Beruflich Dokumente
Kultur Dokumente
BFS 2013:10
EKS 9
materials and products match the reality. The verification shall at least correspond
to what is specified for CE marking of a similar product. (BFS 2013:10).
General recommendation
The assessment of characteristics of a construction product under options a),
c) or d) does not mean that the product has been evaluated against the
Swedish requirements for structures in this statute or in Boverkets Building
Regulations (BFS 2011:6), BBR, but merely that the client/owner shall have
confidence in the accompanying declaration of the characteristics of the
product. (BFS 2013:10).
Coexistence period
Article 5 When a harmonised standard has been published for the actual
product or an European Technical Assessment, ETA has been issued2 for that
product, only an assessment in accordance with the alternative a) in Article 4
would be applicable. The standard may include a coexistence period as been
established and published in the Official Journal of the European Union3. In such
cases, assessments in accordance with alternatives other than alternative a) would
also be valid until the end of the coexistence period. (BFS 2013:10).
Mutual recognition
Article 6 As with the assessment in accordance with alternatives c) or d) in
Article 4, an assessment issued by some other body within the European Union or
European Economic Area or in Turkey would also be acceptable if the body is
1. accredited for the task against the requirements in regulation (EC) No
765/2008, or
2. can in some other way provide similar guarantees concerning technical and
professional competence and guarantees of independence. (BFS 2013:10).
Durability
Article 7 Structural elements and materials that form part of the load-bearing
structure shall either be naturally durable or made durable through protective
measures and maintenance so that the requirements for ultimate and serviceability
limit states are met over the structures working life. If permanent protection is
not possible, anticipated changes in the properties shall be taken into
consideration in the design. In case of preconditioned maintenance, structures
shall be formed so that the affected parts would become accessible for regular
maintenance and protective measures.
For information about current European technical approvals see the EOTA website
http://www.eota.be about Valid ETAs.
3
The coexistence periods, EU's Official Journal starting from issue 2007/12 refers to the
website of the European Commission database NANDO
http://ec.europa.eu/enterprise/newapproach/nando/index.cfm?fuseaction=cpd.hs.
General recommendation
Article 8 Additional requirements regarding materials or protective
measures with regard to the impact on the indoor environment, local
environment and microbial growth can be found in sections 6:11 and 6:5 in
Boverkets Building Regulations (BFS 2011:6), BBR.
Materials
Article 11 Material for bearing structures, including soil and rock, shall have
known, suitable, and documented properties with regard to those aspects that are
of significance for their use.
be performed after it has been established that the function of the structural
element is not compromised. Consultation shall take place, to the extent deemed
necessary, with the person responsible for the construction documents.
Provisional bracing shall be arranged for stabilisation during the installation
period.
Inspection
Design inspection
Article 13 Design inspection in this statute refers to the inspection of the design
preconditions, construction documents, and calculations.
General recommendation
Design inspection is intended to eliminate major errors. The inspection
should be performed by a person who has not previously participated in the
project. The degree of organisational and financial direct or indirect
autonomy for the person performing the design inspection should be
increased for projects of a more complex nature.
Inspection of execution
Article 15 For the purposes of this statute, inspection of execution refers to a
check by the client/owner that
1. previously non-verifiable project design requirements of significance for
safety are met and that
2. the work is carried out in accordance with the relevant specifications,
drawings, and other documentation.
Basic inspection
Article 16 Basic inspection in these provisions refers to the general inspection
of material, products, and execution of work.
General recommendation
Material-specific rules for the basic inspection can be found in the relevant
material part or in execution standards associated with these.
Supplementary inspection
Article 17 Supplementary inspection refers in this statute to the specific
inspection that shall be performed on
1. construction details that are vital for the structures bearing capacity,
stability or durability,
2. construction details that require special type of workmanship, and
3. effects on the surroundings.
A plan shall be drawn up for the supplementary inspection.
General recommendation
Material-specific rules for supplementary inspection can be found in the
relevant material part or in execution standards associated with these.
Documentation
Article 18 The results of the performed inspections shall be documented. Any
deviations with associated measures shall be noted, along with other tasks that are
significant for the quality of the completed structure.
General recommendation
The documentation requirements are also included in Article 10 in this
section and in Section C, Chapter 1.1.2, Article 4.
Terminology
Article 19 Terms that are not explained separately in the main statutes or in this
statute shall have the meaning given in the Swedish Centre for Terminology
publication Planning and Building Terms 1994, TNC 95.
General recommendation
It should be noted that the Eurocodes also contain definitions.
EN standard
EN 1990:2002 +
EN 1990/A1:2005
1.1.1
EN 1991-1-1:2002
1.1.2
EN 1991-1-2:2002
1.1.3
EN 1991-1-3:2002
1.1.4
EN 1991-1-4:2005
1.1.5
EN 1991-1-5:2003
1.1.6
EN 1991-1-6:2005
1.1.7
EN 1991-1-7:2006
1.2
EN 1991-2:2003
1.3
EN 1991-3:2006
Chapter
EN standard
1.4
EN 1991-4:2006
2.1.1
EN 1992-1-1:2005 +
EN 1992-1-1:2005/
AC:2008 + EN 1992-11:2005/AC:2010
2.1.2
EN 1992-1-2:2004
2.2
EN 1992-2:2005+ EN
1992-2:2005/AC:2008
2.3
EN 1992-3:2006
3.1.1
EN 1993-1-1:2005 +
EN1993-1-1:2005/
AC:2006+ EN 1993-11/AC:2009
3.1.2
EN 1993-1-2:2005+ EN
1993-1-2:2005/
AC:2005
3.1.3
EN 1993-1-3:2006
3.1.4
EN 1993-1-4:2006
3.1.5
EN 1993-1-5:2006+
EN 1993-1-5/AC:2009
3.1.6
EN 1993-1-6:2007
3.1.7
EN 1993-1-7:2007
3.1.8
EN 1993-1-8:2005 EN
1993-1-8:2005/
AC:2005
3.1.9
EN 1993-1-9:2005+
EN 1993-1-9:2005/ AC:
2007 + EN 1993-19:2005/AC:2009
3.1.10
EN 1993-1-10:2005 EN
1993-1-10:2005/ AC:
2007 + EN 1993-110:2005/AC:2009
3.1.11
EN 1993-1-11:2006+
EN 1993-111:2006/AC:2009
3.1.12
EN 1993-1-12:2007 +
EN 1993-112:2007/AC:2009
Chapter
EN standard
3.2
EN 1993-2:2006
3.4.1
EN 1993-4-1:2007 + EN
1993-4-1:2007/
AC:2009
3.4.2
EN 1993-4-2:2007 + EN
1993-4-2:2007/
AC:2009
3.6
EN 1993-6:2007 + EN
1993-6:2007/ AC:2009
4.1.1
EN 1994-1-1:2005 + EN
1994-1-1:2004/AC:2009
4.1.2
EN 1994-1-2:2005+
EN 1994-12:2005/AC:2008
4.2
EN 1994-2:2005+ EN
1994-2:2005/AC:2008
5.1.1
EN 1995-1-1:2004+
EN 1995-1-1:2004/
AC:2006 + EN 1995-11:2004/A1: 2008
5.1.2
EN 1995-1-2:2004+
EN 1995-1-2:2004/
AC:2006+EN 1995-12:2004/AC:2010
5.2
EN 1995-2:2004
6.1.1
EN 1996-1-1: 2005+ EN
1996-1-1:2005/AC:2010
6.2
EN 1996-2: 2005+
EN 19962:2005/AC:2009
7.1
EN 1997-1:2004 +
EN 1997-1:2004
/AC:2009
9.1.1
EN 1999-1-1:2007
9.1.2
EN 1999-1-2:2007+
EN 1999-12:2007/AC:2009
9.1.3
EN 1999-1-3:2007 + EN
1999-1-3:2007/A1:2011
9.1.4
EN 1999-1-4:2007 + EN
1999-1-4:2007/AC:2009
+ EN 1999-11:2007/A1:2011
Chapter
EN standard
9.1.5
EN 1999-1-5:2007
(BFS 2013:10).
10
11
12
General recommendation
Article 11 Design values of fatigue loadsis specified in material part at
issue, for concrete see EN 1992-1-1 6.8.3, for steel see EN 1993-1-9:2005
5(1) and for composite structures see EN 1994-1-1 6.8.4.
Comments
A1.1(1)
A1.2.1(1) Note. 2
A1.2.2(1)
A1.3.1(1)
A.1.3.1(5)
A1.4.2(2)
Recommendation used
A1.1(1)
General recommendation
Article 15 Structural elements with design working life category 4 as per
2.3, table 2.1 in EN 1990 which are assigned to safety class 2 or 3 and
which are not accessible for inspection and maintenance should be
designed for a working life of 100 years.
A1.2.2(1)
Article 16 The values of -factors in table B-1 apply.
Table B-1
-factors
0
0.7
0.5
0.3
0.7
0.5
0.3
0.7
0.7
0.6
0.7
0.7
0.6
1.0
0.9
0.8
0.7
0.7
0.6
0.7
0.5
0.3
Category H: roofs
0,0
0,0
0,0
Load
Imposed load in buildings
13
Load
0.8
0.6
0.2
0.7
0.4
0.2
0.6
0.3
0.1
Wind action
0.3
0.2
0,0
0.6
0.5
0,0
A1.3.1(1)
Article 17 Design values of actions in the ultimate limit states (EQU), set A,
shall comply with Table B-2. Partial factor d is determined in Articles 1-6 in this
chapter.
Table B-2
Persistent
and
transient d.
s
Permanent actions
Leading
variable
action
Accompanying variable
actions
(Eq. 6.10)
Unfavourable
Favourable
0.9 G kj,inf
d 1,1G kj,sup
Main
When the load
is
unfavourable:
d 1.5 Q k,1
When the load
is favourable: 0
Other
When the load is
unfavourable:
d 1.5 0,iQ k,i
When the load is
favourable: 0
Design situations
Article 18 Equations 6.10a and 6.10b shall be applied in the ultimate limit
states, which do not include geotechnical actions with design values for actions in
accordance with Table B-3. Partial factor d is determined in Articles 1-6 in this
chapter.
When 6.10a is applied it is not permitted to include permanent actions only.
Table B-3
Persistent
and
transient d.
s
Permanent actions
(Eq. 6.10b)
Unfavourable
d 1.35 Gkj,sup
Favourable
1.00 G kj,inf
d 1.35 Pk
1.00 Pk
d 1.35 Pk
14
Accompanying variable
actions
(Eq. 6.10a)
Leading
variable
action
Design situations
1.00 Pk
Main
When the load
is
Unfavourable:
d 1.5 0,1Qk,1
When the load
is
favourable: 0
When the load
is
Unfavourable:
d 1.5 Qk,1
When the load
is favourable: 0
Other
When the load
is
Unfavourable:
d1.5 0,i Qk,i
When the load
is favourable: 0
When the load
is
Unfavourable:
d1.5 0,i Q k,i
When the load
is favourable: 0
Article 19 When Table A1.2(C) in the standard (Set C) is applicable, the design
values of loads are to be determined using the parameters specified in Table B-4.
Partial factor d is determined in Articles 1-6 in this chapter.
Table B-4
Persistent
and transient
d. s
Permanent actions
(Equivalent
6.10)
Unfavourable Favourable
1.00 Gkj,inf
d 1,10 Gkj,sup
Leading
variable
action
Accompanying variable
actions
Main
Other
When the load is
Unfavourable:
d 1,4 0, i Qk,i
When the load is
favourable: 0
Design situations
A.1.3.1(5)
Article 20 When the verification of structural elements involves geotechnical
actions as well as resistance of the ground, design method 2 or 3 shall be used
with design values in accordance with Table B-3 or B-4 respectively.
General recommendation
Design methods for verification of different types of geo-structures are
shown in Chapter 7.1, Article 15.
Comments
A2.1.1(1) Note 3
A2.2.1(2) Note 1
A2.2.6(1) Note 1
A2.3.1(1)
A2.3.1(5)
A2.3.1(7)
A2.3.1(8)
See A2.3.1(1)
See A2.3.1(1)
See A2.3.1(1)
A2.3.2(1)
Recommendation used
15
National choices
Comments
A2.4.1(1) Note 2
A2.4.1(2)
A2.2.2(1)
A2.2.2(3)
A2.2.2(4)
A2.2.2(6)
A2.2.6(1) Note 2
A2.2.6(1) Note 3
A2.2.3(2)
A2.2.3(3)
A2.2.3(4)
A2.4.3.2(1)
Recommendation used
A.2.2.4(1)
A.2.2.4(4)
A2.4.4.1(1) Note 3
A2.4.4.2.1(4)P
A2.4.4.2.2(3)P
Recommendation used
A2.4.4.2.3(1)
A2.4.4.2.3(2)
A2.4.4.2.3(3)
A2.4.4.2.4(3)
Recommendation used
A2.4.4.3.2(6)
A2.2.3(2)
Article 23 Wind and thermal actions shall be considered to act simultaneously.
A2.2.3(3)
Article 24 For the design of bridges with a roof, snow and the traffic loads shall
be combined.
A.2.2.4(1)
Article 25 For the design of moving swing type bridges, snow loads shall be
combined with other loads.
A2.2.6(1)
Article 26 The value of factors applied to snow and wind loads on the
finished structure shall at least be according to Table B-5.
16
Table B-5
0,3
0,2
1,0
sk 3 kN/m
0,8
0,6
0,2
0,7
0,6
0,4
0,3
0,2
0,1
Load
Symbol
Wind
forces
FWk
Snow
loads
General recommendation
For actions during execution, the recommended values should be applied.
A2.3.1(1)
Article 27 The design values of actions in the ultimate limit states (EQU), set A
in Annex A2, shall comply with Table B-2 in Article 17 of this chapter.
Verification of static equilibrium based on this table must not include verification
of the bearing capacity of structural elements. The partial factor d is determined
in accordance with Articles 1-6 in this chapter.
Article 28 Where Table A2.4(B) in set B in Annex 2 is applicable, expressions
6.10a and 6.10b shall be applied with the design values for loads in accordance
with Table B-3 in Article 18 in this chapter. The partial factor d is determined in
accordance with Articles 1-6 in this chapter.
When expression 6.10a is applied it is not permitted to only include permanent
actions.
Article 29 Where Table A2.4(C) set C in Annex A2 is applicable, the design
values of loads shall be determined with the parameters in Table B-4 in Article 19
in this chapter. The partial factor d is determined in accordance with Articles 1-6
in this chapter.
A2.3.1(5)
Article 30 Method 2 or 3 shall be used.
A2.3.2(1)
Article 31 In accidental design situations, the leading variable action shall be
set to its frequent value.
A2.4.4.1(1)
Article 32 For temporary bridges for train speeds 90 km/h, the same
requirements shall apply as for permanent bridges.
General recommendation
For temporary bridges for train speeds < 90 km/h, the bridge deformation
should not exceed L/500.
17
Comments
2.2 (3)
Recommendation used
5.2.3(1)
Recommendation used
5.2.3(2)
5.2.3(3)
5.2.3(4)
5.2.3(5)
6.3.1.2(10)
Recommendation used
6.3.1.2(11)
Recommendation used
Recommendation used
18
Category
qk [kN/m ]
Qk [kN]
2,0
2,0
3,5
1,0
0,5
2,0
2,0
2,0
1,5
0,5
B: office premises
2,5
3,0
2,5
3,0
2,5
3,0
3,0
3,0
4,0
4,0
5,0
4,5
4,0
5,0
4,0
7,0
b)
C: places of assembly
C1: Spaces with tables, etc. e.g. rooms in schools,
cafs, restaurants, canteens, reading rooms, reception
areas.
C2: Spaces with fixed seats, e.g. churches, theatres or
cinemas, conference halls, lecture halls, places of
assembly, waiting rooms, and waiting rooms at railway
stations.
C3: Unobstructed spaces for people on the move, e.g.
museums, exhibition halls, etc. and communications
facilities in public buildings, hotels, hospitals, and railway
stations.
C4: Spaces where physical activity may occur, e.g.
dance halls, gymnasiums, theatre stages.
C5: Spaces where large gatherings may be present,
such as in buildings designed for public gatherings such
as concert halls, sports halls including standing stands,
terraces, communication facilities, and platforms for
railways.
D: business premises
D1: Premises intended for retail.
D2: Premises in department stores.
a
b
Italicized values are those the standard recommends, the others represent national choices.
Note 6.3.1.1 (2) in EN 1991-1-1. The values in the table do not include dynamic effects.
Article 9 For balconies in connection with floors in category B, the same load
shall be applied as for balconies in category A. For balconies in connection with
floors in categories C to D, the same load shall be applied as for the floor.
For stairs in connection with floors in categories B, C1, C2, C3, C4, D1 and D2
the load as per category C3 is applied. For stairs in connection with floors in
category C5, the same load for the stairs is applied for the floor.
19
6.3.1.2 (10)
General recommendations
Article 9a Reduction factors for imposed loads, A and n, can be combined
in action set B for Categories A and B when the action effect is assessed
using Eq. 6.10b, Table B-3. The factors can even be combined in action set
C for categories A and B when the action effect is assessed using Eq. 6.10
Table B-4. (BFS 2013:10).
20
Figure C-1
Load of vehicles
21
Insignificant
Slight
Moderate
Large
Very large
General recommendation
Examples of the factors to be considered in Article 2 a) include the type of
building and occupancy, as described in Section 5:22 in Boverkets
Building Regulations (BFS 2011:6), BBR. Factors affecting the choice of
safety class for normal load cases should even be relevant for the fire load
case as per Article 2 b) and c), compare Articles 1-5, Chapter 0 in Section
B. Escape routes constitute an example of what is meant by Article 2 d).
Examples of appropriate classifications of structural elements are provided
in Tables C-3C-5. The tables give some guidance for the assignment of
fire safety classes based on safety classes in Articles 15, Chapter 0 in
Section B.
22
Table C-3
Table C-4
23
area, the design temperature-time curve may correspond to the standard fire
curve for 30 minutes (R 30).
Structural elements can be attributed to fire safety class 1 if the scale of
the collapse of the structural elements, i.e. the primary damage of all the
structural elements' collapse for 30 minutes and the adjacent area, are
limited to the maximum damage area indicated in Figure C-2. Otherwise,
the structural elements are assigned to fire safety class 3. The maximum
damage area is made up of a fire-affected area of 20 m2 and the adjacent
area is located not more than 11 m from the fire-affected area. The
assessment is made for all structural elements involved in the fire-affected
area for 30 minutes. The assessment should be based on an unfavourable
location of the fire-affected area.
For Br2-buildings containing healthcare facilities and special
accommodation with people with special care needs, all structural elements
belonging to the buildings main structural system should, however, be
attributed to fire safety class 3 at the least.
Figure C-2
Maximum
damage area
Fire-affected
area
20 m2
Table C-5
11 m
Fire safety
class
Landings and flights of stairs that serve as escape routes and are
located below the top basement level.
24
General recommendations
Examples of appropriate classification are provided by Table C-6.
Requirements for fire compartments follow from Section 5:53 in
Boverkets Building Regulations (BFS 2011:6), BBR.
Table C-6
Fire safety
class
Fire compartment boundaries intended for spaces with a fire load higher than
800 MJ/m2 may require a higher fire safety class or design in a higher fire
resistance class. See also Section 5:53 in Boverkets Building Regulations
(BFS 2011:6), BBR.
Walls that form fire compartment boundaries may however be stabilised by
floors assigned to fire safety classes in accordance with Tables C-3C-5.
(BFS 2013:10).
