Beruflich Dokumente
Kultur Dokumente
User manual
E60439A
Discovering Micrologic P 4
Identification 4
Presentation 5
Setting procedure 6
Setting Micrologic 5.0 P using the dials 8
Setting Micrologic 6.0 P using the dials 9
Setting Micrologic 7.0 P using the dials 10
Selecting the type of neutral protection 11
Main menus 12
Metering 14
History, maintenance and setup 16
Protection 18
Overview of functions 20
Current protection 20
Voltage protection 26
Other protection 27
Load shedding and reconnection 28
Measurements 29
Alarms 31
Optional M2C and M6C contacts 32
Event histories 33
LEDs and display screens 34
COM communications option 36
Setup 38
Setting up the optional M2C / M6C contacts 38
Setting up the Micrologic control unit 40
Setting up the metering functions 43
Setting up the COM communications option 46
Protection settings 48
Fine adjustment of the long-time I2t, short-time and
instantaneous settings using the keypad 48
Fine adjustment of the long-time Idmtl, short-time and
instantaneous settings using the keypad 49
Fine adjustment of the ground-fault and earth-leakage
protection setting using the keypad 50
Setting the neutral protection 51
Setting the It, I unbal, I max, U min, U max, U unbal, rP max,
F min, F max and phase-rotation protection functions
using the keypad 52
Setting load shedding / reconnection 54
Metering 56
Current measurements 56
Voltage measurements 59
Power measurements 61
Energy measurements 63
Frequency measurements 64
Maintenance 66
Resetting fault indications 66
Viewing the event histories 67
Operation counter and contact-wear indicator 68
Checking/replacing the battery 69
Tests 70
E60251B
E60250B
protection thresholds and tripping delays
for overloads, short-circuits, ground faults Micro
logic
5.0
Micro
logic
5.0
c open the protective c make the necessary settings using the dials
cover. c the screen automatically displays the relevant curve
c check the set value on the screen, in absolute value
in amperes (A) and in seconds (s).
È60252B
adjustments of the protection thresholds and c the and buttons under the screen may be
used for fine adjustments of the settings made using
tripping delays for overloads, short-circuits, the dials. Micro
logic
5.0
ground faults and earth leakage. The value c all the settings not available via the dials are made
previously set using a dial automatically in the same manner, using the keypad.
becomes the maximum value for the keypad Caution!
settings. A new overload (long-time) or short-circuit
c they may also be used to activate other (short-time and instantaneous) protection setting
factory-disabled protection functions made using one of the dials:
c deletes all the fine adjustments previously
available on Micrologic P. These other made using the keypad for the overload
protection functions are not accessible (long-time) and short-circuit (short-time and
via the dials. instantaneous) protection
c does not affect the fine adjustments made
using the keypad for ground-fault and
earth-leakage protection
c does not affect any other settings made using
With the protective cover open, make all the keypad.
the necessary settings for your control unit.
Similarly, a new ground-fault or earth-leakage
protection setting made using one of the dials:
All fine adjustments are permanently stored c deletes all the fine adjustments previously
in memory, unless the setting is modified made using the keypad for the ground-fault and
using the adjustment dial. earth-leakage protection
c does not affect the fine adjustments made
using the keypad for the overload (long-time) and
For remote settings using the short-circuit (short-time and instantaneous)
communications option, protection
see the "Remote settings" section in c does not affect any other settings made using
the keypad.
the "Com setup" menu under "History,
maintenance and setup".
E60253B
E60254B
functions. However, it is possible to set
metering functions and alarms, as well as Micro
logic
5.0
Micro
logic
5.0
Caution!
If you notice that the tab on the back of the protective
Micro
logic
5.0 cover has been broken off, contact the Schneider
after-sales support department to replace the cover.
E60325A
long time In = 2000 A
Ir
E60445A
.8
.7 .9 Ir = 0.5 x 2000 = 1000 A
.6 .95
.5 .98
.4 1
Isd = 2 x 1000 = 2000 A
x In
short time instantaneous Ii = 2 x 2000 = 4000 A
Isd Ii
3
4
5 6 8 10
2.5 6 4 12
2 8 3 15
1.5 10 2 off
x Ir x In
1 setting
In = 2000 A
A
2000
In =
See pages 22 and 24 for selection of the Set the time delays
setting ranges.
E60326A
long time tr = 1 s
tr 8
(s) 4 12
2 16
1 20
.5 24
tsd = 0.2 s
@ 6 Ir
short time
tsd
(s) .4 .4 .3
.3 .2
.2 .1
.1 2 0
on I t off
delay
E51372A
E51376A
E51375A
t t t t
Ir Ir
tr tr
Isd Isd
tsd tsd
Ii Ii
0 I 0 I 0 I 0 I
Ir: LT threshold tr: LT tripping delay
Isd: ST pickup tsd: ST tripping delay
Ii: Instantaneous pickup
E60329A
long time In = 2000 A
Ir
E60445A
.8
.7 .9
.6 .95
.5 .98 Ir = 0.5 x 2000 = 1000 A
.4 1
x In
short time instantaneous
Isd Ii Isd = 2 x 1000 = 2000 A
3
4
5 6 8 10
2.5 6 4 12
2 8 3 15
1.5 10 2 off
Ii = 2 x 2000 = 4000 A
x Ir x In
1 setting
Ig
E
B Ig = 640 A
D F
C G
In = 2000 A B H
2000
A
A J
In =
ground fault
long time tr = 1 s
tr 8
(s) 4 12
2 16
1 20
.5 24
@ 6 Ir
short time
tsd
tsd = 0.2 s
(s) .4 .4 .3
.3 .2
.2 .1
.1 2
0
on I t off
delay tg = 0.2 s
tg
(s) .4 .4 .3
.3 .2
.2 .1
.1 2
0
on I t off
ground fault
E51372A
E51376A
E51375A
t t t t
Ir Ir
tr tr
Isd Isd
tsd tsd
Ii Ii
0 I 0 I 0 I 0 I
Ir: LT threshold tr: LT tripping delay
Isd: ST pickup tsd: ST tripping delay
Ii: Instantaneous pickup
E51415A
E51416A
t
E51418A
E51419A
t t t
Ig Ig
tg tg
0 I 0 I 0 I 0 I
Ig: ground-fault pickup tg: ground-fault tripping delay
E60333B
long time In = 2000 A
Ir
E60445A
.8
.7 .9
.6 .95
.5 .98 Ir = 0.5 x 2000 = 1000 A
.4 1
x In
short time instantaneous
Isd Ii Isd = 2 x 1000 = 2000 A
3
4
5 6 8 10
2.5 6 4 12
2 8 3 15
1.5 10 2 off
Ii = 2 x 2000 = 4000 A
x Ir x In
1 setting
I∆n
(A) 5
I∆n = 1 A
3 7
2 10
1 20
In = 2000 A
A
.5 30
2000
In =
earth leakage
long time tr = 1 s
tr 8
(s) 4 12
2 16
1 20
.5 24
@ 6 Ir
E60153A
short time
tsd
tsd = 0.2 s
(s) .4 .4 .3
.3 .2
.2 .1
.1 2
0
on I t off
delay ∆t = 140 ms
∆t
(ms)
230 350
140
60 800
earth leakage
E51372A
E51375A
t
E51376A
Ir t t t
Ir
tr tr
Isd Isd
tsd tsd
Ii Ii
0 I 0 I 0 I 0 I
Ir: LT threshold tr: LT tripping delay
Isd: ST pickup tsd: ST tripping delay
Ii: Instantaneous pickup
E51421A
t t
E51423A
I∆n
∆t
0 I 0 I
I∆n: earth-leakage pickup ∆t: earth-leakage tripping
delay
Caution!
