
expressed as a percentage of design gas side press loss
AH A PA side pressure loss (corrected for deviation from design flow and temperature0
expressed as a percentage of the design rated value of PA side pressure loss
AH B PA side pressure loss (corrected for deviation from design flow and temperature)
expressed as a percentage of the design rated value of PA side pressure loss
AH A sec air side pressure loss (corrected for deviation from design flow and temperature)
expressed as a percentage of the design pressure loss
AH B sec air side pressure loss (corrected for deviation from design flow and temperature)
expressed as a percentage of the design pressure loss
AH A sec air inlet pressure delete from

209

CV267

AH B sec air inlet pressure

210

CV269

Design temperature heater 6 outlet FW

211

CV270

Design temperature heater 5 outlet FW

212

CV272

Design temperature heater 3 condensate outlet

213

CV273

Design temperature heater 2 condensate outlet

214

CV274

Design temperature heater 1A condensate outlet

215

CV275

Design temperature heater 1B Condensate outlet

216

CV276

Temperature deviation from design heater 1A

217

CV277

Temperature deviation from design heater 1B

218

CV278

Economiser pressure drop in gas path with respect to load

Revision 1

219

CV279

Project :

Ramagundam STPS Stage-I DAS R&M

Economizer temperature rise as a function of load

Language :

En

Page :

18

YN1G176789-D

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

Page :

En

19

YN1G176789-D

Calculation details:
CV199

Superheater Outlet Enthalpy


-SH Steam- FUNC OF P & T

=Fn((AV098+AV099)/2 , AV100+KN003)
KCAL/KG

where
AV098 SH Outlet Stm Temp (L)
AV099 SH Outlet Stm Temp (R)
AV100 SH Outlet Stm Pressure
KN003 Atmospheric Pressure
-----------------------------------------------------------------------------------------------------------------------CV139

Main Steam to Aux Steam Enthalpy


=CV199
-Same as Superheater Outlet Enthalpy KCAL/KG
Where
CV199 Superheater Outlet Enthalpy

-----------------------------------------------------------------------------------------------------------------------CV140
BFP Discharge to Desuperheater Enthalpy
= Fn(AV114)
- A function of temp compressed liquid KCAL/KG
Where
AV114 BFP Disch to Desuperheater Temp
-----------------------------------------------------------------------------------------------------------------------CV141
Aux Steam Enthalpy
=Fn(AV115+KN003, AV116)
SH steam A function of press and temp KCAL/KG
Where
AV115 Aux Steam Pressure
KN003 Atmospheric Pressure
AV116 Aux Steam Temp
-----------------------------------------------------------------------------------------------------------------------CV142
Aux Steam Supply Flow =AV117*(CV141-CV140) / (CV139-CV140)
T/Hr
Where
AV117 Aux Steam Flow
CV139 Main Steam to Aux Steam Enthalpy
CV140 BFP Discharge to Desuperheater Enthalpy
CV141 Aux Steam Enthalpy
-----------------------------------------------------------------------------------------------------------------------CV001

Main Steam Flow


=AV001-KN001-CV142+AV076
-Feedwater flow less Blowdown flow and auxiliary steam flow plus SH spray flow
T/Hr
Where

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

AV001
KN001
CV142
AV076

En

Page :

20

YN1G176789-D

Feed Water flow


Blowdown flow
Aux steam Supply Flow
Superheat Spray Flow

-----------------------------------------------------------------------------------------------------------------------CV002
Calculated Throttle Steam Flow
=Fn(AV002 + KN003) * FACTOR
-Throttle steam flow is a function of first stage shell press, adjusted for temperature
and pressure T/Hr
Where
FACTOR = VOPER/VRATED
VOPER Specific volume of steam at operating
conditions
=Fn (AV072,AV073 + KN003)
Where
AV072 Main Steam Temperature after ESV
AV073 Main Steam Pressure after ESV
KN003 Atmospheric pressure
AV002 First stage pressure
Vrated
VRATED
-Specific volume of Steam at 530
deg c & 130 kg/cm2
=Fn(530,130+KN003)
-----------------------------------------------------------------------------------------------------------------------CV003
Per Cent Rated Load
=(CV001/611.635 )*100
-Ratio of Main steam flow to rated steam flow as a percentage. %
Where
CV001 Main Steam Flow
611.635 Rated Steam Flow
-----------------------------------------------------------------------------------------------------------------------CV004
Fraction of Air That is Primary Air
=(AV077+AV078+AV079+AV080+AV081+AV082) /
(AV077+AV078+AV079+AV080+AV081+AV082+AV083+AV084)
-PA flow divided by total air flow
Where
AV077
AV078
AV079
AV080
AV081
AV082
AV083
AV084

Mill B PA flow
Mill C PA flow
Mill D PA flow
Mill E PA flow
Mill F PA flow
Mill A PA flow
Sec Air Flow Left
Sec Air Flow Right

-----------------------------------------------------------------------------------------------------------------------CV005
Fraction of Air that is Secondary Air
= 1.0 - CV004
- One minus PA fraction
Where
CV004 PA fraction

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

Page :

En

21

YN1G176789-D

-----------------------------------------------------------------------------------------------------------------------CV006
Feedwater Saturation Temperature in the Deaerator
- A function of deaerator pressure
=Fn (AV014 + KN003)
Deg C
Where
AV014 Deaerator pressure
KN003 Atmospheric pressure
-----------------------------------------------------------------------------------------------------------------------CV007
Feedwater Enthalpy (at BFP Suction)
=Fn (CV006,AV086 + KN003)
- A function of saturation temperature and pressure
KCAL/KG
Where
CV006 Feedwater saturation temperature
AV086 Feedwater pressure (at BFP suction)
KN003 Atmospheric pressure
-----------------------------------------------------------------------------------------------------------------------CV008
Superheat Spray Water Enthalpy
=Fn(AV088, AV087 + KN003)
- Function of FW Temp & press at Eco inlet
KCAL/KG
Where
AV087 FW pressure at Econ inlet
AV088 FW temperature at Econ inlet
KN003 Atmospheric pressure
.
-----------------------------------------------------------------------------------------------------------------------CV011
HPH 6 Drain Cooler Approach = AV012 - AV011
Deg C
Where
AV012 HPH 6 Drain Temperature
AV011 HPH 6 FW inlet temperature
-----------------------------------------------------------------------------------------------------------------------CV176
HPT Front Seal Leakage
= Fn(CV001)
- HPT Front Seal leakage is a function of main steam flow.
T/Hr
Where
CV001 Main Steam Flow
-----------------------------------------------------------------------------------------------------------------------CV177
HPT Rear Seal Leakage
= Fn(CV001)
-HPT Rear seal leakage is a function of main steam flow. T/Hr
Where
CV001 Main Steam Flow
-----------------------------------------------------------------------------------------------------------------------CV178

HPT CV leakage
=Fn(CV001)
-HPT CV leakage is a function of main steam flow.
Where

T/Hr

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

22

YN1G176789-D

CV001 Main Steam Flow


-----------------------------------------------------------------------------------------------------------------------CV179
Steam supplied from Front sealings of HPT to HPT exhaust
=Fn(CV001)
-This is function of main steam flow
T/Hr
Where
CV001 Main Steam Flow
-----------------------------------------------------------------------------------------------------------------------CV180
Total HPT leakage
= CV176+CV177+CV178-CV179
-Total HPT leakage =HPT front seal leakage + HPT rear seal leakage +HPT CV
leakage-HPT front seal leakage to HPT exhaust. T/Hr
-----------------------------------------------------------------------------------------------------------------------CV014
Enthalpy of Feedwater Out of Heater 6 =Fn(AV007,AV087+KN003)
-A function of feedwater temp and press out of heater 6. Compressed liquid.
KCAL/KG
Where
AV007 Heater 6 feedwater outlet temperature
AV087 FW press at Econ inlet (pressure assumed
constant after BFP discharge to economizer)
KN003 Atmospheric pressure
------------------------------------------------------------------------------------------------------------------------

-----------------------------------------------------------------------------------------------------------------------CV024
Economiser performance of Heat Exchange
=(AV170-GASOUT)*100 / (AV170-AV088)
(%)
Where
AV170 Gas temp before Econ
AV088 Feedwater temp at Econ inlet
-----------------------------------------------------------------------------------------------------------------------CV025
Heater 6 extraction enthalpy
=Fn(AV009,AV010+KN003)
-A function of extraction steam temperature and pressure - SH steam
KCAL/KG
Where
AV009 Ext. temperature heater 6
AV010 Ext. pressure heater 6
KN003 Atmospheric pressure
-----------------------------------------------------------------------------------------------------------------------CV026
Enthalpy of FW into Heater 6
=Fn(AV011, AV087 + KN003)
- A function of FW temperature & pressure into heater 6 - compressed liquid
KCAL/KG
Where
AV011 Inlet temperature heater 6

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

Page :

En

23

YN1G176789-D

AV087 FW press at Econ inlet (pressure assumed


constant after BFP discharge to economizer)
KN003 Atmospheric pressure
-----------------------------------------------------------------------------------------------------------------------CV027
Enthalpy of heater 6 drain
=Fn(AV012)
-A function of heater 6 drain temperature - saturated liquid.
KCAL/KG
Where
AV012 Heater 6 drain temperature
------------------------------------------------------------------------------------------------------------------------CV028
HPH-6 Extraction flow = AV085*(CV014-CV148)/(CV025-CV027) T/Hr.
Calculated by heat balance around heater 6.
CV014= Heater 6 F.W outlet Enthalpy
CV148 = Heater 5 F.W outlet Enthalpy
CV027= Heater 6 drain Enthalpy
CV025= Heater 6 ext. Enthalpy
------------------------------------------------------------------------------------------------------------------------CV029
HPH-6 Drain flow = HPH-6 Extraction flow = CV028 T/Hr
------------------------------------------------------------------------------------------------------------------------CV035
Cold Reheat Flow
=CV012-CV028-AV090
T/Hr
-Equal to HP turbine exhaust flow minus HPH 6 extraction flow and deaerator
extraction flow
Where
CV012 HP turbine exhaust flow
CV028 HPH 6 extraction flow
AV090 Deaerator extraction flow
-----------------------------------------------------------------------------------------------------------------------CV036

Hot reheat flow =CV035+AV013


-The sum of cold reheat and the reheat spray flow.

T/Hr

Where
CV035 Cold Reheat flow
AV013 Reheat spray flow
-----------------------------------------------------------------------------------------------------------------------CV145

High pressure heater 5 extraction enthalpy


=Fn(AV067,AV068+KN003)
-A function of extraction temp and pressure - SH steam KCAL/KG
Where
AV067 HPH 5 extraction temp
AV068 HPH 5 extraction pressure
KN003 Atmospheric pressure

-----------------------------------------------------------------------------------------------------------------------CV146
High pressure heater 5 drain enthalpy =Fn(AV069)
-A function of drain temp; saturated liquid.
KCAL/KG

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

24

YN1G176789-D

Where
AV069 HPH 5 drain temp
-----------------------------------------------------------------------------------------------------------------------CV147

High pressure heater 5 FW inlet enthalpy


=Fn(AV071, AV087 + KN003)
-A function of FW inlet temp & press compressed liquid KCAL/KG
Where
AV071 HPH 5 FW inlet temp.
AV087 FW press at Econ inlet
KN003 Atmospheric pressure

-----------------------------------------------------------------------------------------------------------------------CV148
High pressure heater 5 FW outlet enthalpy
=Fn(AV011, AV087 + KN003)
-A function of temp & press compressed liquid KCAL/KG
Where
AV011 HPH 5 FW outlet temp.
AV087 FW press at Econ inlet
KN003 Atmospheric pressure
-----------------------------------------------------------------------------------------------------------------------CV042
Heater 5 extraction flow
=((AV085*(CV148-CV147) + CV029*(CV146-CV027)) / (CV145-CV146)
-Calculated by a heat balance around Heater 5
T/Hr
Where
AV085
CV148
CV147
CV029
CV146
CV027
CV145

Feedwater flow
HPH 5 FW outlet enthalpy
HPH 5 FW inlet enthalpy
HPH 6 drain Flow
HPH 5 drain enthalpy
HPH 6 drain enthalpy
HPH 5 extraction enthalpy

-----------------------------------------------------------------------------------------------------------------------CV037
Heater 5 drain flow
=CV029+CV042
T/Hr
-Heater 6 drain flow plus heater 5 ext. flow
Where
CV029 Heater 6 drain flow
CV042 Heater 5 ext. flow
---------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------CV040
Enthalpy of FW out of heater 5 =CV026
KCAL/KG
-Equal to heater-6 FW inlet enthalpy
Where
CV026 Heater 6 FW in Enthalpy
----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------

Revision 1

CV044

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

Page :

En

YN1G176789-D

25

Heater 3 condensate out enthalpy


=Fn (AV029, AV008 + KN003)
-A function of condensate temperature & press compressed liquid.
KCAL/KG
Where
AV029 Heater 3 Condensate outlet temperature.
AV008 Condensate pump discharge press
KN003 Atmospheric pressure

-----------------------------------------------------------------------------------------------------------------------CV048

Low pressure heater 3 extraction enthalpy


=Fn(AV031,AV032+KN003)
-A function of extraction temperature and pressure
KCAL/KG
Where
AV031 Extraction temperature of heater 3
AV032 Extraction pressure of heater 3
KN003 Atmospheric pressure

-----------------------------------------------------------------------------------------------------------------------CV049
Heater 2 condensate out enthalpy
=Fn(AV033)
-A function of condensate temperature. Compressed liquid.
KCAL/KG
Where
AV033 Outlet temperature heater 2
-----------------------------------------------------------------------------------------------------------------------CV050
Heater 3 drain enthalpy =Fn(AV034)
-A function of drain temperature, saturated liquid.
KCAL/KG
Where
AV034 Drain temperature heater 3
-----------------------------------------------------------------------------------------------------------------------CV149

Heater 3 condensate inlet enthalpy


=Fn(AV118)
-A function of condensate inlet temp compressed liquid

KCAL/KG

Where
AV118 LPH 3 condensate inlet temp.
-----------------------------------------------------------------------------------------------------------------------CV053

Heater 2 extraction enthalpy


=Fn(AV035,AV036+KN003)
-A function of extraction temperature and pressure.
KCAL/KG
Where
AV035 Heater 2 extraction temperature
AV036 Heater 2 extraction pressure
KN003 Atmospheric pressure

-----------------------------------------------------------------------------------------------------------------------CV054

Heater 1 Condensate out enthalpy


=Fn(AV037)
-A function of Condensate temperature. Compressed liquid.

KCAL/KG

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

26

YN1G176789-D

Where
AV037 Outlet temperature heater 1.
-----------------------------------------------------------------------------------------------------------------------CV055
Heater 2 drain enthalpy
=Fn(AV038)
-A function of drain temperature. Saturated liquid.
KCAL/KG
Where
AV038 Drain temperature heater 2
---------------------------------------------------------------------------------------------------------------------CV150

Gland cooler 2 condensate outlet enthalpy


=Fn(AV119)
-A function of GC-2 condensate outlet temp. Compressed liquid.
KCAL/KG
Where
AV119 Gland cooler 2 condensate outlet temp.