Documentation
Article 4 The description of the design of bearing capacity in the event of fire
shall be included in the fire protection documentation that shall be prepared in
accordance with Section 5:12 in Boverkets Building Regulations (BFS 2011:6),
BBR.
General recommendation
A fire protection documentation should include a description of the
assumptions of the bearing capacity in the event of fire as well as the
structural design in the event of fire.
Comments
2.4(4)
3.1(10)
3.3.1.2(1)
Recommendation used
3.3.1.2(2)
Recommendation used
3.3.1.3(1)
Recommendation used
3.3.2(2)
Recommendation used
4.2.2(2)
4.3.1(2)
25
2.4(4)
Nominal temperature - time curve
Article 6 Upon designing according to classification (nominal temperature time curve), the structural elements shall be designed to ensure that a collapse
does not occur during the time period specified in Table C-7 with a fire load as
described in Section 4.2 of SS-EN 13501-2. The first column (f 800 MJ/m2) in
Table C-7 may be applied for residential and commercial properties , schools,
hotels, car garages, grocery shops, apartment storage rooms and comparable fire
compartments without special investigation.
Table C-7
Fire safety
class
1
2
3
4
5
*
f 1,600 MJ/m
0
R15
R30
R120 (R90*)
R180 (R120*)
f >1,600 MJ/m
0
R15
R30
R180 (R120*)
R240 (R180*)
Upon installation of an automatic water sprinkler system in accordance with Section 5:252
and 5:2521 in Boverket Building Regulations (2011:6).
(BFS 2013:10).
2.4(4)
Natural fire model
Article 7 When designing according to a natural fire model, structural elements
shall be designed for a fire progression as described in Table C-8.
Table C-8
Fire safety
class
1
2
3
4
5
General recommendation
The design should be performed for a fully developed fire. If it can be
shown that a flashover cannot occur, the design can be performed for a local
fire.
If the likelihood of a flashover in a building in Br2 or Br3 can be shown
to be less than 0,5 %, given that a fire has occurred, the building only needs
to be designed for a local fire. This can for example be shown with at least
two independent technical systems with a guaranteed reliability, see also
Article 10. It may also be possible to show that no flashover can occur
based on a low fire load.
26
Local fire
Article 9 The fire progression and temperature development in the event of a
local fire shall be calculated taking into account the conditions likely to occur in
the building.
General recommendation
A local fire should be calculated in accordance with SS-EN 1991-1-2,
Annex C.
For the design of a local fire, account should be taken to the height and
location of the fuel in the room.
Technical systems
Article 10 The effect of permanently installed technical systems that reduce the
likelihood of flashover, limit the temperature in the fire room or otherwise limit or
extinguish the fire may be approved for the design provided that the total
probability of failure is not increased. A prerequisite for taking technical systems
into account is that their reliability is ensured.
The risk-reducing effect of such technical systems can be considered by
reducing the fire load in the design of a complete fire progression or by reducing
the local fire used for the design. The reliability of the system shall be considered.
General recommendation
When designing for complete fire progression, the fire load can be
multiplied by a factor of 0,6, provided that an automatic sprinkler system
has been installed in accordance with Section 5:252 and 5:2521 in
Boverkets Building Regulations (BFS 2011:6), BBR. (BFS 2013:10).
3.1(10)
Article 11 Either a nominal temperature-time curve or a natural fire model may
be used for the design of structures in the event of fire. Only a nominal
temperature time curve may be used for classification of fire resistance.
4.3.1(2)
Article 12 In accordance with Article 21, Chapter 0 in Section B of this statute,
the major variable action shall, in case of fire, be set to its frequent value (1Q1).
(BFS 2013:10).
General recommendations
Additional rules regarding the combination factors can be found in
Section B, Chapter 0, Article 21. (BFS 2013:10).
27
28
Comments
1.1(2)
1.1(3)
1.1(4)
2(3)
2(4)
3.3(1)
3.3(3)
4.1(1)
4.1(2)
Recommendation used
4.2(1)
4.3(1)
5.2(2)
5.2(5)
5.2(6)
Recommendation used
5.2(7)
Recommendation used
5.2(8)
5.3.3(4)
Recommendation used
5.3.4(3)
5.3.5(1)
5.3.5(3)
Recommendation used
5.3.6(1)
Recommendation used
5.3.6(3)
6.2(2)
6.3(1)
6.3(2)
Recommendation used
A(1)
D(2)
1.1(2)
General recommendation
Article 2 Snow loads at altitudes above 1,500 m above sea level should be
determined for each separate project where this is relevant with regard to
the prevailing conditions.
1.1(3)
Article 3 The exceptional load cases B1 and B3 in Annex A need not be taken
into account, as exceptional snow load is not relevant for Swedish conditions. The
exceptional load case B2 need not be taken into account.
General recommendation
Where the client/owner wishes to have higher than normal reliability for a
structure on open terrain where high wind loads may occur in connection
with snowfall, the structure may, however, be even verified for load case B2
with regard to exceptional snow drift.
29
Where verification is carried out for an exceptional snow drift, the snow
load may be regarded as an accidental action.
1.1(4)
General recommendation
Article 4 Where verification is carried out for exceptional snow drift in
accordance with Article 3, Annex B may be used.
4.1(1)
Article 6 Annex C must not be applied. Snow load on the ground with a return
period of 50 years is shown in Figure C-3 in this chapter.
General recommendation
Snow loads on the ground are given for different municipalities in Table C9 in this statute.
4.3(1)
Article 9 The exceptional load cases B1 and B3 in Annex A need not be taken
into account, as exceptional snow load is not relevant for Swedish conditions. The
exceptional load case B2 need not be taken into account.
General recommendation
Where the client/owner wishes to have higher than normal reliability for a
bearing structure on open terrain where high wind loads may occur in
connection with snowfall, the bearing structure may, however, also be
verified for load case B2 with regard to exceptional snow drift.
Where verification is carried out for an exceptional snow drift, the snow
load may be regarded as an accidental action.
30
5.2(2)
General recommendation
Article 10 Where verification is carried out for exceptional snow drift in
accordance with Article 3, Annex B may be used.
5.2(5)
General recommendation
Article 11 Load arrangements that take account of snow clearing should
be taken into consideration if these are not covered by the shape coefficients
referred to in Section 5.3 of the standard and if they are deemed critical for
the bearing capacity or stability of the structure.
5.2(8)
General recommendation
Article 12 ISO 4355 may be used to determine Ct.
5.3.4(3)
General recommendation
Article 13 Where verification is carried out for exceptional snow drift in
accordance with Article 3, Annex B may be used.
5.3.5(1)
Article 14 The upper value for 3 shall be set to 1,6. (BFS 2013:10).
5.3.6(3), 6.2(2)
General recommendation
Article 15 Where verification is carried out for exceptional snow drift in
accordance with Article 3, Annex B may be used.
6.3(1)
General recommendation
Article 16 Snow overhanging the edge of a roof should be taken into
account for sites located above 400 m above sea level. At sites located
below 400 m above sea level, the overhanging snow can be disregarded.
The load due to the overhanging snow can be determined using equation
(6.4) for sites located above 800 m above sea level. For sites located
between 400 and 800 m above sea level, this load can be determined by
rectilinear interpolation between the load value 0 at 400 m and the load
value as given by Eq. (6.4) at 800 m. (BFS 2013:10).
A(1)
General recommendation
Article 17 See Articles 35.
31
32
Figure C-3
Snow load on the ground: Snow zones for snow load on the
ground, sk, which with a probability of 0,98 is not exceeded once
per year (equivalent to 50 year return period) based on measured
data from 148 meteorological stations.
Snow zone
sk ,(kN/m )
1,0
1,5
1,5
2,0
2,5
2,5
3,0
3,5
3,5
4,5
4,5
5,5
5,5
(BFS 2013:10).
33
Table C-9
Municipality
sk
Municipality
sk
Municipality
sk
Ale
1,5
Finspng
2,5
Hr
1,5
Alingss
2,0
Flen
2,0
Jokkmokk
3,0-4,5
Alvesta
2,0
Forshaga
2,5
Jrflla
2,0
Aneby
2,5
Frgelanda
2,0
Jnkping
2,5-3,0
Arboga
2,5
Gagnef
3,0
Kalix
3,0
Kalmar
2,0-2,5
Karlsborg
2,0
Karlshamn
1,5-2,0
Arjeplog
3,0-4,5
Arvidsjaur
3,0
Gislaved
2,0-2,5
Gnesta
2,0
Arvika
2,5
Gnosj
2,0-2,5
Askersund
2,5
Gotland
2,5
Karlskoga
2,5
Avesta
2,5
Grums
2,5
Karlskrona
2,0
Bengtsfors
2,5
Grstorp
2,0
Karlstad
2,5
Berg
3,0-4,5
Gullspng
2,5
Katrineholm
2,0-2,5
Bjurholm
3,0
Gllivare
3,0-4,5
Kil
2,5
Bjuv
1,5
Gvle
2,5-3,0
Kinda
2,0-2,5
Boden
3,0
Gothenburg
1,5
Kiruna
2,5-4,5
Bollebygd
2,0
Gtene
2,0
Klippan
1,5
Bollns
3,0
Habo
2,5
Knivsta
1,5
Borgholm
2,0
Hagfors
2,5
Kramfors
3,0-4,5
Borlnge
3,0
Hallsberg
2,5
Kristianstad
1,5
Kristinehamn
2,5
Krokom
3,0-5,5
Bors
2,0-2,5
Hallstahammar
2,0
Botkyrka
2,0
Halmstad
1,5-2,5
Boxholm
2,0
Hammar
2,5
Kumla
2,5
Bromlla
1,5
Haninge
2,0
Kungsbacka
1,5
Brcke
2,5-3,0
Haparanda
3,0
Kungsr
2,0
Burlv
1,0
Heby
2,0-2,5
Kunglv
1,5
Bstad
1,5
Hedemora
2,5
Kvlinge
1,0-1,5
Dals-Ed
2,0
Helsingborg
1,0
Kping
2,5
Danderyd
2,0
Herrljunga
2,0
Laholm
1,5-3,0
Degerfors
2,5
Dorotea
3,0-4,5
Eda
2,5-3,0
Hjo
2,0
Landskrona
1,0
Hofors
2,5
Lax
2,5
Huddinge
2,0
Lekeberg
2,5
Leksand
2,5-3,0
Eker
2,0
Hudiksvall
3,0-3,5
Eksj
2,5
Hultsfred
2,5
Lerum
1,5
Emmaboda
2,0
Hylte
2,0
Lessebo
2,0
Enkping
2,0
Hbo
1,5
Liding
2,0
Eskilstuna
2,0
Hllefors
3,0
Lidkping
2,0
Lilla Edet
1,5
Lindesberg
2,5
Linkping
2,0
Ljungby
2,0-2,5
Ljusdal
3,0
Ljusnarsberg
3,0
Lomma
1,0
Eslv
1,5
Hrjedalen
3,0-4,5
Essunga
2,0
Hrnsand
3,5
Fagersta
2,5
Hrryda
1,5-2,0
Falkenberg
1,5-2,0
Hssleholm
1,5-2,0
2,0-2,5
Hgans
1,0
Falun
2,5-3,0
Filipstad
2,5
Falkping
34
Hgsby
2,0-2,5
Hrby
1,5
Municipality
sk
Ludvika
2,5-3,0
Lule
3,0
Lund
1,5
Lycksele
3,0-3,5
Lysekil
1,5
Malm
1,0
Malung
2,5-3,5
Mal
Mariestad
Municipality
sk
Municipality
sk
Robertsfors
3,0
Tingsryd
2,0
Ronneby
2,0
Tjrn
1,5
Rttvik
3,0
Tomelilla
1,5
Sala
2,0-2,5
Torsby
2,5-3,5
Salem
2,0
Torss
2,0
Sandviken
2,5-3,0
Tranemo
2,5
Sigtuna
1,5
Trans
2,5
3,0
Simrishamn
1,5
Trelleborg
1,0
2,5
Sjbo
1,5
Trollhttan
2,0
Mark
2,0
Skara
2,0-2,5
Trosa
2,0-2,5
Markaryd
2,5-3,0
Skellefte
3,0-3,5
Tyres
2,0
Mellerud
2,0
Skinnskatteberg
2,5-3,0
Tby
2,0
Mjlby
2,0
Skurup
1,0
Treboda
2,0-2,5
2,5-3,5
Skvde
2,5
Uddevalla
1,5
Motala
2,0-2,5
Smedjebacken
3,0
Ulricehamn
2,5-3,0
Mullsj
2,5
Sollefte
2,5-3,0
Ume
3,0
Sollentuna
2,0
Upplands-Bro
1,5
Upplands-Vsby
2,0
Uppsala
2,0
Mora
Munkedal
1,5-2,0
Munkfors
2,5
Solna
2,0
Mlndal
1,5
Sorsele
3,0-3,5
Mnsters
2,5
Sotens
1,5
Uppvidinge
2,0
Mrbylnga
2,0
Staffanstorp
1,0
Vadstena
2,0
Nacka
2,0
Stenungsund
1,5
Vaggeryd
2,0-2,5
Nora
2,5-3,0
Stockholm
2,0
Valdemarsvik
2,5
Norberg
2,5
Storfors
2,5
Vallentuna
2,0
Vansbro
2,5
Vara
2,0
Nordanstig
3,0-3,5
Storuman
3,0-4,5
Nordmaling
3,0-3,5
Strngns
2,0
Norrkping
2,0-2,5
Strmstad
1,5-2,0
Varberg
1,5-2,0
Norrtlje
2,0
Strmsund
2,5-5,5
Vaxholm
2,0
Norsj
3,0
Sundbyberg
2,0
Vellinge
1,0
Vetlanda
2,0-2,5
Vilhelmina
3,0-5,5
Nybro
2,0-2,5
Nykvarn
2,0
Nykping
2,0-2,5
Nynshamn
2,0-2,5
Nssj
2,5
Ockelbo
2,5-3,0
Olofstrm
2,0
Orsa
2,5-3,0
Orust
1,5
Osby
1,5-2,0
Oskarshamn
2,5
Ovanker
2,5-3,0
Oxelsund
2,5
Pajala
3,0-3,5
Partille
1,5
Perstorp
1,5
Pite
3,0-3,5
Ragunda
2,5
Sundsvall
2,5-3,5
Sunne
2,5
Surahammar
2,0-2,5
Vimmerby
2,5
Svalv
1,5
Vindeln
3,0
Svedala
1,0
Vingker
2,0-2,5
Svenljunga
2,0-2,5
Vrgrda
2,0
Sffle
2,5
Vnersborg
2,0
Vnns
3,0
Vrmd
2,0
Vrnamo
2,0
Vstervik
2,5-3,0
Ster
2,5-3,0
Svsj
2,0-2,5
Sderhamn
3,0
b
Sderkping
2,0-2,5
Sdertlje
2,0
Vsteras
2,0
Slvesborg
1,5
Vxj
2,0
Tanum
1,5
Ydre
2,5
Tibro
2,0
Ystad
1,5
ml
2,5
nge
2,5-3,0
re
3,5-5,5
Tidaholm
2,0-2,5
Tierp
2,5
Timr
3,0-3,5
35
Municipality
Municipality
sk
Municipality
sk
lvsbyn
3,0
stersund
2,5-3,5
rjng
2,5-3,0
sele
3,0
ngelholm
1,5
sterker
2,0
storp
1,5
cker
1,5
sthammar
2,0-2,5
tvidaberg
2,0-2,5
deshg
2,0
stra Ginge
1,5
lmhult
2,0
rebro
2,5
verkalix
3,0-3,5
lvdalen
3,0-3,5
rkelljunga
1,5-2,0
vertorne
3,0-4,5
3,0-3,5
lvkarleby
a
36
sk
2,5
rnskldsvik
The highest value in the range is used above and near to the tree line. The next highest
value is used in the upland forested areas in the western parts of the municipality. The
lowest value is used on low-lying ground in the eastern parts of the municipality. Other
values, if any, are used on low-lying ground in the western parts of the municipality and in
the remaining parts of the municipality. Refer also to the map of snow zones. In cases of
doubt, SMHI [the Swedish Metrological and Hydrological Institute] should be consulted. For
stages in the range, see the table in Figure C-3. The quantity of snow should increase by
about 15 % for every 100 m increase in altitude in the relevant terrain.
The upper value in the range applies to higher-lying ground. Refer also to the map of snow
zones. In cases of doubt the highest value is chosen. For stages in the range, see the table
in Figure C-3. The quantity of snow should increase by about 15 % for every 100 m increase
in altitude in the relevant terrain.
Recommendation used
1.5(2)
Recommendation used
4.1(1)
Recommendation used
4.2(1)P Note 2
4.2(2)P Note 2
Recommendation used
Recommendation used
Recommendation used
4.3.1(1) Note 1
4.3.1(1) Note 2
Recommendation used
4.3.2(1)
Recommendation used
4.3.2(2)
Recommendation used
4.3.3(1)
Recommendation used
4.3.4(1)
4.3.5(1)
4.4(1) Note 2
Recommendation used
4.5(1) Note 2
Recommendation used
5.3.5
Recommendation used
6.1(1)
6.3.1(1) Note 3
6.3.2(1)
7.1.2(2)
Recommendation used
7.1.3(1)
Recommendation used
7.2.1(1) Note 2
7.2.2(1) Note
7.2.2(2) Note 1
Recommendation used
7.2.8(1)
7.2.9(2)
Recommendation used
7.2.10(3) Note 1
Recommendation used
7.2.10(3) Note 2
Recommendation used
7.4.1(1)
Recommendation used
7.4.3(2)
Recommendation used
7.6.(1) Note 1
Recommendation used
7.7(1) Note 1
Recommendation used
7.8(1)
Recommendation used
7.10(1) Note 1
Recommendation used
7.11(1) Note 1
Recommendation used
7.13(1)
Recommendation used
7.13(2)
Recommendation used
8.1(1) Note 1
Recommendation used
8.1(1) Note 2
Recommendation used
8.1(4)
Recommendation used
37
National choices
8.1(5)
Recommendation used
8.2(1) Note 1
Recommendation used
8.3.(1)
Recommendation used
8.3.1(2)
Recommendation used
8.3.2(1)
Recommendation used
8.3.3(1) Note 1
Recommendation used
8.3.4(1)
Recommendation used
8.4.2(1) Note 1
A.2(1)
Recommendation used
4.2(1)P Note 2
Article 2 Map of reference wind speed is given in Figure C-4.
(BFS 2013:10).
General recommendation
Reference wind speeds for different municipalities are given in Table C-10 .
(BFS 2013:10).
38
Figure C-4
The reference wind speed vb in m/s, i.e. mean wind speed over 10
minutes at a height of 10 metres above the ground with a
roughness length z0 = 0,05 and with a return period of 50 years.
