Beruflich Dokumente
Kultur Dokumente
Buyers Guide
RET 541,
RET 543,
RET 545
Transformer Terminal
Features
Fig. 1
ret54_mimic_co180dpi
Transformer Terminal
Application
Transformer Terminal
Design
Protection is one of the most important functions of the RET 54_ transformer terminal.
The protection function blocks (e.g.
NOC3Low) are independent of each other
and have e.g. their own setting groups and
data recording.
The protection function blocks are documented on the CD-ROM Technical Descriptions of Functions (1MRS750889-MCD)
Measurement functions
The measurement function blocks are documented on the CD-ROM Technical Descriptions of Functions (1MRS750889-MCD)
Control functions
Additional functions are available for different general purposes to be used in logics such
as activation of HMI backlight, switchgroups,
and resetting of operation indications, latched
output signals, registers and disturbance
recorder.
Communication functions
The RET 54_ transformer terminal is provided with a low auxiliary voltage indication
feature. The power supply module issues an
internal alarm signal when a drop in the
power supply voltage is detected (ACFail,
active low). The alarm signal is activated if
the power supply voltage falls about 10%
below the lowest rated DC input voltage of
the power supply module.
Transformer Terminal
Design (contd)
Overtemperature indication
The digital inputs of the transformer terminals are voltage controlled and optically isolated with three treshold voltages defined by
the order, see chapter Ordering. The func-
Some specific digital inputs can be programmed to operate either as digital inputs, as
pulse counters or as used for time synchronization. When a digital input operates as a
pulse counter, pulse counting frequency can
be up to100 Hz.
Oscillation suppression
The RET 541 and RET 543 transformer terminals equipped with an RTD/analog module
(RTD1) have eight general purpose analog
inputs for DC measurement. The RTD/analog
inputs are galvanically isolated from the
transformer terminal power supply and enclosure. However, the inputs have a common
ground. The general purpose RTD/analog
inputs accept voltage-, current- or resistancetype signals. For each measuring mode, a
separate parameter is provided for choosing
between the available measurement ranges.
RTD/analog inputs can be applied for e.g.
temperature measurement.
Digital outputs
Transformer Terminal
The RET 541 and RET 543 transformer terminals equipped with an RTD/analog module
have four general purpose 0...20 mA analog
current outputs. All outputs are galvanically
isolated from the supply and enclosure of the
transformer terminal and from each other.
Analog outputs can be utilized for transferring any measured or calculated information
to panel meters or e.g. PLCs.
Alarm LED indicators
Display panel
Serial communication
The 9-pin D-type subminiature male connector (RS-232 connection) on the rear panel
connects the transformer terminal to the distribution automation system via the SPA bus,
IEC_103, DNP 3.0 or Modbus. The fibreoptic interface module type RER 123 is used
to connect the transformer terminal to the
fibre-optic communication bus for SPA and
7
Transformer Terminal
The 9-pin D-type subminiature female connector (RS-485 connection) on the rear panel
connects the transformer terminal to the substation automation system via the SPA bus or
the LON bus. The fibre-optic interface module
type RER 103 is used to connect the transformer terminal to the fibre-optic communication bus. The RER 103 module supports
both SPA bus and LON bus communication.
The SPA-ZC 302 is an interface module that
provides connectivity to the Profibus DP
fieldbus and SPA-ZC 400 interface module
provides connectivity to the IEC 61850-8-1
Station bus.
Transformer
terminal
configuration
Self-supervision
The transformer terminal RET 54_ is provided with an extensive self-supervision system. The self-supervision system handles
run-time fault situations and informs the user
of faults via the HMI and LON/SPA bus communication.
When a fault has been detected, the green
Ready indicator starts flashing, a fault indication text is displayed on the HMI and an
event 0/E57 is generated. The fault indication
text on the HMI consists of two rows: a general message internal fault, followed by the
generated IRF code of the fault.
The relay will try to recover from a fault
either by restarting the module (I/O module
or HMI) that reported the fault, or by restarting the whole relay. During restarting the IRF
state will remain active until the internal selfsupervision program has determined that the
relay is operating normally. If the fault is still
persistent after restarting three times, the
relay will be in permanent IRF state.
All of the eight alarm function blocks can be
configured in the same alarm view of the
mimic editor. ON and OFF state texts (only
one language version at a time can be supported for the alarm) and LED colours can be
defined. Three different colours can be used
to define the ON and OFF state. Three basic
modes are available:
non-latched
latched-steady
latched flashing
Interlocking LED texts can also be defined in
the same alarm view but the colour of the
interlocking LED cannot be changed.
LON network configuration
The Protocol Mapping Tool is used for configuring the DNP 3.0 and Modbus interfaces
of the transformer terminal.
Transformer Terminal
When the parameters are set locally, the setting parameters can be chosen from the hierarchical menu structure. The desired
language for parameter description can be
selected.
External parameterization
The Relay Setting Tool is used for parameterizing and setting the transformer terminals
externally. The parameters can be set off-line
on a PC and downloaded to the transformer
terminal over a communication port. The
menu structure of the setting tool, including
views for parameterization and settings, is the
same as the menu structure of the transformer
terminal.
Auxiliary
voltage
For its operation, the RET 54_ terminal, including the external display module, requires
a secured auxiliary voltage supply. The terminals internal power supply module forms the
voltages required by the terminal electronics.
The power supply module is a galvanically
isolated (fly-back type) dc/dc converter. A
green protection LED indicator on the front
panel is lit when the power supply module is
in operation.
Terminal
connections
All external circuits are connected to the terminal blocks on the rear panel, see figures
2...4. The terminal block for the measuring
transformers consists of fixed screw terminals.
Transformer Terminal
Terminal diagrams
+
PS1_4_ACFail
PS1_4_TempAlarm
X1.1
27
25
24
22
21
19
18
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
100V
1A
5A
1A
5A
1A
5A
100V
1A
5A
1A
5A
1A
5A
1A
5A
Ch 10, VT2
SERIAL BUS
Ch 9, CT7
SERIAL BUS
Ch 8, CT6
X3.2
X3.3
X4.1
3
4
IRF
Ch 7, CT5
X4.1
Mains
Ch 6, VT1
5
6
Ch 5, CT4
Ch 4, CT3
PS1_4_HSPO3
7
9
8
