Beruflich Dokumente
Kultur Dokumente
VOLUME 4 II
ENGINEERING GUIDE
PDVSA No
90619.1.062
TITLE
AUG.93
REV.
DATE
FOR APPROVAL
PAG.
DESCRIPTION DESCRIPTION
DATE AUG. 93
APPR. ELIECER DATE
JIMNEZ APPROVED
L.T.
10
REV.
APPR.
APPR.
DATE AUG. 93
REVISED
PAG.
PAG.
SPECIALISTS
PDVSA, 1983
PAG.
PAG.
PAG.
ENGINEERING GUIDE
PDVSA 90619.1.062
AUG.93
PAGE 1
.
PAG.
PAG.
PAG.
INDEX
A.
Scope ................................................................................................................................... 3
ENGINEERING GUIDE
REVIEW OF MANUFACTURERS DRAWINGS FOR
LARGE MOTORS
PDVSA 90619.1.062
AUG.93
PAGE 2
.
PAG.
PAG.
PAG.
A. Scope
Motors will be checked to guarantee that they meet the specifications and that the required
information for design is provided. In addition, every motor will be checked for specific
requirements indicated in the purchase requisition. The objective of this guide is to present the
testing procedures, in addition to those of routine, to be carried out in medium voltage motors
(usually equal to or higher than 200HP.)
B. Physical Aspects
Taking into account that the wires to be used are medium voltage and shielded cables, it is very
important to check the terminal box so that the cables can be properly installed and connected.
Special attention must be paid to stress cones and radius of curvature placing, and installment
and position of other special devices, such as current transformers.
C. Technical Aspects
1.
Make sure that the motor is adequate for the load acceleration. For small motors, torque
characteristics in function of motor velocity are established in NEMA regulations and
selecting the suitable motor can be relied on the equipment manufacturer. However, for
2
large motors, NEMA regulations specifies the WK inertia, through which the motor can
accelerate based on the torque - velocity characteristics and determined voltage
conditions, none of which can be applied in specific cases. Therefore, it is necessary
that real conditions and/or specified requirements are verified in each large motor
considered. The method to use is the following:
1.A
1.B
1.C
Multiply the torque value from section 1.B by the square of the relation between the
minimum expected value of the starting voltage and the nominal voltage value of the
motor.
It is important to notice that motor specifications will usually require that it is suitable for
starting with 80% of nominal voltage. However, there might be particular cases in which
the motor voltage is even lower. The motor manufacturer will not be responsible for
these cases, but it will be still necessary to check up on the correct performance so that
corrective actions can be taken if necessary.
1.D
Draw the curves indicated in sections 1.A and 1.B on the same sheet so that these can
be compared. Regarding curve acceleration, the curve of the motor will be at least 20%
higher than the one corresponding to the actuated equipment.
ENGINEERING GUIDE
REVIEW OF MANUFACTURERS DRAWINGS FOR
LARGE MOTORS
PDVSA 90619.1.062
AUG.93
PAGE 4
.
PAG.
PAG.
PAG.
1.E
2.
2.1
Very large motors (power being higher than or equal to 500 HP.)
2.1.A
Obtain the curve of the thermal damage, provided by the motor manufacturer, which is
basically a curve of permissible current vs. time.
2.1.B
Plot a curve of real current vs. time. The method to do this curve is indicated in Annex
No. 2.
2.1.C
Obtain the curve of overload relays (combined with its current transformers), provided
by the motor manufacturers control center.
2.1.D
Overlap these three curves on one page. Motor starting curve must be at the bottom,
the one of thermal damage must be above, and the one of overload relays, in the
middle. If this is not the case, corrective actions required will be taken.
2.1.E
The most frequent difference corresponds to that case in which overloadrelays curve is
above the one of thermal damage in the area of stalled rotor current. This could mean
that motor is not being protected from the stalled rotor conditions. Any of the following
options can be taken as corrective action:
2.2
Install a zero-velocity switch. This could protect the real stalled rotor conditions.
Provide an additional relay for protection against stalled rotor. Annex No. 3 contains
an example for this matter.