39
Allmnt rd
Table C-10
40
Municipality
vb
Municipality
vb
Ale
25
Filipstad
23
Alingss
25
Finspng
24
Alvesta
24
Flen
24
Aneby
24
Forshaga
23
Arboga
23
Frgelanda
25
Arjeplog
22-26a
Gagnef
22
Arvidsjaur
21-22a
Gislaved
24
Arvika
23
Gnesta
24
Askersund
24
Gnosj
24
Avesta
23
Gotland
24
Bengtsfors
24
Grums
23
Berg
24
Grstorp
24
Bjurholm
22
Gullspng
24
Bjuv
26
Gllivare
Boden
21-22a
Gvle
21-26a
23
Bollebygd
25
Gothenburg
25
Bollns
23
Gtene
24
Borgholm
24
Habo
24
Borlnge
22
Hagfors
22
Bors
25
Hallsberg
23
Botkyrka
24
Hallstahammar
23
Boxholm
24
Halmstad
25
Bromlla
25
Hammar
23
Brcke
23
Haninge
24
Burlv
26
Haparanda
22
Bstad
25
Heby
23
Dals-Ed
24
Hedemora
23
Danderyd
24
Helsingborg
26
Degerfors
23
Herrljunga
25
Dorotea
24
Hjo
24
Eda
23
Hofors
23
Eker
24
Huddinge
24
Eksj
24
Hudiksvall
23
Emmaboda
24
Hultsfred
24
Enkping
23
Hylte
25
Eskilstuna
23
Hbo
23
Eslv
26
Hllefors
23
Essunga
25
Hrjedalen
Fagersta
23
Hrnsand
23-25a
22
Falkenberg
25
Hrryda
25
Falkping
24
Hssleholm
25
Falun
23
Hgans
26
Municipality
vb
Municipality
vb
Hgsby
24
Ludvika
22
Hrby
25
Lule
Hr
25
Lund
21-22a
26
Jokkmokk
22-26a
Lycksele
23
Jrflla
24
Lysekil
25
Jnkping
24
Malm
26
Kalix
22
Malung
22
Kalmar
24
Mal
22
Karlsborg
24
Mariestad
24
Karlshamn
24
Mark
25
Karlskoga
23
Markaryd
25
Karlskrona
24
Mellerud
24
Karlstad
23
Mjlby
24
Katrineholm
24
Mora
22
Kil
23
Motala
24
Kinda
24
Mullsj
24
Kiruna
21-26a
Munkedal
25
Klippan
25
Munkfors
23
Knivsta
24
Mlndal
25
Kramfors
22
Mnsters
24
Kristianstad
25
Mrbylnga
24
Kristinehamn
23
Nacka
24
Krokom
25
Nora
23
Kumla
23
Norberg
23
Kungsbacka
25
Nordanstig
23
Kungsr
23
Nordmaling
22
Kunglv
25
Norrkping
24
Kvlinge
26
Norrtlje
24
Kping
23
Norsj
22
Laholm
25
Nybro
24
Landskrona
26
Nykvarn
24
Lax
24
Nykping
24
Lekeberg
23
Nynshamn
24
Leksand
22
Nssj
24
Lerum
25
Ockelbo
23
Lessebo
24
Olofstrm
24
Liding
24
Orsa
22
Lidkping
24
Orust
25
Lilla Edet
25
Osby
25
Lindesberg
22
Oskarshamn
24
Linkping
24
Ovanker
23
Ljungby
25
Oxelsund
24
Ljusdal
23
Pajala
Ljusnarsberg
22
Partille
21-22a
25
Lomma
26
Perstorp
25
41
vb
Municipality
vb
Pite
21
Tibro
24
Ragunda
23
Tidaholm
24
Robertsfors
22
Tierp
24
Ronneby
24
Timr
22
Rttvik
23
Tingsryd
24
Sala
23
Tjrn
26
Salem
24
Tomelilla
26
Sandviken
23
Torsby
22
Sigtuna
24
Torss
24
Simrishamn
26
Tranemo
24
Sjbo
26
Trans
24
Skara
24
Trelleborg
26
Skellefte
22
Trollhttan
25
Skinnskatteberg
23
Trosa
24
Skurup
26
Tyres
24
Skvde
24
Tby
24
Smedjebacken
22
Treboda
24
Sollefte
23
Uddevalla
25
Sollentuna
24
Ulricehamn
25
Solna
24
Ume
22
Sorsele
22-25a
Upplands-Bro
24
Sotens
25
Upplands-Vsby
24
Staffanstorp
26
Uppsala
24
Stenungsund
25
Uppvidinge
24
Stockholm
24
Vadstena
24
Storfors
23
Vaggeryd
24
Storuman
Valdemarsvik
24
Strngns
23-25a
23
Vallentuna
24
Strmstad
24
Vansbro
22
Strmsund
23-26a
Vara
24
Sundbyberg
24
Varberg
25
Sundsvall
23
Vaxholm
24
Sunne
22
Vellinge
26
Surahammar
23
Vetlanda
24
Svalv
26
Vilhelmina
23-24a
Svedala
26
Vimmerby
24
Svenljunga
25
Vindeln
Sffle
24
Vingker
22-23a
24
Ster
22
Vrgrda
25
Svsj
24
Vnersborg
25
Sderhamn
23
Vnns
22
Sderkping
24
Vrmd
24
Sdertlje
24
Vrnamo
24
Slvesborg
25
Vstervik
24
Tanum
25
Vsteras
23
Municipality
42
Municipality
vb
Municipality
Vxj
24
lvsbyn
21
Ydre
24
ngelholm
25
Ystad
26
cker
26
ml
24
deshg
24
nge
23
rebro
23
re
24-26a
rkelljunga
25
rjng
23
rnskldsvik
22
sele
22-23a
stersund
23
storp
25
sterker
24
tvidaberg
24
sthammar
24
lmhult
25
stra Ginge
25
lvdalen
22-26a
verkalix
lvkarleby
23
vertorne
21-22a
22
vb
4.2(2)P Note 1
Article 3 The effect of altitude is taken into account in the reference wind
speeds in Article 2.
4.3.1(1) Note 1
General recommendation
Article 4 The effect of topography has not been taken into account.
4.3.4(1)
Article 5 The method in A.4 must not be applied.
General recommendation
The effect of large and considerably higher neighbouring buildings should
be based on wind tunnel tests.
4.3.5(1)
Article 6 The method in A.5 must not be applied.
General recommendation
Determination of the effect of closely spaced buildings and obstacles should
be based on wind tunnel tests.
4.5(1) Note 1
General recommendation
Article 7 Expression 4.8 and Figure 4.2 are replaced by the following
expression and Figure C-5 upon application. Velocity pressures calculated
according to the expression are presented in Table C-9a. These velocity
pressures should be applied. (BFS 2013:10).
2
z
qp ( z ) =
ce ( z ) qb
1 + 6 Iv ( z ) k r ln z qb =
where
Iv ( z ) the turbulence intensity at height z
k r terrain factor
z0 roughness length
43
c (z)
c = 1,0
k = 1,0
Exposure factor e
for o
and I
Figur C-5
Tabell C-10a
vb
(m/s)
21
44
z (m)
II
III
IV
0,55
0,48
0,36
0,32
0,29
0,64
0,57
0,45
0,32
0,29
0,74
0,67
0,56
0,39
0,29
12
0,80
0,74
0,63
0,46
0,32
16
0,84
0,78
0,68
0,51
0,37
20
0,87
0,82
0,71
0,55
0,41
25
0,91
0,86
0,76
0,59
0,45
30
0,94
0,89
0,79
0,62
0,48
35
0,97
0,92
0,82
0,65
0,51
40
0,99
0,94
0,84
0,68
0,54
45
1,01
0,96
0,87
0,71
0,56
45
1,01
0,96
0,87
0,71
0,56
50
1,03
0,98
0,89
0,73
0,59
55
1,04
1,00
0,91
0,75
0,61
60
1,06
1,02
0,92
0,77
0,63
65
1,07
1,03
0,94
0,78
0,64
70
1,08
1,04
0,95
0,80
0,66
75
1,10
1,06
0,97
0,81
0,67
80
1,11
1,07
0,98
0,83
0,69
85
1,12
1,08
0,99
0,84
0,70
90
1,13
1,09
1,01
0,85
0,72
95
1,14
1,10
1,02
0,87
0,73
100
1,15
1,11
1,03
0,88
0,74
vb
(m/s)
22
23
z (m)
Terrngtyp
0
II
III
IV
0,60
0,52
0,39
0,35
0,32
0,70
0,63
0,50
0,35
0,32
0,81
0,74
0,61
0,43
0,32
12
0,87
0,81
0,69
0,50
0,35
16
0,92
0,86
0,74
0,56
0,40
20
0,96
0,90
0,78
0,60
0,45
25
1,00
0,94
0,83
0,65
0,49
30
1,03
0,98
0,87
0,69
0,53
35
1,06
1,01
0,90
0,72
0,56
40
1,08
1,03
0,93
0,75
0,59
45
1,11
1,06
0,95
0,77
0,62
50
1,13
1,08
0,97
0,80
0,64
55
1,14
1,10
0,99
0,82
0,67
60
1,16
1,11
1,01
0,84
0,69
65
1,18
1,13
1,03
0,86
0,71
70
1,19
1,15
1,05
0,88
0,72
75
1,20
1,16
1,06
0,89
0,74
80
1,22
1,17
1,08
0,91
0,76
85
1,23
1,19
1,09
0,92
0,77
90
1,24
1,20
1,10
0,94
0,78
95
1,25
1,21
1,12
0,95
0,80
100
1,26
1,22
1,13
0,96
0,81
0,65
0,57
0,43
0,38
0,35
0,76
0,68
0,54
0,38
0,35
0,88
0,81
0,67
0,47
0,35
12
0,95
0,88
0,75
0,55
0,38
16
1,01
0,94
0,81
0,61
0,44
20
1,05
0,98
0,86
0,66
0,49
25
1,09
1,03
0,91
0,71
0,54
30
1,13
1,07
0,95
0,75
0,58
35
1,16
1,10
0,98
0,79
0,62
40
1,18
1,13
1,01
0,82
0,65
45
1,21
1,16
1,04
0,85
0,68
50
1,23
1,18
1,06
0,87
0,70
55
1,25
1,20
1,09
0,90
0,73
60
1,27
1,22
1,11
0,92
0,75
65
1,28
1,24
1,13
0,94
0,77
70
1,30
1,25
1,15
0,96
0,79
75
1,31
1,27
1,16
0,98
0,81
80
1,33
1,28
1,18
0,99
0,83
85
1,34
1,30
1,19
1,01
0,84
90
1,35
1,31
1,21
1,02
0,86
95
1,37
1,32
1,22
1,04
0,87
100
1,38
1,33
1,23
1,05
0,89
45
vb
(m/s)
24
25
46
z (m)
Terrngtyp
0
II
III
IV
0,71
0,62
0,46
0,41
0,38
0,83
0,75
0,59
0,41
0,38
0,96
0,88
0,73
0,51
0,38
12
1,04
0,96
0,82
0,60
0,42
16
1,10
1,02
0,88
0,66
0,48
20
1,14
1,07
0,93
0,72
0,53
25
1,19
1,12
0,99
0,77
0,59
30
1,23
1,16
1,03
0,82
0,63
35
1,26
1,20
1,07
0,86
0,67
40
1,29
1,23
1,10
0,89
0,71
45
1,32
1,26
1,13
0,92
0,74
50
1,34
1,28
1,16
0,95
0,77
55
1,36
1,31
1,18
0,98
0,79
60
1,38
1,33
1,21
1,00
0,82
65
1,40
1,35
1,23
1,02
0,84
70
1,42
1,36
1,25
1,04
0,86
75
1,43
1,38
1,27
1,06
0,88
80
1,45
1,40
1,28
1,08
0,90
85
1,46
1,41
1,30
1,10
0,92
90
1,47
1,43
1,31
1,11
0,93
95
1,49
1,44
1,33
1,13
0,95
100
1,50
1,45
1,34
1,15
0,97
0,77
0,67
0,50
0,45
0,41
0,90
0,81
0,64
0,45
0,41
1,04
0,95
0,79
0,55
0,41
12
1,13
1,04
0,89
0,65
0,45
16
1,19
1,11
0,96
0,72
0,52
20
1,24
1,16
1,01
0,78
0,58
25
1,29
1,22
1,07
0,84
0,64
30
1,33
1,26
1,12
0,89
0,69
35
1,37
1,30
1,16
0,93
0,73
40
1,40
1,33
1,20
0,97
0,77
45
1,43
1,36
1,23
1,00
0,80
50
1,45
1,39
1,26
1,03
0,83
55
1,48
1,42
1,28
1,06
0,86
60
1,50
1,44
1,31
1,08
0,89
65
1,52
1,46
1,33
1,11
0,91
70
1,54
1,48
1,35
1,13
0,93
75
1,55
1,50
1,37
1,15
0,96
80
1,57
1,52
1,39
1,17
0,98
85
1,58
1,53
1,41
1,19
1,00
90
1,60
1,55
1,43
1,21
1,01
95
1,61
1,56
1,44
1,23
1,03
100
1,63
1,58
1,46
1,24
1,05
z (m)
vb
(m/s)
26
Terrngtyp
0
II
III
IV
0,84
0,73
0,55
0,49
0,44
0,98
0,87
0,69
0,49
0,44
1,13
1,03
0,86
0,60
0,44
12
1,22
1,13
0,96
0,70
0,49
16
1,29
1,20
1,04
0,78
0,56
20
1,34
1,26
1,10
0,84
0,63
25
1,40
1,32
1,16
0,90
0,69
30
1,44
1,37
1,21
0,96
0,74
35
1,48
1,41
1,25
1,00
0,79
40
1,51
1,44
1,29
1,04
0,83
45
1,54
1,48
1,33
1,08
0,87
50
1,57
1,51
1,36
1,11
0,90
55
1,60
1,53
1,39
1,15
0,93
60
1,62
1,56
1,42
1,17
0,96
65
1,64
1,58
1,44
1,20
0,99
70
1,66
1,60
1,46
1,22
1,01
75
1,68
1,62
1,48
1,25
1,03
80
1,70
1,64
1,51
1,27
1,06
85
1,71
1,66
1,52
1,29
1,08
90
1,73
1,67
1,54
1,31
1,10
95
1,74
1,69
1,56
1,33
1,11
100
1,76
1,71
1,58
1,34
1,13
(BFS 2013:10).
6.1(1)
General recommendation
Article 8 cscd should not be separated.
6.3.1(1) Note 3
General recommendation
Article 9 kp, B and R can be calculated using the following equations
0, 6
kp =
2 ln ( vT ) +
; kp =
3, 0 fr statiska konstruktioner
2 ln ( vT )
v = n1, x
R
B2 + R2
h
B 2= exp 0, 05
h ref
R2 =
F=
b
h
+ 1 0, 04 + 0, 01
h
h ref
2 F b h
s + a
4 yC
(1 + 70,8 y )
2
C
5
6
47
yC =
150 n1,x
vm ( h )
h =
1+
b =
1+
1
2 n1,x h
vm ( h )
1
3, 2 n1,x b
vm ( h )
6.3.2(1)
General recommendation
Article 10 The method may be applied to calculate sways in the first
mode of a cantilevered structure with constant mass along the structures
main axis. The maximum acceleration is given by the expression
X
max ( z ) = kp
x( z )
3 I v (h) R qm ( h ) b cf f1,x ( z )
m
1,5
1,x ( z ) =
h
1
=
n Ta 0, 75 n 50 1 0, 2 ln ln 1
T
a
Ta = 0,855 50
where v50 is the characteristic value of the reference wind speed that is
exceeded over one year with a probability of 2 %, which corresponds to an
average return period of 50 years.
7.2.1(1) Note 2
General recommendation
Article 11 The recommended method may be used. As an alternative to
this, cpe,10 can be used for areas over 1 m2.
7.2.2(1) Note
General recommendation
Article 12 For sidewalls and leeward walls, the pressure can be
determined on the basis of the actual velocity pressure distribution in
48
accordance with 4.5 and with the height of the building as the reference
height.
7.2.8(1)
General recommendation
Article 13 Figure 7.11 should not be applied.
Pressure coefficients in Figure C-6 should apply.
Figure C-6
49
50
8.4.2(1) Note 1
General recommendation
Article 14 No simplified calculation methods are given.
51
Comments
6.1.1(1)
6.1.2(2)
6.1.3.1(4)
6.1.3.2(1)P
6.1.3.3(3)
Recommendation used
6.1.4(3)
Recommendation used
6.1.4.1(1)
6.1.4.2(1)
6.1.4.3(1)
Recommendation used
6.1.4.4(1)
Recommendation used
6.1.5(1)
Recommendation used
6.1.6(1)
Recommendation used
6.2.1(1)P
Recommendation used
6.2.2(1)
Recommendation used
6.2.2(2)
Recommendation used
7.2.1(1)
7.5(3)
Recommendation used
7.5(4)
Recommendation used
A.1(1)
A.1(3)
Recommendation used
A.2(2)
6.1.1(1)
General recommendation
Article 3 Wooden bridge decks on steel box or I girders should belong to
Type 2. Aluminium bridge decks should belong to Type 1. The class
division of bridge superstructures should be expanded to include: "Type 4:
Wooden bridge decks on wooden girders.
6.1.2(2)
Article 4 Both methods may be used.
52
6.1.3.1(4)
General recommendation
Article 5 For bridge superstructures of types 1-3, the recommended
values should be used. For type 4 bridge superstructures, the values for type
3 should be used.
6.1.3.2(1)P
Article 6 The isotherm maps of maximum and minimum air temperature in
Figures C-7 and C-8 in this chapter shall be used. These maps apply to local
height above sea level.
General recommendation
The maximum and minimum air temperatures for different municipalities as
listed in Table C-11 in this chapter may be used.
6.1.4.1(1)
General recommendation
Article 7 The recommended values in Tables 6.1 and 6.2 should be used.