PS1_4_HSPO1
PS1_4_TCS1
11
13
12
10
Ch 3, CT2
Ch 2, CT1
TCS
15
PS1_4_HSPO2
PS1_4_TCS2
TCS
16
18
17
X4.2
8
X4.2
1
2
PS1_4_HSPO4
PS1_4_BI1
4
5
PS1_4_BI2
6
7
PS1_4_BI3
X5.1
1
2
3
BIO1_5_BI1
4
5
6
7
8
9
10
11
12
PS1_4_HSPO5
13
14
15
16
17
18
PS1_4_SO1
1
2
18
BIO1_5_BI2
BIO1_5_BI3
X5.2
3
BIO1_5_BI4
BIO1_5_BI5
BIO1_5_SO1
BIO1_5_BI7
BIO1_5_SO2
BIO1_5_BI9
BIO1_5_SO3
BIO1_5_BI10
BIO1_5_BI11
BIO1_5_BI12
4
5
6
7
9
BIO1_5_BI8
BIO1_5_SO4
8
10
12
11
13
15
X5.2
-
13
15
14
16
17
BIO1_5_BI6
9
11
10
12
BIO1_5_SO5
BIO1_5_SO6
14
16
18
17
RET 541
CD541
Fig. 2
10
Transformer Terminal
+
PS1_4_ACFail
PS1_4_TempAlarm
X1.1
27
25
24
22
21
19
18
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
100V
1A
5A
1A
5A
1A
5A
100V
1A
5A
1A
5A
1A
5A
1A
5A
Ch 10, VT2
SERIAL BUS
Ch 9, CT7
SERIAL BUS
Ch 8, CT6
X3.2
X3.3
X4.1
3
4
IRF
Ch 7, CT5
X4.1
Mains
Ch 6, VT1
5
6
Ch 5, CT4
Ch 4, CT3
PS1_4_HSPO3
7
9
8
PS1_4_HSPO1
PS1_4_TCS1
TCS
11
13
12
TCS
16
18
17
10
Ch 3, CT2
Ch 2, CT1
15
PS1_4_HSPO2
PS1_4_TCS2
X4.2
8
X4.2
1
2
PS1_4_HSPO4
PS1_4_BI1
4
5
PS1_4_BI2
6
7
PS1_4_BI3
X5.1
1
2
3
BIO1_5_BI1
4
5
6
7
8
9
PS1_4_HSPO5
10
11
12
13
14
15
16
17
18
PS1_4_SO1
1
2
18
BIO1_5_BI2
BIO1_5_BI3
X5.2
3
BIO1_5_BI4
BIO1_5_BI5
BIO1_5_SO1
BIO1_5_BI7
BIO1_5_SO2
BIO1_5_BI9
BIO1_5_SO3
BIO1_5_BI10
BIO1_5_BI11
BIO1_5_BI12
4
5
6
7
9
BIO1_5_BI8
BIO1_5_SO4
8
10
12
11
13
15
X5.2
-
13
15
14
16
17
BIO1_5_BI6
-
9
11
10
12
BIO1_5_SO5
BIO1_5_SO6
14
16
18
17
X7.1
BIO2_7_PO1
17
18
X7.2
X7.1
1
2
3
4
5
6
7
8
9
10
11
12
BIO2_7_BI1
BIO2_7_PO2
1
2
BIO2_7_PO3
4
5
6
BIO2_7_PO4
8
9
10
BIO2_7_PO5
12
13
14
BIO2_7_PO6
16
17
18
BIO2_7_BI2
BIO2_7_BI3
BIO2_7_BI4
BIO2_7_BI5
BIO2_7_BI6
BIO2_7_BI7
11
BIO2_7_BI8
13
14
BIO2_7_BI9
15
16
BIO2_7_BI10
15
RET 543
CD543
Fig. 3
Transformer Terminal
X4.1
+
PS2_4_ACFail
Mains
-
PS2_4_TempAlarm
X1.1
27
25
24
22
21
19
18
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
100V
Ch 10, VT2
1A
5A
Ch 9, CT7
1A
5A
1A
5A
100V
1A
5A
1A
5A
1A
5A
1A
5A
SERIAL BUS
SERIAL BUS
Ch 8, CT6
X3.2
X3.3
X4.1
3
4
IRF
Ch 7, CT5
Ch 6, VT1
5
6
Ch 5, CT4
Ch 4, CT3
PS2_4_HSPO3
7
9
8
PS2_4_HSPO1
PS2_4_TCS1
11
13
12
10
Ch 3, CT2
Ch 2, CT1
TCS
15
PS2_4_HSPO2
PS2_4_TCS2
TCS
16
18
17
X4.2
1
PS2_4_HSPO4
PS2_4_HSPO5
X5.1
1
2
3
4
5
6
7
8
9
PS2_4_HSPO6
BIO1_5_BI1
BIO1_5_BI2
PS2_4_HSPO7
BIO1_5_BI3
10
11
12
13
14
15
16
17
18
BIO1_5_BI5
PS2_4_HSPO8
10
12
11
13
14
16
15
17
18
X5.2
3
BIO1_5_BI7
BIO1_5_SO1
BIO1_5_BI8
BIO1_5_BI9
BIO1_5_SO2
BIO1_5_BI11
BIO1_5_SO3
BIO1_5_BI12
4
5
6
7
9
BIO1_5_BI10
X5.2
1
2
6
8
7
9
BIO1_5_BI4
BIO1_5_BI6
-
2
4
3
5
BIO1_5_SO4
8
10
12
11
13
15
BIO1_5_SO5
X6.1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
BIO1_6_BI1
BIO1_5_SO6
BIO1_6_BI2
BIO1_6_BI3
BIO1_6_SO1
BIO1_6_BI5
BIO1_6_BI6
BIO1_6_SO2
BIO1_6_BI7
BIO1_6_BI8
BIO1_6_SO3
BIO1_6_BI9
BIO1_6_BI10
BIO1_6_SO4
BIO1_6_BI11
BIO1_6_SO5
BIO1_6_BI12
X7.1
4
5
6
7
8
9
10
11
12
17
BIO1_6_BI4
BIO1_6_SO6
1
2
3
16
18
X6.2
X6.2
1
2
14
4
5
6
7
9
8
10
12
11
13
15
14
16
18
17
X7.1
BIO2_7_BI1
BIO2_7_PO1
BIO2_7_BI2
BIO2_7_PO2
BIO2_7_BI4
BIO2_7_PO3
BIO2_7_BI6
BIO2_7_BI7
BIO2_7_BI8
BIO2_7_BI9
15
16
BIO2_7_BI10
1
2
3
BIO2_7_BI5
13
14
17
18
X7.2
BIO2_7_BI3
BIO2_7_PO4
BIO2_7_PO5
BIO2_7_PO6
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
RET 545
CD545_b
Fig. 4
12
Transformer Terminal
Technical data
Table 1: General functions available for the RET 54_
Function
Description
INDRESET
MMIWAKE
SWGRP1
Switchgroup SWGRP1
SWGRP2
Switchgroup SWGRP2
SWGRP3
Switchgroup SWGRP3
......
SWGRP20
Switchgroup SWGRP20
Description
ABS
Absolute value
ACOS
ADD
Extensible adder
AND
ASIN
ATAN
BCD2INT
BITGET
BITSET
BOOL_TO_*
Type conversion from BOOL to WORD / USINT / UINT / UDINT / SINT / REAL
/ INT / DWORD / DINT / BYTE
BOOL2INT
BYTE_TO_*
COMH
Hysteresis comparator
COS
Cosine in radians
CTD
Down-counter
CTUD
Up-down counter
CTU
Up-counter
DATE_TO_UDINT
DINT_TO_*
DIV
Divider
DWORD_TO_*
EQ
EXP
Natural exponential
EXPT
Exponentiation
F_TRIG
GE
GRAY2INT
GT
INT_TO_*
INT2BOOL
LE
LIMIT
Limitation
LN
Natural logarithm
LOG
Logarithm base 10
LT
MAX
Extensible maximum
MIN
Extensible minimum
MOD
Modulo
MOVE
Move
13
Transformer Terminal
Description
MUL
Extensible multiplier
MUX
Extensible multiplexer
NAT2INT
Type conversion from natural binary coded input to SINT (Tap changer)
NE
NOT
Complement
OR
Extensible OR connection
R_TRIG
REAL_TO_*
Type conversion from REAL to USINT / UINT / UDINT / SINT / INT / DINT
ROL
Rotate to left
ROR
Rotate to right
RS
RS_D
SEL
Binary selection
SHL
Bit-shift to left
SHR
Bit-shift to right
SIN
Sine in radians
SINT_TO_*
SUB
Subtractor
SQRT
Square root
SR
XOR
TAN
Tangent in radians
TIME_TO_*
TOD_TO_*
TOF
Off-delay timer
TON
On-delay timer
TP
Pulse
TRUNC_REAL_TO*
Truncation toward zero from REAL to DINT / INT / SINT / UDINT / UINT /
USINT
UDINT_TO_*
UINT_TO_*
USINT_TO_*
WORD_TO_*
14
Function
Description
CMBWEAR1
CMBWEAR2
CMCU3
CMGAS1
CMGAS3
CMSCHED
Scheduled maintenance
CMSPRC1
CMTCS1
CMTCS2
CMTIME1
Operate time counter 1 for the operate time used (e.g. motors)
CMTIME2
Operate time counter 2 for the operate time used (e.g. motors)
CMTRAV1
CMVO3
Transformer Terminal
Description
CO3DC1
CO3DC2
COCB1
COCB2
COCBDIR
CODC1
CODC2
CODC3
CODC4
CODC5
COIND1
COIND2
COIND3
COIND4
COIND5
COIND6
COIND7
COIND8
COLOCAT
COLTC
COSW1
On/off switch 1
COSW2
On/off switch 2
COSW3
On/off switch 3
COSW4
On/off switch 4
MMIALAR1
MMIALAR2
MMIALAR3
MMIALAR4
MMIALAR5
MMIALAR6
MMIALAR7
MMIALAR8
MMIDATA1
MMIDATA2
MMIDATA3
MMIDATA4
MMIDATA5
15
Transformer Terminal
Operation mode
Not in use
Manual
Automatic single
Automatic master
Automatic follower
Negative Reactance Principle
Minimizing Circulating Current
Controlled via op.mode inputs
Delay mode
Definite time
Inverse time
Bandwith
-36 ... 36
-36 ... 36
Operation accuracies
- voltage measurement:
-10000.00000...10000.00000
-10000.00000...10000.00000
-10000.00000...10000.00000
16
0.020000.0 A
0.080.0% In
Transformer Terminal
0.020000.0 A
0.020000.0 A
0.020000.0 A
0.01000.0% In
0.01000.0% In
0.01000.0% In
0.020000.0 A
0.020000.0 A
0.020000.0 A
0.01000.0% In
0.01000.0% In
0.01000.0% In
Pre-trg time
Over limit ILx
Over limit Io
Over limit Iob
Over limit Uo
Over limit Ux
Over limit Uxy
Over limit U12b
Over limit ILxb
Under limit Ux
Under limit Uxy
AI filter time
Saturation
Overwrite
Extension
0100%
0.0040.00 x In
0.0040.00 x In
0.0040.00 x In
0.002.00 x Un
0.002.00 x Un
0.002.00 x Un
0.002.00 x Un
0.0040.00 x In
0.002.00 x Un
0.002.00 x Un
0.00060.000 s
The recording can be triggered by any (or several) of the alternatives listed below:
triggering on the rising or falling edge of any (or several) of the digital inputs
triggering on overcurrent, overvoltage or undervoltage
manual triggering via the menu or with the push-button F on the front panel (if configured)
triggering via serial communication
periodic triggering
The recording length depends on the number of recordings and inputs used. For example, the following
combination of recording length, number of recordings and number of inputs is available at 50 Hz (60 Hz):
# recordings \ # inputs
10
1163 cyc.
