Generator Set Data Sheet

Model:
Frequency:
Fuel Type:
Emissions Performance NOx:
LT Water Inlet Temperature:
HT Water Outlet Temp:

1400GQKA
60 Hz
Natural Gas MI 75 +
0.7 g/hp-hr
50oC (122oF)
90oC (194oF)
MSP-1007
PTS-158
0500-4321

Measured Sound Performance Data Sheet:


Prototype Test Summary Data:
Remote Radiator Cooling Outline:
100% of Rated
Load

Fuel Consumption (ISO3046/1)

See Note

Fuel Consumption (LHV) ISO3046/1, kW (MMBTU/hr)


Mechanical Efficiency ISO3046/1, percent
Electrical Efficiency ISO3046/1, percent

2,4,6,7 3856 (13.17)


2,4,7
37.6%
2,4,6,7
36.3%

90% of Rated
Load

3514 (12)
37.2%
35.9%

75% of Rated
Load

50% of Rated
Load

2991 (10.21) 2165 (7.39)


36.6%
34.1%
35.1%
32.3%

Engine
Engine Manufacturer
Engine Model
Configuration
Displacement, L (cu.in)
Aspiration
Gross Engine Power Output, kWm (hp)
BMEP, bar (psi)
Bore, mm (in)
Stroke, mm (in)
Rated Speed, rpm
Piston Speed, m/s (ft/min)
Compression Ratio
Lube Oil Capacity, L (qt)
Overspeed Limit, rpm
Regenerative Power, kW
Full Load Lubricating oil consumption, g/kWe-hr (g/hp-hr)

Cummins
QSK60G
V16
60.3 (3683)
Turbocharged (2)
1451 (1945)
16.1 (233)
159 (6.26)
190 (7.48)
1800
11.4 (2244)
11.4:1
380 (401)
2070
N/A
0.15 (0.11)

Fuel
0.24 (3.5)
75

Gas supply pressure to engine inlet, bar (psi)


Minimum Methane Index

Starting System(s)
Electric starter voltage, volts
Minimum battery capacity @ 40 deg.C (104 deg.F), AH
Air Starter Pressure, barg (psig)
Air Starter Flow Nm3/s (scfm)

24
450
NA
NA

Genset Dimensions (see note 1)


5.00 (16.39)
2.33 (7.64)
2.97 (9.75)
13904 (30,653)

Genset Length, m (ft)


Genset Width, m (ft)
Genset Height, m (ft)
Genset Weight (wet), kg (lbs)

@ 2006 Cummins Power Generation

Specifications May Change Without Notice

D-3246c (Oct 06) Page 1 of 4

See 100% of Rated 90% of Rated 75% of Rated


Notes
Load
Load
Load
Energy Data
Continuous Shaft Power, kWm (bhp)
Continuous Generator Electrical Output kWe @ 1.0 pf
Heat Dissipated in Lube Oil Cooler, kW (MMBTU/h)
Heat Dissipated in Block, kW (MMBTU/h)
Total Heat Rejected in LT Circuit, kW (MMBTU/h)
Total Heat Rejected in HT Circuit, kW (MMBTU/h)
Unburnt, kW (MMBTU/h)
Heat Radiated to Ambient, kW (MMBTU/h)
Available Exhaust heat to 105C, kW (MMBTU/h)
Intake Air Flow
Intake Air Flow Mass, kg/s (lb/hr)
Intake Air Flow Volume, m3/s @ 0oC (scfm)
Maximum Air Cleaner Restriction, mmHG (in H2O)

2,10
10
5
5
5
5
13
13
5

4
4

Exhaust Air Flow


Exhaust Gas Flow Mass, kg/s (lb/hr)
Exhaust Gas Flow Volume, m3/s (cfm)
Exhaust Temperature After Turbine, oC (oF)
Max Exhaust System Back Pressure, mmHG (in H2O)

4
4
6
6,14

Min Exhaust System Back Pressure, mmHG (in H2O)

6,14

HT Cooling Circuit
HT Circuit Engine Coolant Volume, l (gal)
HT Coolant Flow @ Max Ext Restriction, m3/h (gal/min)
Max HT Engine Coolant Inlet Temp, oC (oF) Reference
HT Coolant Outlet Temp, oC (oF)
Max Pressure Drop in External HT Circuit, bar (psig)
HT Circuit Maximum Pressure, bar (psig)
Minimum Static Head, bar (psig)
LT Cooling Circuit
LT Circuit Engine Coolant Volume, l (gal)
LT Coolant Flow @ Max Ext Restriction, m3/h (gal/min)
Maximum LT Engine Coolant Inlet Temp, oC (oF)
LT Coolant Outlet Temp, oC (oF) Reference Only
Max Pressure Drop in External LT Circuit, bar (psig)
LT Circuit Maximum Pressure, bar (psig)
Minimum Static Head, bar (psig)