With the 4P 3D setting, the current in the neutral must
not exceed the rated current of the circuit breaker.
The Micrologic P control unit offers access to the main screen and three menus:
c the main screen displaying the continuous measurement of the phase currents
(I1, I2, I3) and the neutral current (IN), if it exists
c the "Metering" menu
c the "History, maintenance and setup" menu
c the "Protection" menu.
Main screen
E60101A
As long as no functions are activated, Micrologic P
50
When a menu button is pressed, a "Metering", "History, maintenance and setup" and
presentation screen is displayed and the "Protection" menus
green LED on the button goes ON.
c "Metering" menu
E60102A
I (A) screen
E (kWh)
F (Hz)
E71711A
v press the or button to return to the main
Event screen
history
v press the button to return to the previous
Contacts screen
M2C / M6C v whatever the screen displayed, if no further action is
taken, the system returns to the main screen after a
Micrologic few minutes
setup v the LED goes OFF on exiting the menu.
Metering
setup
Com.
setup
c "Protection" menu
Current screen
protection
v press the button to return to the previous
Voltage screen
protection v whatever the screen displayed, if no further action is
taken, the system returns to the main screen after a
Other few minutes
protection v the LED goes OFF on exiting the menu.
Load
shedding I
Load
shedding P
c saving settings
E71657A
no
yes
Current measurements
I (A) access to the following sections:
I (A)
U (V)
Instant.
P (kW)
I1, I2, I3, IN currents
E (kWh) I1, I2, I3, IN (depending on the type of
system)
Demand
Voltage measurements
I (A)
access to the following sections:
U (V)
U (V)
Instantaneous phase-to-phase U12, U23, U31 and
Instant. phase-to-neutral V1N, V2N, V3N voltages
P (kW) (depending on the type of system)
F (Hz)
Unbal 3 Φ
Unbalance voltage U unbal. of the phase-to-phase
voltages.
Phase sequence.
Phase
rotation
Power factor PF
F (Hz) Power
factor
Demand
Energy measurements
I (A)
access to the following sections:
E (kWh)
U (V)
Total active energy E.P
P (kW) E total Total reactive energy E.Q
Total apparent energy E.S
E (kWh) E in
Positive component of:
c the total active energy E.P
c the total reactive energy E.Q
F (Hz)
E out
Negative component of:
c the total active energy E.P
c the total reactive energy E.Q
Frequency measurement
I (A)
access to the frequency measurement
F (Hz)
U (V)
P (kW)
E (kWh)
F (Hz)
Press the button to select the "History, maintenance and setup" menu.
indicates that the operator is in the "History, maintenance and setup" menu
and returns to the previous screen.
Event
history Micrologic access to the following sections:
Contacts setup
M2C / M6C
Selection of the display language
Micrologic Language
setup
Metering Setting of the date and time
setup Date / time
Voltage protection
protection
Fine settings of the long-time I2t, short-time and
Other (A)
protection I instantaneous protection functions
Load
shedding P Fine settings of the:
I (A) c ground-fault (Micrologic 6.0 P)
c earth-leakage (Micrologic 7.0 P) protection functions
Voltage protection
Current
protection Voltage access to the following sections:
protection
Voltage
protection Setting of the minimum-voltage protection U min.
Other Umin (V)
protection
Setting of the maximum-voltage protection U max.
Load Umax (V)
shedding I
Load Setting of the voltage-unbalance protection U unbal.
shedding P Uunbal (%)
E71720A
Load
shedding P Setting of the maximum-frequency protection F max
Fmax (Hz)
Setting of the phase-rotation protection
E71721A
Phase
Current rotation
protection
Voltage
protection Load shedding depending on current
Other Load Access to load shedding and reconnection
protection shedding I depending on current
Load
shedding I
Load
shedding P
Current
protection Load Access to load shedding and reconnection
protection
Other
protection
Load
shedding I
Load
shedding P
For the default values, the setting ranges, The long-time protection function protects cables against overloads. This function is
based on true rms measurements.
increment steps and setting accuracies,
It is possible to select either I2t long-time protection or Idmtl long-time protection.
see the technical appendix.
Thermal memory
c the thermal memory continuously accounts for the amount of heat in the cables,
both before and after tripping, whatever the value of the current (presence of an
overload or not). The thermal memory optimises the long-time protection function of
the circuit breaker by taking into account the temperature rise in the cables.
c the thermal memory assumes a cable cooling time of approximately 15 minutes.
Idmtl Protection
Long-time current setting Ir and Idmtl tripping delay tr
For the characteristics and external wiring c zone selective interlocking (ZSI)
The short-time and ground-fault protection functions enable time discrimination by
of the zone selective interlocking function, delaying the upstream devices to provide the downstream devices the time
see the technical appendix on "Zone required to clear the fault. Zone selective interlocking can be used to obtain total
selective interlocking". discrimination between circuit breakers using external wiring.
c intermittent faults are taken into account by Micrologic P and may lead to shorter
tripping times than those set.
If the "without long-time protection" plug is used and the long-time protection
function is disabled, the short-time pickup Isd is automatically multiplied by In
instead of Ir as is the standard case.
Instantaneous protection
c the instantaneous-protection function protects the distribution system against
solid short-circuits. Contrary to the short-time protection function, the tripping delay
for instantaneous protection is not adjustable. The tripping order is sent to the
circuit breaker as soon as current exceeds the set value, with a fixed time delay of
20 milliseconds.
c this function carries out true rms measurements.
Instantaneous pickup Ii
Micrologic control unit 5.0 P, 6.0 P and 7.0 P
pickup Ii = In (*) x ... accuracy ± 10 % 2 3 4 6 8 10 12 15 OFF
(*) In: circuit-breaker rating
c circuit breakers have two types of instantaneous protection:
v adjustable instantaneous protection Ii
v self-protection.
Depending on the circuit breaker, the OFF position corresponds to
the self-protection pickup.
For the default values, the setting ranges, Three-pole circuit breakers
increment steps and setting accuracies, Protection of the neutral is possible on a three-pole circuit breaker by connecting
see the technical appendix. an external sensor.
Settings are made using the and buttons on the control unit.
The and buttons on the control unit may then be used for a more precise
setting. The dial setting constitutes the upper limit for adjustments using the keypad.
For the default values, the setting ranges, Ground-fault protection on Micrologic 6.0 P
increment steps and setting accuracies, c an ground fault in the protection conductors can provoke local temperature rise at
the site of the fault or in the conductors. The purpose of the ground-fault protection
see the technical appendix. function is to eliminate this type of fault.
c there are two types of ground-fault protection.
Type Description
Residual c the function determines the zero-phase sequence
current, i.e. the vector sum of the phase and neutral
currents (depending on the type of installation).