23.3 s (19.4 s)
412 cyc.
8.2 s (6.9 s)
126 cyc.
2.5 s (2.1 s)
232 cyc.
4.6 s (3.9 s)
82 cyc.
1.6 s (1.4 s)
25 cyc.
0.5 s (0.4 s)
10
115 cyc.
2.3 s (1.9 s)
41 cyc.
0.8 s (0.7 s)
12 cyc.
0.24 s (0.2 s)
10.0075.00 Hz
10.0075.00 Hz
0.02.0 x Un
17
Transformer Terminal
-999999999999 kW
-999999999999 kvar
-1.001.00
-1.001.00
-999999999999 kW
-999999999999 kvar
0999999999 kWh
0999999999 kWh
0999999999 kvarh
0999999999 kvarh
0150000 V
0.0120.0% Un
18
0.00999.99 kV
0.00999.99 kV
0.00999.99 kV
0.002.00 x Un
0.002.00 x Un
0.002.00 x Un
0.00999.99 kV
0.00999.99 kV
0.00999.99 kV
0.002.00 x Un
0.002.00 x Un
0.002.00 x Un
Transformer Terminal
Measuring mode
Drop-off time of the operate time counter
Operation accuracy
Start time:
- Injected currents
- internal time
- total time
Reset time
Reset ratio, typically
Retardation time
Operate time accuracy at DT mode
Accuracy class index E at IDMT mode
0.105.00 x In
0.05300.00 s
0.051.00
Not in use
Definite time
Extremely inverse
Very inverse
Normal inverse
Long time inverse
RI-type inverse
RD-type inverse
IEEE curves
Peak-to-peak
Fundamental frequency
0...1000 ms
Note! The values below apply when f/fn = 0.95...1.05
2.5% of set value or 0.01 x In
>2.0 x start current:
<32 ms
<40 ms
40...1000 ms (depends on the minimum pulse width set for
the trip output)
0.95
< 45 ms
2% of set value or 20 ms
Class index E = 5.0 or 20 ms
0.1040.00 x In
0.05300.00 s
Not in use
Definite time
Instantaneous
Measuring mode
Peak-to-peak
Fundamental frequency
0...1000 ms
19
Transformer Terminal
Start current
Operate time
Time multiplier
Basic angle b
Operation direction
Earth-fault protection
Measuring mode
Start time:
- injected currents
- internal time
- total time
Reset time
Reset ratio, typically
Retardation time
Operate time accuracy at DT mode
Accuracy class index E at IDMT mode
Not in use
Definite time
Extremely inverse
Very inverse
Normal inverse
Long-time inverse
RI-type inverse
RD-type inverse
0.0540.00 x In
0.05300.00 s
0.051.00
090
Forward
Reverse
Disabled
Enabled
Phase-to-phase voltages, peak-to-peak measurement
Phase-to-phase voltages, fundamental freq. measurement
Phase-to-earth voltages, peak-to-peak measurement
Phase-to-earth voltages, fundamental freq. measurement
0...1000 ms
Note! The values below apply when f/fn = 0.95...1.05
0.1...10 x In: 2.5% of set value or 0.01 x In
10...40 x In: 5.0% of set value
2.5% of measured voltage or 0.01 x Un
2
>2.0 x start current:
<42 ms
<50 ms
40...1000 ms (depends on the minimum pulse width set for
the trip output)
0.95
< 45 ms
2% of set value or 20 ms
Class index E = 5.0 or 20 ms
Three-phase directional overcurrent function, high-set stage, DOC6High, I>>, and instantaneous
stage, DOC6Inst, I>>>
Operation mode
Start current
Operate time
Basic angle b
Operation direction
Earth-fault protection
Non-directional operation (when the direction
cannot be determined)
Measuring mode
20
Not in use
Definite time
Instantaneous
0.0540.00 x In
0.05300.00 s
090
Forward
Reverse
Disabled
Enabled
Disabled
Enabled
Phase-to-phase voltages, peak-to-peak measurement
Phase-to-phase voltages, fundamental freq. measurement
Phase-to-earth voltages, peak-to-peak measurement
Phase-to-earth voltages, fundamental freq. measurement
0...1000 ms
Transformer Terminal
Operation accuracy
Start time:
- injected currents
- internal time
- total time
Reset time
Reset ratio, typically
Retardation time
Operate time accuracy at DT mode
Measuring mode
Operation accuracy
Start time:
- injected impedance
- internal time
- total time
Reset time
Reset ratio
Retardation time
Operate time accuracy
0.0160.00 p.u.
0.04300.00 s
Not in use; In use
4 selections for ph-e voltages
7 selections for ph-ph voltages
(depends on the signals available)
Peak-to peak; Fund.freq.
Note! The values below apply when f/fn = 0.95...1.05
3.0% of set value or 0.02 p.u.
= 0.50 x Z-setting
<42 ms
<50 ms
70...1030 ms (depends on the minimum pulse width set for
the TRIP output)
Typ. 1.03
< 45 ms
2% of set value or 20 ms
Trip time:
- Injected currents
- internal time
- total time
Reset time
Reset ratio, typically
Retardation time
5...50%
10...50%
0.5 x In
1.0...3.0 x In
5...30 x In
Note! The values below apply when f/fn = 0.95...1.05
Phase difference measurement: 4
Stabilized stage: 4% of set value or 2% x In
Instantaneous stage: 4% of set value or 2% x In
>2.0 x operating current
<35 ms
<45 ms
60...1020 ms (depends on the minimum pulse width set for
the trip output)
0.98
< 40 ms
21
Transformer Terminal
Measuring mode
Drop-off time of the operate time counter
Operation accuracy
Start time:
- Injected currents
- internal time
- total time
Reset time
Reset ratio, typically
Retardation time
Operate time accuracy at DT mode
Accuracy class index E at IDMT mode
1.0100.0% of In
0.05300.00 s
0.051.00
Not in use
Definite time
Extremely inverse
Very inverse
Normal inverse
Long time inverse
RI-type inverse
RD-type inverse
IEEE curves
Peak-to-peak
Fundamental frequency
0...1000 ms
Note! The values below apply when f/fn = 0.95...1.05
2.5% of set value + 0.0005 x In
>2.0 x start current:
<32 ms
<40 ms
40...1000 ms (depends on the minimum pulse width set for
the trip output)
0.95
<45 ms
2% of set value or 20 ms
Class index E = 5.0 or 20 ms
Measuring mode
Drop-off time of the operate time counter
Operation accuracy
Start time:
- Injected currents
- internal time
- total time
Reset time
Reset ratio, typically
Retardation time
Operate time accuracy at DT mode
22
0.1012.00 x In
0.05300.00 s
Not in use
Definite time
Instantaneous
Peak-to-peak
Fundamental frequency
0...1000 ms
Note! The values below apply when f/fn = 0.95...1.05
2.5% of set value or + 0.01 x In
>2.0 x start current
<32 ms
<40 ms
40...1000 ms (depends on the minimum pulse width set for
the trip output)
0.95
< 45 ms
2% of set value or 20 ms
Transformer Terminal
Operation criteria
Operation direction
Basic angle b
Operation characteristic
Intermittent E/F
Measuring mode
Drop-off time of the operate time counter
Operation accuracy
1.025.0% of In
2.0100.0% of Un
0.1300.0 s
0.051.00
Not in use
Definite time
Extremely inverse
Very inverse
Normal inverse
Long time inverse
Basic angle & Uo
Basic angle
IoSin/Cos & Uo
IoSin/Cos
Non-directional Io
Non-directional Uo
Forward
Reverse
-90
-60
-30
0
IoSin()
IoCos()
Not active
Active
Peak-to-peak
Fundamental frequency
0...1000 ms
Note! The values below apply when f/fn = 0.95...1.05
2.5% of set value + 0.0005 x In
2.5% of set value or + 0.01 x Un
Phase angle 2
Start time:
- Injected neutral current and residual voltage >2.0 x start current and
residual voltage >2.0 x start voltage
- internal time
<72 ms
- total time
< 80 ms
Reset time
40...1000 ms (depends on the minimum pulse width set for
the trip output)
Reset ratio, typically
0.95
Retardation time
< 50 ms
Operate time accuracy at DT mode
2% of set value or 20 ms
Accuracy class index E at IDMT mode
Class index E = 5.0 or 20 ms
23
Transformer Terminal
Operation criteria
Operation direction
Basic angle b
Operation characteristic
Intermittent E/F
Measuring mode
Drop-off time of the operate time counter
Operation accuracy
1.0200.0% of In
2.0100.0% of Un
0.1300.0 s
Not in use
Definite time
Instantaneous
Basic angle & Uo
Basic angle
IoSin/Cos & Uo
IoSin/Cos
Non-directional Io
Non-directional Uo
Forward
Reverse
-90
-60
-30
0
IoSin()
IoCos()
Not active
Active
Peak-to-peak
Fundamental frequency
0...1000 ms
Note! The values below apply when f/fn = 0.95...1.05
2.5% of set value + 0.0005 x In
2.5% of set value or + 0.01 x Un
Phase angle 2
Injected neutral current >2.0 x start current
and residual voltage >2.0 x start voltage
<72 ms
<80 ms
40...1000 ms (depends on the minimum pulse width set for
the trip output)
0.95
<50 ms
2% of set value or 20 ms
24
0.5...50%
Note! The values below apply when f/fn = 0.95...1.05
2.5% of set value or 0.004 x In