----------------------------------------------------------------------------------------------------------------------CV051
Heater 3 extraction flow
= AV091*(CV044-CV149) / (CV048-CV05))
-Calculated by a heat balance around heater 3 T/Hr
Where
AV091
CV044
CV149
CV050
CV048

Condensate flow
Heater 3 Condensate out enthalpy
Heater 3 Condensate in enthalpy
Heater 3 drain enthalpy
Heater 3 extraction enthalpy

-----------------------------------------------------------------------------------------------------------------------CV052

Heater 3 drain flow


= CV051
= heater 3 extraction flow
T/Hr
Where
CV051 Heater 3 extraction flow

-----------------------------------------------------------------------------------------------------------------------CV056

Heater 2 extraction flow


=(CV052*(CV055-CV050)+(AV091-CV057) *(CV049-CV150)) /
(CV053-CV055)
-Calculated by a heat balance around heater 2 T/Hr
Where
CV041
AV091
CV049
CV052
CV055
CV050
CV053
CV057

Condensate flow
Condensate flow
Heater 2 condensate out enthalpy
Heater 3 drain flow
Heater 2 drain enthalpy
Heater 3 drain enthalpy
Heater 2 extraction enthalpy
Heater 2 drain flow

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

YN1G176789-D

27

CV150 Gland cooler 2 condensate outlet enthalpy


-----------------------------------------------------------------------------------------------------------------------CV057
Heater 2 drain flow
=CV052+CV056
-The sum of heater 3 drain flow and heater 2 extraction flow
T/Hr
Where
CV052 Heater 3 drain flow
CV056 Heater 2 extraction flow
----------------------------------------------------------------------------------------------------------------------CV058

Temperature correction factor for circulating water in temperature


=Fn(AV092)
Where
AV092 Condenser cooling water temperature

----------------------------------------------------------------------------------------------------------------------CV059

Heater 1 condensate in enthalpy (Ideal) =Fn(AV041)


-A function of condensate temperature. Compressed liquid.

KCAL/KG

Where
AV041 Inlet temperature heater 1.
-----------------------------------------------------------------------------------------------------------------------CV061
Circulating water velocity in condenser A tubes M/S
=1/2 ((AV093)/ (KN021*KN020*3600) + (AV093) / (KN021*KN056*3600))
Where
AV093 Circulating water flow right
KN021 Condenser cross sectional area for tube
KN020 Number of tubes in condenser A first pass
3600 Conversion from m/hr to m/s
KN056 Number of tubes in condenser A second
pass
-----------------------------------------------------------------------------------------------------------------------CV062

Condenser A basic heat transfer coefficient uncorrected


=2290.5* (CV061)1/2
-A function of velocity
KCAL/HR/SQM/Deg C
Where
CV061 Circulating water velocity through condenser
A

-----------------------------------------------------------------------------------------------------------------------CV064

Condenser A basic heat transfer coefficient corrected =(CV062*CV058*KN018)


KCAL/HR/SQM/Deg C
Where

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

28

YN1G176789-D

CV062 Uncorrected heat transfer coefficient for


condenser A
CV058 Temperature correction factor
KN018 Tube metal correction factor.
----------------------------------------------------------------------------------------------------------------------CV065
High pressure heater 6 saturation temperature =Fn(AV010+KN003)
-A function of extraction pressure to the heater. DEG C
Where
AV010 Extraction pressure heater 6
KN003 Atmospheric pressure
----------------------------------------------------------------------------------------------------------------------CV110
Condenser vacuum
=AV050*1.359 E-3
-Condenser absolute pressure KG/SC
Where
AV050 Condenser vacuum mm Hg A
1.359 E-3
Conversion from mm Hg to KG/SC
-----------------------------------------------------------------------------------------------------------------------CV066
Condenser saturation temperature
=Fn(CV110)
-A function of condenser vacuum
DEG C
Where
CV110 Condenser vacuum
-----------------------------------------------------------------------------------------------------------------------CV067

Heater 5 saturation temperature =Fn(AV068+KN003)


-A function of extraction pressure to the heater. DEG C
Where
AV068 Heater 5 extraction pressure
KN003 Atmospheric pressure

----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------CV069
Heater 3 saturation temperature =Fn(AV032+KN003)
-A function of extraction pressure to the heater DEG C
Where
AV032 Heater 3 extraction pressure
KN003 Atmospheric pressure
-----------------------------------------------------------------------------------------------------------------------CV070

Heater 2 saturation temperature =Fn(AV036+KN003)


-A function of extraction pressure to the heater. DEG C
Where
AV036 Heater 2 extraction pressure
KN003 Atmospheric pressure

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

29

YN1G176789-D

-----------------------------------------------------------------------------------------------------------------------CV071

Condenser B terminal temperature difference


=CV066-AV094
Approach to saturation for condensate in condenser A DEG C
Where
CV066 Condenser saturation temperature
AV094 Condenser B outlet temperature

CV073

Condenser cooling range


=CV066-AV092
Difference between condenser saturation temperature and CW inlet temperature
DEG C
Where
CV066 Condenser saturation temperature
AV092 Condenser cooling water temperature

-----------------------------------------------------------------------------------------------------------------------CV074

Terminal temperature difference heater 6


=CV065-AV007
-The approach to saturation for the condensate leaving the heater

DEG C

Where
CV065 Heater 6 saturation temperature
AV007 Heater 6 outlet temperature
----------------------------------------------------------------------------------------------------------------------CV075

Condenser B temperature rise


DEG C

=AV094-AV092

Where
AV094 Condenser B CW outlet temperature
AV092 Cooling water temperature
--------------------------------------------------------------------------------------------------------------------CV076

Terminal temperature difference heater 5


=CV067-AV011
-The approach to saturation for the condensate leaving the heater.

DEG C

Where
CV067 Heater 5 saturation temperature
AV011 FW inlet temperature heater 6
Note: When contact status of XZ503 OR FZ507 OR FZ506 are closed, CV076 = 0

-------------------------------------------------------------------------------------------------------------------CV078
Terminal temperature difference heater 3
=CV069-AV029
-The approach to saturation for the condensate leaving the heater.
DEG C
Where

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

Page :

En

YN1G176789-D

30

CV069 Heater 3 saturation temperature


AV029 Heater 3 outlet temperature
Note: When contact status of XZ502 closed, CV078 = 0
-----------------------------------------------------------------------------------------------------------------------CV079

Terminal temperature difference heater 2


=CV070-AV033
-The approach to the saturation for the condensate leaving the heater.

DEG C

Where
CV070 Heater 2 saturation temperature
AV033 Heater 2 outlet temperature
Note: When contact status of XZ501 closed, CV079 = 0
-----------------------------------------------------------------------------------------------------------------------CV080

logarithmic mean temperature difference for condenser B


=((CV066-AV092) - (CV066-AV094)) / In{(CV066-AV092) / (CV066-AV094)}
DEG C
Where
CV066 Condenser saturation temp
AV094 Cooling water at Condenser B outlet Temp
AV092 Condenser cooling water temp.

-----------------------------------------------------------------------------------------------------------------------CV082

Condensate enthalpy leaving condenser A


=Fn(AV096)
-A function of condensate temperature leaving condenser A

KCAL/KG

Where
AV096 Condensate pump suction temperature
--------------------------------------------------------------------------------------------------------------------CV269
Design temperature heater 6 outlet FW =Fn(AV049)
DEG C
Where
AV049 Gross generation
--------------------------------------------------------------------------------------------------------------------CV083

Temperature deviation from design heater 6


=CV269-AV007
-Difference between design and actual outlet temperature
DEG C

Where
CV269 Design temperature heater 6 FW outlet
AV007 Heater 6 outlet temperature
----------------------------------------------------------------------------------------------------------------------CV084

Steam energy removed in condenser A KCAL/KG


= AV093*KN034*KN035*(AV094 AV092)
Where
AV093 CW flow for condenser A
KN034 CW density

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

Page :

En

31

YN1G176789-D

KN035 Specific heat of CW for mean temp and


salinity
AV094 Cond A CW out temp
AV092 Cond CW in temp
-----------------------------------------------------------------------------------------------------------------------CV270

Design temperature heater 5 outlet FW =Fn(AV049)


DEG C
Where
AV049 Gross generation
Note : BHEL curve MS-0104-E-HW-03040 Sheet 6.

-----------------------------------------------------------------------------------------------------------------------CV085
Temperature deviation from design heater 5
=CV270-AV011
Difference between design and actual outlet temperature DEG C
Where
CV270 Design temperature heater 5 FW outlet
AV011 Heater 6 inlet temperature
-----------------------------------------------------------------------------------------------------------------------CV272
Design temperature heater 3 condensate outlet =Fn(AV049)
DEG C
Where
AV049 Gross generation
----------------------------------------------------------------------------------------------------------------------CV087

Temperature deviation from design heater 3


=CV272-AV029
- Difference between design and actual outlet temperature
DEG C

Where
CV272 Design temperature heater 3 condensate
outlet
AV029 Heater 3 outlet temperature
-----------------------------------------------------------------------------------------------------------------------CV273

Design temperature heater 2 condensate outlet =Fn(AV049)


DEG C
Where
AV049 Gross generation

-----------------------------------------------------------------------------------------------------------------------CV088

Temperature deviation from design heater 2


=CV273-AV033
-Difference between design and actual outlet temperature
DEG C
Where
CV273 Design temperature heater 2 condensate
outlet
AV033 Heater 2 outlet temperature

---------------------------------------------------------------------------------------------------------------------

Revision 1

CV157

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

Page :

En

Low pressure heater 1 extraction enthalpy


=Fn(AV040+KN003, Dryness Fraction)
-A function of extraction pressure and dryness fraction

32

YN1G176789-D

KCAL/KG

Where
AV040 LPH-1 extraction pressure
KN003 Atmospheric pressure
Dryness fraction = The quality of extraction steam
will be from :BHEL curves based on load. Fn(AV049)
----------------------------------------------------------------------------------------------------------------------CV158

Low pressure heater 1 drain enthalpy


=Fn(AV042)
-A function of drain temp saturated liquid KCAL/KG

Where
AV042 LPH -1 drain temp
----------------------------------------------------------------------------------------------------------------------CV159

Heater 1B condensate outlet enthalpy =Fn(AV121)


-A function of condensate temp compressed liquid

KCAL/KG

Where
AV121 Outlet temp heater 1B.
----------------------------------------------------------------------------------------------------------------------CV089

Low pressure heater 1 extraction flow


=(( AV093-CV057)*((CV054+CV159) / 2))-CV059)) /(CV157-CV158 )
T/Hr
Where
AV093
CV057
CV054
CV159
CV059
CV158
CV157

Condensate flow right


Heater 2 drain flow
Heater 1A condensate outlet enthalpy
Heater 1B condensate outlet enthalpy
Heater 1condensate inlet enthalpy
Heater 1 drain enthalpy
Heater 1 extraction enthalpy

Note: When contact status of CZ512 & CZ513 are closed, CV089 = 0
-----------------------------------------------------------------------------------------------------------------------CV090

Enthalpy of main steam at HP turbine =Fn(AV072,AV073+KN003)


-A function of temperature and pressure at CV inlet
KCAL/KG

Where
AV072 Main steam temp after ESV
AV073 Main steam press after ESV
KN003 Atmospheric pressure
-----------------------------------------------------------------------------------------------------------------------CV091

HP turbine exhaust enthalpy


=Fn(AV074,AV075+KN003)
-A function of temperature and pressure KCAL/KG

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

33

YN1G176789-D

Where
AV074 HPT exhaust temp
AV075 HPT exhaust press
KN003 Atmospheric pressure
----------------------------------------------------------------------------------------------------------------------CV092
HP turbine exhaust ideal enthalpy
=Fn(AV072,AV073+KN003, AV075+KN003)
-The enthalpy of main steam after isentropic expansion through the HP turbine
KCAL/KG
Where
AV072 Main steam temp after ESV
AV073 Main steam pressure after ESV
AV075 HPT exhaust pressure
KN003 Atmospheric pressure
-----------------------------------------------------------------------------------------------------------------------CV093

HP turbine efficiency
=(CV090-CV091) / (CV090-CV092) *100
-The ratio of the actual change in enthalpy across the HP turbine compared to the
theoretical change (at constant entropy), expressed as a percentage)
%
Where
CV090 Enthalpy of main steam at CV inlet
CV091 HP turbine exhaust enthalpy
CV092 HP turbine exhaust enthalpy (Ideal)

-----------------------------------------------------------------------------------------------------------------------CV094

Enthalpy of hot reheat steam


=Fn(AV045,AV046+KN003)
-A function of temperature and pressure of steam leaving the reheat section of the
boiler KCAL/KG

Where
AV045 Hot reheat temperature IV inlet
AV046 Hot reheat pressure IV inlet
KN003 Atmospheric pressure
-----------------------------------------------------------------------------------------------------------------------CV095

Enthalpy of IP turbine exhaust =CV053


-A function of temperature and pressure. This is equal to the enthalpy of extraction
steam to LPH-2
KCAL/KG
Where
CV053 LPH 2 extraction enthalpy

----------------------------------------------------------------------------------------------------------------------CV096

IP turbine exhaust enthalpy (Ideal)


=Fn(AV045,AV046+KN003,AV036+KN003)
-A function of temperature and inlet and exhaust pressure. It is the enthalpy of steam
after isentropic (constant entropy) expansion through the IP turbine)
KCAL/KG
Where

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

Page :

En

34

YN1G176789-D

AV045 Hot reheat temperature IV inlet


AV046 Hot reheat pressure IV inlet
AV036 LPH 2 extraction pressure
KN003 Atmospheric pressure
-----------------------------------------------------------------------------------------------------------------------CV097

IP turbine efficiency
=((CV094-CV095/CV094-CV096))*100
-The ratio of the actual change in enthalpy to the theoretical change in enthalpy if
expansion was isentropic, expressed as a percentage. %
Where
CV094 Enthalpy of hot reheat at IV inlet
CV095 IP turbine exhaust enthalpy
CV096 IP turbine exhaust enthalpy (Ideal)

Note: when contact status of XZ501 is closed CV097=0


---------------------------------------------------------------------------------------------------------------------CV098

Condenser A actual heat transfer coefficient


= CV084 / (CV080*KN057*(KN020+KN056))
KCAL/HR/SQ M/DEG C
Where
CV084 Steam energy removed in condenser A
CV080 Log mean temperature for condenser
KN057 Condenser surface area per tube
KN020 No. of condenser tubes in condenser A
KN056 No. of tubes in condenser A second pass

Note: When the contact status of HZ500/ HZ501 is closed, CV098=0.


-------------------------------------------------------------------------------------------------------------------CV099

Condenser A cleanliness factor =(CV098/CV064)*100

Where
CV098 Condenser A actual heat transfer
coefficient
CV064 Condenser A basic heat transfer
coefficient corrected.
-----------------------------------------------------------------------------------------------------------------------CV183

IPT leak off thru control valves =Fn(CV001)


-IPT leak off thru control valves is a function of main steam flow T/Hr
Where :
CV001 Main steam flow

----------------------------------------------------------------------------------------------------------------------CV184

IPT leak off thru rear seals


=Fn(CV001)
-IPT leak off thru rear seals is a function of main steam flow.
Where

T/Hr

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

35

YN1G176789-D

CV001 Main steam flow


-----------------------------------------------------------------------------------------------------------------------CV185

IPT leak off thru front seals


=Fn(CV001)
-IPT leak off thru front seals is a function of main steam flow.