Source Ground Return c using a special external sensor, this function directly
measures the fault current returning to the transformer
via the earth cable
c it detects faults both upstream and downstream of
the circuit breaker
c the maximum distance between the sensor and the
circuit breaker is ten metres.
E71740A
t
3
1
4
2
0 I t Alarm, I unbal,
I max
1: pickup threshold
2: pickup time delay
3: dropout threshold
4: dropout time delay
I t Alarm
c the alarm function is tripped by the rms value of an earth-leakage current
c this alarm signals an earth-leakage current under the pickup value and does not
produce circuit-breaker tripping.
I c from:
v I avg is the average value of the rms currents of the
E max
I avg three phases
I1 + I2 + I3
I avg =
3
v E max is the maximum difference between the
0 I1 I2 I3
current of each phase and I avg
c Micrologic P uses the two values above to calculate
the current unbalance:
E max
I unbal =
I avg
Note:
IN max protection does not take into account the neutral-protection setting (N, N/2, 1.6xN, OFF).
E60489A
E71741A
t t
1 3
3 1
2 4
4 2
0 U min 0 U max
U unbal.
1: pickup threshold
2: pickup time delay
3: dropout threshold
4: dropout time delay
U
v U avg is the average value of the rms voltages of the
E max three phases
U avg
U12 + U23 + U31
U avg =
3
v E max: is the maximum difference between the
0 U12 U23 U31 voltage of each phase and U avg
c Micrologic P uses the two values above to calculate
the voltage unbalance:
E max
U unbal =
U avg
E60487A
E60486A
t t
1 3
3 1
2 4
4 2
0 F min 0 F max
rP max
1: pickup threshold
2: pickup time delay
3: dropout threshold
4: dropout time delay
Note:
The direction of flow is set by the user in the "Power sign" section of the "Micrologic setup"
menu under "History, maintenance and settings".
c + corresponds to the normal direction of flow, i.e. from the top terminals on the circuit breaker
to the bottom terminals
c - is the opposite.
If the voltage protection functions are Minimum and maximum-frequency protection F min.
activated and the voltage measurement and F max
inputs are still energised, it is impossible to These functions monitor the value of the frequency on the distribution system.
reset and close the circuit breaker.
Phase-rotation alarm
This alarm is activated if two of the three phases are inverted.
Note:
The alarm is activated following a fixed 300-millisecond time delay. If one of the phases is
absent, the alarm will not operate. If the 400 Hz frequency is set, the alarm cannot be
activated.
For the pickup and dropout thresholds and Load shedding and reconnection depending on current
time delays, see the technical appendix. The pickup curve for load shedding and reconnection depending on current is
parallel to the LT I2t and Idmtl curves. If a "without long-time protection" rating plug
is installed, the load shedding/reconnection function based on current cannot be
activated.
c I2t protection: the neutral is taken into account
c Idmtl: the neutral is not taken into account.
This function does not trip the circuit breaker, but can be used to set off an alarm
linked to an M2C or M6C contact (disconnection and reconnection of non-priority
loads).
The load-shedding and reconnection function is determined by thresholds and time
delays.
E71754A
t
Long-time
protection
curve
3
1
4
0 I
1: pickup threshold
2: pickup time delay
3: dropout threshold
4: dropout time delay
The pickup threshold is always greater than or equal to the dropout threshold.
3
1
4
2
0 P
1: pickup threshold
2: pickup time delay
3: dropout threshold
4: dropout time delay
The pickup threshold is always greater than or equal to the dropout threshold.
Demand current
c display of the demand current on phases I1, I 2, I 3 and the neutral IN
(depending on the type of distribution system)
c selection of the demand calculation method
c display of the interval over which the value is calculated
c the maximum demand values are displayed and stored in memory
c the stored maximums can be reset at any time.
Note:
The calculation method, the type of calculation window (fixed or sliding) and its duration
may be set in the "Metering setup" menu under "History, maintenance and setup".
Average voltage
Average Uavg of the instantaneous voltages between phases U12, U23 and U31.
Phase rotation
Displays the phase sequence.
U c from:
E max v U avg is the average value of the rms voltages of the
U avg three phases
U12 + U23 + U31
U avg =
3
0 U12 U23 U31
v E max is the maximum difference between the
voltage of each phase and U avg
c Micrologic P uses the two values above to calculate
the voltage unbalance
E max
U unbal =
U avg
For the setting ranges and measurement Instantaneous power and power factor
accuracies, see the technical appendix. Micrologic P offers a number of different measurements.
c total power measurements:
v instantaneous active power P in kW
v instantaneous reactive power Q in kvar
v instantaneous apparent power S in kVA
c measurement of the power factor PF.
Demand power
c display of the demand values for the active power P, reactive power Q and
apparent power S
c selection of the demand calculation method
c display of the interval over which the value is calculated
c the maximum demand values are displayed and stored in memory
c the stored maximums can be reset at at any time.
Note:
c the calculation method, the type of calculation window (fixed or sliding) and its duration may
be set in the "Metering setup" menu under "History, maintenance and setup".
c the synchronisation function (Synchro.Com) is available only with the COM communication
option; with this function, the demand power is determined on the basis of a signal
synchronised by the communication module.
c these settings apply to all demand powers (active power P, reactive power Q and apparent
power S). If the settings are modified, the demand values are systematically recalculated.
Energy
Micrologic P offers a number of different measurements:
c total energy:
v total active energy E.P in kWh
v total reactive energy E.Q in kvarh
v total apparent energy E.S in kVAh
c energy consumed (Energy in), positively incremented:
v active energy E.P in kWh
v reactive energy E.Q in kvarh
c energy supplied (Energy out), negatively incremented:
v active energy E.P in kWh
v reactive energy E.Q in kvarh
c energy values can be reset.
Note:
c the Energy in and Energy out values are incremented according to the power sign set
in the "Metering setup" menu under "History, maintenance and setup".
c as standard, the total calculated energy values are "absolute total values".
They represent the sum of the energy in and out values:
v EP = Σ EP in + Σ EP out
v EQ = Σ EQ in + Σ EQ out
c as an option (access exclusively via the COM communications option), energy can be
calculated algebraically:
v EP = Σ EP in - Σ EP out
v EQ = Σ EQ in - Σ EQ out
These values are called "signed" energies.
Frequency
The frequency of the distribution system is displayed in Hz.
c delayed alarms are activated when the pickup and dropout thresholds are
Dropout T2 overrun and the corresponding time delays have expired.
c history logging
v Alarm mode: as soon as a given protection threshold is overrun, an alarm is
recorded in the "Alarm history"
v Trip mode: as soon as a given protection threshold is overrun, the circuit breaker
trips and the fault is recorded in the "Trip history".
c the "Protection setup" menu under "History, maintenance and setup" is used to
enable or disable the Trip mode that is displayed in the protection-setting screens.
On leaving the factory, the protection functions are set to Alarm mode.
c the "M2C / M6C contacts" menu under "History, maintenance and setup" is used
to link an M2C or M6C contact to an alarm. M2C and M6C contacts may not be
used together. They require a 24 V external power supply.
c the COM communications module can be used to transmit alarms to a
supervisor.
