Project Specification
SECTION 46 07 13
PACKAGED WATER TREATMENT EQUIPMENT
PART 1:
1.01
GENERAL
SECTION INCLUDES
A.
B.
The Contractor shall be fully responsible for the final design, as indicated diagrammatically on the Drawings to supply a complete system to the approval of the Engineer.
1.02
RELATED SECTIONS
A.
Section 23 05 13.13
B.
Section 23 05 13
C.
Section 25 05 00
D.
Section 23 05 53
E.
Section 22 05 13
F.
Section 22 11 13
G.
Section 22 05 23
H.
Section 22 05 29
1.03
SUBMITTALS
A.
B.
C.
D.
E.
Operation and Maintenance Manual: Three (3) Operation and Maintenance manuals in
Arabic and English languages.
1.04
QUALITY ASSURANCE
A.
B.
Installer: Firms engaged for at least 10 years in the installation of plants of similar type,
quality and scope as required for this project.
SECTION 46 07 13 - 1
MINISTRY OF HOUSING
Western Sector Projects
Sitework & Infrastructure
OMRANIA and ASSOCIATES
Project Specification
C.
Perform work in accordance with the standards of the appropriate local authority having
jurisdiction.
D.
Submit proof of license to perform the work as issued by the local authority having
jurisdiction.
1.05
A.
1.06
WARRANTY
A.
B.
Operate and maintain the Water Treatment Plant for a trial period of one (1) month. During
this period, all parts of the plant shall be examined for function, strength, water tightness
and sound performance. If any part installed or constructed by the Contractor is found
faulty on testing, the part shall be rectified or replaced by new and examined again until the
Engineer approves all works. All equipment, chemicals, spare parts, personnel and other
requirements for testing, operating and maintaining the plant during the trial period shall be
provided by the Contractor.
1.07
A.
AMBIENT CONDITIONS
All equipments shall be designed to withstand local ambient conditions.
PART 2:
2.01
PRODUCTS
ACCEPTABLE MANUFACTURERS
Not Used.
2.02
PROCESS DESCRIPTION
A.
The Plant shall be designed to produce disinfected potable water with a TDS not more than
300 mg/l and an irrigation water quality with TDS of 800 mg/l.
B.
Raw water shall be extracted from the raw water storage tank filled from the well. Boosted
raw water will then be fed to the pre-treatment filtration.
C.
Water shall pass through media filters using sand and anthracite with a SDI less than 3.
D.
Dosing of filtered water by proprietary sequestrant shall then take place to inhibit the
formation of fouling scales in the reject of the R.O. membrane by the inhibition of the
crystalline formation.
E.
Water shall then pass through 5-micron cartridge filters to protect the R.O. membrane.
F.
Chemically conditioned water shall then be pressurized by high pressure centrifugal pump
and passed to the reverse osmosis module for production of low total dissolved solid
product water by reverse osmosis and discharge of concentrate reject brine water to reject
brine tank.
G.
Product water shall be treated with chlorine to acceptable levels for drinking water.
2.03
BASIS OF DESIGN
SECTION 46 07 13 - 2
MINISTRY OF HOUSING
Western Sector Projects
Sitework & Infrastructure
OMRANIA and ASSOCIATES
Project Specification
A.
The final water produced from the treatment plant shall comply with the water standards
specified. Blending of filtered raw water with the R.O. product shall be permitted to give
the required final water quality.
B.
The Plant shall be equipped with all interconnecting pipework and measuring gauges,
together with all appropriate electrical equipment.
C.
The following treatment plant characteristics are envisaged, related to the ultimate water
consumption:
1. Water Consumption: 930 m/day.
2. Water Use: Potable/Irrigation.
3. Raw Water Quality: To be analyzed by the Contractor.
4. Source Water Supply: From deep well to be determined by the Contractor.
5. Treated water quality: TDS not more than 300 mg/l for potable water and 800 mg/l for
irrigation.
6. R.O. recovery: 75% minimum.
2.04
A.
B.