50% of Rated
Load

1451 (1945)
1400
214 (0.73)
493 (1.68)
126 (0.43)
958 (3.27)
81 (0.27)
209 (0.71)
1032 (3.52)

1306 (1750)
1260
204 (0.70)
464 (1.58)
115 (0.39)
878 (3.00)
75 (0.26)
201 (0.69)
963 (3.29)

1094 (1466)
1050
195 (0.66)
392 (1.34)
102 (0.35)
727 (2.48)
64 (0.22)
180 (0.62)
840 (2.86)

738 (990)
700
159 (0.54)
321 (1.09)
82 (0.28)
528 (1.80)
47 (0.16)
161 (0.55)
643 (2.19)

2.39 (18913)
1.85 (4124)
18 (9.8)

2.15 (17029)
1.66 (3713)
18 (9.8)

1.83 (14457)
1.41 (3152)
18 (9.8)

1.26 (9965)
0.97 (2173)
18 (9.8)

2.23
4.77
483
37.3

1.89
4.10
493
37.3

1.30
2.94
522
37.3

2.47
5.24
475.1
37.3

(19578)
(11089)
(887)
(20.0)

NA NA

(17634)
(10095)
(902)
(20.0)

NA NA

(14970)
(8682)
(919)
(20.0)

NA NA

(10332)
(6216)
(971)
(20.0)

NA NA

8
8

181
83
80
90
1.50
3.5
0.5

(48)
(365)
(176)
(194)
(22)
(51)
(7)

181
83
80
90
1.50
3.5
0.5

(48)
(365)
(176)
(194)
(22)
(51)
(7)

181
83
80
90
1.50
3.5
0.5

(48)
(365)
(176)
(194)
(22)
(51)
(7)

181
83
80
90
1.50
3.5
0.5

(48)
(365)
(176)
(194)
(22)
(51)
(7)

9
9

34
29
50
54.0
1.00
3.5
0.5

(9)
(125)
(122)
(129)
(15)
(51)
(7)

34
29
50
54.0
1.00
3.5
0.5

(9)
(125)
(122)
(129)
(15)
(51)
(7)

34
29
50
54.0
1.00
3.5
0.5

(9)
(125)
(122)
(129)
(15)
(51)
(7)

34
29
50
54.0
1.00
3.5
0.5

(9)
(125)
(122)
(129)
(15)
(51)
(7)

Emissions
NOx Emissions wet, ppm

108

108

106

103

NOx Emissions at Exhaust Condition, mg/Nm3 (g/hp-h)


THC Emissions wet, ppm
THC Exhaust Emissions, mg/Nm3 (g/hp-h)
CO Emissions (dry), ppm
CO Emissions Rate at Exhaust, mg/Nm3 (g/hp-h)
O2 Emissions (dry), percent
Particulates PM10, g/hp-h

5
13
13
13
13
13
13

307 (0.70)
1068
1192 (2.74)
437
766 (1.74)
9.5
< 0.03

304 (0.70)
1113
1231 (2.85)
431
744 (1.71)
9.3
< 0.03

301 (0.70)
1124
1253 (2.94)
405
709 (1.65)
9.4
< 0.03

279 (0.70)
1210
1289 (3.27)
388
663 (1.67)
8.8
< 0.03

D3246c (Oct 06) Page 2 of 4


@ 2006 Cummins Power Generation

Specifications May Change Without Notice

Genset De-rating
Altitude and Temperature Derate Multiplication Factor
Barometer

Altitude

In Hg

mbar

Feet

20.7
21.4
22.1
22.8
23.5
24.3
25.0
25.8
26.6
27.4
28.3
29.1
29.5
30.0

701
723
747
771
795
820
846
872
899
926
954
983
995
1012

9843
9022
8202
7382
6562
5741
4921
4101
3281
2461
1640
820
492
0

Table A *

Meters

3000
2750
2500
2250
2000
1750
1500
1250
1000
750
500
250
150
0
C
F

Derate Multiplier with Grid Parallel Operation


0.69
0.72
0.75
0.78
0.81
0.84
0.88
0.91
0.94
0.97
1.00
1.00
1.00
1.00
20
68

0.67
0.70
0.74
0.77
0.80
0.83
0.86
0.89
0.92
0.96
0.99
1.00
1.00
1.00
25
77

0.66
0.65
0.63
0.61
0.69
0.68
0.66
0.64
0.72
0.71
0.70
0.67
0.75
0.74
0.73
0.70
0.79
0.77
0.76
0.73
0.82
0.80
0.79
0.76
0.85
0.84
0.82
0.79
0.88
0.87
0.85
0.83
0.91
0.90
0.89
0.86
0.94
0.93
0.92
0.89
0.97
0.96
0.95
0.92
1.00
0.99
0.98
0.95
1.00
1.00
0.99
0.96
1.00
1.00
1.00
0.98
30
35
40
45
86
95
104
113
Air Filter Inlet Temperature