T/Hr

Where
CV001 Main steam flow
-----------------------------------------------------------------------------------------------------------------------CV187
Steam leakage into LPT =Fn(CV001)
-Steam leakage into LPT is a function of main steam flow
T/Hr
Where
CV001 Main steam flow
----------------------------------------------------------------------------------------------------------------------CV188

IPT and LPT leakage

=CV183+CV184+CV185-CV187

Where
CV183 IPT leakoff thru control valves
CV184 IPT leakoff thru rear seals
CV185 IPT leakoff thru front seals
CV187 Steam leakage into LPT
--------------------------------------------------------------------------------------------------------------------CV108
Generator variable losses
=Fn(AV049
-A function of gross generation MW
Where
AV049 Gross generation
---------------------------------------------------------------------------------------------------------------------CV109

LP turbine exhaust enthalpy (Ideal)


=Fn(AV035,AV036 + KN003, CV110)
-A function of temperature inlet and inlet and outlet pressure.
KCAL/KG
Where
AV035 LPH 2 extraction temperature
AV036 LPH 2 extraction pressure
CV110 Condenser vacuum (In absolute)
KN003 Atmospheric pressure

-----------------------------------------------------------------------------------------------------------------------CV189

HPT front seal leakoff enthalpy =Fn(CV001)


-HPT front seal leakoff enthalpy is a function of main steam flow.
Where
CV001 Main steam flow
----------------------------------------------------------------------------------------------------------------------CV190

HPT rear seal leakoff enthalpy

=Fn(CV001)

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

Page :

En

36

YN1G176789-D

-HPT rear seal leakoff enthalpy is a function of main steam flow


Where
CV001 Main steam flow
----------------------------------------------------------------------------------------------------------------------CV191

HPT CV seal leakoff enthalpy =Fn(CV001)


-HPT CV seal leakoff enthalpy is a function of main steam flow

Where
CV001 Main steam flow
-----------------------------------------------------------------------------------------------------------------------CV192

HPT front seal to HPT exhaust steam enthalpy =Fn(CV001)


-HPT front seal to HPT exhaust steam enthalpy is a function of main steam flow
Where
CV001 Main steam flow

----------------------------------------------------------------------------------------------------------------------CV193

IPT front seal leakoff enthalpy =Fn(CV001)


-IPT front seal leakoff enthalpy is a function of main steam flow
Where
CV001 Main steam flow

--------------------------------------------------------------------------------------------------------------------CV194
IPT rear seal leakoff enthalpy =Fn(CV001)
-IPT rear seal leakoff enthalpy is a function of main steam flow.
BHEL drg MS-0105-HW-03020.
Where
CV001 Main steam flow
---------------------------------------------------------------------------------------------------------------------CV195

IPT CV seal leakoff enthalpy


=Fn(CV001)
-IPT CV seal leakoff enthalpy is a function of main steam flow
Where
CV001 Main steam flow

----------------------------------------------------------------------------------------------------------------------CV196
Steam leakage into LPT enthalpy
=Fn(CV001)
-Steam leakage into LPT enthalpy is a function of main steam flow
Where
CV001 Main steam flow

**CV105

LP turbine exhaust flow


=CV036-CV042-CV051 - CV056 - CV089 - AV090 - CV188
-Hot reheat flow minus all extractions of IP and LP turbine sections.

T/Hr

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

Page :

En

37

YN1G176789-D

Where
CV036 Hot reheat flow
CV042 Heater 5 extraction flow
CV051
CV056
CV089
AV090
CV188

Heater 3 extraction flow


Heater 2 extraction flow
Heater 1 extraction flow
Deaerator extraction flow
IPT and LPT leakage

Note :
1) The above equation is valid when the contact status of XZ505 is open
(contact status to be checked at site)
--------------------------------------------------------------------------------------------------------------------------------**CV111

LP turbine exhaust enthalpy (Actual)


= steam-extract-leaks-gener / CV105

steam = CV001*CV090 + CV036*CV094 - CV035*CV091


Where
CV001
CV090
CV036
CV094
CV035
CV091

Main steam flow


Main steam enthalpy
Hot reheat flow
Hot reheat enthalpy
Cold reheat flow
HPT exhaust enthalpy

Extract =
CV028*CV025 + CV042*CV145 + CV051*CV048 + CV056*CV053 + CV089*CV157
+ AV090*HXDEA
Where
CV028
CV025
CV042
CV145

HPH 6 extraction flow


HPH 6 extraction enthalpy
HPH 5 extraction flow
HPH 5 extraction enthalpy

CV051
CV048
CV056
CV053
CV089
CV157
AV090

LPH 3 extraction flow


LPH 3 extraction enthalpy
LPH 2 extraction flow
LPH 2 extraction enthalpy
LPH 1 extraction flow
LPH 1 extraction enthalpy
Deaerator extraction flow

If the contact status of XZ505 is open, then HXDEA = CV145.


GENER=(AV049+CV108 + KN031)860.076
Where
AV049 Gross generation
CV108 Generator variable losses

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

38

YN1G176789-D

KN031 Generation fixed losses


860.076
Conversion from MW to KCAL/Hr
CV105 Low pressure turbine exhaust flow
LEAKS = CV176*CV189 + CV177*CV190 + CV178*CV191 - CV179*CV192 + CV185*CV193 +
CV184*CV194 + CV183*CV195 - CV187*CV196
Where
CV176 HPT leak off thru front seals
CV177 HPT leak off thru rear seals
CV178 HPT leak off thru control valves
CV179 Steam supplied from front sealing of HPT to
HPT exhaust
CV185 IPT leak off thru front seal
CV184 IPT leak off thru rear seals
CV183 IPT leak off thru control valves
CV187 Steam leakage into LPT
CV189 HPT front seal leak off enthalpy
CV190 HPT rear seal leak off enthalpy
CV191 HPT CV seal leak off enthalpy
CV192 HPT front seal to HPT exhaust steam
enthalpy
CV193 IPT front seal leak off enthalpy
CV194 IPT rear seal leak off enthalpy
CV195 IPT CV seal leak off enthalpy
CV196 Steam leakage into LPT enthalpy
**Process TAGS are not available in the database the same to be checked & incorporated at site
along with relevant calculation.
----------------------------------------------------------------------------------------------------------------------------**CV112

LP turbine efficiency
=((CV095-CV111) / (CV095-CV109))*100)
-The ratio of the energy used to the energy theoretically available expressed as a
percentage.
%
Where
CV095 IP turbine exhaust enthalpy
CV109 LP turbine exhaust enthalpy(Ideal)
CV111 LP turbine exhaust enthalpy(Actual)

Note : the contact status to be checked at site CV112 = 0.


-----------------------------------------------------------------------------------------------------------------------------CV205

Ton of Excess Air at AH Inlet Per Ton of Fuel


Fired=54.88*(KN006/100)+20.56*(KN007/100)+ 129.25* (KN008/100)
-16.29*(KN009/100)+4.90*(KN010/100)* ((AV053/100) / (1-4.78*AV053/100))
T/T
Where
KN006
KN007
KN008
KN009

Coal content carbon per cent


Coal content sulfur per cent
Coal content hydrogen per cent
Coal content oxygen per cent

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

39

YN1G176789-D

KN010 Coal content nitrogen per cent


AV053 Economiser outlet oxygen per cent
-----------------------------------------------------------------------------------------------------------------------CV204 Ton of minimum air for complete combustion per ton of fuel fired T/T
=11.51*(KN006/100)+4.35*(KN007/100)+34.30* (KN008/100)-4.35*(KN009/100)
Where
KN006
KN007
KN008
KN009

Coal content carbon percent


Coal content sulfur content
Coal content hydrogen per cent
Coal content oxygen per cent

-----------------------------------------------------------------------------------------------------------------------CV181
Excess air percentage =(CV205/CV204)*100 %
Where
CV205 Ton of excess air per ton of fuel
CV204 Kg of minimum air required for complete
combustion per KG of fuel.
-----------------------------------------------------------------------------------------------------------------------CV182
Excess air percentage standard =Fn(AV049)
-Excess air percentage standard is a function of load.
%
Where
AV049 Gross generation
-----------------------------------------------------------------------------------------------------------------------CV034
Excess Air Deviation
=CV181-CV182 %
Where
CV181 Excess air percentage
CV182 Excess air % standard
-----------------------------------------------------------------------------------------------------------------------CV117

Dry gas per ton of fuel fired

=WAEX+WGMA

Where
WAEX =t of excess air/t of fuel
=(54.88*KN006/100.+20.56*KN007/100. + 129.25 * KN008/100. - 16.29 *
KN009/100. + 4.90*KN010)/100.) * ((AV053/100)/(1-(4.78*AV053/100))
WGMA =T of dry gas/T of fuel in minimum air supply
for complete combustion condition.
=12.482xKN006/100. + 5.301*KN007/100. + 26.260*KN008/100. - 3.309*KN009/100.
+ KN010/100.
Where
KN006
KN007
KN008
KN009
KN010

Coal content carbon


Coal content sulfur
Coal content hydrogen
Coal content oxygen
Coal content nitrogen

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

Page :

En

40

YN1G176789-D

AV053 Economiser outlet oxygen


-------------------------------------------------------------------------------------------------------------------**CV118

Heat loss due to dry gas


=CV117*KN025(AHGOT-AHPAIT * CV004- CV005*AHSAIT)
KCAL/KG

Where
CV117 Dry gas/ fuel fired
KN025 Specific heat of flue gas
AV054 AH A gas out temperature
AV057 AH B gas out temperature
AV060 AH A PA in temperature **
AV062 AH B PA in temperature **
CV004 Fraction of air that is primary air
CV005 Fraction of air that is secondary air
AV064 AH A secondary air in temperature**
AV066 AH B secondary air in temperature**
Note: a) when contact status of SZ517 OR SZ524 is closed the following equation are applicable
AHGOT = AV057, AHPAIT= AV062, AHSPAIT=AV066
b) When contact status of SZ519 OR SZ525 is closed the following equation are applicable
AHGOT = AV054, AHPAIT= AV060, AHSPAIT=AV064
c) When both above note are applicable, CV118=0
d) When none of above notes is applicable the following equations shall be used.
AHGOT = (AV054+AV057)/2, AHPAIT= (AV060+AV062)/2, AHSPAIT=(AV064+AV066)/2
**Process TAGS are not available in the database the same to be checked & incorporated at site
along with relevant calculation.
-----------------------------------------------------------------------------------------------------------------------CV119

Enthalpy of water vapor at exhaust gas temperature


=Fn ((AV054+AV057) / 2, KN003))
-A function of temperature and pressure saturated steam KCAL/KG
Where
AV054 AH A outlet gas temperature
AV057 AH B outlet gas temperature
KN003 Atmospheric pressure

Note: The above equation is valid when contact status of SZ524 AND SZ525 are open.
-------------------------------------------------------------------------------------------------------------------**CV120

Enthalpy of water at ambient temperature =CV004*HPA + CV005*HS A


-A function of inlet air temperature compressed liquid
KCAL/KG
HPA
HS A

= Fn(AV060 + AV062) / 2
= Fn(AV064 + AV066) / 2
Where
AV060
AV062
AV064
AV066
CV004

AH A PA inlet temperature**
AH B PA inlet temperature**
AH A SA inlet temperature
AH B SA inlet temperature
Fraction of air that is primary air

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

41

YN1G176789-D

CV005 Fraction of air that is secondary air


**Process TAGS are not available in the database the same to be checked & incorporated at site
along with relevant calculation.
-----------------------------------------------------------------------------------------------------------------------**CV121

Heat loss due to moisture in fuel =KN011/100. * (CV119-CV120)


-The coal moisture content times the difference in enthalpy of the exhaust gas and
liquid water at ambient. KCAL/KG
Where
KN011 Coal content moisture
CV119 Enthalpy of water vapor at exhaust gas
temperature
CV120 Enthalpy of water at ambient.

**Process TAGS are not available in the database the same to be checked & incorporated at site
along with relevant calculation.
---------------------------------------------------------------------------------------------------------------------**CV122

Heat loss due to water combined from hydrogen


=9.* KN008/100.*(CV119 - CV120)
-A function of moisture and the difference in enthalpy of water at ambient and at
exhaust gas temperature
KCAL/KG
Where
KN008 Coal content hydrogen
CV119 Exhaust gas water vapor enthalpy
CV120 Enthalpy of water at ambient.

-----------------------------------------------------------------------------------------------------------------------CV203
Ton of moisture per ton of dry air (i.e., specific humidity of dry air)
=(KN002* PSAT/100)/(1.608*(KN003-KN002 * PSAT/100))
-Specific humidity is a function of relative humidity, temperature and atmospheric
pressure
Where
KN002 Relative humidity per cent
KN003 Atmospheric pressure kg/sc
PSAT Saturation pressure of water vapor at
ambient temp
PSAT f ((AV140+AV167) / 2)
AV140 FD Fan A discharge temp
AV167 FD Fan B discharge temp
Note:
a) When contact status of SZ506 AND SZ507 are open the above equation is valid
b) When contact status of SZ506 is open AND SZ507 is close, CV203=Fn (KN002, AV140)
c) When contact status of SZ506 is close AND SZ507 is open, CV203=Fn (KN002, AV167)
----------------------------------------------------------------------------------------------------------------------CV164
Heat loss due to moisture in air
=(CV204+CV205)*(CV203*0.477*(TG -TEMP)
KCAL/KG
Where

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

42

YN1G176789-D

CV204 Min air for complete combustion


CV205 Excess air per ton of fuel
CV203 Water vapor content of combustion air
(specific humidity)
0.477 Specific
heat
of
water
vapor
KCAL/KG/Deg C
TG = (AV054+AV057) / 2.
Notes :
1) When the contact status of SZ507 is closed, Temp=AV140
2) When the contact status of SZ506 is closed, Temp =AV167
4) If both the status of SZ506 and SZ507 are closed, CV164=0
3) If both the status of SZ506 and SZ507 are open Temp = (AV140+AV167) / 2
4) TG = (AV054+AV057) / 2. (since the contact status of AH-A GAS O/L Damper and AH-B
O/L Damper not given in database hence AVG. taken)
AV140 Forced draft fan A disch temp
AV167 Forced draft fan B disch temp
AV054 Gas temp after air heater A
AV057 Gas temp after air heater B

gas

---------------------------------------------------------------------------------------------------------------------CV123

Boiler efficiency -Heat loss method


%
=100.*((1-(CV118+CV121 + CV122 + CV164) / KN013)) -(KN014+KN015+KN016)
Where
CV118 Heat loss- dry gas
CV121 Heat loss- moisture in fuel
CV122 Heat loss- combined from hydrogen

KN013 Heating value of coal


KN014 Heat loss refuse
KN015 Heat loss radiation
KN016 Heat loss unmeasured
CV164 Heat loss due to moisture in air
-----------------------------------------------------------------------------------------------------------------------CV124
Net generation =AV049-AV056
-Gross generation less auxiliary power MW
Where
AV049 Gross generation
AV056 Auxiliary power
----------------------------------------------------------------------------------------------------------------------CV125
Auxiliary power per cent = (AV056/AV049) * 100.
-The per cent of gross generation used for auxiliary power.
%
Where
AV056 Auxiliary power
AV049 Gross power
----------------------------------------------------------------------------------------------------------------------CV126

Net turbine heat rate

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

Page :

En

43

YN1G176789-D

=((CV001*(CV090- CV008) + CV035 * (CV094-CV091) + AV013* (CV094-CV008)) /


CV124
-The total heat added to the cycle divided by net generation.
KCAL/ KWH
Where
CV001
CV090
CV035
CV091
CV124
AV013
CV094
CV008

Main steam flow


Enthalpy of main steam
Cold reheat flow
Enthalpy of cold reheat
Net generation
Reheat spray flow
Hot reheat enthalpy
Superheat spray water enthalpy

----------------------------------------------------------------------------------------------------------------------------CV127
Reference Gross turbine heat rate
=Fn(AV049)
-See curve
KCAL KWH
Where
AV049 Gross generation
----------------------------------------------------------------------------------------------------------------------CV166

Gross turbine heat rate =CV126 * CV124/AV049


KCAL/KWH
Where
CV126 Net turbine heat rate
CV124 Net generation
AV049 Gross generation

---------------------------------------------------------------------------------------------------------------------CV133
Adjusted gross turbine heat rate
=CV166*(1-CV128/100.) * (1. + CV129/100.) * (1. + CV130/100.) * (1. +
CV131/100.)* (1+CV167/100)
KCAL/KWH
Where
CV128 Heat rate deviation main steam temperature
CV129 Heat rate deviation reheat steam temp
CV130 Heat rate deviation main steam press
CV131 Heat rate deviation condenser vacuum
CV167 Heat rate deviation Reheater press drop
CV166 Gross turbine heat rate
-----------------------------------------------------------------------------------------------------------------------CV200