For type 4 bridge superstructures both TM,heat and TM,cool can be set to
5 C and ksur set to 1,0.
53
Figure C-7
54
Figure C-8
55
Table C-11
56
Municipality
Max.
temp
Min.
temp
Municipality
Max.
temp
Min.
temp
Ale
36
-36
Filipstad
35
-39
Alingss
35
-36
Finspng
35
-35
Alvesta
36
-32
Flen
35
-32
Aneby
35
-34
Forshaga
34
-38
Arboga
35
-34
Frgelanda
33
-34
Arjeplog
31
-46
Gagnef
35
-41
Arvidsjaur
33
-44
Gislaved
35
-33
Arvika
35
-40
Gnesta
35
-30
Askersund
35
-34
Gnosj
35
-34
Avesta
36
-39
Gotland
34
-27
Bengtsfors
34
-39
Grums
34
-39
Berg
31
-47
Grstorp
34
-34
Bjurholm
31
-42
Gullspng
34
-36
Bjuv
35
-27
Gllivare
31
-41
Boden
32
-42
Gvle
35
-34
Bollebygd
35
-35
Gothenburg
35
-29
Bollns
34
-38
Gtene
34
-36
Borgholm
34
-26
Habo
34
-35
Borlnge
35
-41
Hagfors
35
-40
Bors
35
-35
Hallsberg
35
-33
Botkyrka
35
-30
Hallstahammar
35
-35
Boxholm
36
-36
Halmstad
35
-32
Bromlla
34
-25
Hammar
34
-37
Brcke
33
-44
Haninge
34
-30
Burlv
34
-22
Haparanda
33
-41
Bstad
34
-26
Heby
35
-36
Dals-Ed
33
-37
Hedemora
35
-40
Danderyd
36
-31
Helsingborg
34
-24
Degerfors
35
-37
Herrljunga
34
-36
Dorotea
31
-46
Hjo
34
-33
Eda
35
-40
Hofors
35
-38
Eker
35
-31
Huddinge
35
-29
Eksj
37
-30
Hudiksvall
34
-38
Emmaboda
36
-29
Hultsfred
38
-34
Enkping
35
-34
Hylte
35
-33
Eskilstuna
35
-33
Hbo
35
-33
Eslv
35
-26
Hllefors
35
-38
Essunga
35
-36
Hrjedalen
32
-46
Fagersta
35
-38
Hrnsand
33
-38
Falkenberg
34
-31
Hrryda
35
-32
Falkping
34
-34
Hssleholm
36
-30
Falun
35
-41
Hgans
33
-22
Municipality
Max.
temp
Min.
temp
Municipality
Max.
temp
Min.
temp
Hgsby
37
-33
Lule
32
-41
Hrby
35
-26
Lund
34
-23
Hr
36
-28
Lycksele
33
-43
Jokkmokk
31
-43
Lysekil
32
-30
Jrflla
35
-32
Malm
33
-22
Jnkping
35
-36
Malung
34
-44
Kalix
32
-41
Mal
32
-46
Kalmar
36
-28
Mariestad
34
-36
Karlsborg
33
-34
Mark
34
-32
Karlshamn
34
-27
Markaryd
36
-33
Karlskoga
35
-36
Mellerud
33
-35
Karlskrona
34
-25
Mjlby
35
-34
Karlstad
34
-37
Mora
34
-44
Katrineholm
35
-34
Motala
35
-34
Kil
34
-39
Mullsj
34
-34
Kinda
37
-35
Munkedal
33
-33
Kiruna
30
-45
Munkfors
35
-39
Klippan
36
-30
Mlndal
34
-29
Knivsta
35
-35
Mnsters
36
-31
Kramfors
33
-38
Mrbylnga
34
-24
Kristianstad
35
-26
Nacka
35
-29
Kristinehamn
34
-36
Nora
35
-36
Krokom
31
-42
Norberg
35
-39
Kumla
35
-34
Nordanstig
34
-38
Kungsbacka
34
-28
Nordmaling
30
-39
Kungsr
35
-34
Norrkping
36
-33
Kunglv
35
-32
Norrtlje
33
-36
Kvlinge
34
-24
Norsj
33
-44
Kping
35
-35
Nybro
36
-30
Laholm
36
-32
Nykvarn
35
-30
Landskrona
34
-24
Nykping
35
-31
Lax
35
-35
Nynshamn
33
-29
Lekeberg
35
-35
Nssj
35
-32
Leksand
34
-42
Ockelbo
33
-37
Lerum
35
-34
Olofstrm
35
-28
Lessebo
36
-31
Orsa
34
-44
Liding
36
-28
Orust
33
-30
Lidkping
34
-35
Osby
36
-31
Lilla Edet
35
-35
Oskarshamn
36
-34
Lindesberg
36
-36
Ovanker
35
-40
Linkping
36
-33
Oxelsund
35
-29
Ljungby
36
-34
Pajala
32
-44
Ljusdal
34
-44
Partille
34
-31
Ljusnarsberg
35
-39
Perstorp
36
-30
Lomma
34
-23
Pite
33
-41
Ludvika
35
-40
Ragunda
33
-43
57
58
Municipality
Max.
temp
Min.
temp
Municipality
Max.
temp
Min.
temp
Robertsfors
30
-39
Timr
34
-40
Ronneby
35
-27
Tingsryd
36
-30
Rttvik
34
-42
Tjrn
33
-31
Sala
35
-37
Tomelilla
34
-23
Salem
35
-30
Torsby
35
-41
Sandviken
35
-37
Torss
34
-25
Sigtuna
35
-34
Tranemo
35
-32
Simrishamn
34
-22
Trans
35
-36
Sjbo
34
-23
Trelleborg
33
-21
Skara
34
-34
Trollhttan
35
-35
Skellefte
32
-41
Trosa
33
-28
Skinnskatteberg
35
-37
Tyres
35
-29
Skurup
33
-22
Tby
36
-33
Skvde
34
-31
Treboda
34
-34
Smedjebacken
35
-39
Uddevalla
34
-32
Sollefte
33
-44
Ulricehamn
34
-30
Sollentuna
36
-32
Ume
29
-38
Solna
36
-30
Upplands-Bro
35
-33
Sorsele
31
-45
Upplands-Vsby
35
-33
Sotens
32
-29
Uppsala
35
-35
Staffanstorp
34
-23
Uppvidinge
37
-32
Stenungsund
35
-34
Vadstena
34
-34
Stockholm
36
-29
Vaggeryd
36
-36
Storfors
35
-37
Valdemarsvik
35
-31
Storuman
31
-44
Vallentuna
35
-37
Strngns
35
-32
Vansbro
34
-41
Strmstad
33
-35
Vara
35
-36
Strmsund
31
-44
Varberg
34
-29
Sundbyberg
36
-31
Vaxholm
35
-31
Sundsvall
34
-42
Vellinge
32
-21
Sunne
35
-39
Vetlanda
37
-32
Surahammar
35
-36
Vilhelmina
31
-45
Svalv
35
-27
Vimmerby
37
-34
Svedala
33
-22
Vindeln
32
-42
Svenljunga
34
-33
Vingker
34
-33
Sffle
34
-40
Vrgrda
35
-36
Ster
35
-40
Vnersborg
34
-33
Svsj
36
-34
Vnns
30
-40
Sderhamn
35
-35
Vrmd
34
-30
Sderkping
36
-32
Vrnamo
36
-35
Sdertlje
34
-29
Vstervik
37
-33
Slvesborg
34
-23
Vsteras
35
-34
Tanum
33
-33
Vxj
36
-32
Tibro
34
-32
Ydre
36
-33
Tidaholm
34
-33
Ystad
34
-22
Tierp
34
-34
ml
34
-39
Municipality
Max.
temp
Min.
temp
Municipality
Max.
temp
Min.
temp
nge
34
-45
cker
32
-26
re
30
-45
deshg
34
-35
rjng
34
-41
rebro
36
-33
sele
32
-45
rkelljunga
36
-31
storp
35
-27
rnskldsvik
33
-42
tvidaberg
36
-33
stersund
31
-41
lmhult
36
-32
sterker
35
-35
lvdalen
33
-46
sthammar
33
-34
lvkarleby
35
-33
stra Ginge
35
-29
lvsbyn
33
-43
verkalix
32
-43
ngelholm
35
-28
vertorne
32
-43
6.1.4.2(1)
Article 8
2, and 3.
7.2.1(1)P
Article 9 The isotherm maps of maximum and minimum air temperature in
Figures C-7 and C-8 in this chapter shall be used. These maps apply to local
height above sea level.
General recommendation
The maximum and minimum air temperatures for different municipalities as
listed in Table C-11 in this chapter may be used.
A.1(1)
Article 10 The isotherm maps of maximum and minimum air temperature in
Figures C-7 and C-8 in this chapter shall be used. These maps apply to local
height above sea level.
General recommendation
The maximum and minimum air temperatures for different municipalities as
listed in Table C-11 in this chapter may be used.
A.2(2)
Article 11 When applying Section A.2, the coefficients shall be set to k1 = 0,80;
k2 = 0,0513; k3 = 0,60 and k4 = -0,103.
B(1)
Article 12 The recommended values apply.
General recommendation
For type 4 bridge superstructures, see Article 8.
59
60
National choices
Comments
1.1(3)
2.2(4)
3.1(1)P
Recommendation used
3.1(5) Note 1
Recommendation used
3.1(5) Note 2
Recommendation used
3.1(7)
3.1(8) Note 1
3.3(2)
3.3(6)
4.9(6) Note 2
4.10(1)P
Recommendation used
4.11.2(1)
Recommendation used
4.12(1)P Note 2
Recommendation used
4.12(2)
4.12(3)
4.13(2)
A1.1(1)
Recommendation used
A1.3(2)
Recommendation used
A2.3(1)
Recommendation used
A2.4(2)
Recommendation used
A2.4(3)
Recommendation used
A2.5(2)
Recommendation used
A2.5(3)
Comments
2(2)
3.1(2) Note 4
3.2(1) Note 3
3.3(2) Note 1
Recommendation used
3.3(2) Note 2
3.3(2) Note 3
3.4(1) Note 4
3.4(2)
4.1(1) Note 1
4.1(1) Note 3
4.3.1(1) Note 1
4.3.1(1) Note 2
Recommendation used
4.3.1(1) Note 3
4.3.1(2)
Recommendation used
4.3.1(3)
Recommendation used
4.3.2(1) Note 1
4.3.2(1) Note 3
4.3.2(1) Note 4
Recommendation used
4.3.2(2)
Recommendation used
4.3.2(3) Note 1
4.4.(1)
Recommendation used
4.5(1)
4.5.1.2(1) Note 1
Recommendation used
4.5.1.2(1) Note 2
4.5.1.4(1)
Recommendation used
4.5.1.4(2)
4.5.1.4(3)
4.5.1.4(4)
4.5.1.4(5)
Recommendation used
4.5.1.5(1)
4.5.2(1)
4.5.2(4)
4.6.1(3) Note 1
4.6.2(1)
4.6.2(2)
Recommendation used
4.6.2(3) Note 1
4.6.2.4
4.6.3(1)
4.6.3(3)
4.6.3(4)
4.6.3(5)
5.3(1)P
61
A.4(1) Note 1
Annex A
General recommendations
Additional rules regarding the combination factors can be found in Section
B, Chapter 0, Article 21. (BFS 2013:10).
3.2(1)
Article 2 The risk level must not be higher than that which corresponds to the
safety index = 3,1 for accidental actions and = 2,3 for progressive collapse for
the reference period of one year.
3.3(2) Note 2
General recommendation
Article 3 The proposed limit for localised failure should be applied to
buildings. For other structures, these parameters may be determined by a
risk assessment in accordance with Annex B.
3.3(2) Note 3
General recommendation
Article 4 The strategies recommended in Annex A should be applied to
buildings. For other structures, the client/owner may specify the choice of
alternatives.
3.4.(1)
Article 5 The standards recommendations shall be used.
General recommendation
For bridges, the consequence class CC2 shall be applied.
4.1(1) Note 1
General recommendation
Article 6 For lightweight structures that are designed so as to reduce the
risk of vehicle impact with, for example, a clear height above the road of
> 5,3 m and > 5,9 m above the upper edge of a railway line, the action of
vehicle impact may be set equal to zero.
4.3.1(1) Note 1
General recommendation
Article 7 For bridges and other structures over roads, the values for
Motorways, etc. in Table 4.1 should be applied. For other structures, other
than bridges, adjacent to roads, the values in Table 4.1 may be applied,
whereby the client/owner may specify an appropriate traffic category for the
individual project. As an alternative to the actions in Table 4.1, actions may
be calculated in accordance with Annex C.
4.3.2(1) Note 1
General recommendation
Article 8 Bridges with a clear height of not more than 5,2 m should be
designed for actions in accordance with Table 4.2. For other structures, the
client/owner may specify the values of forces and clear heights for the
individual project. If no values are specified, Table 4.2 and a height of
5,2 m should be applied.
h0 should be set to 5,2 m and h1 should be set to 6,0 m. b is then 0,8 m.
62
4.3.2(1) Note 3
General recommendation
Article 9 h0 should be set to 5,2 m and h1 should be set to 6,0 m. b is then
0,8 m.
4.3.2(3) Note 1
General recommendation
Article 10 The surface area should be set to 0,5 x 0,25 m, with the 0,5 m
dimension along the length of the bridge.
4.5(1)
Article 11 The rules in this section should be applied to structures adjacent to
all types of rail traffic, unless a different requirement is proved to be more
accurate.
4.6.1(3) and 4.6.2(1)
General recommendation
Article 12 Table C.4 (or C.3) in Annex C should be applied for the
classification of ships.
4.6.3(5)
General recommendation
Article 13 If no further information is provided, at least 5 % of the value
Fdx should be applied.
63
64
National choices
Comments
1.1(3)
2.3(1)
2.3(4)
3(5)
5.2.3(2)
Recommendation used
5.3.2.1(1)
Recommendation used
5.3.2.2(1)
Recommendation used
5.3.2.3(1)P Note 1
5.4(2)
Recommendation used
5.6.1(1)
5.6.2.1(1)
5.6.2.2(1)
5.6.3(2) Note 2
Recommendation used
5.7(3)
6.1(2)
6.1(3)P
6.1(7)
6.3.2(3)P
6.3.3(4)P
6.4.4(1)
6.4.5.2(3)P
6.4.5.3(1)
6.4.6.1.1(6)
6.4.6.1.1(7)
Recommendation used
6.4.6.1.2(3)
Recommendation used
6.4.6.3.2(3)
Recommendation used
6.4.6.3.3(3) Note 1
Recommendation used
6.4.6.3.3(3) Note 2
Recommendation used
6.4.6.4(4)
Recommendation used
6.4.6.4(5)
6.5.1 (2)
Recommendation used
6.5.3(5)
6.5.3(9)P
6.5.4.1 (5)
Recommendation used
6.5.4.3(2) Note 1
Recommendation used
6.5.4.3(2) Note 2
Recommendation used
6.5.4.4(2) Note 1
6.5.4.5
6.5.4.5.1(2)
6.5.4.6
6.5.4.6.1(1)
Recommendation used
6.5.4.6.1(4)
Recommendation used
National choices
Comments
6.6.1(3)
Recommendation used
6.7.1(2)P
6.7.1(8)P
6.7.3(1)P
Recommendation used
6.8.3.1(1)
Recommendation used
6.8.3.2(1)
Recommendation used
6.9(6)
6.9 (7)
C (3)P
D2(2)
Recommendation used
6.1(7)
General recommendation
Article 2 Temporary bridges that are intended to be used for longer than
three years should be designed as permanent bridges. Other temporary
bridges should be designed for 80 % of the load that applies to permanent
bridges, except for bridges subject to heavy bulk goods traffic, which
should be designed for 85 % of the load that applies to permanent bridges.
Rules for temporary bridges should also be applied in connection with
lifting when changing the bearings.
6.4.5.2(3)P
Article 6 The dynamic factor 2 may be applied for bridges for all types of
tracks.
65
6.4.5.3(1)
General recommendation
Article 7 The determinant lengths in Table 6.2 should be used. However,
2 may be used for cases 1.4, 2.3, 3.4, 4.5, and 4.6 in Table 6.2.
6.4.6.4(5)
Article 8 The factor (1 + /2) may be applied.
6.5.3(9)P
Article 9 Bridges with two or more tracks having the same permitted direction
of travel shall be assumed to be subject to the simultaneous load from braking
forces on two of the tracks, whereby the braking force on one of the tracks may be
limited to 1000 kN. This force shall be multiplied by in accordance with
6.3.2(3)P.
6.5.4.4(2) Note 1
General recommendation
Article 10 Unless otherwise specified for the individual project, the value
for the longitudinal shear resistance between tracks and bridge deck should
be set to 20 kN/m or 40 kN/m for unloaded tracks, and 50 kN/m or 60 kN/m
for loaded tracks. The higher values are used in connection with
unfavourable actions and the lower values are used in connection with
favourable actions.
6.5.4.5.1(2)
General recommendation
Article 11 Additional stresses in the following rails that are found in
Sweden should not exceed the values given in Table C-12.
Table C-12
Rail type
Pressure
Tension
BV 50/900
72 N/mm
SJ 50/800
65 N/mm
82 N/mm
65 N/mm
82 N/mm
SJ 43/800
92 N/mm
6.7.3(1)P
Article 12 Bridges with seamless tracks with no dilatation devices shall be
designed for actions that may arise as a result of temperature variations in the
rails.
General recommendation
This force should be assumed to be 1000 kN/track acting in the tracks
longitudinal direction.
6.9(6)
General recommendation
Article 14 Unless otherwise specified for the individual project, the
technical working life should be assumed to be 120 years.
66
C (3)P
Article 15 Expression (C.2) may be used to determine the dynamic factor.
67
Comments
2.1(2)
2.5.2.1(2)
2.5.3(2)
2.7.3(3)
A2.2(1)
Recommendation used
A2.2(2)
A2.3(1)
(BFS 2013:10).
2.5.2.1 (2)
General recommendations
Article 3 The eccentricity e may be set equal to zero. (BFS 2013:10).
2.5.3 (2)
General recommendations
Article 4 The maximum number of cranes working independently should be
considered in the design. These may be limited according to Table C-12.
The figure on the right refers to column/support between two shop bays.
(BFS 2013:10).
Table C-12
Cranes in
each runway
Cranes in
each shop
bay
Vertical crane
action
Horizontal
crane action
(BFS 2013:10).
68
A2.3 (1)
General recommendations
Article 5 In case of load combination of cranes working independently, the
loads shall be considered as independent of each other. - factors for crane
loads should be selected according to Table C-13. (BFS 2013:10).
Table C-13.
0
1
2
Horizontal load
0.8
0.5
0.7
0.5
The relationship
between the
permanent crane load
and the total crane
load
(BFS 2013:10).
69
Comments
2.5(5)
3.6(2)
5.2.4.3.1(3)
5.4.1(3)
Recommendation used
5.4.1(4)
Recommendation used
A.4(3)
B.2.14(1)
(BFS 2013:10).
Nationally selected parameters
A.4(3)
General recommendations
Article 2 Load combination factors for snow and wind loads should be
taken from Section B, Chapter 0, Article 26. Otherwise, the recommended
values should also be used. (BFS 2013:10).
70
Preconditions
General recommendation
Article 2 SS-EN 206-1 should always be used together with SS 13 70 03.
EN 13670 should be used instead of ENV 13670-1.
For the general effect of cyclic loading in fatigue calculations, EN 19922 may also be used for structures other than bridges. For fatigue in case of
eccentric pressure, the calculation method described in Annex 2 may be
applied.
Reinforcement
General recommendation
Article 34 In order to facilitate a ductile behaviour in the event of failure,
the reinforcement characteristic strain at maximum force shall not be less
than 3,0 % and the characteristic value for the quotient between the ultimate
strength and the yield strength shall be at least 1,08. These values refer to
the 0,1 fractile.
In constructions where the impact of yielding of support or restraint
forces is negligible, reinforcement with a minimum characteristic strain at
maximum force of 2,5 % may be used.
Inspection
General recommendation
Article 4 Basic inspection described in Section A can be deemed
equivalent to measures taken according to the lowest execution class 2 in
EN 13670. In the event of strength testing of existing concrete structures,
SS-EN 13791 should be used with the following complementary additions.
Evaluation in accordance with the standards Section 7.3.3 is replaced with
SS-ISO 12491, Section 7.4 with associated Table 6, p = 0,95 and = 0,50.
(BFS 2013:10).