0.58
0.61
0.64
0.67
0.70
0.74
0.77
0.80
0.83
0.86
0.89
0.92
0.94
0.96
50
122

0.55
0.58
0.61
0.64
0.68
0.71
0.74
0.77
0.80
0.83
0.86
0.90
0.91
0.93
55
131

0.52
0.55
0.58
0.62
0.65
0.68
0.71
0.74
0.77
0.81
0.84
0.87
0.88
0.90
60
140

Temperature & Altitude Derate


1. Determine derate multiplier vs.
temperature and altitude in Table A
or B depending upon your operating
condition.
2. Assumes the LT return
temperature is 10 deg C above the
air filter inlet with a maximum LT
temperature of 50 deg C.
3. If the LT temperature exceeds 50
deg C, consult factory for
recommendations.
4. Altitude is based upon SAE
standard ambient pressure vs.
altitude. For low barometric
conditions add 150m (500 ft) to site
altitude.

* Based on SAE standard ambient pressure vs. altitude. Assumes LT return temperature is 10C above air filter inlet.

Barometer

Altitude

In Hg

mbar

Feet

Meters

20.7
21.4
22.1

701
723
747
771
795
820
846
872
899
926
954
983
995
1012

9843
9022
8202
7382
6562
5741
4921
4101
3281
2461
1640
820
492
0

3000
2750
2500
2250
2000
1750
1500
1250
1000
750
500
250
150
0

22.8
23.5
24.3
25.0
25.8
26.6
27.4
28.3
29.1
29.5
30.0

C
F

Table B *
Derate Multiplier Off Grid (Island or Load Share)
0.67
0.70
0.73
0.76
0.80
0.83
0.86
0.89
0.92
0.95
0.98
1.00
1.00
1.00

0.66
0.69
0.72
0.75
0.78
0.81
0.85
0.88
0.91
0.94
0.97
1.00
1.00
1.00

20
68

25
77

0.64
0.67
0.71
0.74
0.77
0.80
0.83
0.86
0.90
0.93
0.96
0.99
1.00
1.00

0.63
0.66
0.69
0.72
0.76
0.79
0.82
0.85
0.88
0.91
0.94
0.98
0.99
1.00

0.62
0.65
0.68
0.71
0.74
0.77
0.81
0.84
0.87
0.90
0.93
0.96
0.98
0.99

0.58
0.62
0.65
0.68
0.71
0.74
0.77
0.80
0.84
0.87
0.90
0.93
0.94
0.96

Methane Number Capability

0.55
0.58
0.61
0.65
0.68
0.71
0.74
0.77
0.80
0.84
0.87
0.90
0.91
0.93

0.52
0.55
0.58
0.61
0.65
0.68
0.71
0.74
0.77
0.80
0.83
0.87
0.88
0.90

0.52
0.55
0.58
0.61
0.64
0.68
0.71
0.74
0.77
0.80
0.83
0.85
0.87

30
35
40
45
50
86
95
104
113
122
Air Filter Inlet Temperature

55
131

60
140

Load (Percent of Rated)


75%
50%
100%
90%
75
66
51
42

* Based on SAE standard ambient pressure vs. altitude. Assumes LT return temperature is 10C above air filter inlet.

Heat Rejection Factor (altitude and ambient) for HT and LT Circuits


Barometer

Altitude

In Hg

mbar

Feet

Meters

20.7
21.4
22.1
22.8
23.5
24.3
25.0
25.8
26.6
27.4
28.3
29.1

701
723
747
771
795
820
846
872
899
926
954
983
995
1012

9843
9022
8202
7382
6562
5741
4921
4101
3281
2461
1640
820
492
0

3000
2750
2500
2250
2000
1750
1500
1250
1000
750
500
250
150
0

29.5
30.0

C
F

Table C
Multiplier for HT & LT Heat Rejection vs Alt & Temp.
0.00
1.11
1.10
1.09
1.08
1.07
1.06
1.05
1.04
1.02
1.01
1.00
0.99
0.99