474
484
E60494B
Ir threshold T1 tr delay
Wiring diagram for M6C contacts
T2 = 1 sec
11
17
19
21
23
25
1
5
7
9
E60491C
Ir LED Press
Internal alarm
12
14
16
18
20
22
24
2
6
8
Internal alarm
Non-latching contact
Time-delay Reset possible before
contact delay 1 to 360 s end of delay
Latching Reset possible
contact only after pressing
Pickup
Dropout
Internal alarm
Non-latching contact
Time-delay Reset possible before
contact delay 1 to 360 s end of delay
Latching Reset possible
contact only after T2
Alarm history
c the alarm history is the means to display at any time the parameters measured
during the last ten alarms.
c for each alarm, the following parameters are recorded:
v alarm cause
v alarm threshold
v date
v time (hours, minutes and seconds).
Operation counter
This function is available only via the COM communications option.
c Micrologic P:
v stores and displays the total number of operations (incremented each time the
circuit breaker opens) since the initial installation of the circuit breaker
v stores and displays the total number of operations since the last reset.
Note:
If the control unit is changed, the circuit breaker must be defined again. In this case, see
"Breaker selection" in the "Micrologic setup" menu under "History, maintenance and
setup".
E60444A
E60495A
Micrologic 5.0 P
Alarm
4260A
off
N 1 2 3
100
50
E71600B
Reset
by test/reset
button
c fault-trip LEDs
c the LEDs indicate the type of fault that tripped the circuit breaker
c the LEDs are located in the upper part of the front panel (red Ir, Isd, Ii, Ig, I2n and
Ap LEDs)
c when activated, a LED remains ON until it is locally reset.
E60337B
E60338B
Micrologic 5.0 P Micrologic 5.0 P
E60340B
Communication options
Digipact and ModBus are the indispensable elements when integrating Micrologic P
Chassis in the Digivision and SMS Powerlogic installation-management systems which
communicate via the BatiBus and ModBus protocols.
External gateways are available for communication over other networks, including
COM module on ProfiBus, Ethernet, etc.
chassis (optional)
The communications option makes possible the following remote functions:
c device identification:
v address
v device type
v control-unit type
v type of long-time rating plug
Circuit breaker
c settings:
COM module on circuit breaker
v reading of the dial settings
v fine adjustments within the range determined by the dial
v protection and alarm settings
(Infra Red)
v setup of the M2C / M6C contacts.
c measurement values:
v currents
Micrologic P
control unit v voltages, frequencies, power, etc.
c fault values:
v fault type
v interrupted current.
c indicators:
v contact wear, counters, etc.
v maintenance register.
E71601A
E60146A
E60226A
Alarm S2 S2
type
S1
S2 Ir Ir
then then
Select a contact. Select an alarm. Confirm.
E71603A
E71604A
Setup
Setup
M2C / M6C S2 S2
S1 Mode Mode
S2 latching latching
contact contact
then then
Select a contact. Select a latching mode: Confirm.
c non-latching
c latching
c time-delay
c locked to 1
c locked to 0.
E71605A
E71606A
E71607A
S2 S2 S2
Mode Mode Mode
time delay time delay time delay
then
Select the time delay. Adjust. Confirm.
E60389A
Reset (- / +) Reset (- / +)
then
Reset the contacts to 0… or cancel the reset,
then confirm.
E71608A
E71938B
setup
Language Language
Language
Deutsch English UK
English US Espanol
English UK Français
Espanol Italiano
Français
Select. Confirm.
To return to English
1. Return to the main 2. Select the "History, 4. Select the "Language"
screen by pressing any maintenance and setup" menu by moving the
of the three buttons menu by pressing cursor up on the first
menu.
Confirm by pressing
or press the button 3. Select the "Micrologic
setup" menu by moving
the cursor up on the first
followed by any of the menu. Move the cursor
three buttons down on the third menu
and confirm
by pressing
E71611B
E71612B
18 : 30 : 03 18 : 30 : 03 18 : 30 : 03
E71614B
Date and time are backed up by battery.
Date Date
If time is not synchronised by
the supervisor via the communication
module, a drift of up to one hour per year 01 / 01 / 2000 01 / 01 / 2000
may be observed.
Time Time
18 : 30 : 03 18 : 30 : 03
then then
Enter the year. Set the time in the same
manner.
E89322A
E89323A
setup Breaker Breaker Breaker
Breaker selection selection selection
selection Standard Standard Standard
UL IEC IEC
The circuit-breaker code is required to
identify the device and activate the contact-
Circuit breaker Circuit breaker Circuit breaker
wear counter. Masterpact Masterpact Masterpact
type type type
Note this code if the control unit NT08N NT H1 NT H1
must be changed (example 03E7). 03E7 03E7 03E7
P Logicxxxxxx P Logicxxxxxx P Logicxxxxxx
Enter this code when setting up a new
control unit on the circuit breaker. then then then
For a new device, the code is set to zero. Select the standard. Choose and confirm. Select the circuit breaker.
E89325A
E89326A
E71642B
E71643B
E71644B
setup Power Power Power
Power
sign sign sign sign
By default, Micrologic P uses P+ for the P- P+ P+
power flowing from top to bottom terminals.
The selected direction of flow is valid for:
c measurement of power and the power
factor
c measurement of energy
c load shedding and reconnection
depending on power.
E71625A
E71626A
setup VT ratio VT ratio VT ratio
VT ratio
Primary Primary Primary
If the supply voltage for the control unit 690V 690V 690V
exceeds 690 V, an external voltage Secondary Secondary Secondary
transformer must be installed.
690V 690V 690V
To display the true voltage values, enter the
transformation ratio between the primary
and secondary voltages of the transformer.
E71628A
E71629A
E71631A
E71632A
System System System
type type type
3Φ 4w 3Φ 3w 3Φ 3w
3CT 3CT 3CT
E89200C
E89201C
E89213C
E89214C
E89215C
Current Current Current
demand demand demand
Calculation Calculation Calculation
method method method
block block block
interval interval interval
Window type Window type Window type
sliding sliding sliding
Interval Interval Interval
15 min 20 min 20 min
Select the command Select the calculation method for demand power
Metering
E89216C
E89217C
Power Power
E89218C
setup Power
Power demand demand demand
demand
Calculation Calculation Calculation
The synchronisation function method method method
"Synchro.Com" is available only with the
block block
COM communication option. With this thermal interval
interval
function, the demand power is determined
on the basis of a signal synchronised by
Window type Window type Window type
the communication module. sliding sliding sliding
Interval Interval Interval
Thermal method based on I2t calculation.
15 min 15 min 15 min
Sliding window:
power demand is refreshed
every 15 secondes. Select. Choose between: Confirm.
c thermal
c block interval
Fixed window: c sync. to comms
power demand is refreshed
E89219C
E89220C
E89221C
E89223C
Power Power Power
demand demand demand
Calculation Calculation Calculation
method method method
block block block
interval interval interval
Window type Window type Window type
fixed fixed fixed
Interval Interval Interval
15 min 20 min 20 min
E89226B
E89227B
setup
Sign
Sign Sign Sign
convention convention convention convention
See page 87 for the description of power
factor sign conventions.
Select the command When a COM communications option is used, it is necessary to:
c set up the COM communications option
Com. c authorise remote setting of the Micrologic control unit
setup c authorise remote control of the circuit breaker.
Com.
parameter View and set up the communications option
E71723A
E71724A
E71725A
As soon as the Digipact or ModBus Modbus Modbus Modbus
communications option is connected, the Com Com Com
control unit recognises it and displays the
Address Address Address
type of module on the graphic screen.