71
72
National choices
Comments
2.3.3 (3)
2.4.2.1(1)
2.4.2.2(1)
2.4.2.2(2)
2.4.2.2(3)
2.4.2.3(1)
2.4.2.4(1)
2.4.2.4(2)
2.4.2.5(2)
3.1.2(2)P
3.1.2(4)
3.1.6(1)P
Recommendation used
3.1.6(2)P
Recommendation used
3.2.2(3)P
3.2.7(2)
Recommendation used
3.3.4(5)
Recommendation used
3.3.6(7)
Recommendation used
4.4.1.2(3)
Recommendation used
4.4.1.2(5)
4.4.1.2(6)
Recommendation used
4.4.1.2(7)
4.4.1.2(8)
4.4.1.2(13)
Recommendation used
4.4.1.3(1)P
Recommendation used
4.4.1.3(3)
Recommendation used
4.4.1.3(4)
5.1.3(1)P
Recommendation used
5.2(5)
Recommendation used
5.5(4)
Recommendation used
5.6.3(4)
Recommendation used
5.8.3.1(1)
Recommendation used
5.8.3.3(1)
Recommendation used
5.8.3.3(2)
Recommendation used
5.8.5(1)
5.8.6(3)
Recommendation used
5.10.1(6)
5.10.2.1(1)P
Recommendation used
5.10.2.1(2)
Recommendation used
5.10.2.2(4)
Recommendation used
5.10.2.2(5)
Recommendation used
5.10.3(2)
Recommendation used
5.10.8(2)
Recommendation used
5.10.8(3)
5.10.9(1)P
Recommendation used
6.2.2(1)
Recommendation used
6.2.2(6)
Recommendation used
National choices
Comments
6.2.3(2)
6.2.3(3)
Recommendation used
6.2.4(4)
Recommendation used
6.2.4(6)
Recommendation used
6.4.3(6)
Recommendation used
6.4.4(1)
Recommendation used
6.4.5(3)
6.4.5(4)
Recommendation used
6.5.2(2)
Recommendation used
6.5.4(4)
Recommendation used
6.5.4(6)
Recommendation used
6.8.4(1) Note 2
Recommendation used
6.8.4(5)
Recommendation used
6.8.6(1)
Recommendation used
6.8.6(3)
Recommendation used
6.8.7(1)
7.2(2)
Recommendation used
7.2(3)
Recommendation used
7.2(5)
7.3.1(5)
7.3.2(4)
7.3.4(3)
7.4.2(2)
Recommendation used
8.2(2)
Recommendation used
8.3(2)
8.6(2)
Recommendation used
8.8(1)
Recommendation used
9.2.1.1(1)
Recommendation used
9.2.1.1(3)
9.2.1.2(1)
Recommendation used
9.2.1.4(1)
Recommendation used
9.2.2(4)
9.2.2(5)
9.2.2(6)
Recommendation used
9.2.2(7)
9.2.2(8)
Recommendation used
9.3.1.1(3)
Recommendation used
9.5.2(1)
Recommendation used
9.5.2(2)
9.5.2(3)
9.5.3(3)
Recommendation used
9.6.2(1)
9.6.3(1)
Recommendation used
9.7(1)
Recommendation used
9.8.1(3)
Recommendation used
9.8.2.1(1)
Recommendation used
9.8.3(1)
Recommendation used
73
National choices
Comments
9.8.3(2)
Recommendation used
9.8.4(1)
9.8.5(3)
9.10.2.2(2)
9.10.2.3(3)
Recommendation used
9.10.2.3(4)
9.10.2.4(2)
Recommendation used
11.3.5(1)P
11.3.5(2)P
11.3.7(1)
Recommendation used
11.6.1(1)
Recommendation used
11.6.2(1)
Recommendation used
11.6.4.1(1)
Recommendation used
12.3.1(1)
12.6.3(2)
Recommendation used
A.2.1(1)
A.2.1(2)
A.2.2(1)
A.2.2(2)
A.2.3(1)
C.1 (1)
Recommendation used
C.1(3) Note 1
C.1(3) Note 2
J.1(2)
Recommendation used
J.2.2(2)
Recommendation used
J.3(2)
Recommendation used
J.3(3)
Annex E
2.3.3(3)
General recommendation
Article 6 The value of djoint should be determined for each individual case.
3.1.2(4)
General recommendation
Article 9 kt can be set to 1,0.
3.2.2(3)P
Article 9a Reinforcement with yield strength 500 < fyk 600 MPa can be used
if the relative rib area, fr 0,11. (BFS 2013:10).
74
4.4.1.2(5)
General recommendation
Article 10 When determining the necessary minimum concrete cover,
account should be taken of the intended service life. The service life classes
L100, L50, and L20 refer to structures with an expected service life of 100,
50, and 20 years respectively.
For reinforcing steel with a diameter of not less than 4 mm, that is not
prestressing steel and that is not cold-formed reinforcing steel with a
permanent stress above 400 MPa, the concrete cover, cmin,dur, pursuant to
Table D-1 should be used.
For reinforcing steel with a diameter less than 4 mm, for prestressing
steel and for cold-formed reinforcing steel with a permanent stress above
400 MPa, and for sheaths in case of post-stressed reinforcing steel, the
values for the cover given in Table D-1 should be increased by 10 mm.
For values of vctekv other than those given in Table D-1, the required
minimum concrete cover may, in individual cases, be calculated in
accordance with the guidelines in SS EN 206-1, Annex J.
Table D-1
Exposure class
Max vctekv
L 100
L 50
L 20
X0
XC1
0,90
15
10
10
0,60
10
10
10
0,60
25
20
15
0,55
20
15
10
0,50
15
10
10
0,55
25
20
15
0,50
20
15
10
0,45
30
25
15
0,40
25
20
15
0,45
40
30
25
0,40
35
30
20
0,35
30
25
20
0,40
45
35
25
0,35
40
30
25
0,45
50
40
30
0,40
45
35
25
0,35
40
30
25
0,40
45
35
25
0,35
40
30
25
XC2
XC3, XC4
XS1, XD1
XD2
XD3
XS2
XS3
1)
1)
75
4.4.1.3(4)
General recommendation
Article 12 The following values should be used
k1 = cmin + 15 mm,
k2 = cmin + 65 mm.
5.10.1(6)
General recommendation
Article 13 Method D, in combination with at least one of the other
methods, should be used.
5.10.8(3)
Article 14 The recommended values for P,sup and P,inf shall be used.
6.2.3(2)
General recommendation
Article 15 When determining the shear force capacity of non-prestressed
structures, the condition 1,0 cot 2,5 should be met. When determining
the shear force capacity of prestressed structures, the condition 1,0 cot
3,0 should be met.
6.4.5(3)
General recommendation
Article 16 vRd,max should be determined as follows
0, 5n fcd
u1
vRd,max
1, 6 vRd,c
u0
7.2(5)
General recommendation
Article 19 k3 should be set to 1,0. For k4 and k5 the recommended values
should be used.
7.3.1(5)
General recommendation
Article 20 Unless otherwise justified, the value of wmax calculated for a
quasi-permanent combination of actions should be restricted to the value in
Table D-2. If the tensile stress does not exceed fctk/ the concrete may be
76
regarded as uncracked. The values of the crack safety factor in Table D-3
should be applied.
For frequent combination of actions, no requirements are given regarding
crack width limitation.
Table D-2
Exposure
class
Corrosion sensitivity
L 100
Little corrosion
1
sensitivity
L 50
L 20
L 100
L 50
L 20
XC0
XC1
0,40
0,45
0,45
XC2
0,30
0,40
0,45
0,40
0,45
XC3, XC4
0,20
0,30
0,40
0,30
0,40
XS1, XS2
XD1, XD2
0,15
0,20
0,30
0,20
0,30
0,40
XS3, XD3
0,10
0,15
0,20
0,15
0,20
0,30
7.3.2(4)
General recommendation
Article 21 When determining the permitted tensile stress before the need
to insert minimum reinforcement to limit the crack width, account should be
taken of the intended service life. The value should be determined as
follows:
ct,p = fctk/
where the values of the crack safety factor in Table D-3 are used.
Table D-3
L 50
L 20
XC0, XC1
0,9
0,9
0,9
XC2
1,0
0,9
0,9
XC3, XC4
1,2
1,0
1,0
XS1, XS2,
XD1, XD2
1,5
1,2
1,0
XS3, XD3
1,8
1,5
1,2
Exposure
class
L 100
The service life classes L100, L50, and L20 refer to structures with an
expected service life of at least 100, 50, and 20 years respectively.
7.3.4(3)
General recommendation
Article 22 k3 should be set to 7 /c. As regards k4 the recommended value
should be applied.
77
8.3(2)
General recommendation
Article 23 Weldable reinforcement that has been bend-tested in
accordance with SS-EN ISO 15630-1 can be bent with a bending radius, i.e.
internal radius of curvature, which is not less than 0,75 times the mandrel
diameter used in the bending test, provided that bending is done at
temperatures above 0 C. Otherwise, the recommended values should be
applied.
9.2.1.1(3)
General recommendation
Article 24 As,max can be assumed to be unlimited.
9.2.2(4)
General recommendation
Article 25 If the shear reinforcement that is not designed as closed
stirrups comprises of bent up or bent down longitudinal reinforcing, 3
should be set to 0. Otherwise, the recommended value should be applied.
9.2.2(5)
General recommendation
Article 26 The recommended value should be applied. For bridges,
however, the following should also be complied with:
Webs of box girders should be provided with shear reinforcement
corresponding to at least 0,30 %. For webs with a width bw greater than the
beam height h, the minimum shear reinforcement may be reduced to (0,20 +
0,10 h/bw) %.
In beams other than box girders, the web should be provided with shear
reinforcement corresponding to at least 0,15 %. For webs with a width bw
greater than the beam height h, the minimum shear reinforcement may be
reduced to (0,10 + 0,05 h/bw) %.
The reinforcement ratio is calculated in a cross-section that is at right
angles to the shear reinforcement. When calculating the area of the
concrete, the mean width of the beam web may be used.
9.2.2(7)
General recommendation
Article 27 sb,max should be set to 0,75 d (1+cot).
9.5.2(2)
General recommendation
Article 28 As,min should be set to 0,002Ac.
9.5.2(3)
General recommendation
Article 29 As,max can be assumed to be unlimited.
9.6.2(1)
General recommendation
Article 30 As,vmax can be assumed to be unlimited and As,vmin should be set
to the recommended value.
78
9.8.4(1)
General recommendation
Article 31 q2 should be set to the ground pressure that would cause
splitting in concrete with the geometry in question and min should be set to
the recommended value.
9.8.5(3)
General recommendation
Article 32 As,bpmin should be set to the recommended value.
(BFS 2013:10).
9.10.2.2(2)
General recommendation
Article 33 Q2 can be assumed to be unlimited and q1 should be set to the
recommended value. (BFS 2013:10).
9.10.2.3(4)
General recommendation
Article 34 q4 can be assumed to be unlimited and q3 should be set to the
recommended value.
11.3.5(1)P
Article 35 lcc shall be set to 1,0.
11.3.5(2)P
Article 36 lct shall be set to 1,0.
12.3.1(1)
General recommendation
Article 37 The value for cc,pl should be set to 1,0 and the value for ct,pl to
0,5.
Article 39 If at least 8 tests are carried out, a = 40 MPa should be used for fyk
and a = 0 for k and uk . (BFS 2013:10).
C.1(3) Note 2
General recommendation
Article 40 The values in Table D-4 should be used.
Table D-4
Parameter
Minimum value
fyk
0,97 Cv
Maximum value
Unlimited
0,98 Cv
Unlimited
uk
0,95 Cv
Unlimited
79
J.3(3)
General recommendation
Article 41 k2 should be set to 0,5 ac/z0.
80
Comments
2.1.3(2)
2.3(2)P
Recommendation used
3.2.3(5)
Recommendation used
3.2.4(2)
3.3.3(1)
4.1(1)P
4.5.1(2)
Recommendation used
5.2(3)
5.3.1(1)
5.3.2(2)
Recommendation used
5.6.1(1)
5.7.3(2)
6.1(5)
Recommendation used
6.2(2)
6.3(1)
6.4.2.1(3)
Recommendation used
6.4.2.2(2)
Recommendation used
2.1.3(2)
General recommendation
Article 2 The values for the average temperature rise and the maximum
temperature rise during the cooling phase should be set to
1 = 180 K,
2 = 220 K.
3.2.4(2)
General recommendation
Article 3 Class A should be used.
3.3.3(1)
General recommendation
Article 4 The lower limit value should be used.
4.1(1)P
General recommendation
Article 5 Advanced methods of calculation under Section 4.3 in EN 19921-2 may be used.
5.2(3)
Article 6 The value of fi shall be determined in accordance with 2.4.2.
5.6.1(1)
General recommendation
Article 7 Class WB should be applied.
81
6.2(2)
General recommendation
Article 8 The method B, C or D may be used.
6.3(1)
General recommendation
Article 9 Unless otherwise indicated by testing, the upper limit value in
accordance with Section 3.3.3 in EN 1992-1-2 should be used.
82
Comments
3.1.2(102)P
3.1.6(101)P
3.1.6(102)P
Recommendation used
3.2.4(101 )P
Recommendation used
4.2(105)
4.2(106)
4.4.1.2(109)
Recommendation used
5.1.3(101)P
5.2(105)
Recommendation used
5.3.2.2(104)
Recommendation used
5.5(104)
Recommendation used
5.7(105)
6.1(109)
6.1(110)
Recommendation used
6.2.2(101)
Recommendation used
6.2.3(103)
Recommendation used
6.2.3(107)
Recommendation used
6.2.3(109)
Recommendation used
6.8.1(102)
6.8.7(101)
Recommendation used
7.2(102)
Recommendation used
7.3.1(105)
7.3.3(101)
7.3.4(101)
Recommendation used
8.9.1(101)
8.10.4(105)
8.10.4(107)
Recommendation used
9.1(103)
Recommendation used
9.2.2(101)
Recommendation used
9.5.3(101)
9.7(102)
Recommendation used
9.8.1(103)
Recommendation used
11.9(101)
113.2(102)
Recommendation used
113.3.2(103)
Annex E
83
3.1.2(102)P
Article 2 The following values shall be used:
Cmax = C100/115
Cmin = C25/30
3.1.6(101)P
Article 3 cc shall be set to 1,0.
4.2(105)
General recommendation
Article 4 The exposure class for concrete surfaces protected by
waterproofing should be set to XD1.
4.2(106)
General recommendation
Article 5 In the presence of de-icing salt, all surfaces in the road
environment should be considered to be directly exposed to the de-icing
salt. Road environment refers to the surfaces within the border marked on
the figure below as well as surfaces of pylons and arches down to 2,0 m
below the upper edge of the carriageway. Upper surfaces of the carriageway
and trafficked bottom plates that are provided with waterproofing are not to
be considered within the road environment.
For bridges situated along or next to roads on which de-icing salt is used
or which may be expected to be exposed to de-icing salt, x should be set to
6 m. The vertical extent of the road environment is considered to stretch
from 6 metres below to 6 metres above the top edge of the carriageway.
Concrete surfaces that are directly exposed to de-icing salt should be
designed in exposure classes XD3 and XF4. In the road environment,
concrete walls, the rear sides of which are backfilled with earth, may be
designed in exposure class XD1.
Figure D-1
Road environment
5.7(105)
General recommendation
Article 6 Non-linear analysis should not be used.
84
6.1(109)
General recommendation
Article 7 Method c should not be used. Moreover, fctx should be set to the
recommended value.
7.3.1(105)
General recommendation
Article 8 When determining the limiting calculated crack width wmax, the
service life class should be taken into consideration. Unless different values
are deemed justified, the values in Table D-5 should be used as the upper
limit for the calculated crack width.
Table D-5
Exposure
class
Structural components
with reinforcement or with
unbonded prestressing
steel
Structural components
with bonded prestressing
steel
Quasi-permanent
combination of actions
Frequent combination of
actions
L 100
XC0, XC1
XC2
0,45
0,40
L 50
0,45
0,45
L 100
0,40
L 20
0,45
-
XC3, XC4
0,30
0,40
XS1, XS2
XD1, XD2
0,20
0,30
0,40
XS3, XD3
0,15
L 50
0,45
0,30
0,20
L 20
0,40
0,45
0,30
0,40
Decompression
0,20
0,30
1 The service life classes L100, L50, and L20 refer to structures with an
expected service life of at least 100, 50, and 20 years respectively.
2 For exposure classes X0 and XC1, the crack widths have no effect on
durability and the stated limit is intended to ensure an acceptable
appearance. If there are no requirements on appearance, the limit can be
relaxed.
3 In these exposure classes, the decompression should also be checked for the
quasi-permanent combinations of actions.
The distance between bonded prestressing steel, or sheaths for such steel,
and the calculated tensile stress should be at least 100 mm.
7.3.3(101)
General recommendation
Article 9 The recommended method should not be used.
8.10.4(105)
General recommendation
Article 10 The value X should be set to 20 % and the maximum
proportion of jointed prestressing steel to 80 %. The distance a should be set
to the recommended values.
9.5.3(101)
General recommendation
Article 11 Transverse reinforcing steel of less than 8 mm in diameter
should not be used.
85
113.3.2(103)
General recommendation
Article 12 k should to be set to 0,5.
86
Comments
7.3.1(111)
Recommendation used
7.3.1(112)
8.10.1.3 (103)
9.11.1 (102)
The list of possible national choices in EN 1992-3 contains a further two choices, namely 7.3.3
and 8.10.3.3 (102), but the possibility for national choices is not included in the standard's
text.
2
In the list of possible national choices, this choice is mentioned as 8.10.3.3 (103).
(BFS 2013:10).
87
Comments
2.3.1(1)
Recommendation used
3.1(2)
3.2.1(1)
3.2.2(1)
3.2.3(1)P
3.2.3(3)B
Recommendation used
3.2.4(1)
5.2.1(3)
Recommendation used
5.2.2(8)
5.3.2(3)
Recommendation used
5.3.2(11)
5.3.4(3)
Recommendation used
6.1(1)
6.3.2.2(2)
Recommendation used
6.3.2.3(1)
6.3.2.3(2)
Recommendation used
6.3.2.4(1)B
6.3.2.4(2)B
Recommendation used
6.3.3(5)
6.3.4(1)
7.2.1(1)B
7.2.2(1)B
7.2.3(1)B
BB.1.3(3)
Recommendation used
Article 2 Materials in steel grade S 355 shall be impact tested at -20 C with at
least 27 J impact energy.
Nationally Determined Parameters
3.1(2)
General recommendation
Article 3 Steel grades in accordance with Table E-1 can also be used.
88
Table E-1
Steel grades
Standard
Steel grade
fy MPa
fu MPa
EN 10149-2
S 315MC
S 355MC
S 420MC
S 460MC
315
355
420
460
390
430
480
520
EN 10149-3
S 260NC
S 315NC
S 355NC
S420NC
260
315
355
420
370
430
470
530
SS-EN 10149-3
S 315MC S 355MC
S 420MC S 460MC
S 260NC
S 315NC S 355NC
S420NC
Factor w
0,85
0,9
1,0
3.2.1(1)
Article 5 Alternative a shall be used.
3.2.2(1)
Article 6 The following values shall be used:
fu
1,10
fy
Elongation at failure 14 %
u 15 y
3.2.3(1)P
Article 7 For bridge design, the lowest service temperature shall be -40 C.
General recommendation
For other buildings, the lowest service temperature can be calculated with
the aid of EN 1991-1-5:2003 and the associated national annex, or
alternatively, a lowest service temperature for outdoor structures or in a
non-heated space can be taken to be -40 C for the choice of toughness
class.
3.2.4(1)
General recommendation
Article 8 Fljande val av riktvrden fr ZEd enligt 3.2(2) i EN 1993-1-10
fr respektive kvalitetsklass i EN 10164.br anvndas. (BFS 2013:10).
89
Table E-3
Target value
according to EN
1993-1-10
ZEd 10
no requirements
ZEd>10
Z35
(BFS 2013:10).
5.2.2(8)
General recommendation
Article 9 The method should not be used for bridges.
Plastic hinge method of structural analysis should only be used for single
storey frames.
When the method is used, joints and attachments should be designed
taking into account second order effects.
5.3.2(11)
General recommendation
Article 10 The method may be used provided that elastic analysis is used.
LT , 0 = 0,4
= 0,75
6.3.2.4(1)B Note 2B
General recommendation
Article 13 The following values should be used c 0 = 0,5 for beams in
class 1 or 2 cross sections and c 0 = 0,4 for class 3 and 4 cross sections.
6.3.3(5) Note 2
General recommendation
Article 14 Method 1 should be used.
90
6.3.4(1)
General recommendation
Article 15 The method may be used, in which case interpolation between
and LT should be done as follows:
+ LT
=
+
where
n=
N Ed
N Rk
and
m=
M y,Ed
M y,Rk
7.2.1(1)B
General recommendation
Article 16 For thin gauge steel structures in walls, the deformation in the
serviceability limit states should not exceed l/200 in the combination
frequent combination of actions, reversible limit states.
7.2.2(1)B
General recommendation
Article 17 For thin gauge steel structures in roofs, the deformation in the
serviceability limit states should not exceed l/200 in the combination
frequent combination of actions, reversible limit states.