0.00
1.13
1.12
1.10
1.09
1.08
1.07
1.06
1.05
1.04
1.03
1.02
1.00
1.00

20
68

25
77

@ 2006 Cummins Power Generation

0.00
1.14
1.13
1.12
1.11
1.09
1.08
1.07
1.06
1.05
1.04
1.03
1.02
1.01

0.00
1.15
1.14
1.13
1.12
1.11
1.10
1.09
1.07
1.06
1.05
1.04
1.03
1.03

0.00
1.17
1.15
1.14
1.13
1.12
1.11
1.10
1.09
1.08
1.07
1.05
1.04
1.04

0.00
1.18
1.17
1.16
1.14
1.13
1.12
1.11
1.10
1.09
1.08
1.07
1.06
1.05

0.00
1.19
1.18
1.17
1.16
1.15
1.14
1.12
1.11
1.10
1.09
1.08
1.07
1.06

0.00
1.20
1.19
1.18
1.17
1.16
1.15
1.14
1.13
1.12
1.10
1.09
1.08
1.08

0.00
1.22
1.21
1.20
1.18
1.17
1.16
1.15
1.14
1.13
1.12
1.11
1.10
1.09

30
35
40
45
50
86
95
104
113
122
Air Filter Inlet Temperature

55
131

60
140

Specifications May Change Without Notice

LT & HT Circuit Heat Rejection


Calculation
1. Determine derate multiplier vs.
temperature derate per above.
2. Using the multiplier from #1
above as the percent load factor
determine the Heat rejection from
the previous page.
3. From Table C find the HT and LT
circuit multiplier.
4. Multiply the result of step 2 by the
result of step 3 to obtain the heat
rejection at your altitude and
temperature.

D3246c (Oct 06) Page 3 of 4

Alternator Data
Voltage Range
380-480
416-480
600
380-416
440-480
480
600
440-480
4160
4160
12470-13800

Connection
Configuration
Wye, 3 Phase
Wye, 3 Phase
Wye, 3 Phase
Wye, 3 Phase
Wye, 3 Phase
Wye, 3 Phase
Wye, 3 Phase
Wye, 3 Phase
Wye, 3 Phase
Wye, 3 Phase
Wye, 3 Phase

Continuous Rating
Definition

Temp Rise
Degrees C
80
80
80
105
105
105
105
125
80
105
80

11

Duty
Cycle
C
C
C
C
C
C
C
C
C
C
C

Single Phase Maximum


Factor
Surge kVA12
N/A
7361
N/A
6716
N/A
6716
N/A
5743
N/A
5743
N/A
5521
N/A
5521
N/A
5521
N/A
7926
N/A
7005
N/A
5948

Alternator
Data Sheet
334
333
333
332
332
331
331
331
324
323
521

Feature
Code
B830-2
B587-2
D589-2
B831-2
B832-2
B583-2
B582-2
B650-2
B590-2
B834-2
B591-2

Applicable for supplying power continuously to a constant load up to the full


output rating for unlimited hours. No sustained overload capability is available
for this rating. Consult authorized distributor for rating. (Equivalent to
Continuous Power in accordance with ISO8528, ISO3046, AS2789, DIN6271, and
BS5514). This rating is not applicable to all generator set models.

Notes
1) Weights and set dimesions represent a generator set with its standard features only. See outline drawing for other configurations.
2) At ISO3046 reference conditions, altitude 1013 mbar (30in Hg), air inlet temperature 25oC (77oF)
3) Nominal performance +/- 2 1/2%
4) According to ISO 3046/I with fuel consumption tolerance of +5% -0% or efficiency tolerance of +0% -5%.
5) Production variation/tolerance 5%.
6) With air intake at 25oC (77F). Tolerance 5F.
7) Tested using pipeline natural gas with LHV of 33.44mJ/Nm3 (980BTU/ft3)
8) Outlet temperature controlled by thermostat. Inlet temperature for reference only.
9) Inlet temperature controlled by thermostat, outlet temperature for reference only.
10) With engine driven coolant pump.
11) Standby (S), Prime (P), Continuous ( C)
12) Maximum rated starting kVA that results in minimum of 90% of rated sustained voltage during starting.
13) Tolerance +/- 15%
14) Exhaust system back pressure is a rated load and will decrease at lower loads.

See your distributor for more information.

Cummins Power Generation


1400 73rd Avenue N.E.
Minneapolis, MN 55432 USA
Telephone: +1 (763) 574-5000
Fax: +1 (763) 574-5298
Email: pgamail@cummins.com
Web: www.cumminspowergeneration.com

Cummins Power Generation


Manston Park, Columbus Avenue
Manston, Ramsgate
Kent CT12 5BF, UK
Telephone: +44 (0) 1843 255000
Fax: +44 (0) 1843 255902
E-Mail: cpg.uk@cummins.com
Web: www.cumminspower.com

Cummins Power Generation


8 Tanjong Penjuru
Singapore 609019
Telephone: +65 265-0155
Fax: +65 264-0664 or 265-6909
Email: mktg@sing.cummins.com

Cummins and PowerCommand are registered trademarks of Cummins Inc. AmpSentry is a trademark of Cummins Inc.
Important: Back feed to a utility system can cause electrocution and/or property damage. Do not connect to any building's electrical system
except through an approved device or after building main switch is open.

@ 2006 Cummins Power Generation

Specifications May Change Without Notice

D3246c (Oct 06) Page 4 of 4