Automatic time updates are possible only 47 45 45
with the ModBus system.
Baud-rate Baud-rate Baud-rate
9600 9600 9600
Parity Parity Parity
None None None
then
Select an existing Adjust. Confirm.
parameter.
Adjust all the other parameters for the communications option in the same manner.
DIGIPACT MODBUS
(read only) (read and set up)
Address 1 - 255 1 - 47
Baud rate 9 600 bauds
19 200 bauds
Parity Even
None
E71728A
then
Select existing setting. Choose. Confirm.
E71730A
E71731A
If the operator does not enter a specific
access code, the default access code is
Remote Remote Remote
0000 and is requested by the supervisor. settings settings settings
Access Access Access
permit permit permit
Yes Yes Yes
Select the existing Enter the first digit. Confirm and proceed in
access code setting. the same manner for the
other digits.
E71733A
E71734A
setup Remote Remote Remote
Remote control control control
control
E71738A
Select the command.
Current I(A)
protection Trip
E60276A
E60275A
E60149A
I(A) I(A) I(A)
Trip Trip Trip
1000 A 998 A 998 A
1.0 s 1.0 s 1.0 s
then
Select a setting. Adjust the value. Confirm.
E71657A
E60277A
then
Adjust the other settings Quit the setting screen. Confirm.
and confirm.
E71739A
Select the command
Current Idmtl (A)
protection Trip
Idmtl (A) 1000 A long-time current setting Ir
1.0 s long-time tripping delay tr
EIT Idmtl protection:
DT, SIT, VIT, EIT, HVF
2000 A short-time pickup Isd
0.2 s short-time tripping delay tsd
4000 A instantaneous pickup Ii
E60151A
E71718A
E60278A
Idmtl (A) Idmtl (A) Idmtl (A)
Trip Trip
1000 A 1000 A
Change I(A)
1.0 s 1.0 s
settings with
Idmtl(A)? EIT VIT
2000 A 2000 A
0.2 s 0.2 s
No 4000 A 4000 A
Yes
then then
Select yes. Select a setting. Change the setting.
E71657A
E60279A
E60280A
puis
Confirm. Adjust the other settings. Confirm.
E89230A
Select the command
E89231A
Current I (A) I (A)
protection Trip Trip
I (A)
1200A threshold 1200A
then
Select a setting.
E89232A
E89233A
E89234A
I (A) I (A) I (A)
Trip Trip Trip
then
Adjust the value. Confirm. Go to the next setting.
E89236A
E89236A
E89237B
E89238B
E89239B
protection Ineutral (A) Ineutral (A) Ineutral (A)
Ineutral (A) Neutral CT Neutral CT Neutral CT
E89242B
E89241B
E89240B
then
Select. Choose. Confirm.
E89242B
E71657A
Ineutral (A)
Neutral CT
Do you want
External to save new
settings?
Protection no
N/2 yes
Note:
On four-pole circuit breakers, setting of the neutral using the keypad is limited by the dial
setting.
E71661B
Select the corresponding menu
type of protection
Current
protection
operating mode
(Off, Alarm or Trip)
I Alarm Pick up
pickup threshold
I unbal (%)
pickup time delay
I3 max (A)
Specific case for It alarm
c only the following choices are available:
IN max (A) v On: activation of the alarm without fault tripping by the circuit breaker
v Off: alarm disabled.
Voltage
protection Example: Maximum voltage setting (U max)
c select Alarm mode
Umin (V)
E60292B
E60171B
E60293B
Umax (V) Umax (V) Umax (V)
Umax (V)
Off Alarm Alarm
Uunbal (%) Pick up Pick up Pick up
690V 690V 690V
Other 5.00s 5.00s 5.00s
protection
Drop out Drop out Drop out
rPmax (W) 690V 690V 690V
0.50s 0.50s 0.50s
Fmin (Hz)
then
Fmax (Hz)
Select the first setting. Choose Off or Alarm. Confirm.
Phase
E60292B
E89294B
rotation
Umax (V) Umax (V)
Off Trip
Pick up Pick up
690V 690V
In trip mode, the dropout threshold is equal 5.00s 5.00s
to the pickup threshold.
The dropout time delay is fixed and equal Drop out
to 1 second. 690V
0.50s
then
Select the first setting. Choose Trip.
no
yes
then
Confirm.
For protection tripped by a maximum value, c set the pickup and dropout thresholds and time delays
the dropout threshold is always less than or
E71665A
E71666A
E71667A
equal to the pickup threshold.
Umax (V) Umax (V) Umax (V)
For protection tripped by a minimum value,
the dropout threshold is always greater Alarm Alarm Alarm
than or equal to the pickup threshold. Pick up Pick up Pick up
If both the minimum and maximum 690V 690V 690V
protection values are activated, the 5.00s 5.00s 5.00s
minimum threshold is automatically limited
to the value of the maximum and vice
Drop out Drop out Drop out
versa. 690V 685V 685V
0.50s 0.50s 0.50s
then
Select the existing Adjust. Confirm.
dropout threshold setting
E71668A
E71668A
E71657A
then
Set the other parameters. Quit the setting screen. Confirm
E71673B
Select the command
Load type of shedding (I or P)
Load shedding
shedding I
operating mode (On, Off)
Load
shedding P Pick up
pickup threshold
pickup time delay
Drop out
dropout threshold
dropout time delay
E71670A
E71671A
E71672A
Load Load Load
shedding P shedding P shedding P
Off On On
Pick up Pick up Pick up
1000kW 1000kW 1000kW
3600s 3600s 3600s
Drop out Drop out Drop out
1000kW 1000kW 1000kW
10s 10s 10s
then
Select the first setting. Select: Confirm.
c Off: load shedding
disabled
c On: load shedding
enabled.
E71674A
E71675A
E71676A
Load Load Load
shedding P shedding P shedding P
On On On
Pick up Pick up Pick up
1000kW 1000kW 1000kW
3600s 3600s 3600s
Drop out Drop out Drop out
980kW 985kW 985kW
10s 10s 10s
then
Select the existing Adjust. Confirm.
dropout threshold.
E71677A
E71677A
E71657A
then
Set the other parameters. Quit the setting screen. Confim.
E60184A
E60185A
E60187A
The neutral current is displayed if the
neutral CT is set to internal or external
4260A 3850A 3410A
(see "Ineutral (A)" settings in the "Current 1 2 3 1 2 3 1 2 3
protection" menu).
100 100 100
50 50 50
0 0 0
The and buttons may be used to display the currents on the three
phases. If the operator no longer uses the buttons for a few seconds, the bargraph
returns to the display of the most heavily loaded phase.
E60189A
then
Select. View.
E60191A
I inst. Imax
I1, I2, I3, IN instant.
I1 = 5600 A
Max I2 = 4800 A
I3 = 4700 A
IN = 800 A
I = 28 A
Reset ( - / + )
then
Select. View.
E60192A
E60191A
Imax Imax
instant. instant.
I1 = 0A I1 = 5600 A
I2 = 0A I2 = 4800 A
I3 = 0A I3 = 4700 A
IN = 0A IN = 800 A
I = 0A I = 28 A
Reset ( - / + ) Reset ( - / + )
E71679A
then
Select. View.
