Sie sind auf Seite 1von 60

Product Manual

KPMHP00511-09EN
Date: November 2009
Supersedes: --

Inverter air to Water Heat Pumps


McEnergy HPI Extension
SE (Standard Efficiency) 072.2 167.3
Cooling Capacity from 254 up to 583 kW
Heating Capacity from 270 up to 615 kW
Refrigerant: R-134a

McQuay is participating in the Eurovent Certification Programme.


Product are as listed in the Eurovent Directory of Certified
Products and on the web site www .eurovent-certification. com

Index
Features and advantages ................................................................................................................................................. 3
High part load efficiency ................................................................................................................................................. 3
Seasonal quietness ........................................................................................................................................................ 3
Quick comfort conditions ................................................................................................................................................ 3
Low starting current ........................................................................................................................................................ 3
Power factor always > 0.95 ............................................................................................................................................ 3
Redundancy ................................................................................................................................................................... 3
Infinitely capacity control ................................................................................................................................................ 3
Code requirements Safety and observant of laws/directives ....................................................................................... 4
Certifications................................................................................................................................................................... 4
Versions ......................................................................................................................................................................... 4
Noise Configuration ........................................................................................................................................................ 4
General characteristics..................................................................................................................................................... 5
Cabinet and structure ..................................................................................................................................................... 5
Screw compressors with integrated oil separator ........................................................................................................... 5
Ecological HFC 134a refrigerant..................................................................................................................................... 5
Evaporator ...................................................................................................................................................................... 5
Condenser coils.............................................................................................................................................................. 5
Condenser coil fans........................................................................................................................................................ 5
Electronic expansion valve ............................................................................................................................................. 5
Refrigerant Circuit........................................................................................................................................................... 5
Electrical control panel ................................................................................................................................................... 6
Standard accessories (supplied on basic unit) ............................................................................................................... 7
Options (on request)....................................................................................................................................................... 8
Nomenclature .................................................................................................................................................................... 9
Specifications McEnergy HPI Extension SE-ST........................................................................................................ 10
Specifications McEnergy HPI Extension SE-LN ....................................................................................................... 14
Sound Levels................................................................................................................................................................... 18
Cooling Mode - McEnergy HPI Extension SE ST....................................................................................................... 18
Cooling Mode - McEnergy HPI Extension SE LN....................................................................................................... 18
Heating Mode - McEnergy HPI Extension SE ST....................................................................................................... 19
Heating Mode - McEnergy HPI Extension SE LN....................................................................................................... 19
Sound pressure level correction factors for different distances - McEnergy HPI Extension SE ST/LN ...................... 19
Operating limits............................................................................................................................................................... 20
Water charge, flow and quality ..................................................................................................................................... 23
Water content in cooling circuits ................................................................................................................................... 24
Automatic and Manual Boost - Cooling Mode .............................................................................................................. 25
Automatic and Manual Boost - Heating Mode .............................................................................................................. 25
Heating Capacity correction factors for different evaporator inlet air temperature and relative humidity conditions ..... 26
Integrated Heating Capacity - Automatic Boost ............................................................................................................ 26
Integrated Heating Capacity - Manual Boost ................................................................................................................ 27
Standard ratings.............................................................................................................................................................. 28
Cooling Mode - McEnergy HPI Extension SE-ST....................................................................................................... 28
Cooling Mode - McEnergy HPI Extension SE-LN....................................................................................................... 31
Heating Mode - McEnergy HPI Extension SE-ST ...................................................................................................... 34
Heating Mode - McEnergy HPI Extension SE-LN ...................................................................................................... 38
Evaporator water pressure drops.................................................................................................................................. 42
Options............................................................................................................................................................................. 43
Dimensions McEnergy HPI Extension SE ST / LN .................................................................................................... 49
Installation notes............................................................................................................................................................. 50
Warning ........................................................................................................................................................................ 50
Handling ....................................................................................................................................................................... 50
Location........................................................................................................................................................................ 50
Space requirements ..................................................................................................................................................... 50
Acoustic protection ....................................................................................................................................................... 52
Storage......................................................................................................................................................................... 52
GENERAL .................................................................................................................................................................... 53
REFRIGERANT............................................................................................................................................................ 53
PERFORMANCE.......................................................................................................................................................... 53
UNIT DESCRIPTION.................................................................................................................................................... 53
NOISE LEVEL AND VIBRATIONS ............................................................................................................................... 54
DIMENSIONS............................................................................................................................................................... 54
HEAT PUMP COMPONENTS ...................................................................................................................................... 54