>2.0 x operating current:
<20 ms
<30 ms
60...1020 ms (depends on the minimum pulse width set for
the trip output)
0.80...0.98
This function block cannot be retarded but trips once the
current exceeds the operate value
Transformer Terminal
0.5...50%
0.04...300.00 s
10...50 %
Not in use / In use
Note! The values below apply when f/fn = 0.95...1.05
4% of set value or 0.02 x In
2%
Operation accuracy
Start time:
-injected voltages
- internal time
- total time
Reset time
Reset ratio, typically
Retardation time
Operate time accuracy at DT mode
2.020.0% of Un
0.05300.00 s
Not in use
Definite time
Peak-to-peak
Fundamental frequency
Note! The values below apply when f/fn = 0.95...1.05
2.5% of set value or 0.01 x Un
>2 x start voltage:
<32 ms
<40 ms
40...1000 ms (depends on the minimum pulse width set for
the trip output)
0.95
Total time for blocking: < 25 ms
Total time when voltage drops below start value: < 50 ms
2% of set value or 20 ms
25
Transformer Terminal
Operation accuracy
Start time
- injected voltages
- internal time
- total time
Reset time
Reset ratio, typically
Retardation time
Operate time accuracy at DT mode
26
2.080.0% of Un
0.05300.00 s
Not in use
Definite time
Peak-to-peak
Fundamental frequency
Note! The values below apply when f/fn = 0.95...1.05
2.5% of set value or 0.01 x Un
>2 x start voltage
<32 ms
<40 ms
40...1000 ms (depends on the minimum pulse width set for
the trip output)
0.95
Total time for blocking: < 25 ms
Total time when voltage drops below start value: < 50 ms
2% of set value or 20 ms
Transformer Terminal
Three-phase thermal overload protection for motors, generators and transformers, TOL3Dev, 3
BASIC SETTINGS:
Starting current of the motor
Max. starting time permitted for the motor
Number of starts allowed from cold state
Type of device to be protected
Trip temperature
Prior alarm temperature
Restart inhibit (temperature limit for
successful restarting)
Ambient temperature
Cooling time-constant
Heating time-constant for generator or
transformer
ADVANCED SETTINGS:
Short time-constant for stator
Long time-constant for stator
Weighting factor of the short time-constant for
stator
Temperature rise of stator at rated current
Maximum temperature of stator
Short time-constant for rotor
Long time-constant for rotor
Weighting factor of the short time-constant for
rotor
Temperature rise of rotor at rated current
Maximum temperature of rotor
Operation mode (principle of ambient
temperature compensation)
0.10...10.00 x In
0.1...120.0 s
1...3
Motor; through-ventilated, rated power < 1500 kW
Motor; through-ventilated, rated power > 1500 kW
Motor; surface cooling, rated power < 500 kW
Motor; surface cooling, rated power > 500 kW
Generator; hydro or small air-cooled turbine generators
Generator; large turbine generators
Transformer
80.0120.0%
40.0100.0%
40.0100.0%
-50.0100.0C
1.0...10.0 x time constant
1...999 min
0.0...999.0 min
0.0...999.0 min
0.00...1.00
0.0...350.0 C
0.0...350.0 C
0.0...999.0 min
0.0...999.0 min
0.00...1.00
0.0...350.0 C
0.0...350.0 C
Not in use
No sensors; the set ambient temperature
1 sensor used
2 sensors used
0...86400 s
0...86400 s
Note! The values below apply when f/fn = 0.95...1.05
1.0%, I = 0.1...10.0 x In
(Calculated temp. rise - 0.1) / Trip temperature
(Calculated temp. rise - 0.1) / Prior alarm temperature
(Calculated temp. rise - 0.1) / Restart inhibit temperature
limit
27
Transformer Terminal
Not in use
Definite time
Inverse time
0.01...0.50 x In
0.1....120.0 s
5.0...100.0
0.1...60.0 s
0.1...120.0 s
500...10000 s
5...10000 s
2 or 3
Forward
Reverse
0...1000 ms
Note! The values below apply when f/fn = 0.95...1.05
2.5% of set value or 0.01 x In
= 2.00 x start value
<32 ms
<40 ms
70...1030 ms (depends on the minimum pulse width set for
the trip output)
0.96
<45 ms
2% of set value or 20 ms
2% of the calculated ideal operate time or 20 ms
Measuring mode
Operation hysteresis
Operation accuracy
Start time:
-injected voltages
- internal time
- total time
Reset time
Reset ratio
Retardation time
Operate time accuracy at DT mode
Accuracy class index E at IDMT mode,
typically
28
0.101.60 x Un
0.05300.0 s
0.051.00
Not in use
Definite time
A curve
B curve
Phase-to-phase voltages; peak-to-peak measurement
Phase-to-phase voltages; fundamental freq. measurement
Phase-to-earth voltages; fundamental freq. measurement
1.0...5.0%
Note! The values below apply when f/fn = 0.95...1.05
2.5% of set value
= 1.1 x start voltage
<42 ms
<50 ms
40...1000 ms (depends on the minimum pulse width set for
the trip output)
0.96 (range 0.95...0.99)
< 50 ms
2% of set value or 20 ms
20 ms
Transformer Terminal
Operation hysteresis
Operation accuracy
Start time:
- injected voltages
- internal time
- total time
Reset time
Reset ratio
Retardation time
Operate time accuracy at DT mode
0.101.60 x Un
0.05300.0 s
Not in use
Definite time
Phase-to-phase voltages; peak-to-peak measurement
Phase-to-phase voltages; fundamental freq. measurement
Phase-to-earth voltages; fundamental freq. measurement
1.0...5.0%
Note! The values below apply when f/fn = 0.95...1.05
2.5% of set value
= 1.1 x start voltage
<42 ms
<50 ms
40...1000 ms (depends on the minimum pulse width set for
the trip output)
0.96 (range 0.95...0.99)
< 50 ms
2% of set value or 20 ms
Measuring mode
Operation hysteresis
Operation accuracy
Start time:
- injected voltages
- internal time
- total time
Reset time
Reset ratio
Retardation time
Operate time accuracy at DT mode
Accuracy class index E at IDMT mode,
typically
0.101.20 x Un
0.1300.0 s
0.11.0
Not in use
Definite time
C curve
Phase-to-phase voltages; peak-to-peak measurement
Phase-to-phase voltages; fundamental freq. measurement
Phase-to-earth voltages; fundamental freq. measurement
1.0...5.0%
Note! The values below apply when f/fn = 0.95...1.05
2.5% of set value or 0.01 x Un
<0.5 x start voltage:
<32 ms
<40 ms
40...1000 ms (depends on the minimum pulse width set for
the trip output)
1.04 (range 1.01...1.05)
< 60 ms
2.5% of set value
35 ms
29
Transformer Terminal
Operation hysteresis
Operation accuracy
Start time:
- injected voltages
- internal time
- total time
Reset time
Reset ratio
Retardation time
Operate time accuracy at DT mode
0.101.20 x Un
0.1300.0 s
Not in use
Definite time
Phase-to-phase voltages; peak-to-peak measurement
Phase-to-phase voltages; fundamental freq. measurement
Phase-to-earth voltages; fundamental freq. measurement
1.0...5.0%
Note! The values below apply when f/fn = 0.95...1.05
2.5% of set value or 0.01 x Un
<0.5 x start voltage:
<32 ms
<40 ms
40...1000 ms (depends on the minimum pulse width set for
the trip output)
1.04 (range 1.01...1.05)
<60 ms
2.5% of set value
Retardation time
Operate time accuracy
30
0.011.00 x Un
0.011.20 x Un
0.801.60 x Un
0.0460.00 s
0.0460.00 s
0.0460.00 s
Not in use; U1< & U2> & U1>; U1< & U2>; U2> & U1>;
U1< & U1>; U2>; U1<; U1>
Forward; Reverse; Input ROT_DIR
Note! The values below apply when f/fn = 0.95...1.05
2.5% of set value or 0.01 x Un
= 1.1 x start value
<42 ms
<50 ms
= 0.50 x start value
<32 ms
<40 ms
= 1.1 x start value
<42 ms
<50 ms
70...1030 ms (depends on the minimum pulse width
set for the TRIP output)
U2> operation: 0.96
U1< operation: 1.04
U1> operation: 0.99
<45 ms (for all operations)
2% of set value or 20 ms
Transformer Terminal
Not in use
f</f> 1 timer
f</f> 2 timers
f</f> OR df/dt>
f</f> AND df/dt>
f</f> OR df/dt<
f</f> AND df/dt<
0.300.90 x Un
25.0075.00 Hz
0.10120.00 s
0.210.0 Hz/s
0.12120.00 s
Under-/overfrequency (f</f>): 10 mHz
<5 Hz/s: 100 mHz/s
<15 Hz/s: 2.0% of real df/dt
1.0% of set value
<100 ms
<120 ms
140...1000 ms (depends on the minimum pulse width set
for the trip output)
2% of set value or 30 ms
Overexcitation protection, low-set stage, OE1Low, U/f>, and high-set stage, OE1High, U/f>>
U/f start (DT mode)
U/f start (IDMT mode)
U max cont.