E71681A
E71680A
Demand Imax
Demand
I1, I2, I3, IN
15min
I1 = 4020 A
Max
I2 = 4450 A
I3 = 4300 A
IN = 600 A
Reset ( - / +)
then
Select. View.
E71683A
Imax Imax
Demand Demand
15min 15min
I1 = 0A I1 = 4020 A
I2 = 0A I2 = 4450 A
I3 = 0A I3 = 4300 A
IN = 0A IN = 600 A
Reset ( - / +) Reset ( - / +)
U (V)
E89257B
E60193A
U (V) Uinst.
Instant.
The phase-to-neutral voltages are U12 = 400 V
displayed if the selected system type is U23 = 404 V
3-phase, 4-wire (see page 43).
Average 3Φ
U31 = 401 V
Unbal 3Φ
Phase U1N = 230 V
rotation U2N = 229 V
U3N = 233 V
then
Select. View.
E71687A
U (V) Uavg.
Instant. 3Φ
Average 3Φ
402 V
Unbal 3Φ
Phase
rotation
then
Select. View.
E71689A
U (V) Uunbal
Instant.
3Φ
Average 3Φ
1%
Unbal 3Φ
Phase
rotation
then
Select. View.
E89260A
E89261A
U (V) Phase
rotation
Instant.
Average 3Φ
Unbal 3Φ
∆Φ : 1, 2, 3
Phase
rotation
then
Select. View.
E60199B
P
E71690A
(kW) Pinst.
Pinst.
Instant. P, Q, S
P (kW)
Power 2180
To ensure reliable power and power-factor factor
measurements, the "Power sign" and "Sign
convention" parameters must be set. Q (kvar)
-650
S (kVA)
2280
then
Select. View.
E71692A
Power
Pinst. factor
P, Q, S
Power
factor 1.00
then
Select. View.
S (kVA)
2640
then
Select. View.
E71695A
E71696B
Demand Pmax
Demand
P, Q, S P (kW)
2450
Max
Q (kvar)
-800
S (kVA)
2700
Reset (- / +)
then
Select. View.
E71698B
Pmax Pmax
Demand Demand
P (kW) P (kW)
0 2450
Q (kvar) Q (kvar)
0 -800
S (kVA) S (kVA)
0 2700
Reset (- / +) Reset (- / +)
E (kWh)
E71699A
Select the energy value to be measured:
E (kWh) c total energy
c energy in (positive component in the total energy)
To ensure reliable energy measurements, E total c energy out (negative component in the total energy).
the "Power sign" and "Sign convention"
parameters must be set. E in
E out
Reset
energy
then
Select.
E71700B
E71701B
E71702B
E total E in E out
E.P (kWh) E.P (kWh) E.P (kWh)
20168 +21320 168
E.S (kVAh)
22926
View the total energy View the energy View the energy
values. in values. out values.
E71705A
E71703A
E (kWh) Reset
To reset
E total Energy energy
E in press
Are you enter
sure ?
E out
Reset
Energy No
Yes
then then
Select. Select yes or no. If yes, confirm.
E60110A
Select the command
F (Hz)
F (Hz)
60.0
View.
Caution! The fault indication is maintained until it is reset on the control panel.
Press the reset button.
If the circuit breaker remains closed and
the Ap LED remains ON after the reset,
E60306B
open the circuit breaker and contact the Micrologic 7.0 P
Fault
22/11/1999
02:04:04
Umin 100V
Reset
by test/reset
button
E71706A
E71707A
history Trip Trip
Trip history 22/11/1999
history 02:04:04
U min Umin 160V
27/01/1999
Ir
27/06/1998
Ir
18/02/1998
then
Select a fault. View.
E71709A
Alarm Alarm
Alarm history 27/01/1999
history
13:06:09
I2 max I2 max 3400A
27/01/1999
In max
23/03/1998
U max
12/02/1998
then
Select an alarm. View.
E71736A
E71737A
E71735A
history Number of Number of Number of
operations operations operations
Operation
counter Total Total Total
17824 17824 17824
Operations Operations Operations
since last since last since last
reset reset reset
6923 0 6923
then
Reset… … or cancel the reset,
then confirm.
history Contact
Contact wear
wear
E60307A
Micrologic 7.0 P
1 2 3
Press and hold down the test button on the control unit to check the LEDs and the
battery. The battery information is displayed if the control unit is equipped with an
external power supply or if the circuit breaker is ON.
E71751A
If the battery must be replaced, use a new Replacing the control-unit battery
battery with the Schneider part number
1. remove 2. remove the battery
33593 (technical characteristics available the battery cover
on the battery-slot cover).
E60308A
E51443A
E60481A
E60309A
5.0 P
logic
Micro
If the circuit breaker does not trip, contact the after-sales support department.
E60311A
5.0 P 5.0 P
logic logic
Micro Micro
E71753A
5 000 Ir = 0.4…1 x In
2 000
1 000
500 tr = 0.5…24 s
200
100
50
20
10
5
t(s) Isd = 1.5…10 x Ir
2
1
I2t ON
.5 0.4 0.4
0.3 0.3
.2 0.2 0.2
0.1 0.1
.1 I2t OFF
0 0
.05
Ii = 2…15 x In . OFF
.02
.01
.005
.002
.001
.5 .7 1 2 3 4 5 7 10 20 3 5 7 10 20 30
x Ir x In
HVF
10 000
5 000
2 000
1 000
500 EIT
t(s) 200
100 VIT
50
20 SIT
10
DT
5
1
.5
.5 .7 1 2 3 4 5 7 10 20
I / Ir
E46266A
10 000
5 000
2 000
Ig = A…J x In (1)
1 000 1200 A max.
500
200
100
50
20
10
5
t(s) I2t ON
2
1
.5 0.4 0.4
0.3 0.3
.2 0.2 0.2
2 0.1 0.1
.1 It OFF
0 0
.05
.02
.01
.005
.002
.001
.05.07 .1 .2 .3 .4 .5 .7 1 2 3 5 7 10 200 300
I / In
Micrologic P is equipped with a three-phase voltage power supply that, with respect
to the distribution system, may be considered a delta load. The three-phase power
supply reinjects voltage on an open phase.
The voltage-protection functions react as indicated below.
Minimum-voltage protection
This function is based on the measurement of the phase-to-phase voltages.
In diagrams 1, 3 and 4 on the next page, a fuse has blown. The control unit
reinjects voltage on the failed phase and measures a phase-to-phase voltage
higher than the actual voltage.
The phase-to-neutral voltage should be zero, but the value measured is not zero.
Voltage-unbalance protection
This function is based on the measurement of the phase-to-phase voltages.
In diagrams 1, 3 and 4 on the next page, a fuse has blown. The control unit
reinjects voltage on the failed phase and measures a phase-to-phase voltage
higher than the actual voltage.
The phase-to-neutral voltage should be zero, but the value measured is not zero.
Phase failure
Detection of phase failure is not possible on the basis of the minimum-voltage and
voltage-unbalance protection functions.
The Micrologic power supply requires at least two phases (between 100 and 690 V).
In diagrams 1, 3 and 4, if two phases have failed, Micrologic H measures for the
three phases the value of the single voltage present (e.g. U12 = U23 = U31 = 410 V).