7.2.3(1)B
General recommendation
Article 18 For criteria for vibrations in lightweight steel floors, see
Consolidated results from European development projects relating to
lightweight construction using steel, Swedish Institute of Steel Construction
Report 259:1.
91
Comments
2.3(1)
2.3(2)
4.1(2)
4.2.3.6(1) Note 2
4.2.4(2)
Recommendation used
2.3(1), 2.3(2)
Article 2 The following value shall be used.
M.fi = 1,0
4.1 (2)
General recommendation
Article 3 Advanced calculation methods can be used.
4.2.3.6(1) Note 2
General recommendation
Article 4 crit = 350 C is a conservative value.
Calculation in accordance with Annex E can be used.
92
Comments
2(3)P
2(5)
3.1(3) Note 1
3.1(3) Note 2
3.2.4(1)
5.3(4)
Recommendation used
8.3(5)
Recommendation used
8.4(5)
8.5.1(4)
9(2)
Recommendation used
10.1.1(1)
Recommendation used
10.1.4.2(1)
Recommendation used
A.1(1) Note 2
Recommendation used
A.1(1) Note 3
A.6.4(4)
Annex E
2(3)P
Article 2 The partial factors M0 , M1 and M 2 shall be chosen in accordance
with the following
M0=1,0
M1=1,0
M2=1,2
2(5)
Article 3 The following value shall be used.
M,ser = 1,0
3.1(3) Note 1
Article 4 The recommended values shall be used unless it can be shown that the
values in Table 3.1a can be achieved both in the rolling direction and at right
angles to the rolling direction.
3.1(3) Note 2
Article 5 Steel in accordance with Table 3.1b may be used. For steel in
accordance with EN 10327, the following additional requirements shall apply.
93
When steel in accordance with EN 10327 is used, the design shall be based on
the 0,2 limit and the ultimate strength, whichever is lowest. These values shall be
verified by means of material certificates taken from the product in question. The
values shall be complied with in the directions in which the steel is employed.
EN 1993-1-3 may also be used for the following steels:
Steel in accordance with EN 10025-5. Steel in accordance with EN 100256, provided that the restrictions pursuant to EN 1993-1-3 and EN 1993-1-12 are
observed.
Steel S550GD+Z in accordance with EN 10326-5.
3.2.4(1)
General recommendation
Article 6 No limits for thickness are given. These may be governed by
functional requirements, for example its ability to be walked on.
For joints, the validity of the formulae in 8.1(2) is given in the standard.
8.3(5)
Article 7
Fv,Rk
M2
Rivet diameter
Rivet material
(mm)
Steel
Stainless steel
Monel
4,0
4,8
5,0
6,4
1600
2400
2600
4400
2800
4200
4600
-
2400
3500
6200
1
2
2)
Aluminium
800
1100
2000
(BFS 2013:10).
8.3(13) Table 8.2
Article 9 The characteristic shear resistance Fv,Rk for self-tapping screws may
be chosen in accordance with Table E-5. The design values for tensile resistance
Ft,Rd and shear resistance Fv,Rd are determined according to
Ft, Rd = 1,25 Fv,Rd =
1,25 Fv,Rk
M2
94
Table E-5
Screw diameter
(outer diameter of the
thread)
(mm)
Screw material
Hardened
steel
Stainless
steel
4,8
5,5
6,3
8,0
5,200
7,200
9,800
16,300
4,600
6,500
8,500
14,300
8.5.1(4)
Article 12
A.1(1) Note 3
General recommendation
Article 13 The conversion factors may be set equal to 1,00.
A.6.4(4)
95
National choices
Comments
2.1.4(2)
Recommendation used
2.1.5(1)
Recommendation used
5.1(2)
5.5(1)
Recommendation used
5.6(2)
Recommendation used
6.1(2)
Recommendation used
6.2(3)
Recommendation used
5.1(2)
Article 2 The following partial factors shall be used
M0 = 1,0
M1 = 1,0
M2 = 1,2
96
Comments
2.2(5)
Recommendation used
3.3(1)
Recommendation used
4.3(6)
5.1(2)
Recommendation used
6.4(2)
Recommendation used
8.(2)
Recommendation used
9.1(1)
Recommendation used
9.2.1(9)
Recommendation used
10(1)
10(5)
Recommendation used
C.2(1)
Recommendation used
C.5 (2)
Recommendation used
C.8 (1)
Recommendation used
C.9 (3)
Recommendation used
D.2.2(2)
Recommendation used
Annex E
4.3(6)
General recommendation
Article 2 For bridge design, h=1,5 should be used. For other structures,
the recommendation should be used.
10(1)
General recommendation
Article 3 The method should not be used.
97
Comments
3.1(4)
Recommendation used
4.1.4(3)
Recommendation used
5.2.4(1)
Recommendation used
6.3(5)
7.3.1(1)
Recommendation used
7.3.2(1)
Recommendation used
8.4.2(3)
Recommendation used
8.4.3(2)
8.4.3(4)
Recommendation used
8.4.4(4)
Recommendation used
8.4.5(1)
Recommendation used
8.5.2(2)
8.5.2(4)
Recommendation used
8.7.2(7)
Recommendation used
8.7.2(16)
Recommendation used
8.7.2(18)
Recommendation used
9.2.1(2)P
6.3(5)
General recommendation
Article 2 The value should be set to nmps = 0,05E/fyd i.e. mps = 0,05.
8.4.3(2)
General recommendation
Article 3 Absolute figures should not be used. The relative values in
Table 8.3 should be used.
8.5.2(2)
Article 4 The partial factor M1 that shall be applied is given in the national
annexes to EN 1993-1 to 1993-6.
9.2.1(2)P
Article 5 The partial factor Mf that shall be applied is given in the national
annexes to EN 1993-1 to 1993-6.
98
Comments
6.3.2(4)
Rekommendationen anvnds
(BFS 2013:10).
99
Comments
1.2.6
2.2(2)
3.1.1(3)
3.4.2(1)
4.5.3.2(6)
5.2.1(2)
Recommendation used
6.2.7.2(9)
Recommendation used
Article 2 Bolts and nuts in High Strength preloaded bolted joints shall have such
properties that nuts and threads are normally stronger than the bolts, even in case
of unfavourable combinations of properties and dimensions. For other joints, the
strength of the nut shall at least equal the nominal tensile strength of the screw.
Nationally Determined Parameters
1.2.6
General recommendation
Article 3 Rivets should comply with the requirements in SS 39 and SS
318. Material for rivets in accordance with SS-EN 10263-2 may be used.
2.2(2)
Article 4 Partial factors in accordance with Table E-6 shall be applied.
Table E-6
Partial factors
Partial factors
Bolts
Rivets
Pins
Welds
Plates in bearing
M2 = 1,2
Slip resistance
M3 = 1,2
M3,ser = 1,0
Injection bolts
M4 = 1,0
M5 = 1,0
M6,ser = 1,0
M7 = 1,0
Concrete
c se EN 1992
(BFS 2013:10).
100
3.1.1(3)
General recommendation
Article 5 Only strength classes 8.8 and 10.9 should be used, except for
bolted connections in Category A for which strength class 4.6 may also be
used. For bolted connections in Categories B, C, and E, bolts and nuts in
accordance with EN 14399-3:2002 should be used.
3.4.2(1)
General recommendation
Article 6 Preloading force should be 0,7 fubAs.
4.5.3.2(6)
Article 7 See Article 4 in Chapter 3.1.1.
101
Comments
1.1(2)
Recommendation used
2(2)
Recommendation used
2(4)
Recommendation used
3(2)
Recommendation used
3(7)
5(2)
6.1(1)
Recommendation used
6.2(2)
Recommendation used
7.1(3)
Recommendation used
7.1(5)
Recommendation used
8(4)
Recommendation used
3(7)
Article 2 The following partial factors shall be used.
For damage tolerant method:
In safety classes 1 and 2
Mf = 1,0.
In safety class 3
Mf = 1,15.
For safe-life method:
In safety classes 1 and 2
Mf = 1,15.
In safety class 3
Mf = 1,35.
(BFS 2013:10).
General recommendation
Article 3 For bridges, the safe-life method should be used.
(BFS 2013:10).
5(2)
General recommendation
Article 4 For class 4 cross sections, stresses should be calculated for the
gross cross section with a reduction for the effect of shear deformations in
wide flanges.
102
Comments
2.2(5)
Recommendation used
3.3(1)
Recommendation used
(BFS 2013:10).
103
Comments
2.3.6(1)
Recommendation used
2.3.6(2)
Recommendation used
2.4.1(1)
Recommendation used
3.1(1)
Recommendation used
4.4(2)
4.5(4)
Recommendation used
5.2(3)
Recommendation used
5.3(2)
Recommendation used
6.2(2)
Recommendation used
6.3.2(1)
Recommendation used
6.3.4(1)
Recommendation used
6.4.1(1)P
Recommendation used
7.2(2)
Recommendation used
A.4.5.1(1)
A.4.5.2(1)
B(6)
4.4(2)
General recommendation
Article 2 With regard to corrosion, stainless steel for wire should be
chosen in accordance with Table A.1 in EN 1993-1-4.
104
Comments
2.1 (3.1(2))
Recommendation used
2.1 (3.2.2(1))
Recommendation used
2.1 (5.4.3(1))
2.1 (6.2.3(2))
Recommendation used
2.8 (4.2(2))
3 (1)
(BFS 2013:10).
105
106
National choices
Comments
2.1.3.2(1)
Recommendation used
2.1.3.3(5)
Recommendation used
2.1.3.4(1)
Recommendation used
2.1.3.4(2)
2.3.1(1)
Recommendation used
3.2.3(2)
3.2.3(3)
Recommendation used
3.2.4(1)
3.4(1)
3.5(1)
3.6(1)
3.6(2)
4(1)
4(4)
5.2.1(4)
Recommendation used
5.4.1(1)
6.1(1)P
6.2.2.3(1)
Recommendation used
6.2.2.5(1)
6.3.2.3(1)
Recommendation used
6.3.4.2(1)
6.3.4.2(7)
Recommendation used
7.1(3)
7.3(1)
Recommendation used
7.4(1)
8.1.3.2.1(1)
8.1.6.3(1)
8.2.1.4(1)
8.2.1.5(1)
8.2.1.6(1)
8.2.10(1)
8.2.13(1)
8.2.14(1)
9.1.2(1)
9.1.3(1)
Recommendation used
9.3(1)P
Recommendation used
9.3(2)P
Recommendation used
9.4.1(6)
Recommendation used
9.5.2(2)
Recommendation used
9.5.2(3)
Recommendation used
9.5.2(5)
Recommendation used
9.5.2(6)
Recommendation used
9.5.2(7)
Recommendation used
National choices
Comments
9.5.3(2)
Recommendation used
9.6(1) Note 1
9.6(1) Note 2
9.7(1)
Recommendation used
A.3.3(1)P
Recommendation used
A.3.6(2)
Recommendation used
A.4.2.1(2)
Recommendation used
A.4.2.1(3)
Recommendation used
A.4.2.1(4)
A.4.2.4(2)
Recommendation used
C.1.1(2)
Recommendation used
C.1.2.2(1)
Recommendation used
C.1.2.2(2)
Recommendation used
E.2(1)
Recommendation used
2.1.3.4(2)
General recommendation
Article 2 The safe life method should be applied.
3.2.3(2)
General recommendation
Article 3 Materials should satisfy the requirements in Table E-7.
Table E-7
Additional requirements
Material thickness t
mm
T27J C
Steel type
t 30
-20
30 < t 80
-20
t > 80
-40
3.2.4(1)
General recommendation
Article 4 For the relationship between the target value ZEd according to
3.2(3) in EN 1993-1-10 and the quality class according to EN 10164, Table
E-3 in Chapter 3.1.1, Article 8 should be used. (BFS 2013:10).
5.4.1(1)
General recommendation
Article 5 Plastic analysis may be used for accident load.
107
6.1(1)P
Article 6 The following partial factors shall be used:
M0=1,0
M1=1,0
M2= 0,9 fu/fy but not greater than 1,1 fr resistance of net cross-section
M2=1,2 for joints
M3 =1,2
M3,ser =1,0
M4 =1,0
M5 =1,0
M6 =1,0
M7 =1,0
(BFS 2013:10).
6.2.2.5(1)
General recommendation
Article 7 The method in point 1 should be used.
6.3.4.2(1)
Article 8 The following values shall be applied.
c,0 = 0,4
kfl = 1,0
8.1.3.2.1(1)
General recommendation
Article 9 Injection bolts should not be used.
8.1.6.3(1)
General recommendation
Article 10 Hybrid connections should not be used.
8.2.1.4(1)
General recommendation
Article 11 Partial penetration butt welds may be used as an alternative to
fillet welds.
8.2.1.5(1)
General recommendation
Article 12 Plug welds should not be used.
8.2.1.6(1)
General recommendation
Article 13 Flare groove welds may be used.
8.2.10(1)
General recommendation
Article 14 Welds in accordance with 4.12(1) and (2) in EN 1993-1-8
should not be used.
8.2.13(1)
General recommendation
Article 15 Only equally strong joints should be used.
108
9.1.2(1)
General recommendation
Article 16 For bridge deck sheets having a thickness in accordance with
C.1.2.2, verification of fatigue due to local bending may be neglected.
9.6(1) Note 2
General recommendation
Article 17 For bridge deck sheets having a thickness in accordance with
C.1.2.2, verification of fatigue due to local bending may be neglected.
A.4.2.1(4)
General recommendation
Article 18 T can be assumed to be 5 C.
109
110
National choices
Comments
2.2(1)
2.2(3)
2.9.2.2(3)P
3.4(1)
4.1.4(2)
4.1.4(4)
4.2.2.3(6)
4.3.1(6)
4.3.1(8)
5.3.2.3(3)
5.3.2.4(10)
5.3.2.4(12)
5.3.2.4(15)
5.3.2.5(10)
5.3.2.5(14)
5.3.2.6(3)
5.3.2.6(6)
5.3.2.8(2)
5.3.3.5(1)
5.3.3.5(2)
5.3.4.3.2(2)
5.3.4.3.3(2)
5.3.4.3.3(5)
5.3.4.3.4(5)
5.3.4.5(3)
5.4.4(2)
5.4.4(3)
5.4.4(4)
5.4.7(3)
5.5.2(3)
5.6.2(1)
5.6.2(2)
6.1.2(4)
6.3.2.3(2)
6.3.2.3(4)
6.3.2.7(3)
7.3.1(4)
8.3.3(4)
8.4.1(6)
No further regulation
8.4.2(5)
No further regulation
8.5.3(3)
9.5.1(3)
No further regulation
9.5.1(4)
No further regulation
9.5.2(5)
National choices
Comments
9.8.2(1)
9.8.2(2)
A.2(1)
A.2(2)
A.3.2.1(6)
A.3.2.2(6)
A.3.2.3(2)
A.3.3(1)
A.3.3(2)
A.3.3(3)
A.3.4(4)
General recommendations
Rules on silos are also issued by the Arbetsmiljverket (Eng: Swedish Work
Environment Authority). (BFS 2013:10).
2.2(1)
General recommendations
Article 2 Consequence classes are equated with safety classes according to
Chapter 2 (about EN 1990). Silos in consequence class 1 may be executed
in EXC1. Silos in consequence classes 2 and 3 should be executed in at
least EXC2 and EXC3 respectively. (BFS 2013:10).
2.9.2.2(3)P
Article 3 The following values shall be used:
M0 = 1.0
M1 = 1.0
M2 = 0.9 fu/fy though maximum 1.1 (for the net cross-section)
M4 = 1.0
M5 = 1.2
M6 = 1.1
(BFS 2013:10).
5.3.2.3(3)
General recommendations
Article 4 The recommended values may be used provided that the fillet
weld is designed to be equally strong like the thinner goods if j1 = 1.0 is
used. (BFS 2013:10). (BFS 2013:10).
6.1.2(4)
General recommendations
Article 5 M0g should be set to 1.2. (BFS 2013:10).
111
A.2(1)
General recommendations
Article 7 kM = 1.0 should be used. (BFS 2013:10).
A.3.2.1(6)
General recommendations
Article 8 The recommended values may be used provided that the fillet
weld is designed to be equally strong like the thinner goods if j1 = 1.0 is
used. (BFS 2013:10).
A.3.2.2(6)
General recommendations
Article 9 M1 = 1.0 should be used. (BFS 2013:10).
A.3.2.3(2)
General recommendations
Article 10 n = 0.5 and M1 = 1.0 should be used. (BFS 2013:10).
A.3.3(1)
General recommendations
Article 11 M0g should be set to 1.2. (BFS 2013:10).
A.3.3(3)
General recommendations
Article 12 kr = 0.9 (as recommended) and M2 according to 2.9.2.2(3)
should be used. (BFS 2013:10).
Comments
2.2(1)
2.2(3)
2.9.2.1(1)P
2.9.2.1(2)P
2.9.2.1(3)
No further regulation
2.9.2.2(3)
2.9.3(2)
No further regulation
3.3(3)
No further regulation
4.1.4(3)
No further regulation
4.3.1(6)
No further regulation
4.3.1(8)
No further regulation
General recommendations
Rules on tanks are even issued by Arbetsmiljverket (Eng. the Swedish
Work Environment Authority). (BFS 2013:10).
112
2.2(1)
General recommendations
Article 2 Consequence classes are equated with safety classes according to
Chapter 2 (about EN 1990). In the case of design assisted by testing, safety
class 1 may be applied to all tanks.
Tanks in consequence class 1 may be performed in EXC1. Tanks in
impact class 2 and 3 should be performed in at least EXC2 and EXC3
respectively. (BFS 2013:10).
2.2(3)
General recommendations
Article 3 The classification is used, and the size limit for consequence class
3 is a volume greater than or equal to 50 m3. (BFS 2013:10).
2.9.2.1(1)P
Article 4 When applying the expressions 6.10a and b in EN 1990, the following
values shall be used:
G,sup = 1.35
G,inf = 1.00
Qi = 1.4 for variable loads from fluids (Qi is designated as F in EN 1993-4-2)
0,1 =1.0
= 0.89
(BFS 2013:10).
2.9.2.1(2)P
Article 5 When applying the expression 6.11b in EN 1990, the following value
shall be used:
1,1 = 1.0 for variable loads from liquids
(BFS 2013:10).
2.9.2.2(3)P
Article 6 The following values shall be used:
M0 = 1.0
M1 = 1.0
M2 = 0.9 fu/fy though maximum 1.1
M4 = 1.0
M5 = 1.2
M6 = 1.1
The condition above concerns M2 in the expressions (6.7) and (6.16) in EN
1993-1-1. For M2 when designing joints, see Chapter 3.1.8, Article 4, Table E-6.
(BFS 2013:10).
113
Comments
2.1.3.2(1)P
2.8(2)P
3.2.3(1)
3.2.3(2)P
Recommendation used
3.2.4(1)
3.6.2(1)
3.6.3(1)
6.1(1)
6.3.2.3(1)
7.3(1)
Recommendation used
7.5(1)
8.2(4)
9.1(2)
9.2(1)P
9.2(2)P
Recommendation used
9.3.3(1)
9.4.2(5)
(BFS 2013:10)
2.1.3.2(1)P
Article 2 Provided that the service life, is at least 25 years, unless special
circumstances warrant otherwise. (BFS 2013:10).
3.2.3(1)
General recommendations
Article 3 The lowest service temperature for the selection of ductility class
should be assumed to be 10oC for heated premises and-40oC for unheated
premises. (BFS 2013:10).