Operate time
k
Maximum time
Constant delay
Cooling time
Operation mode
1.00...2.00 x U/f
1.00...2.00 x U/f
0.80...1.60 x Un
0.10...600.00 s
0.1...100.0
500...10000 s
0.1...120.0 s
5...10000 s
Not in use; Definite time; Curve#1; Curve#2
Operation accuracies
Start time:
- Injected U/f
- internal time
- total time
Reset time
Reset ratio:
- 20...40 Hz
- 40...80 Hz
Retardation time
Operate time accuracy at definite-time mode
Operate time accuracy at inverse-time modes
>2.0 x Un/fn
<60 ms,
<70 ms
1001060 ms (depends on the set minimum pulse width
for the TRIP output)
typ. 0.99
typ 0.97
<105 ms
20...80 Hz: 4% of set value or 40 ms
100 ms or the accuracy appearing when the measured
voltage varies 1.0%
31
Transformer Terminal
Three-phase transformer inrush and motor start-up current detector Inrush3, 3I2f>
Ratio I2f/I1f>
Start current
Operation mode
550%
0.105.00 x In
Not in use
Inrush mode
Start-up mode
Note! The values below apply when f/fn = 0.95...1.05
Operation accuracy:
- current measurement
- ratio I2f/I1f measurement
Start time:
- internal time
- total time
10...50%
10...50%
Operation accuracy:
- when f/fn = 0.98...1.02:
- when f/fn = 0.95...1.05:
- injected negative-sequence voltage
BSOUT activation time:
- f/fn=0.98...1.02
Reset time
Reset ratio:
- for Ratio U2/U1>
- for Ratio I2/I1<
2.0 percentage units (of settings Ratio U2/U1> and Ratio I2/I1<)
4.0 percentage units (of settings Ratio U2/U1> and Ratio I2/I1<)
= 2.00 x Ratio U2/U1>
< 35 ms (within the same task and when the task interval is 10 ms)
20 ms (within the same task)
0.8...0.96
1.04...1.2
50.0/60.0 Hz
rated current
1 A/5 A
thermal withstand
capability
Voltage inputs
continuously
4 A/20 A
for 1 s
100 A/500 A
250 A/1250 A
input impedance
<100 m/<20 m
2 x Un (240 V)
<0.5 VA
PS1/240V
(RET 541,
RET 543)
PS2/240V
(RET 545
only)
Input voltage, ac
110/120/220/240 V
Input voltage, dc
110/125/220 V
24/48/60 V
Voltage variation
ac 85110%, dc 80120%
of rated value
Burden
<50 W
32
+78C (+75+83C)
External
display
module
PS1/48V
(RET 541,
RET 543)
PS2/48V
(RET 545
only)
Transformer Terminal
PS1/240 V (High)
PS1/240 V (Medium),
PS2/240 V
PS1/48 V (Low),
PS2/48V
Input voltage, dc
220 V
110/125/220 V
24/48/60/110/125/
220 V
155 V
155265 V
80 V
80...265 V
18 V
18...265 V
Current drain
~225 mA
Power consumption/input
<0.8 W
100 Platinum
250 Platinum
TCR 0.00385
1000 Platinum
TCR 0.00385
100 Nickel
120 Nickel
TCR 0.00618
250 Nickel
TCR 0.00618
1000 Nickel
TCR 0.00618
10 Copper
TCR 0.00427
120 Nickel
Isolation
Sampling frequency
5 Hz
Response time
0...20 mA
Accuracy
Max load
600
Isolation
Response time
85 ms
250 V ac/dc
Continuous carry
5A
10 A
8A
33
Transformer Terminal
250 V ac/dc
Continuous carry
5A
30 A
15 A
20265 V ac/dc
-10+55C
-40+70C
IP 54
IP 20
Mechanical tests
Dielectric test
IEC 60255-5
Test voltage
Test voltage
Insulation resistance
measurements
IEC 60255-5
Insulation resistance
Seismic test
34
2.5 kV
6 kV
8 kV
radiated, amplitude-modulated
IEC 61000-4-3
10 V/m (rms),
f = 801000 MHz
radiated, pulse-modulated
ENV 50204
f = 77.2 MHz, P = 6 W;
f = 172.25 MHz, P = 5 W
1.0 kV
Transformer Terminal
power supply
4 kV
I/O ports
2 kV
power supply
I/O ports
30%, 10 ms
>90%, 5000 ms
EN 55011, class A
radiated RF emission
EN 55011, class A
CE approval
RS-232 connection
the fibre-optic interface module RER 123 for SPA and IEC_103
protocol
SPA, IEC_103
RS-485 connection
the RS-485 interface module RER 133 for DNP 3.0 and Modbus
protocol
RS-485 connection
LON bus or SPA bus, selectable
the fibre-optic interface module RER 103 is needed for galvanic
isolation
protocol
SPA, LON
RJ45 connection
galvanically isolated RJ45 connection for an external display module
communication cable
Front panel
1MRS 120511.001 (1 m)
1MRS 120511.003 (3 m)
optical connection
protocol
SPA
1MRS 120511.001 (1 m)
baud rates
4.8/9.6/19.2 kbps
start bits
data bits
parity
even
stop bits
LON protocol
bit rates
IEC_103 protocol
baud rates
9.6/19.2 kbps
data bits
parity
even
stop bits
bit rates
data bits
stop bits
1, 2
parity
SPA protocol
DNP 3.0
35
Transformer Terminal
bit rates
data bits
5, 6, 7, 8
stop bits
1, 2
parity
CAP 501
CAP 505
LNT 505
Event recording
Data recording
Protection functions
Control functions
Condition monitoring functions
Measurement functions
Self-supervision
RAMs
ROMs
EEPROMs
all analog reference voltages
automatic test sequences for I/Os and HMI modules
output contact condition monitoring (all contacts)
Mechanical dimensions
36
~8 kg
Width: 223.7 mm
Height: 265.9 mm
Depth: 74 mm
Transformer Terminal
Ordering
RET54_AB230AAAA
A = fixed display, B = external display module
Reserved for future use
Reserved for future use
Auxiliary voltage range of the power supply module and
voltage range of the digital inputs
A: power supply:
PS1/240 V (Medium) or PS2/240 V
Ur = 110/120/220/240 V AC;
110/125/220 V DC
digital inputs:
Ur = 110/125/220 V DC
threshold voltage:
Ut = 80 V DC
B: power supply:
PS1/240 V (High) or PS2/240 V
Ur = 110/120/220/240 V AC;
110/125/220 V DC
digital inputs:
Ur = 220 V DC
threshold voltage:
Ut = 155 V DC
C: power supply:
PS1/48 V (Low) or PS2/48 V
Ur = 24/48/60 V DC
digital inputs:
Ur = 24/48/60/110/125/220 V DC
Hardware number: 230, 231, 232, 233, 234, 235,
240, 241, 242, 243, 244, 245,
250, 251, 252
Functionality level: C = Control, B = Basic, M = Multi
Software revision: A
Transformer terminal type: RET 541, RET 543, RET 545
ret54_ordernumber_
Fig. 5
Language combinations
Suffix
Language combination
001
English-German
002
English-Swedish
003
English-Finnish
007
English-Portuguese
008
English-Polish
009
English-Russian
010
English-Spanish
The RET 541, RET 543 and RET 545 transformer terminals differ from each other as to
Number of inputs/outputs
Digital inputs
Trip circuit supervision inputs
Power outputs (NO single-pole)
Power outputs (NO double-pole)
Signal outputs (NO)
Signal outputs (NO/NC)
Self-supervision outputs
RET 541
15
2
0
5
2
5
1
25
2
2
9
2
5
1
RET 545
34
2
3
11
4
8
1
37
Transformer Terminal
Functionality levels
Functionality level
C (Control)
B (Basic)
M (Multi)
1) The COLTC Tap Changer control function block comes as standard in the Control version. In the Basic and the Multi
versions, COLTC is available as an option.