Reheater outlet enthalpy

=Fn((AV101+AV102),AV103+KN003)
Where
AV101 Reheater outlet steam temp left
AV102 Reheater outlet steam temp right
AV103 Reheater outlet steam pressure
KN003 Atmospheric pressure

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

Page :

En

YN1G176789-D

44

----------------------------------------------------------------------------------------------------------------------CV138

Boiler efficiency by input-output method


={{ (AV001-KN001)* (CV199-CV008) + AV076*(CV199-CV008) + CV035*(CV200CV091) +(AV013 (CV200-(KN032-CV008) + KN001*CV008) } /
{KN013*(AV104+AV105 + AV106 + AV107 + AV108 + AV109) + ((AV110 -AV111) /
1000) * KN026 + (KN033 / 1000) }} 100 %

Where
AV001 Feedwater flow
KN001 Blowdown flow
CV199 Superheater outlet enthalpy
CV008 Superheater spray water enthalpy
Economiser inlet enthalpy
AV076 Superheat spray water flow
CV035 Cold reheat flow
CV200 Reheater outlet enthalpy
CV091 HP turbine exhaust enthalpy
AV013 Reheat spray flow
KN032 Blow down enthalpy
KN013 Heating value of coal
AV104 Mill A coal flow
AV105 Mill B coal flow
AV106 Mill C coal flow
AV107 Mill D coal flow
AV108 Mill E coal flow
AV109 Mill F coal flow
AV110 Heavy oil supply flow
AV111 Heavy oil return flow
KN026 Heating value of fuel oil
KN033 Heat added other than chemical
-----------------------------------------------------------------------------------------------------------------------CV137

Average boiler efficiency


-Heat loss and input/output method

=(CV123+CV138) / 2

Where
CV123 Boiler efficiency by heat loss method
CV138 Boiler efficiency by input/output method
-----------------------------------------------------------------------------------------------------------------------CV136

Gross unit heat rate


= (CV166/CV137) * 100
-Net heat rate adjusted for gross generation
KCAL/KWH
Where
CV166 Gross turbine heat rate
CV137 Boiler efficiency (Average of heat loss and
input/output methods)

-----------------------------------------------------------------------------------------------------------------------CV169
Net unit heat rate
=CV136 * AV049/CV124
KCAL/KWH

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

45

YN1G176789-D

Where
CV136 Gross unit heat rate
AV049 Gross generation
CV124 Net generation
----------------------------------------------------------------------------------------------------------------------CV152
Circulating water velocity in condenser B tubes
=1/2((AV120/KN021*KN036*3600)+( AV120/KN021*KN058*3600)) M/S
Where
AV120 Condenser flow, left
KN021 Condenser cross section area per tube
KN036 Number of tubes condenser B first pass
3600 Conversion from m/hr to m/s
KN058 Number of tubes condenser B Second pass
-----------------------------------------------------------------------------------------------------------------------CV153

Condenser B basic heat transfer coefficient uncorrected 2290.5 * (CV152)1/2


-A function of velocity KCAL/HR/SQM/DEG C
Where
CV152 Circulating water velocity through condenser
B

-----------------------------------------------------------------------------------------------------------------------CV154

Condenser B basic heat transfer coefficient corrected


=CV152*CV058*KN018
KCAL/HR/SQM/DEG C
Where
CV153 Uncorrected heat transfer coefficient for
condenser B
CV058 Temperature correction factor
KN018 Tube metal correction factor

-----------------------------------------------------------------------------------------------------------------------CV155
Condenser B terminal temperature difference
=CV066 - AV095
DEG C
Where
CV066 Condenser saturation temp
AV095 Condenser B outlet temp
Note: When HZ503 contact status closed, CV155=0.
-----------------------------------------------------------------------------------------------------------------------CV156

Condenser B temperature rise


DEG C

=AV095-AV092
Where
AV095 Condenser B outlet temp
AV092 Cooling water temp

Note: When the contact status of HZ501 is closed, CV156=0.

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

Page :

En

46

YN1G176789-D

-----------------------------------------------------------------------------------------------------------------------CV160

Condensate enthalpy leaving condenser B


=Fn(AV122)
-A function of condensate temp leaving condenser B
KCAL/KG

Where
AV122 Condensate suction pump temp
----------------------------------------------------------------------------------------------------------------------CV161

Steam energy removed in condenser B


= AV120*KN034*KN035 * (AV095-AV092)
KCAL/HR
Where
AV120 condenser flow, left
KN034 Circulating water density
KN035 Specific heat of circulating water for mean
temp and salinity
AV092 Condenser cooling water temp
AV095 Circulating water at condenser B outlet temp

-----------------------------------------------------------------------------------------------------------------------CV197

Logarithmic mean temperature for condenser B


=((CV066-AV092)-(CV066-AV095))/ln ((CV066-AV092)/(CV066-AV095))
DEG C
Where
CV066 Condenser saturation temp
AV092 Condenser cooling water temp
AV095 Cooling water at condenser B outlet temp

Note : When contact status of HZ501 is closed, CV197=0.


----------------------------------------------------------------------------------------------------------------------CV162

Condenser B actual heat transfer coefficient


=CV161/(CV197*KN057*(KN036 + KN058)
KCAL/HR/SQM/DEG C
Where
CV161 Steam energy removed in condenser B
CV197 LMTD for condenser B
KN057 Condenser surface area per tube
KN036 Number of tubes in first pass of condenser B

KN058 Number of tubes in second


condenser B
Note : When contact status of HZ501 is closed, CV162=0.
-----------------------------------------------------------------------------------------------------------------------CV163

condenser B cleanliness factor =CV162/CV154 * 100

pass of

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

YN1G176789-D

47

Where
CV162 Condenser B actual heat transfer rate
CV154 Condenser B basic heat transfer rate
corrected.
----------------------------------------------------------------------------------------------------------------------CV170
Boiler efficiency deviation between heat loss and input/output method
=ABS (CV123-CV138)
-Percentage deviation of heat loss method and input/output method
%
Where
CV123 Boiler efficiency by heat loss method
CV138 Boiler efficiency by input/output method
ABS
Absolute value
-----------------------------------------------------------------------------------------------------------------------CV171

Heater 1 saturation temperature =Fn(AV040+KN003)


-A function of extraction pressure to the heater Deg C

Where
AV040 Heater 1 extraction pressure
KN003 Atmospheric pressure
-----------------------------------------------------------------------------------------------------------------------CV172

Heater 1A terminal temp difference


=CV171-AV037
-The approach to the saturation for the condensate leaving the heater.

Deg C

Where
CV171 Heater 1 saturation temp
AV037 Heater 1A condensate temp out
-----------------------------------------------------------------------------------------------------------------------CV173

Heater 1B terminal temp difference


=CV171-AV121
-The approach to the saturation for the condensate leaving the heater.

Deg C

Where
CV171 Heater 1 saturation temp
AV121 Heater 1B condensate temp out
Note : When contact status of CZ512 and CZ513 are closed, CV162=0.
----------------------------------------------------------------------------------------------------------------------CV278

Economiser pressure drop in gas path with respect to load


KG/SC

Fn(AV049)

Where
AV049 Gross generation
----------------------------------------------------------------------------------------------------------------------CV174

Economiser press drop performance deviation


={(AV136-CV278) / CV278} *100
Where

-See curve

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

Page :

En

48

YN1G176789-D

CV278 Economiser press drop in gas path with


respect to load
AV136 Measured press drop in gas path across
economiser
-----------------------------------------------------------------------------------------------------------------------CV279

Economiser temperature rise as a function of load


DEG C

=Fn(AV049)

Where
AV049 Gross generation
-----------------------------------------------------------------------------------------------------------------------CV175

Economiser temp rise performance deviation


=CV279-((AV138+AV139)/2- AV088))
-See curve
DEG C
Where
CV279
AV138
AV139
AV088

Econ temp rise as a function of load


Econ temp outlet left of feedwater
Econ temp outlet right of feedwater
Econ temp inlet of feedwater

----------------------------------------------------------------------------------------------------------------------CV198

HPH-5 drain cooler approach


DEG C

=AV069-AV071
Where
AV069 HPH-5 drain temperature
AV071 HPH-5 CNDS in temp

Note: When contact status of XZ503 OR FZ507 OR FZ506 are closed, CV198 = 0
----------------------------------------------------------------------------------------------------------------------CV201

Ton of dry air leakage in AH A per the quantity of wet flue gas per ton of fuel fired
entering AH A = (54.88*KN006/100 + 20.56 * KN007/100 + 129.25 * KN008/10016.29 * KN009/100+4.90 * KN010/100) * (
KN037/100/((1-4.78*KN037/100)(AV053/100)*(1-4.78*AV053/100))
Where
KN037 Entered value = per cent oxygen by volume
for gas at AH A outlet
AV053 Per cent oxygen by volume for gas at AH
inlet
KN006 Coal content carbon per cent
KN007 Coal content sulper per cent
KN008 Coal content hydrogen per cent
KN009 Coal content oxygen per cent
KN010 Coal content nitrogen per cent

Note: When contact status of SP573 is ON, CV201=0.


-----------------------------------------------------------------------------------------------------------------------

Revision 1

CV202

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

49

YN1G176789-D

Ton of dry air leakage in AH B per the quantity of wet flue gas per ton of fuel fired
entering AH B
= (( 54.88 * KN006/100 + 20.56 * KN007/100 + 129.25 * KN008/100 16.29 *
KN009/100 + 4.90 * KN010/100) * (KN038/100) / ((1-4.78 * KN038/100)
(AV053/100) * (1-.78 * AV053/100))
Where
KN038 Entered value = per cent oxygen by volume
for gas at AH B outlet
AV053 Percent oxygen by volume for gas at AH
inlet
KN006 Coal content carbon per cent
KN007 Coal content sulfur per cent
KN008 Coal content hydrogen per cent
KN009 Coal content oxygen per cent
KN010 Coal content nitrogen per cent

Note: When contact status of SP574 is ON, CV202=0


---------------------------------------------------------------------------------------------------------------------CV206

Ton of wet air leakage in AH A per the quantity of wet flue gas per ton of fuel fired
entering AH A =CV201*(1+CV203)
T

Where
CV201 Ton of dry air leakage in AH A per the
quantity of wet flue gas per ton of fuel fired entering
AH A
CV203 Ton of moisture per ton of dry air (i.e.,
specific humidity per ton)
-----------------------------------------------------------------------------------------------------------------------CV207

Ton of wet air leakage in AH B per the quantity of wet flue gas per ton of fuel fired
entering AH B =CV202*(1+CV203)
T
Where
CV202 Ton of dry air leakage in AH B per the
quantity of wet flue gas per ton of fuel fired entering
AH B
CV203 Ton of moisture per ton of dry air (I.e.,
specific humidity per ton)

-----------------------------------------------------------------------------------------------------------------------CV208

Ton of moisture in flue gas at AH inlet per ton of fuel fired


=KN011/100+9 * KN008/100+CV203 * (CV204+CV205) T/T
Where
KN011 Coal content moisture per cent
KN008 Coal content hydrogen per cent
CV203 Sp. Humidity of air T/T
CV204

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

50

YN1G176789-D

imum air for complete combustion per ton of fuel


fired
CV205 Ton of excess air at economiser outlet per
ton of fuel fired.
-----------------------------------------------------------------------------------------------------------------------CV209

Ton of wet gas at AH inlet per ton of fuel fired


=CV117+CV208
T
Where
CV117 Dry gas per ton of fuel fired
CV208 Ton of moisture in AH inlet flue gas per ton
of fuel fired.

-----------------------------------------------------------------------------------------------------------------------CV210

Percentage air leakage of AH A =(CV206/CV209) * 100

Where
CV206 Ton of wet air leakage in AH A per the
quantity of wet flue gas per ton of fuel fired entering
AH A
CV209 Ton of wet gas at AH inlet per ton of fuel
fired.
----------------------------------------------------------------------------------------------------------------------CV211

Percentage air leakage of AH B =(CV207/CV209)*100


Where
CV207 Ton of wet air leakage in AH B per the
quantity of wet flue gas per ton of fuel fired entering
AH B
CV209 Ton of wet gas at AH inlet per ton of fuel
fired.

-----------------------------------------------------------------------------------------------------------------------CV266

AH A sec air inlet pressure


=AV165-37*((AV083)2/(KN055)2 )* ((AV064+273.2) / (KN044+273.2))
Where
AV165 FD fan A disch pressure
AV166 FD fan B disch pressure
KN055 Sec air flow at MCR through each air heater
KN044
AV083
AV064
AV084

Design temp AH inlet sec air


Sec air flow left
AH A sec air in temp**
Sec air flow right

Note :
1) The above equation is applicable when the contact status of SP573 or SS556 and SS558,
SP574are on and SZ506 and SZ507 are open.
2) When the contacts of SZ506, SZ507 are open and SP573or SS556 is on, & SP574 and SS558
off, use the following equation
CV266=AV165-37 * (AV083+AV084)2/(KN055)2 * (AV064+273.2)/(KN044+273.2)

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

51

YN1G176789-D

3) When the contacts of SZ506 is open and SP573 or SS556 and SP574 or SS558 are on, and
SZ507 is closed, use the following equation
CV266=AV165-37 * (AV083)2/(KN055)2 * (AV064+273.2)/(KN044+273.2)
4) When the contacts of SP573 or SS556 is on and SZ506 is open, and SP574 and SS558 are off
and SZ507 is closed, use the following equation
CV266=AV165-37 * (AV083+AV084)2/(KN055)2 * (AV064+273.2)/(KN044+273.2)
5) When the contacts of SZ507 is open, SP573 or SS556 and SP574 or SS558 are on, and SZ506 is
closed, use the following equation
CV266=AV166-37 * (AV083)2/(KN055)2 * (AV064+273.2)/(KN044+273.2)
6) When the contacts of SZ507 is open, and SP573 or SS556 is on, and SZ506 is closed & SP574
and SS558 are off, use the following equation
CV266=AV166-37 * (AV083+AV084)2/(KN055)2 * (AV064+273.2)/(KN044+273.2)
7) When the contact status of SP573 is closed, CV266=0.
-----------------------------------------------------------------------------------------------------------------------**CV212 Fraction of the total air leakage of AH A coming from primary of air side
= { ((( AV155 AV156) * (AV064 + 273.2)) / ((CV266 AV156) * (AV060 + 273.2))) 1/2 /
{ 1 + ((( AV155 AV156) * (AV064 + 273.2)) / ((CV266 AV156) * (AV060 + 273.2))) 1/2 }}
Where
AV060 AH A PA in temp**
AV064 AH A sec air in temp
AV155 AH A PA in press
AV156 AH A gas out press
CV266 AH A sec air in press
Note : When the contact status of SP573 and SS556 is off, CV212=0.
**Process TAGS are not available in the database the same to be checked & incorporated at site
along with relevant calculation.
-----------------------------------------------------------------------------------------------------------------------CV213

Fraction of the total air leakage of AH A coming from secondary air side
=1-CV212
Where
CV212 Fraction of AH A total air leakage coming
from primary air side

Note : When contact status of SP573 & SS556 is off, CV213=0.


-----------------------------------------------------------------------------------------------------------------------CV267

AH B sec air inlet pressure


=AV166-37*((AV084)2/(KN055)2 )* ((AV066+273.2)/(KN044+273.2))
Where
AV165 FD fan A disch pressure
AV166 FD fan B disch pressure
KN055 Sec air flow at MCR through each air heater
KN044
AV066
AV083
AV084

Design temp AH inlet sec air


AH B sec air in temp
Sec air flow left
Sec air flow right

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

Page :

En

52

YN1G176789-D

-----------------------------------------------------------------------------------------------------------------------CV214

Fraction of the total air leakage of AH B coming from primary air side
= { ((( AV158 AV157) * (AV066 + 273.2)) / (( CV267 AV157) * (AV062 + 273.2))) 1/2 } / { 1 +
((( AV158 AV157) * (AV066 + 273.2)) / (( CV267 AV157) * (AV062 + 273.2))) 1/2 }}
Where
AV062
AV066
AV157
AV158
CV267

AHA B PA in temp**
AH B sec air in temp
AH B gas out press
AH B PA in press
AH B sec air in press

Note : When contact status of SP574 & SS558 is off, CV214=0.