KPMHP00511-09EN page 2/60

Features and advantages


High part load efficiency
McEnergy HPI Extension is the result of careful design, aimed to optimizing the energy efficiency of the chillers, with
the objective of bringing down operating costs and improving installation profitability, effectiveness and economical
management.
Per European Seasonal Energy Efficiency Ratio (ESEER), chillers operate at design conditions only three percent of the
time. As a result better part load efficiencies are required at part load conditions in a heat pump application. McEnergy
HPI Extension maximizes chiller efficiency by optimizing single screw compressor operation dramatically reducing the
electric power consumption when the motor speed slows.

Seasonal quietness
Very low noise levels in part load conditions are achieved by varying the fan speed, but especially thanks to the variation
of compressor frequency, which ensure the minimum noise level at all the time.

Quick comfort conditions


The ability to vary the output power in direct relation to the cooling requirements of the system, allow the possibility to
achieve building comfort conditions much faster at start-up.

Low starting current


No current spikes at start-up. The starting current is always lower than current absorbed in the maximum operating
conditions (FLA).

Power factor always > 0.95


McEnergy HPI Extension can operate always > 0.95 power factor, which can allows building owners avoid power factor
penalties and decreases electrical losses in cable and transformers.

Redundancy
McEnergy HPI Extension has two or three truly independent refrigerant circuits in every size, in order to assure
maximum safety for any maintenance, whether planned or not.

Infinitely capacity control


Cooling capacity control is infinitely variable by means of a
Inverter driven screw compressor controlled by microprocessor
system. Each unit has infinitely variable capacity control from
100% down to 13,5% (two compressors units) and down to 7%
(three compressors). This modulation allows the compressor
capacity to exactly match the building cooling load without any
leaving evaporator water temperature fluctuation. This chilled
water temperature fluctuation is avoided only with a stepless
control.

Compressor Load

Building Load

tim e

ELWT fluctuation with steps capacity control (4 steps)

With a compressor load step control in fact, the compressor


capacity, at partial loads, will be too high or too low compared
to the building cooling load. The result is an increase in chiller
energy costs, particularly at the part-load conditions at which
the chiller operates most of the time.

Compressor Load

Building Load

Units with stepless regulation offer benefits that the units with step regulation are unable to match. The ability to follow
the system energy demand at any time and the possibility to provide steady outlet water temperature without deviations
from the set-point, are the two points that allow you to understand how the optimum operating conditions of a system can
be met only through the use of a unit with step-less regulation.

KPMHP00511-09EN page 3/60

Code requirements Safety and observant of laws/directives


All McEnergy HPI Extension units are designed and manufactured in accordance with applicable selections of the
following:

Rating of chillers
Construction of pressure vessel
Machinery Directive
Low Voltage
Electromagnetic Compatibility
Electrical & Safety codes
Manufacturing Quality Stds

EN 12055
97/23/EC (PED)
98/37/EC as modified
2006/95/EC
2004/108/EC
EN 602041 / EN 60335-2-40
UNI EN ISO 9001:2000

Certifications
All units manufactured by McQuay Italia S.p.A. are CE marked, complying with European directives in force, concerning
manufacturing and safety. On request units can be produced complying with laws in force in non European countries
(ASME, GOST, etc.), and with other applications, such as naval (RINA, etc.).

Versions
McEnergy HPI Extension is available in the following versions:
S: Standard Efficiency
13 sizes to cover a range from 254 up to 583 kW (Cooling Capacity) and from 270 up to 615 kW
(Heating Capacity), with an EER up to 2.87, an ESEER up to 4.29 and a COP up to 3.04.
The EER (Energy Efficiency Ratio) is the ratio of the Cooling Capacity to the Power Input of the
unit. The Power Input includes: the power input for operation of the compressor, the power input
of all control and safety devices, the power input for fans.
The COP (Coefficient of Performance) is the ratio of the heating capacity to the power input of the
unit.
The ESEER (European Seasonal Energy Efficiency Ratio) is a weighed formula enabling to take
into account the variation of EER with the load rate and the variation of air inlet condenser
temperature.
ESEER = A x EER100% + B x EER75% + C x EER50% + D x EER25%

Coefficient
Air inlet condenser temperature

0.03 (3%)
35C

0.33 (33%)
30C

0.41 (41%)
25C

0.23 (23%)
20C

Noise Configuration
McEnergy HPI Extension is available in two different noise level configurations:
ST: Standard Noise
Condenser fan rotating at 920 rpm, rubber antivibration on compressor
LN: Low Noise
Condenser fan rotating at 715 rpm (920 rpm in heating mode), rubber antivibration on
compressor, compressor sound enclosure.