87T
3I >, 3I >>
51
50 / 51 / 51B
50 / 51B
3I >
3I >>
3I >>>
67
67
67
21G
21G
3I > ->
3I >> ->
3I >>> ->
Z<
Z<<
51N
50N / 51N
50N
67N / 51N
67N
67N
59N
59N
59N
87N
87N
87N
Io > / SEF
Io >>
Io >>>
Io > / SEF ->
Io >> ->
Io >>> ->
Uo >
Uo >>
Uo >>>
Io >
Io >
Io >, REF
49T
46
46
3
I2 >
I2 >>
59
59
27
27
47
47
3U >
3U >>
3U <
3U <<
U1< & U2> & U1>
U1< & U2> & U1>
81U / 81O
81U / 81O
81U / 81O
81U / 81O
81U / 81O
24
24
68
60
62BF
f</
f</
f</
f</
f</
f > / df/dt
f > / df/dt
f > / df/dt
f > / df/dt
f > / df/dt
U/f>
U/f>>
3I2f >
FUSEF
CBFP
3I
3I
Io
Io
3U
3U
Uo
Uo
E / P / Q / pf
f
38
Code
Diff6T
NOC3Low
NOC3High
NOC3Inst
NOC3LowB
DOC6Low
DOC6High
DOC6Inst
UI6Low
UI6High
REF541/3/5
MULTI
IEC Symbol
RET541/3/5
BASIC
IEEE Code
RET541/3/5
CONTROL
FUNCTIONALITY LEVELS
X
X
NEF1Low
NEF1High
NEF1Inst
DEF2Low
DEF2High
DEF2Inst
ROV1Low
ROV1High
ROV1Inst
REF4A
REF4B
REF1A
TOL3Dev
NPS3Low
NPS3High
X
X
X
X
OV3Low
OV3High
UV3Low
UV3High
PSV3St1
PSV3St2
X
X
X
Freq1St1
Freq1St2
Freq1St3
Freq1St4
Freq1St5
OE1Low
OE1High
Inrush3
FuseFail
-
MECU3A
MECU3B
MECU1A
MECU1B
MEVO3A
MEVO3B
MEVO1A
MEVO1B
X
X
X
X
X
MEPE7
MEFR1
MEDREC16
MEAI18
MEAO14
Transformer Terminal
IEC Symbol
CBCM
CBCM
CBCM
CBCM
CBCM
CBCM
CBCM
CBCM
CBCM
TCS
TCS
MCS
MCS
Code
CMBWEAR1
CMBWEAR2
CMTIME1
CMTIME2
CMGAS1
CMGAS3
CMSPRC1
CMTRAV1
CMSCHED
CMTCS1
CMTCS2
CMCU3
CMVO3
COCB1...2
CODC15
CO3DC1...2
COIND18
MMIDATA15
MMIALAR18
COSW14
COCBDIR
COLOCAT
INDRESET
MMIWAKE
SWGRP1....20
EVENT230
-
Options
Dual HMI language, desired language combination must be stated in the purchase order
On-load tap changer controller (voltage regulator), to be ordered as a
COLTC
separate item (1MRS 100144)
RET54_ Functionality2.xls
39
Transformer Terminal
RET541A_230CAAA
RET541A_230AAAB
RET541A_230BAAB
RET541A_233AAAA
RET541A_233BAAA
RET541A_233CAAA
RET541A_233AAAB
RET541A_233BAAB
Order number
RET541A_230AAAA
HW modules
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
Analog interface
Current rafo 1/5 A
Voltage trafo 100 V
Main processor boards
CPU module
Power supply boards
1
1
1
1
1
1
1
1
1 1
Display boards
Graphic HMI display, fixed
Mechanic
1/2 enclosure
15
15
IRF outputs
RTD/analog inputs
Analog outputs
Digital inputs
40
Transformer Terminal
RET541A_231CAAA
RET541A_231AAAB
RET541A_231BAAB
RET541A_234AAAA
RET541A_234BAAA
RET541A_234CAAA
RET541A_234AAAB
RET541A_234BAAB
Order number
RET541A_231AAAA
HW modules
7
2
7
2
7
2
7
2
7
2
7
2
Analog interface
Current trafo 1/5 A
Voltage trafo 100 V
Main processor boards
CPU module
Power supply boards
1
1
1
1
1
1
Display boards
Graphic HMI display, fixed
Mechanic
1/2 enclosure
15
15
IRF outputs
RTD/analog inputs
Analog outputs
Digital inputs
41
Transformer Terminal
RET541A_232CAAA
RET541A_232AAAB
RET541A_232BAAB
RET541A_235AAAA
RET541A_235BAAA
RET541A_235CAAA
RET541A_235AAAB
RET541A_235BAAB
Order number
RET541A_232AAAA
HW modules
8
1
8
1
8
1
8
1
8
1
8
1
8
1
8
1
8
1
8
1
Analog interface
Current rafo 1/5 A
Voltage trafo 100 V
Main processor boards
CPU module
Power supply boards
1
1
1
1
1
1
1
1
Display boards
Graphic HMI display, fixed
Mechanic
1/2 enclosure
15
15
IRF outputs
RTD/analog inputs
Analog outputs
Digital inputs
42
Transformer Terminal
RET543A_240CAAA
RET543A_240AAAB
RET543A_240BAAB
RET543A_243AAAA
RET543A_243BAAA
RET543A_243CAAA
RET543A_243AAAB
RET543A_243BAAB
Order number
RET543A_240AAAA
HW modules
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
Analog interface
Current trafo 1/5 A
Voltage trafo 100 V
Main processor boards
CPU module
Power supply boards
1
1
1
1
1
1
1
Display boards
Graphic HMI display, fixed
Mechanic
1/2 enclosure
25
25
IRF outputs
RTD/analog inputs
Analog outputs
Digital inputs
43
Transformer Terminal
RET543A_241CAAA
RET543A_241AAAB
RET543A_241BAAB
RET543A_244AAAA
RET543A_244BAAA
RET543A_244CAAA
RET543A_244AAAB
RET543A_244BAAB
Order number
RET543A_241AAAA
HW modules
7
2
7
2
7
2
7
2
7
2
7
2
7
2
7
2
7
2
7
2
Analog interface
Current trafo 1/5 A
Voltage trafo 100 V
Main processor boards
CPU module
Power supply boards
1
1
1
1
1
1
1
Display boards
Graphic HMI display, fixed
Mechanic
1/2 enclosure
25
25
IRF outputs
RTD/analog inputs
Analog outputs
Digital inputs
44
Transformer Terminal
RET543A_242CAAA
RET543A_242AAAB
RET543A_242BAAB
RET543A_245AAAA
RET543A_245BAAA
RET543A_245CAAA
RET543A_245AAAB
RET543A_245BAAB
Order number
RET543A_242AAAA
HW modules
8
1
8
1
8
1
8
1
8
1
8
1
8
1
8
1
Analog interface
Current trafo 1/5 A
Voltage trafo 100 V
Main processor boards
CPU module
Power supply boards
1
1
1
1
Display boards
Graphic HMI display, fixed
Mechanic
1/2 enclosure
25
25
IRF outputs
RTD/analog inputs
Analog outputs
Digital inputs
45
Transformer Terminal
RET545A_250CAAA
RET545A_250AAAB
RET545A_250BAAB
Order number
RET545A_250AAAA
HW modules
6
3
6
3
6
3
6
3
6
3
Analog interface
Current trafo 1/5 A
Voltage trafo 100 V
Main processor boards
CPU module
Power supply boards
PS1: 80...265 VDC/AC (High)
PS1: 80...265 VDC/AC (Medium)
PS1: 18...80 VDC/AC (Low)
PS2: 80...265 VDC
2
2
1
1
Mechanic
1/2 enclosure
Digital inputs
46
34
11
IRF outputs
RTD/analog inputs
Analog outputs
Transformer Terminal
RET545A_251CAAA
RET545A_251AAAB
RET545A_251BAAB
Order number
RET545A_251AAAA
HW modules
7
2
7
2
7
2
7
2
7
2
Analog interface
Current trafo 1/5 A
Voltage trafo 100 V
Main processor boards
CPU module
Power supply boards
PS1: 80...265 VDC/AC (High)
PS1: 80...265 VDC/AC (Medium)
PS1: 18...80 VDC/AC (Low)
PS2: 80...265 VDC
2
2
1
1
Mechanic
1/2 enclosure
Digital inputs
1
34
11
IRF outputs
RTD/analog inputs
Analog outputs
47
Transformer Terminal
RET545A_252CAAA
RET545A_252AAAB
RET545A_252BAAB
Order number
RET545A_252AAAA
HW modules
8
1
8
1
8
1
8
1
8
1
Analog interface
Current trafo 1/5 A
Voltage trafo 100 V
Main processor boards
CPU module
Power supply boards
PS1: 80...265 VDC/AC (High)
PS1: 80...265 VDC/AC (Medium)
PS1: 18...80 VDC/AC (Low)
PS2: 80...265 VDC
2
2
1
1
Mechanic
1/2 enclosure
Digital inputs
48
1
34
11
IRF outputs
RTD/analog inputs
Analog outputs
Transformer Terminal
Software configuration
Parts and
assembly
descriptions
To achieve the best possible operation accuracy, all parts of a RET 54_ product have
been calibrated together. Thus, each product
forms a whole for which no separate spare
parts can be supplied. In the event of malfunction, please consult your transformer terminal supplier.