**Process TAGS are not available in the database the same to be checked & incorporated at site
along with relevant calculation.
-----------------------------------------------------------------------------------------------------------------------CV215

Fraction of the total air leakage of AH B coming from secondary air side
=1-CV214
Where
CV214 Fraction of the total air leakage of AH B
coming from primary air side

Note: When contact status of SP574 & SS558 is off, CV215=0


-----------------------------------------------------------------------------------------------------------------------**CV216

AH A gas out temperature corrected for no leakage


={CV212*CV210 * 0.242 * (AV054-AV060)} / (100*KN025) + {CV213 * CV210 *
0.242*(AV054-AV064)}/100 *KN025) + AV054
DEG C
Where
CV212 Fraction of the total air leakage of AH A
coming from primary air side
CV213 Fraction of the total air leakage of AH A
coming from secondary air side
CV210 Percentage air leakage AH A
0.242 Mean specific heat of air between design air
inlet and gas outlet temp
KN025 Sp heat of flue gas
AV054 AH A gas out temperature
AV060 AH A PA in temperature **
AV064 AH A sec air in temperature

Note : When contact status of SP573 and SS556 is off, CV216=0.


**Process TAGS are not available in the database the same to be checked & incorporated at site
along with relevant calculation.
-----------------------------------------------------------------------------------------------------------------------

Revision 1

**CV217

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

53

YN1G176789-D

AH B gas out temperature corrected for no leakage =CV214*CV211*0.242*(AV057AV062)+/100*KN025 + CV215*CV211*0.242 (AV057-AV066)/(100*KN025) + AV057
DEG C
Where
CV214 Fraction of the total air leakage of AH B
coming from primary air side
CV215 Fraction of the total air leakage of AH B
coming from secondary air side
CV211 Percentage air leakage of AH A
0.242 Mean specific heat of air between design air
inlet and gas outlet temp
KN025 Sp heat of flue gas
AV057 AH B gas out temperature
AV062 AH B PA in temperature **
AV066 AH B sec air in temperature

Note : When contact status of SP574 & SS558 is off, CV217=0


**Process TAGS are not available in the database the same to be checked & incorporated at site
along with relevant calculation.
-----------------------------------------------------------------------------------------------------------------------**CV218

Gas side efficiency-AH A


%
={(AV055-CV216) / (AV055 -(CV004 * AV060+CV005*AV064))} * 100
Where
AV055 AH A gas in temp
CV216 AH A gas out temp corrected for no leakage
CV004
CV005
AV060
AV064

Fraction of air that is primary


Fraction of air that is secondary
AH A primary air inlet temperature**
AH A secondary air inlet temperature

Note : When contact status of SP573 and SS556 is off, CV218=0.


**Process TAGS are not available in the database the same to be checked & incorporated at site
along with relevant calculation.
-----------------------------------------------------------------------------------------------------------------------CV219

Gas side efficiency-AH B


%
={(AV058-CV217) / (AV058 -(CV004*AV062+CV005*AV066))} * 100
Where
AV058 AH B gas in temp
CV217 AH B gas out temp corrected for no leakage
CV004 Fraction of air that is primary
CV005 Fraction of air that is secondary
AV062 AH B primary air inlet temperature

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

54

YN1G176789-D

AV066 AH Bsecondary air inlet temperature


Note : When contact status of SP574 & SS558 is off, CV219=0
----------------------------------------------------------------------------------------------------------------------**CV220

Fraction of mill A primary air which is heated in air heater


=(AV149- (AV060+AV062)/2) / {(AV059+AV061)/2 - (AV060+AV062/2)}
-This is obtained by equating the heat excess of mill air to heat excess of hot primary
air taking cold primary air temp as reference.
Where
AV149
AV059
AV060
AV061
AV062

Mill A inlet PA temp


AH A PA out temp
AH A PA in temp
AH B PA out temp
AH B PA in temp**

Notes :
1) The above equation is applicable when the contact status of SP573 or SS556 and SP574 or
SS558 are on.
2) When the contact status of SP573 SS556 is on and the contact status of SP574 and SS558 is of
use the following
equation for CV220.
CV220=(AV149-AV060)/(AV059-AV060)
3) When the contact status of SP573 and SS556 is off and the contact status of SP574 or SS558 is
on, use the following equation
CV220=(AV149-AV062)/(AV061-AV062)
4) When the contact status of SS576 is off, CV220=0.
**Process TAGS are not available in the database the same to be checked & incorporated at site
along with relevant calculation.
----------------------------------------------------------------------------------------------------------------------**CV221

Fraction of mill B primary air which is heated in air heater


=(AV150-(AV060+AV062)/2) / ((AV059+AV061)/2 - (AV060+AV062)/2)
-This is obtained by equating the heat excess of mill air to heat excess of hot primary
air taking cold primary air temp as reference.
Where
AV150
AV059
AV060
AV061
AV062

Mill B inlet PA temp


AH A PA out temp
AH A PA in temp
AH B PA out temp
AH B PA in temp**

Notes :
1) The above equation is applicable when the contact status of SP573 or SS556 and SP574 or
SS558 are on.
2) When the contact status of SP573 SS556 is on and the contact status of SP574 and SS558 is of
use the following
equation for CV220.
CV221=(AV150-AV060)/(AV059-AV060)
3) When the contact status of SP573 and SS556 is off and the contact status of SP574 or SS558 is
on, use the following equation
CV221=(AV150-AV062)/(AV061-AV062)

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

55

YN1G176789-D

4) When the contact status of SS578 is off, CV221=0.


**Process TAGS are not available in the database the same to be checked & incorporated at site
along with relevant calculation.
-----------------------------------------------------------------------------------------------------------------------**CV222

Fraction of mill C primary air which is heated in air heater


=(AV151-(AV060+AV062)/2) / ((AV059+AV061)/2 - (AV060+AV062)/2)
-This is obtained by equating the heat excess of mill air to heat excess of hot primary
air taking cold primary air temp as reference.
Where
AV151 Mill C inlet PA temp
AV059 AH A PA out temp
AV060 AH A PA in temp**
AV061 AH B PA out temp
AV062 AH B PA in temp**

Notes :
1) The above equation is applicable when the contact status of SP573 or SS556 and SP574 or
SS558 are on.
2) When the contact status of SP573 SS556 is on and the contact status of SP574 and SS558 is of
use the following
equation for CV220.
CV222=(AV151-AV060)/(AV059-AV060)
3) When the contact status of SP573 and SS556 is off and the contact status of SP574 or SS558 is
on, use the following equation
CV222=(AV151-AV062)/(AV061-AV062)
4) When the contact status of SS580 is off, CV222=0.
**Process TAGS are not available in the database the same to be checked & incorporated at site
along with relevant calculation.
-----------------------------------------------------------------------------------------------------------------------**CV223

Fraction of mill D primary air which is heated in air heater


=(AV152-(AV060+AV062)/2) / ((AV059+AV061/2) - (AV060+AV062)/2))
-This is obtained by equating the heat excess of mill air to heat excess of hot primary
air taking cold primary air temp as reference.
Where
AV152
AV059
AV060
AV061
AV062

Mill D PA inlet temp


AH A PA out temp
AH A PA in temp
AH B PA out temp
AH B PA in temp**

Notes :
1) The above equation is applicable when the contact status of SP573 or SS556 and SP574 or
SS558 are on.
2) When the contact status of SP573 SS556 is on and the contact status of SP574 and SS558 is of
use the following
equation for CV223.
CV223=(AV152-AV060)/(AV059-AV060)
3) When the contact status of SP573 and SS556 is off and the contact status of SP574 or SS558 is
on, use the following equation

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

56

YN1G176789-D

CV223=(AV152-AV062)/(AV061-AV062)
4) When the contact status of SS582 is off, CV223=0.
**Process TAGS are not available in the database the same to be checked & incorporated at site
along with relevant calculation.
-----------------------------------------------------------------------------------------------------------------------**CV224

Fraction of mill E primary air which is heated in air heater


=(AV153-(AV060+AV062)/2) / ((AV059+AV061)/2) - (AV060+AV062)/2))
-This is obtained by equating the heat excess of mill air to heat excess of hot primary
air taking cold primary air temp as reference.
Where
AV153
AV059
AV060
AV061
AV062

Mill E PA inlet temp


AH A PA out temp**
AH A PA in temp**
AH B PA out temp**
AH B PA in temp**

Notes :
1) The above equation is applicable when the contact status of SP573 or SS556 and SP574 or
SS558 are on.
2) When the contact status of SP573 SS556 is on and the contact status of SP574 and SS558 is of
use the following
equation for CV220.
CV224=(AV153-AV060)/(AV059-AV060)
3) When the contact status of SP573 and SS556 is off and the contact status of SP574 or SS558 is
on, use the following equation
CV224=(AV153-AV062)/(AV061-AV062)
4) When the contact status of SS584 is off, CV224=0.
**Process TAGS are not available in the database the same to be checked & incorporated at site
along with relevant calculation.
-----------------------------------------------------------------------------------------------------------------------**CV225

Fraction of mill F primary air which is heated in air heater


=(AV154-(AV060+AV062)/2) / ((AV059+AV061)/2) - (AV060+AV062)/2))
-This is obtained by equating the heat excess of mill air to heat excess of hot primary
air taking cold primary air temp as reference.
Where
AV154
AV059
AV060
AV061
AV062

Mill F PA inlet temp


AH A PA out temp**
AH A PA in temp**
AH B PA out temp**
AH B PA in temp**

Notes :
1) The above equation is applicable when the contact status of SP573 or SS556 and SP574 or
SS558 are on.
2) When the contact status of SP573 SS556 is on and the contact status of SP574 and SS558 is of
use the following
equation for CV220.
CV225=(AV154-AV060)/(AV059-AV060)

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

57

YN1G176789-D

3) When the contact status of SP573 and SS556 is off and the contact status of SP574 or SS558 is
on, use the following equation
CV225=(AV154-AV062)/(AV061-AV062)
4) When the contact status of SS586 is off, CV225=0.
**Process TAGS are not available in the database the same to be checked & incorporated at site
along with relevant calculation.
-----------------------------------------------------------------------------------------------------------------------CV226

Fraction of total PA which is hot PA =(AV082*CV220+AV077*CV221+AV078*CV222


+ AV079*CV223+AV080*CV224 + AV081 * CV225 ) / (AV082+AV077 + AV078 +
AV079 + AV080 + AV081)

Where
CV220 Fraction of mill A primary air which
in AH
CV221 Fraction of mill B primary air which
in AH
CV222 Fraction of mill C primary air
heated in AH
CV223 Fraction of mill D primary air
heated in AH
CV224 Fraction of mill E primary air
heated in AH
CV225 Fraction of mill F primary air which
in AH
AV082 Mill A PA flow
AV077 Mill B PA flow
AV078 Mill C PA flow
AV079 Mill D PA flow
AV080 Mill E PA flow
AV081 Mill F PA flow
----------------------------------------------------------------------------------------------------------------------**CV229

is heated
is heated
which is
which is
which is
is heated

Test X ratio AH A
=(AV055-CV216) * (1-CV004*CV228) / (CV004*CV226 * (AV059-AV060) + CV005 *
(AV063-AV064))
-This is found as the ratio of heat capacity of the total air passing through the air
heater to the heat capacity of the gas passing through the heater.
Where
AV055 AH A gas in temp
CV216 AH A gas out temp corrected for no
leakage
CV004 Fraction of air that is primary air
CV228 Fraction of total PA which is cold
PA=1-CV266
CV226 Fraction of total PA which is hot PA
CV005 Fraction of air that is secondary air
AV059 AH A PA out temp**
AV060 AH A PA in temp**
AV063 AH A sec air out temp

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

58

YN1G176789-D

AV064 AH A sec air in temp


Note : When contact status of SP573 is closed, CV229=0.
**Process TAGS are not available in the database the same to be checked & incorporated at site
along with relevant calculation.
---------------------------------------------------------------------------------------------------------------------**CV230

Test X ratio AH B
=(AV058-CV217) * (1-CV004*CV228) / (CV004*CV226 * (AV061-AV062) + CV005 *
(AV065-AV066))
Where
AV058 AH B gas in temp
CV217 AH B gas out temp corrected for no leakage
CV004
CV228
CV226
CV226
CV005
AV061
AV062
AV065
AV066

Fraction of air that is primary air


Fraction of total PA which is cold PA=1Fraction of total PA which is hot PA
Fraction of air that is secondary air
AH B PA out temp**
AH B PA in temp**
AH B sec air out temp
AH B sec air in temp

**Process TAGS are not available in the database the same to be checked & incorporated at site
along with relevant calculation.
-----------------------------------------------------------------------------------------------------------------------CV233

Ton of coal fired per hour


=AV104+AV105 + AV106 + AV107 + AV108 + AV109
Where
AV104
AV105
AV106
AV107
AV108
AV109

T/HR

Mill A coal flow


Mill B coal flow
Mill C coal flow
Mill D coal flow
Mill E coal flow
Mill F coal flow

-----------------------------------------------------------------------------------------------------------------------*CV231

Corrected percentage air leakage of AH A for deviation from design pressure


differential and from design air temperature
= ( CV212 * CV210 * CV209 * CV233 / ( 2 * KN039 )) * ((( KN040 KN042) / (AV155
AV156)) * (( AV060 + 273.2) + (KN041 + 273.2))) 1/2
+ ( CV213 * CV210 * CV209 * CV233 / ( 2 * KN039 )) * ((( KN043 KN042) / (CV266
AV156)) * (AV064 + 273.2) + (KN044 + 273.2))) 1/2
Where

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

59

YN1G176789-D

CV212 Fraction of the total air leakage of AH A


coming from primary air side
CV213 Fraction of the total air leakage of AH B
coming from secondary air side
CV210 Per cent air leakage of AH A
CV209 Ton of wet gas at AH inlet per ton of fuel
fired
CV233 Ton of coal fired per hour
CV266 AH A secondary air inlet pressure
KN039 Design rated value of wet gas flow through
each air heater
KN040 Design pressure AH inlet PA
KN041 Design temp AH inlet PA
KN042 Design press AH outlet gas
KN043 Design press AH inlet sec air
AV060 AH A PA in temp*
KN044 Design temp AH inlet sec air
AV064 AH A sec air in temp
AV155 AH A PA in press
AV156 AH A gas out press
Notes :
1) The above equation is applicable when the contact status of SP573 SS556 and SP574 or SS558
are on
2) When the contact status of SP573 or SS556 is on and the contact status of SP574 and SS558 is
off use the following equation
CV231 = (CV212 * CV210 * CV209 * CV233 / (KN039)) * (((KN040 KN042) /
(AV155 AV156)) * ((AV060 + 273.2) + (KN041 + 273.2))) 1/2
+ ( CV213 * CV210 * CV209 * CV233 / (KN039)) * ((( KN043 KN042) /
(( CV266 AV156 )) * (( AV064 + 273.2) + ( KN044 + 273.2 ))) 1/2
* To be checked at site
----------------------------------------------------------------------------------------------------------------------*CV232

Corrected percentage air leakage of AH B for deviation from design pressure


differential and from design air temperature
CV232 = ( CV214 * CV211 * CV209 * CV233 / (KN039)) * ((( KN040 KN042) /
(AV158 AV157)) * ((AV062 + 273.2) + (KN041 + 273.2))) 1/2
+ ( CV215 * CV211 * CV209 * CV233 / (KN039)) * ((( KN043 KN042) /
(( CV267 AV157 )) * (( AV066 + 273.2) + ( KN044 + 273.2 ))) 1/2
Where
CV214 Fraction of the total air leakage of AH B
coming from primary air side
CV215 Fraction of the total air leakage of AH B
coming from secondary air side
CV211 Per cent air leakage of AH B
CV209 Ton of wet gas at AH inlet per ton of fuel
fired
CV233 Ton of coal fired per hour
KN039 Design rated value of wet gas flow through
each air heater