SECTION 46 07 13 - 3
MINISTRY OF HOUSING
Western Sector Projects
Sitework & Infrastructure
OMRANIA and ASSOCIATES
Project Specification
D.
E.
SECTION 46 07 13 - 4
MINISTRY OF HOUSING
Western Sector Projects
Sitework & Infrastructure
OMRANIA and ASSOCIATES
Project Specification
G.
H.
Cartridge Filtration:
1. Material of Construction: 316 Stainless steel.
2. No. of cartridge filter units: 3
3. Capacity each unit: 22.51 cu.m./hr.
4. Maximum Pressure: 10 bar.
5. Particle Cut Off Size: 5 micron.
6. Cartridge Material: Polypropylene.
7. Accessories: Pressure gauges.
I.
SECTION 46 07 13 - 5
MINISTRY OF HOUSING
Western Sector Projects
Sitework & Infrastructure
OMRANIA and ASSOCIATES
Project Specification
K.
L.
M.
SECTION 46 07 13 - 6
MINISTRY OF HOUSING
Western Sector Projects
Sitework & Infrastructure
OMRANIA and ASSOCIATES
N.
Project Specification
O.
Flush Tank
1. Type: Cylindrical, vertically mounted
2. Material: Polypropylene
3. Capacity: 1000 liters
4. Pipework: interconnecting pipework for flushing of membranes.
P.
Control Panel:
1. Type: Completely assembled, wired and tested at the factory. The panel shall be
fabricated in sheet steel, shaped and reinforced to form a rigid front access enclosure.
The panel shall be for indoor use in a humid 50 oC ambient temperature to IP 54
standard.
2. Mounting: All push buttons, fuses, selectors, switches, contactors, relays, indicating
lights, timers, etc. to form a local central control station.
3. Cabling: Wiring shall be brought out to screw type terminal blocks, labeled and
identified in accordance with wiring diagram.
4. Nameplates: All push buttons and selector switches shall be appropriately tagged.
5. Finish: All steelwork shall be bonderised or given similar treatment before priming with
epoxy paint to a smooth finish.
Q.
Instrumentation:
1. pH Meter:
a. Quantity: Three (3).
b. Application: R.O. Feed Line.
c. Range: 0 - 14.
d. Type: Indicating, flush mounted meter complete with sensor and fittings.
2. Pressure Gauges:
SECTION 46 07 13 - 7
MINISTRY OF HOUSING
Western Sector Projects
Sitework & Infrastructure
OMRANIA and ASSOCIATES
Project Specification
S.
T.
Pipework: Process and interconnecting pipework for the Water Treatment Plant shall
generally be uPVC Class 5 SASO 14 with flanged joints, as described under the various
sections of this Specification.
U.
Plant Wiring: Cables shall be suitably sized for the appropriate duty, PVC sheathed and
extend only between the panel and the individual drives and controls.
PART 3:
3.01
EXECUTION
INSTALLATION
A.
All work shall be executed in a first-class and workmanlike manner by workmen skilled in
the trade to which they are assigned.
B.
Equipment and plant shall be seated and secured strictly in accordance with manufacturers
instructions.
C.
Adequate supervision shall be provided to maintain high quality workmanship. The work
shall present a neat, mechanical appearance when completed.
3.02
A.
All piping, equipment and system components shall be installed with the utmost precautions
to prevent noise and vibration transmission.
B.
Equipment that would tend to cause noise or vibration shall be isolated with suitable
vibration isolators to reduce noise or vibration transmission to buildings and /or other
equipment. Piping connected to this equipment shall also be isolated.
3.03
TRAINING
A.
B.
Provide instructions and training to the Owners staff for the operation and maintenance of the
equipment. Provide a minimum of 5 days classroom and 5 days on the job training. Each
training session shall be 4 hours long.
SECTION 46 07 13 - 8
MINISTRY OF HOUSING
Western Sector Projects
Sitework & Infrastructure
OMRANIA and ASSOCIATES
Project Specification
END OF SECTION