49
Transformer Terminal
RET/1U
Application
examples
MF
RET/4I
Q
p>
3DI>
87TG
3I>
HV
51
50
3
HV
49T
3I>
LV
51
50
I2>
46
I0>
HV
51N
50N
3I2f>
68
CBFP 62BF
LV
RET/RTD
RET 54_
RET/1U
3I>
51
50
CBFP 62BF
REF/3I, REA 101/3I
RET/31
CBFP 62BF
HV
3U>
59
3U<
27
U0>
59N
000
000
3I
Io
P
3I
TO
Tw
R
TCS
CBCM
000
3I>
&
3I
R
3U
TCS
REA 101
MF
REF/3U
REF/1U
REF 54_
Yd transformer
Fig. 6
50
Transformer Terminal
MF
RET/3I
REF/4I
p>
RET/1I
REF/1I
RET/RTD
3DI>
87T
3I>
HV
51
50
DI0>
LV
87TN
3I>
LV
51
50
49T
I 0>
HV
51N
50N
I2>
HV
46
I0>
LV
51N
50N
3I2f >
HV
68
CBFP 62BF
HV
I0
3I
3I
I0
o
TO
Tw
TCS
U
CBFP 62BF
LV
RET 54_
000
000
3I>
51
50
I0>
51N
50N
LO
86
3I
I0
000
TCS
CBFP 62BF
REF 610
90
RET/1U
REF/3U
REF/3I
3I>
51
50
3U>
59
I0>
51N
50N
3U<
27
RET/3I
CBFP 62BF
000
3I
I0
R
3U
P
TCS
REF 54_
MF
Dyn-trafo_impEarthedLVn
Fig. 7
Protection, control, measurement and supervision functions of an Dyn-connected power transformer, implemented with RET 543 transformer terminal and an REF 543 feeder terminal. The
neutral point of the low-voltage network is earthed via a high impedance. REF 610 is used as a
backup relay on the high-voltage side. This sceme can be applied also for parallel connected
transformers.
51
Transformer Terminal
REF/3U
REF/3U
MF
3I>
51
50
3U>
59
3I 2f >
68
3U<
27
I 0>
51N
50N
RET/3I
000
I0
3I
3U
TCS
CBFP 62BF
REF/3I
REF 54_
RET/1I
REF/1I
P>
M
RET/1U
REF/1I
3I>
HV
51
50
I0>
HV
87TN
3I>
LV
51
50
3I
I0
I0>
LV
87TN
I 0>
HV
51N
50N
3I
49T
I 0>
LV
51N
50N
3I 2f >
HV
68
RET/3I
I0
TO
Tw
CBFP 62BF
LV
67
3U>
59
I 0>
51N
50N
3U<
27
CBFP 62BF
f>
81O
df/dt 81O-R
TCS
U
CBFP 62BF
HV
3I>
REF,REA/3I
RET/1I
000
87T
RET 54_
M
000
3I>
90
000
3I>
&
3I
I0
3U
pf
Q
3I-harm
R
TCS
REA 101
REF/3U
REF/3U
3U-harm
REF 54_
MF
M
YNd transformer with earthing transformer on LV side
Fig. 8
52
Protection, control, measurement and supervision functions of a YNd-connected power transformer, implemented with an RET 543 transformer terminal, REF 543 feeder terminals and REA
101 arc protection. The low-voltage network is earthed via a zig-zag earthing transformer.
Transformer Terminal
MF
REF/3U
REF/3U
3I>
51
50
3U>
59
3I 2f >
68
3U<
27
I0>
51N
50N
RET/3I
REF/3I
000
3I
I0
R
3U
TCS
CBFP 62BF
REF 54_
REF/1I
P>
RET/RTD
3I>
HV
51
50
I0 > 87TN
HV
3I>
LV
51
50
3I
I0
I0>
LV
87TN
I0>
HV
51N
50N
3I
49T
I0>
LV
51N
50N
3I 2f >
HV
68
I0
REF/1I
RET/1I
TO
Tw
REF/3U
RET/1U
3I>
67
3U>
59
I0>
51N
50N
3U<
27
TCS
U
CBFP 62BF
LV
CBFP 62BF
HV
RET 54_
REF, REA/3I
000
000
3I > 87T
RET/1I
90
000
3I>
&
RET/3I
MF
CBFP 62BF
REF 54_
f>
81O
df/dt 81O-R
3I
I0
3U
pf
R
TCS
REA 101
CBCM
E
MCS
Fig. 9
Protection, control, measurement and supervision functions of YNyn-connected power transformers, implemented with RET 543 transformer terminals, REF 543 feeder terminals and REA 101 arc
protection. The neutral point of the low-voltage network is earthed via a low resistance. The
scheme is also applicable to other types of low-impedance earthed networks, where the neutral
point is earthed effectively or via a low reactance. This sceme can be applied also for parallel connected transformers.
53
Transformer Terminal
3U<
27
3U>
59
U0 >
59N
3U
U0
000
RET/2U (Multi)
REX/3U
REX/1U
MF
CBCM
R
TCS
RET/4I (Basic)
MCS
RET/3I (Multi)
Q
p>
RET/1I (Basic)
REF/1I
81O
81O-R
f<
df/dt
81U
81U-R
U/f>
24
CBFP 62BF
HV
Z<
21
CBFP 62BF
LV
U<
27
I0>
HV
51N
50N
3I
I0
DI0 >
LV
87TN
I0>
LV
51N
50N
3I
I0
3I>
HV
51
50
49T
3I>
LV
51
50
3I2f >
HV
68
000
R
TCS
U
f
TO
TTC
U
U
3I>
51
50
3U>
59
I0>
51N
50N
3U<
27
CBFP 62BF
U0>
59N
000
3I
3U
3I>
&
I0
R
TCS
REA 101
REF/3U
RET/3I (Basic)
000
000
RET/1U (Multi)
MF
f>
df/dt
REF 54_
Yyn-trafo_highresEarthedLV
Fig. 10
54
Transformer Terminal
MF
REX521/1U
REX521/3U
1MRS755543
RET_/3I
3DI>
87TG
3I>
HV
51
50
DI0>
LV
87TN
3I>
LV
51
50
3I
I0
49T
I0>
HV
51N
50N
3I
I0>
LV
51N
50N
I2>
HV
46
CBFP 62BF
HV
RET_/1I
000
R
TCS
I0
o
Q
P>
REM_/3I
REM_/3U
REM_/1U
G
3~
REM/RTD
REM_/3I
RET_/3I
27
3U>
59
U0>
59N
f>
81U
TO
Tw
3U
U0
000
f
CBCM
R
TCS
MCS
RET 54_
3U<
000
3DI>
87G
X<
40
3I>
51
50
P>
32
3I
I(U)>
51V
I2>
46
I0>
50N
51N
49G
U0
pf
TCS
MCS
3U>
59
3U<
27
U 0>
59N
f
F
60
Q>
49
38
CBFP 62BF
REM 54_
gener_blockconn-trafo1
Fig. 11
Transformer in block connection with a generator. The transformer terminal RET 543 is used for
overall differential protection. An earthing resistor is recommended for the generator. The REX 521
protection relay is used for abnormal voltage and frequency supervision and protection of the network and the machine.