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

KN040
KN041
KN042
KN043
KN044
AV062
AV066
AV157
AV158
CV267

En

Page :

60

YN1G176789-D

Design pressure AH inlet PA


Design temp AH inlet PA
Design press AH outlet gas
Design press AH inlet sec air
Design temp AH inlet sec air
AH B PA in temp*
AH B sec air inlet temp
AH B gas outlet press
AH A PA in press
AH B sec air in press

Notes :
1) The above equation is applicable when the contact status of SP573 SS556 and SP574 or SS558
are on
2) When the contact status of SP573 or SS556 is on and the contact status of SP574 and SS558 is
off use the following equation
CV232 = ( CV214 * CV211 * CV209 * CV233 / (KN039)) * ((( KN040 KN042) /
(AV158 AV157)) * ((AV062 + 273.2) + (KN041 + 273.2))) 1/2
+ ( CV215 * CV211 * CV209 * CV233 / (KN039)) * ((( KN043 KN042) /
(( CV267 AV157 )) * (( AV066 + 273.2) + ( KN044 + 273.2 ))) 1/2
* To be checked at site
-----------------------------------------------------------------------------------------------------------------------CV234

Gas side pressure loss of AH A corrected for deviation from design flow and
temperature
CV234 = AV159*(KN039)2 * ((KN045+273.2) + (KN046 + 273.2)) / ((CV209 *
CV233/2)2 * ((AV055 + 273.2) + (AV054 + 273.2)))
MMWCL
Where
AV159 Gas pressure drop across AH A
KN039 Design rated value of wet gas flow through
each air heater
KN045 AH entering gas temp in design rated
condition
KN046 AH exit gas temp in design rated
condition
CV209 Ton of wet gas at AH inlet per ton of fuel
fired
CV233 Ton of coal fired per hour
AV055 AH A gas in temp
AV054 AH A gas out temp

Note :
1) The above equation is applicable when the contact status of SP573 SS556 and SP574 or SS558
are on
2) When the contact status of SP573 or SS556 is on and the contact status of SP574 and SS558 is
off use the following equation

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

61

YN1G176789-D

CV234 = AV159*(KN045)2 * ((KN045+273.2) + (KN046 + 273.2)) / ((CV209 *


CV233/2)2 * ((AV055 + 273.2) + (AV054 + 273.2)))
MMWCL
-----------------------------------------------------------------------------------------------------------------------CV235

Gas side pressure loss of AH B corrected for deviation from design flow and
temperature
CV235 = AV160*(KN039)2 * ((KN045+273.2) + (KN046 + 273.2)) / ((CV209 *
CV233/2)2 * ((AV058 + 273.2) + (AV057 + 273.2)))
MMWCL
Where
AV160 Gas pressure drop across AH B
KN039 Design rated value of wet gas flow through
each air heater
KN045 AH entering gas temp in design rated
condition
KN046 AH exit gas temp in design rated condition
CV209
fired
CV233
AV057
AV058

Ton of wet gas at AH inlet per ton of fuel


Ton of coal fired per hour
AH B gas in temp
AH B gas out temp

Note :
1) The above equation is applicable when the contact status of SP573 SS556 and SP574 or SS558
are on
2) When the contact status of SP573 or SS556 is on and the contact status of SP574 and SS558 is
off use the following equation
CV235 = AV160 * (KN045)2 * ((KN045+273.2) + (KN046 + 273.2)) / ((CV209 *
CV233/2)2 * ((AV058 + 273.2) + (AV057 + 273.2)))
MMWCL
-----------------------------------------------------------------------------------------------------------------------CV238

PA flow through AH A
T/HR
=(AV077+AV078 + AV079 + AV080+ AV081+AV082) * CV226/2
Where
AV077
AV078
AV079
AV080
AV081
AV082
CV226

Mill B PA flow
Mill C PA flow
Mill D PA flow
Mill E A flow
Mill F PA flow
Mill A PA flow
Fraction of total PA which is hot PA

Note :
1) The above equation is applicable when the contact status of SP573 & SS556 and SP574 & SS558
are on
2) When the contact status of SP573 & SS556 are on and the contact status of SP574 or SS558 are
off, use the following equation
(AV077+AV078 + AV079 + AV080+ AV081+AV082) * CV226
3) When the contact status of SP573 or SS556 is off, CV238=0.

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

Page :

En

62

YN1G176789-D

----------------------------------------------------------------------------------------------------------------------**CV236

Primary air side pressure loss of AH A corrected for deviation from design flow and
temperatures =AV161* (KN047)2 * ((KN041 + 273.2) + ( KN038 + 273.2)) /
((CV238)2 * ((AV060 + 273.2) + (AV059 + 273.21)))
MMWCL
Where
AV161
KN047
heater
KN041
KN048
CV238
AV060
AV059

PA pressure drop across AH A


Design rated PA flow through each air
Design PA in temp
Design PA out temp
PA flow through AH A
AH A PA in temp**
AH A PA out temp**

**Process TAGS are not available in the database the same to be checked & incorporated at site
along with relevant calculation.
-----------------------------------------------------------------------------------------------------------------------CV239

PA flow through AH B
T/HR
=(AV077+AV078 + AV079 + AV080+ AV081+AV082) * CV226/2
Where
AV077
AV078
AV079
AV080
AV081
AV082
CV226

Mill B PA flow
Mill C PA flow
Mill D PA flow
Mill E PA flow
Mill F PA flow
Mill A PA flow
Fraction of total PA which is hot PA

Note :
1) The above equation is applicable when the contact status of SP573 & SS556 and SP574 & SS558
are on
2) When the contact status of SP573 & SS556 are on and the contact status of SP574 or SS558 are
off, use the following equation
(AV077+AV078 + AV079 + AV080+ AV081+AV082) * CV226
3) When the contact status of SS598 or SS555 is off, CV239=0.
----------------------------------------------------------------------------------------------------------------------**CV237

Primary air side pressure loss of AH B corrected for deviation from design flow and
temperatures =AV162* (KN047)2 * ((KN041 + 273.2) + KN048 + 273.2)) /
(CV239)2 * ((AV062 + 273.2) + (AV061 + 273.21)
MMWCL
Where
AV162
KN047
heater
KN041
KN048
CV239
AV062

PA pressure drop across AH B


Design rated PA flow through each air
Design PA in temp
Design PA out temp
PA flow through AH B
AH B PA in temp**

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

63

YN1G176789-D

AV061 AH B PA out temp**


**Process TAGS are not available in the database the same to be checked & incorporated at site
along with relevant calculation.
----------------------------------------------------------------------------------------------------------------------**CV240

Secondary air side pressure loss of AH A corrected for deviation from design flow and
temperatures =AV163* (KN049)2 * ((KN044 + 273.2) + ( KN050 + 273.2)) /
((AV083)2 * ((AV064 + 273.2) + (AV063 + 273.21)))
MMWCL
Where
AV163
KN049
KN044
KN050
AV083
AV084
AV064
AV063

AH A Sec air press drop


Design rated Sec air flow of each AH
Design rated sec air inlet temp
Design rated sec air outlet temp
Sec air flow left
Sec air flow right
AH A sec air in temp**
AH A sec air out temp**

Notes :
1) The above equation is applicable when the contact status of SP573 & SS556 and SP574 & SS558
are on
2) When the contact status of SP573 & SS556 are on, and the contact status of SP574 or SS558 are
off, use the following equation
AV163* (KN049)2 * ((KN044 + 273.2) + (KN050 + 273.2)) / (AV083) 2 * ((AV064 + 273.2) + (AV063 +
273.21))
3) When the contact status of SP573 or SS556 is off, CV240=0.
**Process TAGS are not available in the database the same to be checked & incorporated at site
along with relevant calculation.
-----------------------------------------------------------------------------------------------------------------------**CV241

Secondary air side pressure loss of AH B corrected for deviation from design flow
and temperatures
=AV164* (KN049)2 * ((KN044 + 273.2) + (KN050 + 273.2)) /
2
((AV084) * ((AV066 + 273.2) + (AV065 + 273.21)))
MMWCL
Where
AV164
KN049
KN044
KN050
AV083
AV084
AV066
AV065

AH B Sec air press drop


Design rated Sec air flow of each AH
Design rated sec air inlet temp
Design rated sec air outlet temp
Sec air flow left
Sec air flow right
AH B sec air in temp**
AH B sec air out temp**

Notes:
1) The above equation is applicable when the contact status of SP573 & SS556 and SP574 & SS558
are on
2) When the contact status of SP573 or SS556 is off and the contact status of SP574 & SS558 is on,
use the following equation
AV164* (KN049)2 * ((KN044 + 273.2) + (KN050 + 273.2)) / ((AV084) 2 * ((AV066 + 273.2) + (AV065 +
273.21)))

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

64

YN1G176789-D

3) When the contact status of SP574 or SS558 is off, CV241=0.


**Process TAGS are not available in the database the same to be checked & incorporated at site
along with relevant calculation.
-----------------------------------------------------------------------------------------------------------------------CV242

Corrected gas temperature leaving AH A for deviation from design entering air
temperature
=KN044 * (AV055 - AV054) + AV055 * ((AV054-(CV004 * AV060 +
CV005 * AV064)) / (AV055- (CV004 * AV060 + CV005 * AV064))
DEG C
Where
KN044
AV055
AV054
AV060
AV064
CV004
CV005

Design air inlet temp of AH


AH A gas in temp
AH A gas out temp
AH A PA in temp
AH A sec air in temp
Fraction of air that is PA
Fraction of air that is Sec air

Note : When contact status of SP573 or SS556 is off, CV242=0.


----------------------------------------------------------------------------------------------------------------------CV243

Corrected gas temperature leaving AH B for deviation from design entering air
temperature
=KN044 * (AV058 - AV057) + AV058 * ((AV057-(CV004 * AV062+
CV005 * AV066)) / (AV058- (CV004 * AV062 + CV005 * AV066))
DEG C
Where
KN044
AV058
AV057
AV062
AV066
CV004
CV005

Design air inlet temp of AH


AH B gas in temp
AH B gas out temp
AH B PA in temp
AH B sec air in temp
Fraction of air that is PA
Fraction of air that is Sec air

---------------------------------------------------------------------------------------------------------------------CV244

Corrected gas temperature leaving AH A for deviation from design entering gas
temperature
=(KN045*((AV054-(CV004*AV060 + CV005 * AV064)) + (CV004 *
AV060 + CV005 * AV064) * (AV055 - AV054))) / (AV055-(CV004 * AV060 + CV005 *
AV064))
DEG C
Where
KN045
AV054
AV055
AV060
AV064
CV004

Design air inlet temp of AH


AH A gas in temp
AH A gas out temp
AH A PA in temp
AH A sec air in temp
Fraction of air that is PA

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

65

YN1G176789-D

CV005 Fraction of air that is Sec air


Note : When contact status of SP573 or SS556 is off, CV244=0.
---------------------------------------------------------------------------------------------------------------------**CV245

Corrected gas temperature leaving AH B for deviation from design entering gas
temperature
=(KN045*((AV057-(CV004*AV062 + CV005 * AV066)) + (CV004 *
AV062 + CV005 * AV066) * (AV058 - AV057)) )/ (AV058-(CV004 * AV062 + CV005 *
AV066))
DEG C
Where
KN045
AV057
AV058
AV062
AV066
CV004
CV005

Design air inlet temp of AH


AH B gas out temp
AH B gas in temp
AH A PA in temp**
AH A sec air in temp
Fraction of air that is PA
Fraction of air that is Sec air

Note : When contact status of SP574 or SS558 is off, CV245=0.


**Process TAGS are not available in the database the same to be checked & incorporated at site
along with relevant calculation.
-----------------------------------------------------------------------------------------------------------------------CV248

Correction factor for gas out temp of AH A as a function of test X ratio


=Fn(CV229)
Where
CV229 Test X ratio of AH A

Note : When contact status of SP573 or SS556 is off, CV248=0.


-----------------------------------------------------------------------------------------------------------------------CV246

Corrected gas temp leaving air heater A for deviation from design X ratio
=AV054 * CV248
Deg C
Where
AV054 AH A gas out temperature
CV248 Correction factor for gas out temp of AH A as
a function of the test X ratio

Note : When contact status of SP573 or SS556 is off, CV246=0.


-----------------------------------------------------------------------------------------------------------------------CV249

Correction factor for gas out temp of AH B as a function of test X ratio


=Fn(CV230)
Where
CV230 Test X ratio of AH B

Note : When contact status of SP574 or SS558 is off, CV249=0.

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

66

YN1G176789-D

----------------------------------------------------------------------------------------------------------------------CV247

Corrected gas temp leaving air heater B for deviation from design X ratio
=AV057 * CV249
Deg C
Where
AV057 AH B gas out temperature
CV248 Correction factor for gas out temp of AH B
as a function of the test X ratio
Note : When contact status of SP574 or SS558 is
off, CV247=0.

-----------------------------------------------------------------------------------------------------------------------CV252

Correction factor for gas temp of AH A for deviation from design entering flue gas
flow
=Fn(CV209 * CV233/2)
-This is found as function of flue gas flow through AH A
Where
CV209 Ton of wet gas at AH inlet per ton of fuel
fired
CV233 Ton of fuel fired per hour

Notes :
1) The above equation is applicable when the contact status of SP573 or SS556 and SP574 or
SS558 are on.
2) When the contact status of SP573 or SS556 is on and the contact status of SP574 or SS558 is off
use the following equation
CV252=Fn(CV209*CV233)
3) When the contact status of SP573 or SS556 is off, CV252=0.
----------------------------------------------------------------------------------------------------------------------CV250

Corrected gas temperature leaving air heater A for deviation from design entering flue
gas flow
=AV054 * CV252
Deg C
Where
AV054 AH A gas out temp
CV252 Correction factor for gas out temp of AH A
for deviation from design entering flue gas flow

Note : When the contact status of SP573 or SS556 is off, CV250=0.


-----------------------------------------------------------------------------------------------------------------------CV253

Correction factor for gas out temp of AH B for deviation from design entering flue gas
flow
=Fn(CV209 * CV233/2)
-This is found as a function of flue gas flow through AH B
Where
CV209 Ton of wet gas at AH inlet per ton of fuel
fired
CV233 Ton of fuel fired per hour

Notes :

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

67

YN1G176789-D

1) The above equation is applicable when the contact status of SP573 or SS556 and SP574 or
SS558 are on
2) When the contact status of SP573 or SS556 is off and the contact status of SP574 or SS558 is on
use the following equation
CV253=Fn(CV209*CV233)
3) When the contact status of SP574 or SS558 is off, CV253=0.
---------------------------------------------------------------------------------------------------------------------CV251

Corrected gas temp leaving air heater B for deviation from design entering flue gas
flow
=AV057 * CV253
DEG C
Where
AV057 AH B gas out temp
CV253 Correction factor for gas out temp of AH B
for deviation from design entering flue gas flow
Note : When the contact status of SP574 or SS558
is off, CV251=0.

-----------------------------------------------------------------------------------------------------------------------CV254

Totally corrected gas temp leaving AH A


=(CV242 + CV244 + CV 246 + CV250-3 * AV054)

DEG C

Where
CV242 Corrected gas temp leaving
deviation from design entering air temp
CV244 Corrected gas temp leaving
deviation from design entering gas temp
CV246 Corrected gas temp leaving
deviation from design X ratio
CV250 Corrected gas temp leaving
deviation from entering flue gas flow
AV054 AH A gas out temp

AH A for
AH A for
AH A for
AH A for

Note : When the contact status of SP573 or SS556 is off, CV254=0.