3.2.4(1)
General recommendations
Article 4 For relationship between the target value ZEd according to 3.2(3)
in EN 1993-1-10 and the quality class in EN 10164, Table E-3 in Chapter
3.1.1, Article 8 should be applied. (BFS 2013:10).
114
6.1(1)
Article 5 The values as per Table E-8 shall be used:
Tabell E-8
Resistance of cross-sections
or elements
Resistance of joints
M0 = 1,0
M2 = 1,2
M1 = 1,0
M3 = 1,2
M3,ser = 1,0
M4 = 1,0
M5 = 1,0
M6,ser = 1,0
M7 = 1,0
(BFS 2013:10).
6.3.2.3(1)
General recommendations
Article 6 Annex A may be used for simply supported beams. As an
alternative, the following method may be used for all beams with rails
mounted without elastomeric bearing pads.
The flanges are considered as rods with an area equal to the flange area
plus one third of the compression zone area (different for upper and lower
flanges). The force in the rod is calculated as the moment divided by the
distance between the flanges' centre of gravity. Critical force for the rod
should be calculated taking into account the force's variation along the rod.
The top flange is assumed to take up the horizontal load by bending
sideways. No horizontal load is assumed for the lower flange. The bearing
capacity is verified according to EN 1993-1-1. (BFS 2013:10).
8.2 (4)
General recommendations
Article 7 In this context, no crane classes are regarded as "high fatigue".
Transverse web stiffeners should be used only at the supports and these
should be welded to the top flange if they transfer horizontal support
reaction. (BFS 2013:10).
9.3.3(1)
General recommendations
Article 8 Bending stresses in the web can be disregarded for all crane
classes. (BFS 2013:10).
9.4.2(5)
General recommendations
Article 9 For the combined effect of two cranes, dup should be selected two
classes lower than the crane with the lowest class. More than two cranes
need not to be considered. In this case, the load combination factor is set to
1.0. (BFS 2013:10).
115
Comments
2.4.1.1(1)
2.4.1.2(5)P
2.4.1.2(6)P
2.4.1.2(7)P
3.1(4)
3.5(2)
6.4.3(1) h)
6.6.3.1(1)
6.6.3.1(3)
6.6.4.1(3)
6.8.2(1)
6.8.2(2)
9.1.1(2)P
Recommendation used
9.6(2)
9.7.3(4)
9.7.3(8)
9.7.3(9)
Recommendation used
B.2.5(1)
B.3.6(5)
2.4.1.1(1)
Article 25 Recommended value P = 1,0 shall be used. (BFS 2013:10)
2.4.1.2(5)P
Article 36 Recommended value P = 1,25 shall be used. (BFS 2013:10).
2.4.1.2(6)P
Article 47 Following value VS = 1,2 shall be used. (BFS 2013:10)
2.4.1.2(7)P
Article 58 Recommended value Mfs = 1,0 shall be used. (BFS 2013:10)
116
3.1(4)
General recommendation
Article 6 Values for shrinkage of concrete in Annex C may be applied to
buildings.
3.5 (2)
General recommendation
Article 7 The minimum nominal sheet thickness should be taken as 0,7
mm, excluding zinc.
6.6.3.1(1)
Article 8 Values in accordance with Article 3 in this chapter shall be used.
6.6.3.1(3)
General recommendation
Article 9 The rules in SS-EN 1994-2 may also be used for buildings.
6.8.2(1)
Article 10 Values in accordance with Article 5 in this chapter shall be used.
6.8.2(2)
Article 11 Ff shall be used.
9.6(2)
General recommendation
Article 12 No limit is set, provided that 9.3.2(2) is applied.
117
Comments
1.1(16)
2.1.3(2)
2.3(1)P
Recommendation used
2.3(2)P
Recommendation used
2.4.2(3)
3.3.2(9)
4.1(1)P
4.3.5.1(10)
1.1(16)
Article 2 This part may only be used with concrete strength classes equal to or
higher than C20/25 and LC20/22, but not higher than C50/60 and LC50/55.
2.1.3(2)
General recommendation
Article 3 1=180 K and 2=220 K should be used.
3.3.2(9)
General recommendation
Article 4 The function in 3.6b in the standard should be used.
4.1(1)P
Article 5 Advanced calculation methods should be used.
4.3.5.1(10)
General recommendation
Article 6 Buckling length for a column in an intermediate storey is ei =
0,5 times the system length and for a column in the top floor, the buckling
length is ei = 0,7 times the system length.
118
Comments
1.1.3(3)
2.4.1.1(1)
2.4.1.2(5)P
2.4.1.2(6)P
5.4.4(1)
6.2.1.5(9)
6.2.2.5(3)
Recommendation used
6.3.1(1)
6.6.1.1(13)
6.6.3.1(1)
6.8.1(3)
Recommendation used
6.8.2(1)
7.4.1(4)
Recommendation used
7.4.1(6)
8.4.3(3)
2.4.1.1(1)
Article 29 The recommended value P = 1,0 shall be used in bridges.
(BFS 2013:10).
2.4.1.2(5)P
Article 310 The recommended value V shall be used in bridges. (BFS 2013:10).
2.4.1.2(6)P
Article 411 The recommended value Mfs shall be used in bridges.
(BFS 2013:10).
5.4.4.1 (1)
General recommendation
Article 5 Interaction between global and local action effects needs
normally not to be taken into account.
6.2.1.5(9)
Article 6 Chapter 10 of EN 1993-1-5 must not be used.
6.6.3.1(1)
Article 7 The value given in Article 3 in this chapter shall be used.
119
6.8.2(1)
Article 8 The value given in Article 4 in this chapter shall be used.
7.4.1(6)
General recommendation
Article 9 The risk of premature cracking should be treated with the
methods given by AMA Anlggning 10, EBE.11. (BFS 2013:10).
120
Fastener
Service class
1
1
2
Zinc-plated
min 12 m
Hot3
galvanized
Zinc-plated
min 12m
Stainless steel
Untreated1
Staples
Zinc-plated
min 3m
Untreated
Punched metal
plate fasteners
Z275
Z275
Stainless steel
Steel plates up to 5
mm thickness
Z275
Z275
Z350
Untreated
Untreated
Hot3
galvanized
Hot3
galvanized
Hot3
galvanized
121
(BFS 2013:10).
Preconditions
General recommendation
Article 5 General rules on execution can be found in Section A.
Finger jointed structural timber can be used in load-bearing structures,
provided that such a structure is designed such that a failure of a single
finger joint does not cause the collapse of essential parts of the structure in
general.
Finger jointed structural timber should not be used in scaffolding or in
other structures exposed to impacts and shock loads.
Material
Article 5a CE marking according to method B in EN 14081-1: A1:2011 (socalled package marking) must not be used for structural timber in load-bearing
structures. (BFS 2013:10).
Comments
2.3.1.2(2)P
2.3.1.3(1)P
2.4.1(1)P
Recommendation used
6.1.7(2)
6.4.3(8)
Recommendation used
7.2(2)
7.3.3(2)
8.3.1.2(4)
8.3.1.2(7)
Recommendation used
9.2.4.1(7)
Recommendation used
9.2.5.3(1)
Recommendation used
10.9.2(3)
10.9.2(4)
2.3.1.2(2)P
General recommendation
Article 7 In Table G-2, a breakdown is given of loads according to
duration as is relevant for the Swedish conditions. (BFS 2013:10).
122
Table G-2
Load-duration class
Examples of loads
Permanent
Self-weight
Long-term
Medium-term
Short-term
Momentary
Wind load
Gusts
Accidental load
Single concentrated load on the roof
(BFS 2013:10).
4.2(2)
General recommendation
Article 7a Table 4.1 should be replaced by Table G-1 in the General
recommendation of Article 4. (BFS 2013:10).
6.1.7(2)
General recommendation
Article 7b For Glued laminated timber and solid timber fully or partially
exposed to precipitation and solar radiation, kcr = 0.67 should be used.
For other Glued laminated timber and solid timber
kcr
3, 0
f
v,k
= min
1,0
7.2(2)
Article 8 Limits for deflection related to health and safety shall be determined
where necessary on a case-by-case basis with regard to the circumstances.
General recommendation
Limits according to e.g. appearance and comfort can be provided by the
client/owner.
7.3.3(2)
General recommendation
Article 9 For Swedish conditions, the following values may be applied: a
= 1,5 mm/kN and b = 100 m/Ns2.
8.3.1.2(4)
Article 10 Section 8.3.1.2(4) must not be applied.
10.9.2(3)
General recommendation
Article 11 After erection and adequately securing, bow,perm should not
exceed 10 mm. (BFS 2013:10).
123
10.9.2(4)
General recommendation
Article 12 dev,perm should be the smallest of zero, 0,02h or 50 mm. h is the
largest height of the truss. (BFS 2013:10).
124
Comments
2.1.3(2)
2.3(1)P
Recommendation used
2.3(2)P
Recommendation used
2.4.2(3)
Recommendation used
4.2.1(1)
Recommendation used
2.1.3(2)
General recommendation
Article 2 The values for the average temperature rise and the maximum
temperature rise during the cooling phase should be set to
1 = 180 K,
2 = 220 K.
125
Comments
2.3.1.2(1)
2.4.1
Recommendation used
7.2
7.3.1(2)
2.3.1.2(1)
General recommendation
Article 2 Loads during execution should be attributed to the load-duration
class medium-term.
7.2
General recommendation
Article 3 Deflection due to traffic loads, including pedestrian loads,
should be limited to l/400.
126
Comments
2.4.3(1)P
2.4.4(1)
3.2.2(1)
3.6.1.2(1)
3.6.2(3)
3.6.2(4)
3.6.2(6)
3.6.3(3)
3.7.2(2)
3.7.4(2)
Recommendation used
4.3.3(3)
4.3.3(4)
Recommendation used
5.5.1.3(3)
Recommendation used
6.1.2.2(2)
Recommendation used
8.1.2(2)
8.5.2.2(2)
8.5.2.3(2)
Recommendation used
8.6.2(1)
Recommendation used
8.6.3(1)
Recommendation used
2.4.3(1)P
Article 2 Values of M for the ultimate limit state as per Table H-1 shall be
used.
Table H-1
a, b, d
II
1,9
2,1
2,1
2,5
2,6
3,0
e
Execution class
(characteristic value)
Masonry executed using:
a
II
1,8
2,0
2,0
2,3
2,3
2,7
127
Execution class
II
2,0
2,5
1,3
1,3
2,5
2,7
Wall ties
a.
b.
c.
d.
e.
2.4.4(1)
Article 3 The standards recommendation of 1,0 for M in the serviceability limit
states shall be used.
3.2.2(1)
General recommendation
Article 4 The following acceptable equivalent mixing proportions for
mortar should be used.
Table H-2
Mortar class
Binder
Mortar class M10
(A)
Cement
Lime, cement
Lime, cement
Masonry cement
Mortar class M2.5
(B)
Lime, cement
Masonry cement
Mortar class M1
(C)
Lime, cement
Masonry cement
Mortar class M0.5
(D)
Lime, cement
Hydraulic lime
Parts by
weight
Parts by
volume
Mortar class
Designation 1
C 100/450
KC 20/80/400
KC 10/90/350
M 100/350
C 1:4
KC 1:3:15
KC 1:4:15
M 1:3
KC 35/65/550
M 100/600
KC 1:1:8
M 1:5
KC 50/50/650
M 100/900
KC 2:1:12
M 1:7
KC 2:1:18
Kh 1:5
KC 50/50/950
Kh 100/850
1 The designation indicates the mortar class and parts by volume of cement,
lime, sand, as well as the binder type
128
Table H-3
Mortar class
1
Term
Binder
Cement
Cement, lime
Cement, lime
Masonry cement
100:450
80:20:400
90:10:350
100:350
Cement, lime
Masonry cement
65:35:550
100:600
Cement, lime
Masonry cement
50:50:650
100:900
Cement, lime
Hydraulic lime
50:50:950
100/850
1. The designation indicates the mortar class and parts by volume of cement,
lime, sand, as well as the binder type
3.6.1.2(1)
General recommendation
Article 5 The following characteristic compressive strength of masonry fk
should be used.
Table H-4
Masonry Unit
Characteristic values
Strength
class
fk (MPa)
Mortar class in
accordance with EN 998-2
M10
Clay blocks
Clay brick
M2,5
M1
Thin
layer
mortar
M0,5
4,1
12
5,2
3,6
2,7
1,0
15
5,8
4,2
3,2
1,3
25
7,5
6,0
4,5
1,8
35
8,9
7,5
5,7
2,3
45
10,0
9,0
6,8
2,3
55
11,1
10,3
7,8
2,3
65
12,1
11,6
8,8
2,3
Calcium silicate
25
6,0
4,5
12,3
Concrete brick
25
7,5
6,0
2,0
1,5
2,6
10
2,4
2,4
2,4
4,6
10
3,8
3,6
2,8
5,7
15
4,7
4,7
3,7
8,0
2,0
1,2
0,9
1,4
2,5
1,4
1,0
1,7
Hollow concrete
block
Solid concrete
block
Autoclaved
Aerated
Concrete
129
Masonry Unit
Strength
class
Lightweight
aggregate concrete
fk (MPa)
Mortar class in
accordance with EN 998-2
Thin
layer
mortar
1,6
1,2
2,0
3,5
1,7
1,3
2,3
4,0
1,9
1,5
2,6
4,5
2,1
1,6
2,9
2,2
1,7
3,1
1,8
1,2
0,8
1,4
2,4
1,6
1,0
2,0
3,4
2,2
1,2
3,1
10
4,3
3,4
1,2
5,7
3.6.2(3)
General recommendation
Article 6 The following values of fvlt (MPa)should be used
Clay blocks and clay bricks = 1,0,
Calcium silicate bricks, concrete bricks, hollow concrete blocks, solid
concrete blocks and autoclaved Aerated concrete blocks = 0,6,
Thin joint autoclaved aerated concrete blocks = 0,8,
Lightweight aggregate blocks = 1,1.
3.6.2(4)
General recommendation
Article 7 fvlt in accordance with Article 6 should be applied.
3.6.2(6)
General recommendation
Article 8 The following initial shear strengths fvko should be used.
Table H-5
Masonry unit
General purpose
mortar of the
strength class
given
Thin layer
mortar (bed
joints 0,5
3,0 mm)
Lightweightmortar
Clay
M10M20
M2,5M9
M1M2
0,30
0,20
0,10
--
0,15
M10M20
M2,5M9
M1M2
0,20
0,15
0,10
0,40
0,15
Concrete and
lightweight
aggregate
concrete
M10M20
0,20
Lightweight
M2,5M9
0,20
Calcium silicate
130
fvko (MPa)
Masonry unit
General purpose
mortar of the
strength class
given
Thin layer
mortar (bed
joints 0,5
3,0 mm)
Lightweightmortar
M2,5M9
0,15
0,30
0,15
M1M2
0,15
M1M2
0,10
aggregate
concrete
Autoclaved
aerated concrete
Manufactured
stone and
Dimensioned
natural stone
3.6.3(3)
General recommendation
Article 9 The following characteristic flexural strength fxk1 and fxk2 should
be used.
Table H-6
Masonry unit
fxk1
(MPa)
M1,0M2,4
fxk1
(MPa)
M2,5M10
fxk1
Thin
layer
mortar
fxk2
(MPa)
M1,0M2,4
fxk2
(MPa)
M2,5M10
fxk2
Thin
layer
mortar
Clay block
0,12
0,15
--
0,12
0,15
--
Hollow clay
brick
1565
0,12
0,3
--
0,9
1,1
--
1565
0,12
0,25
--
0,9
1,1
--
Calcium
silicate brick
25
0,05
0,1
0,20
0,7
0,9
0,30
Concrete brick
25
0,05
0,2
0,20
0,7
0,9
0,30
Hollow
concrete block
5-10
0,05
0,2
0,20
0,30
0,4
0,30
Solid concrete
block
1015
0,05
0,2
0,20
0,30
0,4
0,30
2,0
0,08
0,1
0,15
0,08
0,1
0,30
2,5
3
3,5
4,0
4,5
5
0,08
0,15
0,15
0,15
0,15
0,15
0,1
0,15
0,15
0,15
0,15
0,15
0,15
0,20
0,20
0,20
0,20
0,20
0,15
0,20
0,20
0,20
0,20
0,20
0,2
0,25
0,25
0,25
0,25
0,25
0,30
0,30
0,30
0,30
0,30
0,30
0,12
0,15
0,20
0,12
0,15
0,30
3
5
10
0,12
0,12
0,12
0,15
0,15
0,15
0,20
0,20
0,20
0,25
0,25
0,25
0,3
0,3
0,3
0,30
0,30
0,30
Autoclaved
aerated
concrete
Lightweight
aggregate
concrete
131
3.7.2(2)
General recommendation
Article 10 Choice of KE for the module of elasticity.
When the effect of the module of elasticity is very significant it should
be determined by testing in accordance with SS-EN 1052-1.
If the module of elasticity E is not determined by testing, the following
values of KE may be used
KE = 500
for solid clay bricks and calcium silicate bricks
(a)
KE = 500
for hollow clay bricks and thin joint autoclaved
(b)
aerated concrete blocks
KE = 1000
for lightweight aggregate blocks
(c)
KE = 1000
for concrete bricks, hollow concrete blocks,
(d)
solid concrete blocks, and autoclaved aerated
concrete blocks
4.3.3(3)
General recommendation
Article 11 The following choices of reinforcing steel with regard to
durability should be used.
Table H-7
Durability
Corrosion protection and concrete cover (mm) for
reinforcing steel in relation to exposure classes
Materials
Ref.
No
Exposure class
MX1
MX2
MX3
MX4
MX5
Austenitic
stainless steel,
acid resistant
steel
R1
15
15
15
15
15
Austenitic
stainless steel
R3
15
15
15
20
--
Galvanised steel
R 13
15
35*
50*
--
--
Galvanised,
epoxy-coated
steel
R 18
15
35*
50*
--
--
Unprotected
non-alloy steel
ob
25
--
--
--
--
132
Table H-8
Material description
Ref
no.
Material designation
Material description
R1
EN 10088
R3
EN 10088
R 13
EN 10020
ob
EN 10020
EN 10245 epoxy
EN 10020
Table H-9
Exposure classes
Exposure
class
Micro conditions of
the masonry
Type of structure
MX1
Dry environment
Insignificantly
corrosion aggressive.
MX2
MX3
Damp or wet
environment not
exposed to frost/thaw
cycles.
Moderately corrosion
aggressive.
Damp or wet
environment exposed
to frost/thaw cycles.
Corrosion aggressive.
MX4
MX5
Aggressive chemical
environment
Particularly corrosion
aggressive.
Masonry exposed to
salt/thaw cycles, nonplastered cavity walls
exposed to pelting rain,
construction parts exposed
to high moisture load and
chlorides.
Exterior and interior walls in
aggressive industrial
atmosphere.
8.1.2(2)
General recommendation
Article 12 The following values of tmin should be used.
Masonry should have a minimum nominal thickness in accordance with
the following table.
133
Table H-10
Height of masonry
Cavity wall
85
55
around 100
85
8.5.2.2(2)
General recommendation
Article 13 The cavity walls should use at least 3 ties per m2 and used for
channel walls, at least 4 ties per m2 should be used.