55
Transformer Terminal
3DI> 87TG
MF
RET_/3I
RET_/1U
RET_/1U
51
3I>
HV
50
000
DI0 >
LV
87TN
3I>
LV
51
50
3I
49T
I0>
HV
51N
50N
3I
46
I0>
LV
51N
50N
U>
59N
I2>
HV
RET_/1I
I0
R
U
TCS
I0
o
TO
Tw
CBFP 62BF
RET 54_
P>
REM_/3I (A)
REM_/3I (B)
REM_/2U(A)/3U(B)
REM_/1U (A)
3DI>
87G
f>/f<
81O
81U
Ios>
64S
X<
40
P>
32
I>
2
46
CBFP 62BF
000
3I
pf
R
TCS
MCS
G
3~
REM_/3I (A)
RET_/3I
REK 510
REM/I0R
(B)
REM_/1I (A)
51
50
P>
32
Z<
21G
49G
3I
U/f>
24
60
3U
IOR >
64R
3U>
59
U0
pf
3U<
27
CBFP 62BF
U0 >
59N
000
R
TCS
MCS
f
E
Fig. 12
56
Transformer in block connection with a generator. The transformer terminal RET 543 is used for
overall differential protection. An earthing resistor is recommended for the generator. Generator
protection functions are divided for two REM 543 machine terminals (A and B). The current injection device REK 510 is used in the rotor earth-fault protection scheme.
Transformer Terminal
3I >
3I>
I0>
50/51
67
I2 >
46
3I2f >
68
= inrush detection based on the 2nd harmonic content of phase currents, applied for
preventing possible unnecessary operation of overcurrent or earth-fault protection
during transformer switching-in or to start cold load pick-up logic (Inrush3_)
3D I >
87T
3D I >
87TG
= overall differential protection for generator and transformer blocks, stabilized and
instantaneous stages (Diff6T)
DI0>
87TN
I(U)>
51V
I 0S>
64S
I 0R>
64R
U/f
24
U<
27
3U <
27
3U >
59
U0>
59N
f>
81U
f>
df/dt
81U
= overfrequency protection and frequency rate of change function (incl. in Freq1St_)
81U-R
f<
df/dt
81O
= underfrequency protection and frequency rate of change function (incl. in Freq1St_)
81O-R
f>/f<
81O
81U
49G
49T
Q>
49
38
= thermal supervision for generator windings and bearings with RTDs (MEAI_)
62BF
CBFP
SYMNOT1_RET
Fig. 13
57
Transformer Terminal
Z<
21G
3Z<
21
X<
40
P>
32
60
3I >
&
MCS
TCS
CBCM
90V
3I
3U
pf
I0
U0
Fig. 14
58
Transformer Terminal
oT
oT
oT
TC
oT
E
3I-harm
3U-harm
000
= HMI/MIMIC display
000
Fig. 15
59
Transformer Terminal
Application selection tables for RET 541, RET 543 and RET 545
functions
Table 30: Protection functions
Types of fault
IEC Symbol
Protection function
Function block
code
Differential
protection
87T
3I>, 3I>>
Stabilized and
instantaneous differential
protection for
transformers
Diff6T
51
3I>
NOC3Low
51
3I>
NOC3LowB
50/51/51B
3I>>
NOC3High
50/51B
3I>>>
NOC3Inst
67
3I>
Three-phase directional
o/c, low-set stage
DOC6Low
67
3I>>
Three-phase directional
o/c, high-set stage
DOC6High
67
3I>>>
Three-phase directional
o/c, instantaneous stage
DOC6Inst
21
Z<
Three-phase
underimpedance,low-set
stage
UI6Low
21
Z<<
Three-phase
underimpedance, highset stage
UI6High
51N
Io>/SEF
NEF1Low
50N/51N
Io>>
NEF1High
50N
Io>>>
Non-directional earthNEF1Inst
fault, instantaneous stage
67N/51N
Io>/SEF
Directional earth-fault,
low-set stage (or SEF =
sensitive earth-fault
protection)
DEF2Low
67N
Io>>
Directional earth-fault,
high-set stage
DEF2High
67N
Io>>>
Directional earth-fault,
instantaneous stage
DEF2Inst
59N
Uo>
Residual overvoltage,
low-set stage
ROV1Low
59N
Uo>>
Residual overvoltage,
high-set stage
ROV1High
59N
Uo>>>
Residual overvoltage,
instantaneous stage
ROV1Inst
87N
Io>
High-impedance based
restricted earth-fault
protection
REF1A
Underimpedance
Earth fault
60
Transformer Terminal
IEC Symbol
Protection function
Function block
code
Earth-fault
87TN
Io>
Stabilized restricted
earth-fault protection
REF4A
87TN
Io>
Stabilized restricted
earth-fault protection
REF4B
Overload
49M/49G/49T
Three-phase thermal
protection for devices
(motors, generators and
transformers)
TOL3Dev
Negative phaseseguence
46
I2 >
NPS3Low
46
I2>>
NPS3High
59
3U>
Three-phase
overvoltage, low-set
stage
OV3Low
59
3U>>
Three-phase
overvoltage, high-set
stage
OV3High
27
3U<
Three-phase
undervoltage, low-set
stage
UV3Low
27
3U<<
Three-phase
undervoltage, high-set
stage
UV3High
27, 47, 59
U1<
U2>
U1>
Phase-sequence voltage
protection, stage 1
PSV3St1
27, 47, 59
U1<
U2>
U1>
Phase-sequence voltage
protection, stage 2
PSV3St2
81U/81O
f</f>, df/dt
Underfrequency or
overfrequency, stage 1
(incl. rate of change)
Freq1St1
81U/81O
f</f>, df/dt
Underfrequency or
overfrequency, stage 2
(incl. rate of change)
Freq1St2
81U/81O
f</f>, df/dt
Underfrequency or
overfrequency, stage 3
(incl. rate of change)
Freq1St3
81U/81O
f</f>, df/dt
Underfrequency or
overfrequency, stage 4
(incl. rate of change)
Freq1St4
81U/81O
f</f>, df/dt
Underfrequency or
overfrequency, stage 5
(incl. rate of change)
Freq1St5
24
U/f>
24
U/f>>
68
3I2f>
60
FUSEF
Overvoltage/
undervoltage
Overfrequency/
underfrequency
Overexcitation
Additional functions
FuseFail
61
Transformer Terminal
IEC Symbol
Measurement function
General measurement/
analog input or analog
output
mA/V/C/
General measurement/
analog input on
RTD/analog module
MEAI1...8
mA
Analog output on
RTD/analog module
MEAO1...4
3I
Three-phase current
measurement, stage A
MECU3A
3I
Three-phase current
measurement, stage B
MECU3B
Io
Neutral current
measurement, stage A
MECU1A
Io
Neutral current
measurement, stage B
MECU1B
3U
Three-phase voltage
measurement, stage A
MEVO3A
3U
Three-phase voltage
measurement, stage B
MEVO3B
Uo
Residual voltage
measurement, stage A
MEVO1A
Uo
Residual voltage
measurement, stage B
MEVO1B
Energy / Power
E, P, Q, pf
MEPE7
Frequency
System frequency
measurement
MEFR1
Transient disturbance
recorder
MEDREC16
Control function
Current
Voltage
Recording
Symbol
Circuit breaker
0 1
0 1
0 1
Disconnector
0 1
0 1
0 1
62
COCBDIR
Disconnector 1...5
CODC1...CODC5
(2 state inputs / 2 control
outputs)
Three state disconnector CO3DC1
1 (3 state inputs/ 4 control
outputs)
Three-state disconnector CO3DC2
2 (3 state inputs/ 4 control
outputs)
Transformer Terminal
Symbol
Control function
COIND1...COIND8
COSW1...COSW4
COLOCAT
MMIDATA1...MMIDATA5
Alarm 1...8
(HMI, remote)
MMIALAR1...MMIALAR8
Symbol
Condition monitoring
function
Circuit breaker
CBCM
CB electric wear 1
CMBWEAR1
CBCM
CB electric wear 2
CMBWEAR2
CBCM
CMTIME1
CBCM
CMTIME2
CBCM
CBCM
CBCM
CBCM
CMTRAV1
CBCM
Scheduled maintenance
CMSCHED
TCS
TCS
MCS
Supervision function of
the energizing current
input circuit
CMCU3
MCS
Supervision function of
the energizing voltage
input circuit
CMVO3
Trip circuit
Measuring circuit
63
Transformer Terminal
References
Additional information
Transformer Terminal RET 54_ Technical Reference 1MRS755225
Manual, General
Technical Descriptions of Functions
Installation Manual
1MR 750526-MUM
Operators Manual
1MR 750500-MUM
1MRS750532-MUM
1MRS751143-MUM
1MRS750745-MUM
1MRS755163
Document
changes
64
Version Date
Changes
Table 7: Reset ratio of OV3Low and OV3High changed from 0.96 to 1.04
15.06.2005
ABB Oy
Distribution Automation
P.O. Box 699
FI-65101 Vaasa, FINLAND
Tel +358 10 22 11
Fax +358 10 224 1094
www.abb.com/substationautomation