2.2.A
Obtain permissible time and stalled-rotor current (hot) values, corresponding to nominal
voltage of the motor (Section 1). See example in Annex No. 4.
2.2.B
2.2.C
Calculate the permissible time and stalled-rotor current (hot) values, corresponding to
the starting voltage (Section 2)
2.2.D. Follow subsections 2.1.B to 2.1.E above mentioned. See example in Annex No. 2.
ENGINEERING GUIDE
REVIEW OF MANUFACTURERS DRAWINGS FOR
LARGE MOTORS
PDVSA 90619.1.062
AUG.93
PAGE 5
.
PAG.
PAG.
PAG.
ANNEX No. 1
A. Torque Velocity curve in nominal voltage provided by the manufacturer
B. Torque Velocity curve in 0.87 of nominal tension which is obtained by multiplying
2
values of curve A by (0.8) .
C. Torque Velocity of the pump provided by the manufacturer
D. The minimum torque of the motor must be at least 20% of the toque of the bomb
required for this velocity.
ENGINEERING GUIDE
REVIEW OF MANUFACTURERS DRAWINGS FOR
LARGE MOTORS
PDVSA 90619.1.062
AUG.93
PAGE 6
.
PAG.
PAG.
PAG.
ANNEX No. 2
METHOD TO PLOT THE ACTUAL CURVE TIME CURRENT
Step No. 1
1.1
Draw the motor torque velocity curve at the actual starting voltage vs. torque velocity of the pump according to Annex 1.
1.2
Calculate time for accelerating the pump from zero to a value close to 10% of
the nominal velocity using the formula:
=
1.3
Step No. 2
2
308
t
= time in seconds
2
2
WK = moment of inertia in Lb Ft
T
= diferential torque in Lb Ft
RPM = Revolutions per minute
Repeat this calculation for small velocity increases up to 90% of the nominal
velocity. Add 0,5 sec. to reach total velocity.
Obtain the current velocity curve from the motor manufacturer.
ENGINEERING GUIDE
REVIEW OF MANUFACTURERS DRAWINGS FOR
LARGE MOTORS
PDVSA 90619.1.062
AUG.93
PAGE 7
.
PAG.
PAG.
PAG.
Step No. 3
Times calculated in Step 1 are showed replacing RPM and the time vs. current
curve is drawn.
STANDARD TIME CURRENT CURVE
PDVSA 90619.1.062
ENGINEERING GUIDE
REVIEW OF MANUFACTURERS DRAWINGS FOR
LARGE MOTORS
AUG.93
PAGE 8
.
PAG.
PAG.
PAG.
ANNEX No. 3
MOTOR PROTECTION VERIFICATION (POWER OF 500 HP)
When theoverload relay curve (B) is positioned between the current curve (C) and the damage
curve (a), the protection is complete.
When the overload relay curve (B) does not coordinate, an additional relay (D) for protecting the
stalled rotor can be added.
PDVSA 90619.1.062
ENGINEERING GUIDE
REVIEW OF MANUFACTURERS DRAWINGS FOR
LARGE MOTORS
AUG.93
PAGE 9
.
PAG.
PAG.
PAG.
ANNEX No. 4
METHOD TO PLOT THE MOTOR DAMAGE CURVE FOR MOTORS BETWEEN 250 HP AND
4500 HP
(This shall only be used when de manufacturers information is not available)
STEP 1.
Obtain the permissible time for stalled rotor at nominal voltage from the motor
manufacturer.
STEP 2.
Calculate the current value for actual starting voltage, assuming that it is directly
proportional to voltage.
STEP 3.
Having calculated the new current value, calculate the new permissible value of
2
starting time, assuming that l t is constant in the stalled-rotor current area.
STEP 4.
Previous steps will throw two points that can be shown on the graph and can be
joined together with a straight line. This line can be considered as the motor
damage curve.
Example:
STEP 3: I t = constant
STEP 4. Information provided by the manufacturer and the one calculated are
shown on the graph as follows:
Point (2) obtained
from calculations
PAGE 10