134
Comments
2.3.4.2(2)
Recommendation used
3.5.3.1(1)
Recommendation used
1.1.(2)P
Recommendation used
2.3.1 (1)
Recommendation used
3.4(3)
Recommendation used
135
136
National choices
Comments
2.1(8)P
2.4.6.1(4)P
2.4.6.2(2)P
2.4.7.1(2)P
2.4.7.1(3)P
2.4.7.1(4)
Recommendation used
2.4.7.1(5)
Recommendation used
2.4.7.1(6)
2.4.7.2(2)P
2.4.7.3.2(3)P
2.4.7.3.3(2)P
2.4.7.3.4.1(1)P
2.4.7.4(3)P
2.4.7.5(2)P
2.4.8(2)
National choices
Comments
2.4.9(1)P
2.5(1)
7.6.2.2(8)P
7.6.2.2(14)P
7.6.2.3(4)P
7.6.2.3(5)P
Recommendation used
7.6.2.3(8)P
7.6.2.4(4)P
7.6.3.2(2)P
7.6.3.2(5)P
7.6.3.3(3)P
7.6.3.3(4)P
Recommendation used
7.6.3.3(6)P
8.5.2(2)P
8.6(4)
11.5.1(1)P
Annex D
Annex E
Annex F
2.1(8)P
Article 6 Geotechnical constructions shall be divided into three categories
dependent on extent and complexity. Geotechnical category 1 shall include small
and simple structures which are executed with negligible risk and with known
ground conditions. Geotechnical category 2 shall include conventional types of
structures and foundations where there is no exceptional risk of affecting the
surrounding and with no special soil or load conditions.
Geotechnical category 3 shall include structures or parts of structures which
fall beyond the limitations of geotechnical categories 1 and 2.
Geotechnical category 1 must not be applied to geotechnical constructions in
reliability class 3.
General recommendation
Supporting constructions where the shaft depth is greater than 4 m or where
water is of crucial importance should be treated as being a construction in
geotechnical category 3 and be designed for example using numerical
methods.
2.4.6.1(4)P
Article 7 Partial factors for loads in persistent and transient design situations
shall be selected in accordance with Section B, Chapter 0, Articles 17-19 and
Article 46, Table I-13 and Article 47, I-15 in this chapter.
2.4.6.2(2)P
Article 8 Partial factors for material and bearing capacity parameters for
persistent and transient design situations shall be selected in accordance with
Article 37, Table I-5, Article 39, Table I-6, Article 41, Tables I-7 I-9, Article 43,
Table I-12, and Article 46, Table I-14 in this chapter.
137
2.4.7.1(2)P
Article 9 Partial factors for persistent and transient design situations shall be
selected in accordance with Articles 3647 in this chapter.
2.4.7.1(3)
Article 10 Partial factors for material and bearing capacity parameters for
accidental situations are to be set to 1.0 if not otherwise specified in this statute.
General recommendation
Accident situations in the form of loss of bracing should be taken into
consideration in anchorages.
2.4.7.1(6)
General recommendation
Article 11 An example of a model factor, Rd for piles can be found in
Article 23 in the Vgverket's (Eng. Swedish Road Administrations)
publication 2009:46, TK Geo. The factors use is shown in EN 1997-1,
Section 6.3.5.
2.4.7.2(2)P
Article 12 Partial factors for the verification of static equilibrium shall be
selected in accordance with Section B, Chapter 0, Article 17 and Article 37, Table
I-5 in this chapter.
General recommendation
Static equilibrium (EQU) requires normally only to be verified for spread
foundation on heavily compacted soil or rock.
2.4.7.3.2(3)P
Article 13 For loads, load effects, and material parameters, partial factors for
the verification of structural (STR) and geotechnical (GEO) limit states
shall be selected in accordance with Section B, Chapter 0, Articles 18-19
and Article 39, Table I-6 in this chapter. 2.4.7.3.3(2)P
Article 14 Partial factors for bearing capacity shall, for the verification of
structural (STR) and geotechnical (GEO) limit states, be selected in accordance
with Article 41, Tables I-7I-9 and Article 43, Table I-12 in this chapter.
2.4.7.3.4.1(1)P
Article 15
Design
DA 2
DA 3
Support structures
DA 3
DA 3
Plates
DA 3
Anchorages
DA 2
2.4.7.4(3)P
Article 16 Partial factors for the verification of risk of uplift (UPL) shall be
selected in accordance with Article 46, Tables I-13 and I-14 in this chapter.
138
2.4.7.5(2)P
Article 17 Partial factors for the verification of risk of heave (HYD) due to
seepage of water shall be selected in accordance with Article 47, Table I-15 in
this chapter.
2.4.8(2)
General recommendation
Article 18 Refer to EN 1990, section 6.5.4(1) for partial factors for
material parameters for the serviceability limit state.
2.4.9(1)P
Article 19 Limit value for the movements of foundations are to be set by the
client/owner.
2.5(1)
General recommendation
Article 20 For spread foundations in geotechnical category 1, a simplified
verification based on soil pressure values in accordance with Table I-2 shall
be used.
Table I-2
Materials
Mountain (unweathered)
1
2
fd (kPa)
400
Materials
Sand
fd (kPa)
100
Moraine
200
Silt
Gravel
150
Solid clay
50
1
100
7.6.2.2(8)P
Article 21 Correlation factors for the determination of characteristic
geotechnical bearing capacity of piles, based on results from static pile load tests,
shall be selected in accordance with Article 42, Table I-10 in this chapter.
7.6.2.2(14)P
Article 22 Partial factors for the verification of geotechnical bearing capacity
of piles, through the use of static pile load tests , shall be selected in accordance
with Article 41, Tables I-7I-9 in this chapter.
7.6.2.3(4)P
Article 23 Partial factors for the verification of geotechnical bearing capacity of
piles, based on the results from geotechnical surveys combined with documented
experience of pile load tests under similar conditions, shall be selected in
accordance with Article 41, Tables I-7I-9 in this chapter.
General recommendation
Table I-3 provides examples of model factors for the verification of
geotechnical bearing capacity of friction piles.
139
Tabell I-3
Method
Rd
1,6
1,4
1,5
Method
Undrained analysis ( -metod )
Drained analysis (-method)
1
1,1
1,2
7.6.2.3(8)P
Article 24 Model factor for the correction of partial factors when verifying the
geotechnical bearing capacity of piles, based on the results from geotechnical
surveys combined with documented experience of pile load tests under similar
conditions, shall for alternative procedure be selected equal to 1.4.
7.6.2.4(4)P
Article 25 Partial factors and correlation factors for the verification of
geotechnical bearing capacity of piles, based on dynamic testing, shall be selected
in accordance with Article 41, Table I-7I-9 and Article 42, Table I-11 in this
chapter.
7.6.3.2(2)P
Article 26 Partial factors for the verification of geotechnical bearing capacity of
piles loaded in tension, based on results from pile load tests, shall be selected in
accordance with Article 41, Table I-7I-9 in this chapter.
7.6.3.2(5)
Article 27 Correlation factors for the determination of the characteristic
geotechnical bearing capacity of piles loaded in tension, based on results from
static pile load tests, shall be selected in accordance with Article 42, Table I-10 in
this chapter.
7.6.3.3(3)P
Article 28 Partial factors for the verification of geotechnical bearing capacity of
piles loaded in tension, based on the results from geotechnical surveys combined
with documented experience of pile load tests under similar conditions, shall be
selected in accordance with Article 41, Table I-7I-9 in this chapter.
140
7.6.3.3(6)P
Article 29 The model factor for correction of partial factors for the verification
of geotechnical bearing capacity of piles loaded in tension, based on the results
from geotechnical surveys combined with documented experience of pile load
tests under similar conditions, shall for alternative procedure be selected equal to
1.4.
8.5.2(2)P
Article 30 Partial factors for the verification of geotechnical bearing capacity of
pre-stressed anchorages, based on the results from testing, shall be selected in
accordance with Article 43, Table I-12 in this chapter.
8.6(4)
General recommendation
Article 31 Model factors for load on anchorage in serviceability limit
state should be selected equal to 1.0.
10.2.3
Article 32 Partial factors for the verification of risk of uplift (UPL) can be
found in Article 16. Friction and anchorage forces shall not be treated as loads in
expression 2.8.
11.5.1(1)P
Article 33 Partial factors for actions and strengths for the verification of total
stability in slopes and banks shall be selected in accordance with Section B,
Chapter 0, Articles 18-19 and Article 39, Table I-6 in this chapter.
Application of informative annexes
Article 34 Annex D maintains its informative character for national application,
under the condition that the impact of foundation level, strength above the
foundation level and inclined adjacent ground surface are taken into
consideration.
Soil parameter
Term
Factor
1.3
Effective cohesion
1.3
cu
1.5
qu
1.5
Weight density
1.0
141
A.3.1(1)P
Article 38 For the verification of (STR/GEO), the partial factors for actions and
the effects of actions in accordance with Table A.3 shall to be equal to the factors
specified in Section B, Chapter 0, Articles 1819, Tables B-3 and B-4.
A.3.2(1)P
Article 39 For the verification of (STR/GEO), partial factors for soil parameters
(M) are to be selected in accordance with Table I-6.
Table I-6
Soil parameter
Term
Set
M2
1.3
Effective cohesion
1.3
cu
1.5
qu
1.5
Weight density
1.0
A.3.3.1(1)P
Article 40 Table A.5, which handles partial resistance factors (R) of spread
foundations, with the associated verification method, must not be used.
A.3.3.2(1)P
Article 41 For the verification of foundations using driven piles, partial
resistance factors (R) shall be selected in accordance with Table I-7
Table I-7
Resistance
Term
Set
R2
Tip
1.3
Mantel (compression)
1.3
Total/combined (compression)
1.3
Mantel (driven)
s;t
1.4
For railway applications, the partial factor in the table may be reduced by 0.1. The reduction
is due to different load models.
For the verification of foundations using bored piles, partial resistance factors
(R) shall be selected in accordance with table I-8.
142
Table I-8
Resistance
Term
Set
R2
Tip
1.4
Mantel (compression)
1.4
Total/combined (compression)
1.4
Mantel (driven)
s;t
1.5
For railway applications, the partial factor in the table may be reduced by 0.1. The reduction
is due to different load models.
For the verification of foundations using CFA piles, partial resistance factors
(R) shall be selected in accordance with table I-9.
Table I-9
Resistance
Term
Set
Tip
1.4
Mantel (compression)
1.4
Total/combined (compression)
1.4
Mantel (driven)
s;t
1.5
R2
For railway applications, the partial factor in the table may be reduced by 0.1. The reduction
is due to different load models.
A.3.3.3(1)P
Article 42 Correlation factors for the determination of the characteristic
geotechnical bearing capacity of piles, based on the results from static pile load
tests, are to be selected in accordance with Table I-10.
Table I-10
fr n =
1.40
1.30
1.20
1.10
1.00
1.40
1.20
1.05
1.00
1.00
1 Applicable only where uniform geotechnical conditions prevail and where the distance
between piles within the control object is not more than 25 metres. The control object here
refers to a group of piles with a unified method of installation and mode of action in a unified
soil volume.
143
Tabell I-11
fr n
10
15
20
40
All piles
1.60
1.55
1.50
1.45
1.42
1.40
1.35
1.30
1.50
1.45
1.35
1.30
1.25
1.25
1.25
1.25
5
6
7
In the table, the given values of are valid for dynamic impact tests that are evaluated using
the CASE method.
I In the table, the given values are multiplied by the model factor of 0.85 when dynamic
impact tests with signal matching is carried out or when there is a permanent sinkage
2 mm per impact or when the evaluated toe rebound is < D/60 for toe bearing piles.
If a foundation consists of different types of piles, each type is considered separately when
selecting the number of test piles, n.
For the evaluation of tensile resistance from signal matching, a maximum of 70 % of the
mantels bearing capacity may be used. The model factor for bearing capacity for piles in
tension shall, when the evaluation is based on signal matching, be selected equal to 1.3.
Signal matching shall always be carried out for primarily mantle borne piles.
Pile driving formulas must not be combined using these correlation factors.
Applicable only where uniform geotechnical conditions prevail and where the distance
between piles within the control object is not more than 25 metres. The control object here
refers to a group of piles with a unified method of installation and mode of action in a unified
soil volume.
For railway applications, in cases where the resistance is not determined by the local value
of the material properties and where the structural element has sufficient rigidity and strength
to transfer loads from weak to strong piles, the correlation factors 5 and 6 are divided by
1.1.
A.3.3.4(1)P
Article 43 For the verification of pre-stressed anchorages, partial factors for
bearing capacity (R) shall be selected in accordance with Table I-12.
Tabell I-12
Type
Permanent anchorages
1
Term
a;p
R2
1.0
A.3.3.5(1)P
Article 44 Table A.13, which treats partial resistance factors, (R) for the
verification of retaining structures with an associated verification method, must
not be used.
A.3.3.6(1)P
Article 45 Table A.14, which treats partial resistance factors, (R) for the
verification of slopes and embankments with an associated verification method,
must not be used.
A.4(1)P
Article 46 For the verification of (UPL), partial factors for actions, (F) shall be
selected in accordance with Table I-13.
144
Table I-13
Action
Term
Value
Permanent
1
Adverse
2
Favourable
G;dst
G;stb
1,2 d
0,9
Variable
1
Adverse, dominant
1
Adverse, other
Q;dst
Q;dst
1,5 d
1,5 d 0,1
1
2
3
Destabilising.
Stabilising.
For railway applications, the values in Table A.15 of EN 1997-1 shall be used.
For the verification of (UPL), partial factors for soil parameters, M and
resistance, R shall be selected in accordance with Table I-14.
Table I-14
Partial factors for soil parameters, (M) and bearing capacity, (R) in
verification of (UPL)
Soil parameter /
resistance
Term
Value
1,3
Effective cohesion
1,3
cu
1,5
s;t
1,4
A.5(1)P
Article 47 For the verification of (HYD), partial factors for actions, (F) shall be
selected in accordance with Table I-15.
Tabell I-15
Action
Term
Value
Permanent
1
Adverse
2
Favourable
G;dst
G;stb
1,35 d
0,9
Variable
1
Adverse, dominant
1
Adverse, other
Q;dst
Q;dst
1,5 d
4
1,5 d 0,i
1
2
3
4
Destabilising.
Stabilising.
In railway applications G;dst =1 may be use.
For railway applications Q;dst =1,5 is to be used.
145
Comments
1.1.2(1)
Recommendation used
2.1.2(3)
2.3.1(1)
3.2.1(1)
3.2.2(1)
3.2.2(2) Note 1
3.2.3.1(1) Note 2
3.3.2.1(3) Note 1
3.3.2.2(1)
5.2.1(3)
Recommendation used
5.3.2(3)
Recommendation used
5.3.4(3)
Recommendation used
6.1.3(1) Note 1
6.1.3(1) Note 2
6.2.1(5)
Recommendation used
7.1(4)
7.2.1(1)
7.2.2(1)
7.2.3(1)
8.1.1(2)
8.9(3)
A.6(1)
Recommendation used
C.3.4.1(2)
C.3.4.1(3)
C.3.4.1(4)
K.1(1)
Recommendation used
K.3(1) Note 1
Recommendation used
K.3(1) Note 3
6.1.3(1) Note 1
Article 2 The recommended values shall be used
M1 = 1,1
M2 = 1,25
7.2.3(1)
General recommendation
Article 3 For criteria for vibrations in lightweight floors, see the
Stlbyggnadsinstitutet report Samlade resultat frn europeiska
utvecklingsprojekt med stl, Report 259:1.
146
8.1.1(2)
Article 4 The recommended values in the table shall be used.
C.3.4.1(2), C.3.4.1(3), C.3.4.1(4)
Article 5 The recommended partial factors shall be used.
147
Comments
2.3(1)
2.3(2)
2.4.2(3)
4.2.2.1(1)
4.2.2.3(5)
4.2.2.4(5)
2.3(1)
Article 2
2.3(2)
Article 3
2.4.2(3)
Article 4 The recommended values for G, Q,1, fi, and in accordance with
Section B, Chapter 0 shall be used. The recommendation to use 2.1, for fi, shall
be followed.
4.2.2.1(1)
General recommendation
Article 5 The calculation methods in EN 1999-1-1 should be used.
However the modulus of elasticity and the 0,2 limit should be replaced with
the values Eal, and fo, at raised temperatures al. In addition M is to be
replaced by M,fi.
The reduction factors o,haz and u,haz in the zone affected by heat can be
assumed to be the same at elevated temperatures.
To determine the cross section class, the slenderness parameters 1, 2
and 3 in Table 6.2 in EN 1999-1-1 are calculated using
= 0,05 Eal, / f o, .
4.2.2.3(5)
General recommendation
Article 6 The method in accordance with Note in 4.2.2.1(1) should be
used.
4.2.2.4(5)
General recommendation
Article 7 The method in accordance with Note in 4.2.2.1(1) should be
used. When calculating the buckling load Ncr and the slenderness parameter
, a further reduced modulus of elasticity of Eal, /1,2 should be used, and
the buckling curve for buckling class B should be selected.
148
Comments
2.1.1(1)P
2.2.1(3)
Recommendation used
2.3.1(3)
2.3.2(6)
Recommendation used
2.4(1) Note 1
2.4(1) Note 2
3 (1)
4(2)
5.8.1(1)
5.8.2(1)
Recommendation used
6.2.1(2)
6.2.1 (7)
6.2.1(11)
Recommendation used
6.2.4(1)
A.3.1(1)
Recommendation used
E(5)
E(7)
I.2.2 (1)
I.2.3.2(1)
I.2.4(1)
2.4(1) Note 1
Article 2 Recommended value Ff = 1,0 shall be used.
2.4(1) Note 2
Article 3 The recommended value in accordance with Table 2.1 on Ff shall be
used.
6.2.1(2)
Article 4
6.2.4(1)
General recommendation
Article 5 The hot spot reference detail method specified in Annexe K
should be used in combination with Annex J.
E(5)
Article 6
149
Comments
2(3)
2(4)
2(5)
3.1(3)
7.3(3)
A.1(1) Note 2
A.1(1) Note 3
A.3.4(3)
2(3)
Article 2 The following values shall be used:
M1 = 1,0
M2 = 1,25
M3 = 1,25
2(4)
Article 3
7.3(3)
General recommendation
Article 4 In accordance with EN 1990, deformations in the serviceability
limit states are calculated for frequent combination of actions.
If the limit is set with regard to aesthetics, a quasi-permanent
combination of actions shall be used in accordance with EN 1990.
Examples of limit values for deflections and deformations that can be
used are indicated in the table below.
Table J-1
Structure
Deflection requirement
Floor beams
L/300
Rooftops
a)
L/200
a)
L/100
a)
Profiled sheeting
in roof constructions
in intermediate floors
in wall constructions
in cantilevers
L/200
See SS-EN 1993-1-1
L/100
L/100
150
A.1(1) Note 3
General recommendation
Article 5 The conversion factors may be set equal to 1,00.
A.3.4(3)
Article 6 The partial factor M shall be determined on the basis of testing in
accordance with Annex D in EN 1990. In addition, the applicable rules of
Annex A in EN 1999-1-4 shall be followed. If the intent of testing is only to
determine the design value irrespective of any calculation model, the value
M =1,0 shall be used.
The recommended value sys =1,0 shall be used.
151
Comments
2.1(3)
2.1(4)
2.1(3)
Article 2 The following recommended values shall be used:
M1 = 1,10
M2 = 1,25
2.1(4)
Article 3 The following recommended value shall be used:
M1, ser= 1,0
152
Annex 1
153
154
Geotechnical constructions
The safety class for geotechnical structures depends, among
other things, on the overlying structures. The foundation can in
certain cases be assigned to a lower safety class than the
overlying structure.
Railway bridges
For railway bridges and their components, safety classes in
accordance with TRVKBro may be applied.
(BFS 2013:10).
155
Annex 2
156
Figure Bil2.2
157