-----------------------------------------------------------------------------------------------------------------------CV255

Totally corrected gas temp leaving AH B


=(CV243 + CV245 + CV 247 + CV251-3 * AV057)

DEG C

Where
CV243 Corrected gas temp leaving
deviation from design entering air temp
CV245 Corrected gas temp leaving
deviation from design entering gas temp
CV247 Corrected gas temp leaving
deviation from design X ratio
CV251 Corrected gas temp leaving
deviation from entering flue gas flow
AV057 AH B gas out temp
Note: When the contact status of SP574 or SS558 is off, CV255=0.
-----------------------------------------------------------------------------------------------------------------------

AH B for
AH B for
AH B for
AH B for

Revision 1

CV256

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

68

YN1G176789-D

AH A air leakage expressed as a percentage of design leakage


=(CV231/KN051) * 100 %

Where
CV231 Corrected percent air leakage of AH A for
deviation from design pressure differential and from
design air temperature
KN051 Design percent leakage of each air heater at
rated condition
-----------------------------------------------------------------------------------------------------------------------CV257

AH B air leakage expressed as a percentage of design leakage


=(CV232/KN051) * 100 %

Where
CV232 Corrected percent air leakage of AH Bfor
deviation from design pressure differential and from
design air temperature
KN051 Design percent leakage of each air heater at
rated condition
-----------------------------------------------------------------------------------------------------------------------CV258

Deviation of corrected exit gas temperature of AH A from design value of exit gas
temperature
=CV254-KN046
Where
CV254 Totally corrected gas temperature leaving
AH A
KN046 AH exit gas temp in design condition

Note: When the contact status of SP573 or SS556 is off, CV258=0.


-----------------------------------------------------------------------------------------------------------------------CV259

Deviation of corrected exit gas temperature of AH B from design value of exit gas
temperature
=CV255-KN046
Where
CV255 Totally corrected gas temperature leaving
AH B
KN046 AH exit gas temp in design condition

Note: When the contact status of SP574 or SS558 is off, CV259=0.


-----------------------------------------------------------------------------------------------------------------------CV260

AH A gas side pressure loss (corrected for deviation from design flow and temp)
expressed as a percentage of design gas side press loss
=(CV234/KN052) * 100%
Where
CV234 Gas side press loss of AH A corrected for
deviation from design flow and temperatures
KN052 Design gas side pressure loss of AH

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

69

YN1G176789-D

-----------------------------------------------------------------------------------------------------------------------CV261

AH B gas side pressure loss (corrected for deviation from design flow and temp)
expressed as a percentage of design gas side press loss
=(CV235/KN052) * 100 %
Where
CV235 Gas side press loss of AH B corrected for
deviation from design flow and temperatures
KN052 Design gas side pressure loss of AH A

----------------------------------------------------------------------------------------------------------------------CV262

AH A PA side pressure loss (corrected for deviation from design flow and
temperature) expressed as a percentage of the design rated value of PA side
pressure loss =(CV236/KN053) *100 %
Where
CV236 Corrected PA side press loss of AH A
KN053 Design PA side press loss of AH

-----------------------------------------------------------------------------------------------------------------------CV263
AH B PA side pressure loss (corrected for deviation from design flow and
temperature) expressed as a percentage of the design rated value of PA side
pressure loss =(CV237/KN053) *100 %
Where
CV237 Corrected PA side press loss of AH A
KN053 Design PA side press loss of AH
---------------------------------------------------------------------------------------------------------------------CV264

AH A sec air side pressure loss (corrected for deviation from design flow and
temperature) expressed as a percentage of the design pressure loss
=(CV240/KN053 *100 %
Where
CV240 Corrected sec air side press loss of AH A
KN053 Design sec air side press loss of AH

---------------------------------------------------------------------------------------------------------------------CV265

AH B sec air side pressure loss (corrected for deviation from design flow and
temperature) expressed as a percentage of the design pressure loss
=(CV241/KN054) *100 %
Where
CV241 Corrected sec air side press loss of AH B
KN054 Design sec air side press loss of AH

---------------------------------------------------------------------------------------------------------------------CV274

Design temperature heater 1A condensate outlet


=Fn(AV049)
DEG C
Where

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

70

YN1G176789-D

AV049 Gross generation


----------------------------------------------------------------------------------------------------------------------CV275

Design temperature heater 1B condensate outlet


=Fn(AV049)
DEG C
Where
AV049 Gross generation

-----------------------------------------------------------------------------------------------------------------------CV276

Temperature deviation from design heater 1A


=CV274-AV037 DEG C
Where
CV274 Design temperature heater 1A condensate
outlet
AV037 LPH 1A CNDS temp out

---------------------------------------------------------------------------------------------------------------------CV277
Temperature deviation from design heater 1B
=CV275-AV121 DEG C
Where
CV275 Design temperature heater 1B condensate
outlet
AV121 LPH 1B CNDS temp out
---------------------------------------------------------------------------------------------------------------------

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

71

YN1G176789-D

Class I calculations:
Class I calculations will be carried out in the FIX process database. Appropriate calculation blocks will be
employed in the database for Class I calculations. Calculation results will be displayed on the operator
console. Calculation methodology adopted for Class I calculations is as below:
S.No.

PID

Description

Variable
name

Engg.
Unit

Calculation equation

1.

RC401

TSAT8

Deg C

F(RP001+ KN003)

2.

RC402

CRHAL

Deg C

RC401- RT011

3.

RC403

TSAT9

Deg C

F(RP004+ KN003)

4.

RC404

CRHPAL

Deg C

RC403- RT012

5.

SC401

TSAT1

Deg C

SP003+ KN003

6.

SC402

SHAPL

Deg C

F(SP026+KN003)-ST079

7.

SC403

SHAPR

Deg C

F(SP027+KN003)-ST078

8.

TC401

HPDT1

Deg C

TT012-TT013

9.

TC402

HPDT2

Deg C

TT026-TT027

10.

TC404

HPDT4

Deg C

TT024-TT029

11.

TC405

HPDT5

Deg C

TT030-TT031

12.

TC406

HPDT6

Deg C

TT032-TT033

13.

TC500

HPDT7

Deg C

TT018-TT034

14.

TC501

HPDT8

Deg C

TT042-TT043

15.

TC502

HPDT9

Deg C

TT044-TT045

16.

TC503

HPDT10

Deg C

TT062-TT063

17.

TC504

Reheater inlet left


saturation
Cold reheat (left)
temperature approach to
saturation temperature
Reheater inlet right
saturation temperature
Cold reheat (right)
temperature approach to
saturation temperature
Boiler drum saturation
steam temperature
Super heater attemperation
(left) temperature approach
to saturation temperature
Super heater attemperation
(right) temperature
approach to saturation
temperature
HPT Stm Adm Pipe MTL
Temp B Difference (Left
B/Right B)
HPT Exht UPR/LWR INR
SURF MTL TEMP
Difference
UPR/LWR RH BOWL INLT
INR SURF MTL TEMP
Difference
UPR/LOW 3rd STG MP EXT
INR MTL TEMP Difference
UPR/LOW 6th STG MP EXT
INR MTL TEMP Difference
UPR/LOW HP TURB EXT
IN SUR MTL TEMP
Difference
HPT Stm Adm Pipe MTL
TEMP Left A/RightA
Difference
IPT Stm Adm Pipe MTL
TEMP Left/Right Difference
RGT STOP VLV IN/OUT
SURF MTL TEMP
Difference
Lft STOP VLV IN/OUT
SURF MTL TEMP

HPDT11

Deg C

TT064-TT065

Revision 1

18.

TC416

19.

TC417

20.

TC418

21.

TC419

22.

TC420

23.

TC421

24.

TC422

25.

TC423

26.

TC424

27.

TC425

28.

TC426

29.

TC427

30.

TC428

31.

TC429

32.

TC430

33.

TC431

34.

TC432

35.

TC433

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

Difference
Rate of change of UPR HT
TURB EXHT IN SUR MTL
TEMP.
Rate of change of HPT
EXHT LWR INR MTL
TEMP.
Rate of change of HPT
EXHT UPR RH BOWL INR
SUR MTL TEMP.
Rate of change of UPR RH
BOWL INLT INR SUR
MTL TEMP.
Rate of change of LWR RH
BOWL INLT INR SUR
MTL TEMP.
Rate of change of UPR 3rd
STG MP EXT INR MTL
TEMP.
Rate of change of LOWR
3rd STG MP EXT INR
MTL TEMP.
Rate of change of UPR 6th
STG MP EXT INR MTL
TEMP.
Rate of change of LOW 6th
STG MP EXT INR MTL
TEMP.
Rate of change of HPT
STM ADM PIPE MTL
TEMP. LEFT A
Rate of change of HPT
STM ADM PIPE MTL
TEMP. RIGHT

En

Page :

72

YN1G176789-D

RCMT3

Deg
C/Min

R(TT018)

RCMT4

Deg
C/Min

R(TT026)

RCMT5

Deg
C/Min

R(TT027)

RCMT6

Deg
C/Min

R(TT024)

RCMT7

Deg
C/Min

R(TT029)

RCMT8

Deg
C/Min

R(TT030)

RCMT10

Deg
C/Min

R(TT031)

RCMT10

Deg
C/Min

R(TT032)

RCMT11

Deg
C/Min

R(TT033)

RCMT12

Deg
C/Min

R(TT042)

RCMT13

Deg
C/Min

R(TT043)

Rate of change of HPT


STM ADM PIPE MTL
TEMP. LEFT A

RCMT14

Deg
C/Min

R(TT042)

Rate of change of HPT


STM ADM PIPE MTL
TEMP. RIGHT
Rate of change of IPT STM
ADM PIPE MTL TEMP.
LEFT
Rate of change of IPT STM
ADM PIPE MTL TEMP.
RIGHT
Rate of change of RGT
STOP VLV IN SURF MTL
TEMP.
Rate of change of RGT
STOP VLV OUT SURF MTL
TEMP.
Rate of change of LEFT

RCMT15

Deg
C/Min

R(TT043)

RCMT16

Deg
C/Min

R(TT044)

RCMT17

Deg
C/Min

R(TT045)

RCMT18

Deg
C/Min

R(TT062)

RCMT19

Deg
C/Min

R(TT063)

RCMT20

Deg

R(TT064)

Revision 1

36.

TC434

37.

FC401

38.

FC402

39.

FC403

40.

FC407

41.

FC408

42.

FC409

43.

CC401

44.

CC402

45.

CC403

46.

CC404

47.

CC405

48.

CC406

49.

CC407

50.

CC408

51.

CC409

52.

SC404

53.

SC413

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

STOP VLV IN SURF MTL


TEMP.
Rate of change of LEFT
STOP VLV OUT SURF MTL
TEMP.
HP heater 6 saturation
temperature

En

Page :

73

YN1G176789-D

C/Min
RCMT21

Deg
C/Min

R(TT065)

TSAT6

Deg C

XP005 + KN003

HP heater 6 terminal
temperature difference
HP heater 6 drain cooler
approach temperature
HP heater 5 saturation
temperature
HP heater 5 terminal
temperature difference
HP heater 5 drain cooler
approach temperature
LP heater 3 saturation
temperature
LP heater 3 terminal
temperature difference
LP heater 3 drain cooler
approach temperature
LP heater 2 saturation
temperature
LP heater 2 terminal
temperature difference
LP heater 2 drain cooler
approach temperature

TTD6A

Deg C

FC401-FT001

DCA6A

Deg C

XT012 - FT013

TSAT16

Deg C

F(XP004 + KN003)

TTD5A

Deg C

F407-FT013

DCA5A

Deg C

XT011-FT012

TSAT24

Deg C

F(XP003 + KN003)

TTD3

Deg C

CC401-CT008

DCA3

Deg C

XT010-CT007

TSAT26

Deg C

F(XP002 + KN003)

TTD2

Deg C

CC404-CT007

DCA2

Deg C

XT009-CT006

LP heater 1 saturation
temperature
LP heater 1 terminal
temperature difference
LP heater 1 drain cooler
approach temperature
Rate of change of drum
water saturation
temperature
Deviation in feed water at
HPH 6 outlet

TSAT28

Deg C

F(XP001 + KN003)

TTD1

Deg C

CC407-CT006

DCA1

Deg C

XT008-CT005

Rcdwt

Deg C

R(F(SP003+KN003))

DVFWT1

Deg C

F(GE001)-FT001

F = Function of
R= rate of change of

Revision 1

Project :

Ramagundam STPS Stage-I DAS R&M

Language :

En

Page :

74

YN1G176789-D

Heat rate deviation calculations:


Heat rate deviation calculations will be handled as part of the performance calculation package. The
calculation methodology adopted will be as per the document given by NTPC. Deviation of the actual values
from design values is computed for the following parameters:
a)
b)
c)
d)
e)

Main steam temperature


Main steam pressure
Hot reheat steam temperature
Reheater pressure drop
Condenser vacuum

Using the deviation of the above parameters from the design value, heat rate deviation is calculated using the
heat rate deviation curves provided by the manufacture. Summation of these deviations will give the total heat
rate deviation for the unit. Monetary loss due to heat rate deviation for each shift is then computed as follows:
Loss (in rupees) = (Net generation in MW X 1000) X (Number of hours in shift) X (Heat rate deviation in kCal /
kWh) X (Cost of coal in rupees / Kg) / (Heating value of coal in kCal / kg)
Heat rate deviation will be handled as a separate module outside of the performance calculation package.
Actual values of the process parameters will be made available to the external module. Design values for
each of the parameters as well as the heat rate deviation curves will be provided as static data in the external
module (this can be modified by users, as and when required). Using the heat rate deviation values, loss in
rupees will be computed using the above equation. Results will be made available as a separate report
through the module.
Heat rate deviation Class II tag list:
S No.
1
2
3
4
5
6
7
8
10
11
12
13
14

Tag
HD001
KD001
KD002
KD003
KD004
KD005
HD003
HD004
HD005
HD006
HD007
HD002
HD008

Description
Average power generation (in MW) for the shift
Design value of main steam temperature
Design value of main steam pressure
Design value of hot reheat temperature
Design value of hot reheat pressure
Design value of condenser vacuum
Heat rate deviation due to deviation in main steam temperature
Heat rate deviation due to deviation in main steam pressure
Heat rate deviation due to deviation in hot reheat temperature
Heat rate deviation due to deviation in hot reheat pressure
Heat rate deviation due to deviation in condenser vacuum
Net heat rate deviation
Total loss in rupees due to heat rate deviation

Calculation details:
-------------------------------------------------------------------------------------------------------------------------------------------HD001 = Avg.(GE001)
Where
HD001: Average power generation (in MW) for the shift
GE001: Gross generation
-------------------------------------------------------------------------------------------------------------------------------------------KD001 = Fn(AV049)

Revision 1

Project :

Ramagundam STPS Stage-I DAS R&M

Language :

En

Page :

75

YN1G176789-D

Where
KD001: Design value of main steam temperature (obtained from manufacturers curve as a function of gross
generation)
AV049: Gross generation
-------------------------------------------------------------------------------------------------------------------------------------------KD002 = Fn(AV049)
Where
KD002: Design value of main steam pressure (obtained from manufacturers curve as a function of gross
generation)
AV049: Gross generation
-------------------------------------------------------------------------------------------------------------------------------------------KD003 = Fn(AV049)
Where
KD003: Design value of hot reheat temperature (obtained from manufacturers curve as a function of gross
generation)
AV049: Gross generation
-------------------------------------------------------------------------------------------------------------------------------------------KD004 = Fn(AV049)
Where
KD004: Design value of hot reheat pressure (obtained from manufacturers curve as a function of gross
generation)
AV049: Gross generation
-------------------------------------------------------------------------------------------------------------------------------------------KD005 = Fn(AV049)
Where
KD005: Design value of condenser vacuum (obtained from manufacturers curve as a function of gross
generation)
AV049: Gross generation
-------------------------------------------------------------------------------------------------------------------------------------------HD003 = Fn(KD001 AV072)
Where
HD003: Heat rate deviation due to deviation in main steam temperature (obtained from heat rate deviation
curve)
KD001: Design value of main steam temperature
AV072: Actual main steam temperature (process value obtained from DAS)
-------------------------------------------------------------------------------------------------------------------------------------------HD004 = Fn(KD002 AV073)
Where
HD004: Heat rate deviation due to deviation in main steam pressure (obtained from heat rate deviation curve)
KD002: Design value of main steam pressure
AV073: Actual main steam pressure (process value obtained from DAS)
--------------------------------------------------------------------------------------------------------------------------------------------