E71916A
Contactor
Fuses
Motor
Open
c diagram 2
E71917A
Contactor
Fuses
Motor
Open
c diagram 3
E71918A
Contactor
Motor
Open
Fuses
c diagram 4
E71919A
Load
Fuses
Other
measurement
and protection
systems
Operating principle
c a fault occurs at point A
Downstream device no. 2 clears the fault and sends a signal to upstream device no.
1, which maintains the short-time tripping delay tsd or the ground-fault tripping
delay tg to which it is set.
c a fault occurs at point B
Upstream device no. 1 detects the fault. In the absence of a signal from a
downstream device, the set time delay is not taken into account and the device
1
trips according to the zero setting. If it is connected to a device further upstream, it
B
sends a signal to that device, which delays tripping according to its tsd or tg setting.
Note:
On device no. 1, the tsd and tg tripping delays must not be set to zero because this
would make discrimination impossible.
2
A
Connections between control units
A logic signal (0 or 5 volts) can be used for zone selective interlocking between the
upstream and downstream circuit breakers.
c Micrologic 5.0 A, 6.0 A, 7.0 A
c Micrologic 5.0 P, 6.0 P, 7.0 P
c Micrologic 5.0 H, 6.0 H, 7.0 H.
An interface is available for connection to previous generations of trip units.
Caution! Wiring
lf the protection function is not used on c maximum impedance: 2.7 Ω / 300 metres
circuit breakers equipped for ZSI c capacity of connectors: 0.4 to 2.5 mm2
protection, a jumper must be installed to c wires: single or multicore
short terminals Z3, Z4 and Z5. If the jumper c maximum length: 3000 metres
c limits to device interconnection:
is not installed, the short-time and ground- v the common ZSI - OUT (Z1) and the output ZSI - OUT (Z2) can be connected to
fault tripping delays are set to zero, a maximum of ten inputs
whatever the position of the adjustment v a maximum of 100 devices may be connected to the common ZSI - IN (Z3) and
dial. to an input ZSI - IN CR (Z4) or GF (Z5).
E71912A
point B
2 Z1
Z2
Z3 tsd = 0. 2
Z4
Z5
point A
Z1 downstream Z1
Z2 circuit-breaker Z2
Z3 Z3
Z4 Z4
Z5 Z5
Test
The portable test kit may be used to check the wiring and operation of the zone
selective interlocking between a number of circuit breakers.
Battery module
Use of a BAT battery module, mounted in series with the AD power-supply module,
ensures a continous supply of 24 V DC power for 12 hours if the AD module fails.
Wiring diagrams
v reliable or backed-up auxiliary system
E60449A
L4
L3 Input
AC
220V
0V t
OutpuC +
AD 22 – 24VD
G2
G1
F2
F1 +
-
L4 H4
L3 Input H3 InputC +
220V
AC
- 24VD
0V t
OutpuC + 24 V t
OutpuC
-
AD 22 – 24VD
G2 BAT + 24VD
H1
G1 H2
F2
F1 +
-
2 Q3
Q1 Q
25
21 23
17 19
L4
M6C
L3 Input
AC
220V
0V t
OutpuC +
AD 22 – 24VD
G2
G1
c if the 24 V DC external power supply (AD module) is used, the maximum cable
length between 24 V DC (G1, G2) and the control unit (F1-, F2+) must not exceed
10 metres.
c the communications bus requires its own 24 V DC power source (E1, E2).
This source is not the same as the 24 V DC external power-supply module
(F1-, F2+).
When the PTE option is implemented, the supply circuit of the voltage-
measurement input must be protected against short-circuits. Installed as close
as possible to the busbars, this protection function is ensured by a P25M circuit
breaker (1 A rating) with an auxiliary contact (cat. no. 21104 and 21117).
A number of long-time rating plugs are available for Micrologic P control units.
Caution!
Change the long-time rating plug
Following any modifications to the long-
Proceed in the following manner.
time rating plug, all control-unit protection
parameters must be checked. 1. open the circuit breaker
2. open the protective 3. completely remove
cover of the control unit the long-time rating plug screw
E89252A
E89253A
H
logic
5.0 5.0 H
Micro logic
Micro
Caution! 4. snap out the rating 5. clip in the new rating plug
plug
If no long-time rating plug is installed, the
E89254A
control unit continues to operate under the 6. refit the screw for the
following downgraded conditions: long-time rating plug
5.0 H
logic
Ir .8 .9
.7 2 20
.95
.6 1 24
.98 .5 @ 6 Ir
.5 1
.4 x In
alarm
long
time tr 8 12
(s) 4 16
Ir .8 .9
.7 2 20
.95
.6 1 24
.98 .5 @ 6 Ir
.5 1
.4 x In
Thermal memory
The thermal memory is the means to take into account temperature rise and
cooling caused by changes in the flow of current in the conductors.
Control units with a thermal memory record the temperature rise caused by each
overload, even very short ones. This information stored in the thermal memory
reduces the tripping time.
c for all protection functions, prior to tripping, the temperature-rise and cooling time
constants are equal and depend depend on the tr tripping delay:
v if the tripping delay is short, the time constant is low
v if the tripping delay is long, the time constant is high.
c for long-time protection, following tripping, the cooling curve is simulated by the
control unit. Closing of the circuit breaker prior to the end of the time constant
(approximately 15 minutes) reduces the tripping time indicated in the tripping
curves.
Setup / Maintenance
c setting of the control-unit date and time
c password for the measurement module
c control-unit ID code
c control-unit ID name
c selection of the measurement calculation algorithm
c sign convention for the active power
c total-energy measurement mode
c interval for the demand-current calculation window
c power quality indication
c demand-power calculation mode
c interval for the demand-power calculation window
c battery-charge indication
c trip and alarm histories
c operation counter and contact-wear indicator
c assignment and setup of programmable contacts
c event log and maintenance register.
Protection
c circuit-breaker rated current
c type of neutral protection
c long-time I2t protection settings
c long-time Idmtl protection settings
c short-time protection settings
c instantaneous-protection settings
c ground-fault protection settings
c earth-leakage protection settings
c current-unbalance, It alarm and maximum-current protection settings
c voltage-protection settings
c setting for other protection functions.
Short-time protection
Instantaneous protection
Neutral protection
Voltage protection
Type Range Factory setting Step Accuracy
minimum voltage U min
Pickup threshold 100 V to U max pickup threshold 100 V 5V -5 %, +0 %
Dropout threshold pickup threshold to U max pickup threshold 5V -5 %, +0 %
pickup threshold
Pickup time delay 1.2 s to 5 s 5s 0.1 s -0 %, +20 %
Dropout time delay 1.2 s to 36 s 1.2 s 0.1 s -0 %, +20 %
maximum voltage U max
Pickup threshold U min pickup threshold to 1200 V 725 V 5V -0 %, +5 %
Dropout threshold 100 V to pickup threshold pickup threshold 5V -0 %, +5 %
Pickup time delay 1.2 s to 5 s 5s 0.1 s -0 %, +20 %
Dropout time delay 1.2 s to 36 s 1.2 s 0.1 s -0 %, +20 %
voltage unbalance U unbal
Pickup threshold 2% to 30% 30 % 1% -20 %, +0 %
Dropout threshold 2% to pickup threshold pickup threshold 1% -20 %, +0 %
Pickup time delay 1 s to 40 s 40 s 1s -20 %, +0 %
Dropout time delay 10 s to 360 s 10 s 1s -20 %, +0 %
Other protection
Type Range Factory setting Step Accuracy
reverse power rP max
Pickup threshold 5 to 500 kW 500 kW 5 kW ± 2.5%
Dropout threshold 5 kW to pickup threshold pickup threshold 5 kW ± 2.5%
Pickup time delay 0.2 s to 20 s 20 s 0.1 s -0 %, +20 % (1)
Dropout time delay 1 s to 360 s 1s 0.1 s -0 %, +20 %
maximum frequency F max
Pickup threshold F min pickup threshold to 440 Hz 65 Hz 0.5 Hz ± 0.5 Hz
Dropout threshold 45 Hz to pickup threshold pickup threshold 0.5 Hz ± 0.5 Hz
Pickup time delay 1.2 s to 5 s 5s 0.1 s -0 %, +20 % (2)
Dropout time delay 1.2 s to 36 s 1.2 s 0.1 s -0 %, +20 % (2)
minimum frequency F min
Pickup threshold 45 Hz to F max pickup threshold 45 Hz 0.5 Hz ± 0.5 Hz
Dropout threshold pickup threshold to F max pickup threshold 0.5 Hz ± 0.5 Hz
pickup threshold
Pickup time delay 1.2 s to 5 s 5s 0.1 s -0 %, +20 % (2)
Dropout time delay 1.2 s to 36 s 1.2 s 0.1 s -0 %, +20 % (2)
phase rotation
Pickup threshold Ph1, Ph2, Ph3 or Ph1, Ph3, Ph2 Ph1, Ph2, Ph3 none none
Dropout threshold pickup threshold pickup threshold none none
Pickup time delay 0.3 s 0.3 s none - 0 %, + 50 %
Dropout time delay 0.3 s 0.3 s none - 0 %, + 50 %
(1) + 30 % on dial 0.2 s
(2) + 30 % up to 1.5 s
Micrologic setup
Type Range Factory setting Step
language German English UK
English US
English UK
Italian
French
Spanish
Chinese
date / time 1s
circuit-breaker "no def"
selection
neutral TC no TC
VT ratio
primary voltage min. 100 V, max. 1150 V 690 V 1V
secondary voltage min. 100 V, max. 690 V 690 V 1V
system 50/60 Hz 50/60 Hz
frequency or
400 Hz
Measurement setup
Type Range Factory setting Step
system type 3 Φ, 3 w, 3 CT 3 Φ, 4 w, 4 CT
3 Φ, 4 w, 3 CT
3 Φ, 4 w, 4 CT
demand-current
calculation method thermal or block interval
block interval
type of window fixed or sliding sliding
calculation interval 5 to 60 minutes 15 minutes 1 minute
demand-power
calculation method thermal or block interval
block interval or
sync. to comms
type of window fixed or sliding sliding
calculation interval 5 to 60 minutes 15 minutes 1 minute
power sign P+ P+
P- (flow from top to
bottom)
sign convention IEEE IEEE
IEEE alternate
IEC
Communication setup
Type Range Factory setting
com parameter MODBUS
address 1-47 47
baud rate 9600 to 19 200 bauds 19 200 bauds
parity even even
none
remote settings
access authorisation yes / no yes
access code 0000 to 9999 0000
remote manual automatic
control automatic
Protection setup
Type Range Factory setting
current protection alarm / trip / OFF OFF
voltage protection
other protection
E71920B
Flow of active and
reactive power Q
E71921B
IEC
Q
P=- P=+
Q=+ Q=+
pf = - pf = +
P
P=- P=+
Q=- Q=-
pf = - pf = +
E71922B
IEEE
Q
P=- P=+
Q=+ Q=+
pf = + (leading) pf = - (lagging)
P
P=- P=+
Q=- Q=-
pf = - (lagging) pf = + (leading)
E71923B
IEEE Alt
Q
P=- P=+
Q=- Q=-
pf = + (leading) pf = - (lagging)
P
P=- P=+
Q=+ Q=+
pf = - (lagging) pf = + (leading)
A
Activation 25, 26, 27, 28, 31
Active, reactive, apparent energy 30, 63
Active, reactive, apparent power 30
AD power-supply module 77
Address 36
Alarm 31
Alarm history 33, 67
B
Baud rate 46
Buttons 5, 6
C
Circuit-breaker selection 41
COM communication option 36, 46, 81
Contact 32, 38
Contact wear 68
Control unit identification 4
Control-unit battery 5, 69
Current demand calculation 29, 43
D
Date and time 40
Demand current 29, 57
Demand power 30, 61
Digipact 46
Dropout 25, 26, 27, 28, 31
DT 21, 49
E
Earth-leakage protection 24
Earth-leakage protection tripping delay ∆ 24
EIT 21, 49
F
F max 30, 52
F min 30, 52
Fault 66
Frequency 30, 64
Full neutral protection 23, 51
Graphic display 5
Ground-fault / Earth-leakage fault protection test 70
Ground-fault protection 24
H
Half neutral protection 23, 51
History, setup and maintenance menu 13, 16
HVF 21, 49
I
It 50
I t Alarm 25, 52
I avg 25
I max 25, 52
I unbal 25, 52
I∆n pickup 24
I2t 20, 48
Idmtl 21, 49
Ig pickup 24
Ii pickup 22
Infrared link 5
Instantaneous current 29, 56
Instantaneous protection 22
Ir current setting 20, 21
Isd pickup 22
L
Language 40
Latching 32
Lead seal for cover 5
LEDs 5, 34, 69
Load shedding / reconnection 28, 54
Long-time I2t protection 20
Long-time Idmtl protection 21
Long-time plug 5, 79
N
Negatively incremented energy 30, 63
Neutral CT 51
Neutral protection 11, 23
Neutral protection setting 11, 51
No neutral protection 23, 51
O
Operation counter 68
Oversized neutral protection 23, 51
P
Parity 46
Phase rotation 27, 52
Phase sequence 27
Phase-to-neutral and phase-to-phase voltage 29, 59
Portable test kit 70
Positively incremented energy 30, 63
Power demand calculation 30, 44
Power factor 61
Power sign 42
Power supply 77
Protection menu 13, 18
R
Remote control 47
Remote settings 46
Resetting the alarms and fault indications 66
Resetting the contacts 32, 38
Resetting the energy values 63
Resetting the maximum demand current values 58
Resetting the maximum demand power values 62
Resetting the maximum instantaneous current values 57
Resetting the operation counter 68
rP max 27, 52
S
Self-protection 35
Setting dials 5, 6
Short-time protection 22
Sign convention 87
SIT 21, 49
System frequency 42
System type 43
T
Tab 7
Temperature 35
Test connector 5, 70
tg tripping delay 24
Thermal memory 20, 80
tr tripping delay 20, 21
Transformation ratio 42
Trip 4
Trip history 33, 67
Tripping curves 72
tsd tripping delay 22
U
U max 26, 52
U min 26, 52
U unbal 26, 52, 59
V
VIT 21, 49
Voltage U avg 26, 29, 59
Z
Zone selective interlocking 76
http://www.schneider-electric.com
04443726AA-D 05-02