Revision 1

Project :

Ramagundam STPS Stage-I DAS R&M

Language :

En

Page :

76

YN1G176789-D

HD005 = Fn(KD003 (AV101+AV102)/2)


Where
HD005: Heat rate deviation due to deviation in hot reheat temperature (obtained from heat rate deviation
curve)
KD003: Design value of hot reheat temperature
AV101: Actual hot reheat temperature, left (process value obtained from DAS)
AV102: Actual hot reheat temperature, right (process value obtained from DAS)
-------------------------------------------------------------------------------------------------------------------------------------------HD006 = Fn(KD004 AV103)
Where
HD006: Heat rate deviation due to deviation in hot reheat pressure (obtained from heat rate deviation curve)
KD004: Design value of hot reheat
AV103: Actual hot reheat pressure (process value obtained from DAS)
-------------------------------------------------------------------------------------------------------------------------------------------HD007 = Fn(KD005 AV050)
Where
HD007: Heat rate deviation due to deviation in condenser vacuum (obtained from heat rate deviation curve)
KD005: Design value of condenser vacuum
AV050: Actual condenser vacuum (process value obtained from DAS)
-------------------------------------------------------------------------------------------------------------------------------------------HD002 = Sum(HD003, HD004, HD005, HD006, HD007)
Where
HD002: Net heat rate deviation
HD003: Heat rate deviation due to deviation in main steam temperature(AV072)
HD004: Heat rate deviation due to deviation in main steam pressure(AV073)
HD005: Heat rate deviation due to deviation in hot reheat steam temperature (AV101,102)
HD006: Heat rate deviation due to deviation in reheater pressure drop (AV103)
HD007: Heat rate deviation due to deviation in condenser vacuum(AV050)
-------------------------------------------------------------------------------------------------------------------------------------------HD008 = (HD001 * 1000) * (KN099) * (HD002) * (KN098) / KN013
Where
HD008: Total loss in rupees due to heat rate deviation
KN098: Number of hours in a shift
KN099: Cost of coal in rupees per kilogram
KN013: Heating value of coal in kCal/kg

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

77

YN1G176789-D

Frequency excursion time integration and other time accounting functions:


Time accounting for deviation from acceptable limits will be provided for the following parameters:
a)
b)
c)
d)

Frequency
Turbine speed
HPT inlet steam temperature
IPT inlet steam temperature

In addition to these, power generation will also be accumulated over one hour and one day.
All time accounting calculations will be handled in the FIX database. A combination of calculation block and
totalizer block will used for the same purpose. Results of the time accounting calculations will be made
available through the operator console (similar to Class I calculation results).
Sno
1
2
3
4
5

Tag id
TA001
TA002
TA003
TA004
TA005

TA006

TA007

TA008

Description
Generation frequency high time accumulation
Generation frequency low time accumulation
Turbine high speed running time accumulation
Turbine low speed running time accumulation
Time duration for which HP turbine
temperature is high
Time duration for which HP turbine
temperature is low
Time duration for which IP turbine
temperature is high
Time duration for which IP turbine
temperature is low

metal

Calculation
TA(GC001 > 50)
TA(GC001 < 50)
TA(TM007 > 3150)
TA(TM007 < 2850)
TA((TT068 + TT069)/2) > 552

metal

TA((TT068 + TT069)/2) < 522

metal

TA((RT007 + RT008)/2) > 552

metal

TA((RT007 + RT008)/2) < 522

Notes:
1. TA() indicates the time accumulation function. This will be a database tag that will calculate the time in
seconds when the process tag is in the state specified
2. Turbine metal high and low temperature calculation will be done only when the generation is greater than
30% of the rated capacity. Else the time accumulation function will be fed a constant value of 0,
irrespective of the value of the process tag

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

78

YN1G176789-D

3. Min, max and average calculations:


Four hourly, daily and monthly min, max and average values will be computed for different process
parameters as specified by NTPC. All calculations related to min, max and average will be handled in the FIX
database. A combination of calculation blocks, trend blocks, extended trend blocks and totalizer blocks will be
used for this purpose. Results of these calculations will be made available to the operator as reports.
Sample calculations:
S.Num

Description

Calculation

Remarks

Process
tag
MC001

Daily average for CEP A winding


temperature

Avg(CT009)

MC002

Max(CT009)

MC003

TAA(CT009)

-do-

MC004

Daily max for CEP A winding


temperature
Total duration in alarm for CEP A
winding temperature
Daily average for CEP B winding
temperature

CT009 is the process tag


in DAS indicating CEP A
winding temperature
-do-

Avg(BAD2)

MC005

Max(BAD2)

MC006

TAA(BAD2)

-do-

MC007

Daily max for CEP B winding


temperature
Total duration in alarm for CEP B
winding temperature
Daily average for BFP A winding
temperature

CEP
B
winding
temperature
is
being
indicated as a BAD point
in IO list presently.
Alternate tag will have to
be provided or the
calculation will need to be
omitted
-do-

Avg(FT017)

MC008

Max(FT017)

MC009

TAA(FT017)

-do-

10

MC010

Daily max for BFP A winding


temperature
Total duration in alarm for BFP A
winding temperature
Daily average for BFP B winding
temperature

FT017 is the process tag


in DAS indicating BFP A
winding temperature
-do-

Avg(FT018)

11

MC011

Max(FT018)

12

MC012

TAA(FT018)

-do-

13

MC013

Daily max for BFP B winding


temperature
Total duration in alarm for BFP B
winding temperature
Daily average for BFP C winding
temperature

FT018 is the process tag


in DAS indicating BFP A
winding temperature
-do-

Avg(FP019)

14

MC014

Max(FP019)

15

MC015

TAA(FP019)

-do-

16

MC016

Daily max for BFP C winding


temperature
Total duration in alarm for BFP C
winding temperature
Daily average for FD fan A winding
temperature

FP019 is the process tag


in DAS indicating BFP A
winding temperature
-do-

Avg(ST080)

ST080 is the process tag


in DAS indicating FD fan
A winding temperature

Revision 1

17

MC017

18

MC018

19

MC019

20

MC020

21

MC021

22

MC022

23

MC023

24

MC024

25

MC025

26

MC026

27

MC027

28

MC028

29

MC029

30

MC030

31

MC031

32

MC032

33

MC033

34

MC034

35

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

Page :

79

YN1G176789-D

Daily max for FD fan A winding


temperature
Total duration in alarm for FD fan A
winding temperature
Daily average for FD fan B winding
temperature

Max(ST080)

-do-

TAA(ST080)

-do-

Avg(ST081)

Daily max for FD fan B winding


temperature
Total duration in alarm for FD fan B
winding temperature
Daily average for ID fan A winding
temperature

Max(ST081)

ST081 is the process tag


in DAS indicating FD fan
B winding temperature
-do-

TAA(ST081)

-do-

Avg(ST084)

Daily max for ID fan A winding


temperature
Total duration in alarm for ID fan A
winding temperature
Daily average for ID fan B winding
temperature

Max(ST084)

ST080 is the process tag


in DAS indicating ID fan A
winding temperature
-do-

TAA(ST084)

-do-

Avg(ST085)

Daily max for ID fan B winding


temperature
Total duration in alarm for ID fan B
winding temperature
Daily average for PA fan A winding
temperature

Max(ST085)

ST081 is the process tag


in DAS indicating ID fan B
winding temperature
-do-

TAA(ST085)

-do-

Avg(ST082)

Daily max for PA fan A winding


temperature
Total duration in alarm for PA fan A
winding temperature
Daily average for PA fan B winding
temperature

Max(ST082)

ST080 is the process tag


in DAS indicating PA fan A
winding temperature
-do-

TAA(ST082)

-do-

Avg(ST083)
Max(ST083)
TAA(ST083)

-do-

Avg(GE001)

MC035

Daily max for PA fan B winding


temperature
Total duration in alarm for PA fan B
winding temperature
Average power generated for the
day
Hours in operation for HP cylinder

ST081 is the process tag


in DAS indicating PA fan
B winding temperature
-do-

36

MC036

Hours in operation for IP cylinder

37

MC037

Time in hours for MS steam


temperature in 480 500 deg C

TAA{(RP005 > 10 AND


TZ003>2%
)
OR
(RP006>10
AND
TZ004>2%)}
TAA(500
>
(TT068+TT069)/2
>

GE001 is the generator


output tag in DAS
Process
tag
corresponding to main
steam
pressure
and
HPCV position is AVG.
(TP003+TP004)/2
AND
TZ001>2%available in IO
list.
RP005 & RP006 are the
process tags available in
DAS for hot reheat
pressure
TT068 and TT069 are
process available in DAS

TAA(AV073 > 10 AND


TZ001>2% )

Revision 1

Project :

Language :

Ramagundam STPS Stage-I DAS R&M

En

range

480)

Time in hours for MS steam


temperature in 500 520 deg C
range
Time in hours for MS steam
temperature in 520 535 deg C
range
Time in hours for MS steam
temperature in 535 545 deg C
range
Time in hours for MS steam
temperature in 545 565 deg C
range
Time in hours for MS steam
temperature greater than 565 deg C
Time in hours for HRH steam
temperature in 480 500 deg C
range

TAA(520
>
(TT068+TT069)/2
>
500)
TAA(535
>
(TT068+TT069)/2
>
520)
TAA(545
>
(TT068+TT069)/2
>
535)
TAA(565
>
(TT068+TT069)/2
>
545)
TAA((TT068+TT069)/2
> 565)
TAA(500
>
(RT013+RT016)/2
>
480)
TAA(520
>
(RT013+RT016)/2
>
500)
TAA(535
>
(RT013+RT016)/2
>
520)
TAA(545
>
(RT013+RT016)/2
>
535)
TAA(565
>
(RT013+RT016)/2
>
545)
TAA((RT013+RT016)/2
> 565)
COUNT(TZ001>2% is
SET AND TT026>350
deg c)
COUNT(TZ001>2% is
SET AND TT026<350
but > 250 deg c)
COUNT(TZ001>2% is
SET AND TT026< 250
deg c)
Time
count
from
startup to setting of
GS550

38

MC038

39

MC039

40

MC040

41

MC041

42

MC042

43

MC043

44

MC044

45

MC045

46

MC046

47

MC047

48

MC048

49

MC050

Time in hours for HRH steam


temperature in 500 520 deg C
range
Time in hours for HRH steam
temperature in 520 535 deg C
range
Time in hours for HRH steam
temperature in 535 545 deg C
range
Time in hours for HRH steam
temperature in 545 565 deg C
range
Time in hours for HRH steam
temperature greater than 56 deg C
Nos of Hot startups

50

MC051

Nos of warm startups

51

MC052

Nos of cold startups

51

MC053

Cumulative time taken from startup


to synchronization

Page :

80

YN1G176789-D

for
main
temperature
-do-

steam

-do-do-do-doRT013 and RT016 are


process available in DAS
for
main
steam
temperature
-do-do-do-do-doTo be checked at site
TT026=HPT EXHT UPR
INR SURF MTL TEMP
-----do-------------------do--------GEN BKR status GS550
to be tracked at instant T
and instant (T-1)(pl. refer
sample calculation)

Note: The sample calculations shown above are indicated how min, max, average and time duration
calculations will be carried out. Similar calculations shall be carried out for the following tags:
T001 to GT011 (Gen wdg. Temp)
GT014 to GT016 (Gen hot gas temp)
GT017 to GT020 (Gen cold gas temp)
H2 purity GP001

Revision 1

Project :

Ramagundam STPS Stage-I DAS R&M

PH in CEP discharge WA013


PH in blr water WA014
CAT CONDTY of makeup wtr to cond WA004
BFP A inbrd brg vib FV001
BFP A OUTBRD BRG VIB FV002
BFP B INBRD BRG VIB FV003
BFP B OUTBRD BRG VIB FV004
BFP C INBRD BRG VIB FV005
BFP C OUTBRD BRG VIB FV006
BLR WTR SILICA LVL WA003
CAT CONDTY OF SAT STEAM WA007
SPEC CONDTY OF SAT STEAM WA012
SP CONDVTY OF FW AT ECON I/L WA010
CAT CONDTY OF FW AT ECO INLET WA006
SP CONDVTY OF FW AT ECON I/L WA010
COND MAKE UP FLOW WF001
CONDENSER VACCUM/PRESSURE HP006
CW TEMP AT COND INLET B SIDE HT001
CW TEMP AT COND INLET A SIDE HT002
CW TEMP AT COND OUTLET B SIDE HT003
CW TEMP AT COND OUTLET A SIDE HT004
LPT EXHST STM TEMP TT074
COND PUMP SUC TEMP(AVG. of CT011, BAD5, CT012,
TURB 1ST STAGE PRESS TP005
MAIN STM PRESS BEF ESV AVG(TP003+ TP004)
HPT EXHAUST STM PRESS RIGHT TP013
HPT EXHAUST STM TEMP RIGHT TT011
EXT STM TEMP TO HPH 5 TURB SIDE XT005
EXT STM TEMP TO HPH 6 HTR SIDE XT006
EXT STM TEMP TO HPH 5 HTR SIDE XT014
HPH 5 EXT STM PRESS HTR SIDE XP004
HPH 6 EXT STM PRESS HTR SIDE XP005
HPH 5 DRAIN TEMP XT011
HPH 6 DRAIN TEMP XT012
EXT STM TMP TO LPH2 TURB SIDE XT002
EXT STM TEMP TO LPH 3 TRB SIDE XT003
EXT STM TMP TO LPH2 TURB SIDE XT002
EXT STM TEMP TO LPH 3 TRB SIDE XT003
LPH 2 DRAIN TEMP XT009
LPH 3 DRAIN TEMP XT010
ECONOMISER OUTLET WATER TEMP LEFT FT010
ECONOMISER OUTLET WATER TEMP RIGHT FT011
FW TEMP AT ECON INLET FT009
DRUM METAL TEMPERATURE ST002
DRUM METAL TEMPERATURE ST003
DRUM METAL TEMPERATURE ST004
DRUM METAL TEMPERATURE ST005
DRUM METAL TEMPERATURE ST006
DRUM METAL TEMPERATURE ST007

Language :

En

Page :

81

YN1G176789-D

Revision 1

Project :

Ramagundam STPS Stage-I DAS R&M

Language :

En

SEC SH TUBE MTL TEMP from ST132 to ST143


PRI PLATEN SH TUBE MTL TEMP from ST157 to ST168
TER SH TUBE MTL TEMP from ST175 to ST190
RH TUBE METAL TEMP from RT017 to RT032
RH DESH OUTLET STM TEMP LEFT RT038
RH DESH OUTLET STM TEMP RIGHT RT039
SH OUTLET STM TEMP LEFT ST073
SH OUTLET STM TEMP RIGHT ST075
SH OUTLET STM PRESS LEFT SP001
SH OUTLET STM PRESS RIGHT SP002
RH OUTLET STM TEMP LEFT RT013
RH OUTLET STM TEMP RIGHT RT016
Calculated point for SH OUTLET STM TEMP DIFF. LEFT/RIGHT(ST073-ST075)
Calculated point for RH OUTLET STM TEMP DIFF. LEFT/RIGHT(RT013-RT016)
BOILER DRUM PRESSURE SP003

Page :

82

YN1G176789-D