KPMHP00511-09EN page 4/60

General characteristics
Cabinet and structure
The cabinet is made of galvanized steel sheet and painted to provide a high resistance to corrosion. Colour Ivory White
(Munsell code 5Y7.5/1) (RAL7044).The base frame has eye-hook for lifting the unit with ropes for an easy installation.
The weight is uniformly distributed along the profiles of the base and this facilitates the arrangement of the unit.

Screw compressors with integrated oil separator


The compressors are semi-hermetic, single-screw type with gate-rotor (made of carbon impregnated engineered
composite material). Each compressor has one inverter managed by the unit microprocessor for infinitely modulating the
capacity. An integrated high efficiency oil separator maximises the oil separation.
Start is inverter type.

Ecological HFC 134a refrigerant


The compressors have been designed to operate with R-134a, ecological refrigerant with zero ODP (Ozone Depletion
Potential) and very low GWP (Global Warming Potential) that means low TEWI (Total Equivalent Warming Impact).

Evaporator
The units are equipped with a Direct Expansion shell&tube evaporator with copper tubes rolled into steel tubesheets. The
evaporators are single-pass on both the refrigerant and water sides for pure counter-flow heat exchange and low
refrigerant pressure drops. Both attributes contribute to the heat exchanger effectiveness and total units outstanding
efficiency.
The external shell is covered with a 10mm closed cell insulation material. Each evaporator has 2 or 3 circuits, one for
each compressor and is manufactured in accordance to PED approval. The evaporator water outlet connections are
provided with Victaulic Kit (as standard).

Condenser coils
The condenser is manufactured with internally enhanced seamless copper tubes arranged in a staggered row pattern
and mechanically expanded into lanced and rippled aluminium condenser fins with full fin collars. An integral sub-cooler
circuit provides sub-cooling to effectively eliminate liquid flashing and increase in cooling capacity without increasing the
power input.

Condenser coil fans


The condenser fans are propeller type with high efficiency design blades to maximize performances. The material of the
blades is glass reinforced resin and each fan is protected by a guard. Fan motor is thermally protected (as standard) by
internal thermal motor and protected by circuit breaker installed inside the electrical panel as a standard. The motors are
IP54.

Electronic expansion valve


The unit is equipped with the most advanced electronic expansion valves to achieve precise control of refrigerant mass
flow. As todays system requires improved energy efficiency, tighter temperature control, wider range of operating
conditions and incorporate features like remote monitoring and diagnostics, the application of electronic expansion
valves becomes mandatory. Electronic expansion valve proposes features that make it unique: short opening and
closing time, high resolution, positive shut-off function to eliminate use of additional solenoid valve, continuous
modulation of mass flow without stress in the refrigerant circuit and corrosion resistance stainless steel body.
Electronic Expansion Valves are typically working with lower P between high and low pressure side, than a thermostatic
expansion valve. The electronic expansion valve allows the system to work with low condenser pressure (winter time)
without any refrigerant flow problems and with a perfect chilled water leaving temperature control.

Refrigerant Circuit
Each unit has 2 or 3 independent refrigerant circuits and each one includes:

Compressor with integrated oil separator

Air Cooled Condenser

Electronic expansion valve

Evaporator

Discharge line shut off valve

Liquid line shut off valve

Suction line shut off valve

Sight glass with moisture indicator

Filter drier

Charging valves

KPMHP00511-09EN page 5/60

High pressure switch


High and low pressure transducers

Electrical control panel


Power and control are located in two sections of the main panel that is manufactured to ensure protection against all
weather conditions. The electrical panel is IP54 and (when opening the doors) internally protected with Plexiglas panel
against possible accidental contact with electrical components (IP20). The main panel is fitted with a main switch
interlocked door.
Power Section
The power section includes circuit breaker, compressors inverters, fans contactors, fans thermal overload relays,
fans inverter and control circuit transformer.
MicroTech II controller
MicroTech II C Plus controller is installed as standard; it can be used to modify unit set-points and check control
parameters. A built-in display shows machine's operating status, programmable values, set-points, like temperatures
and pressures of water, refrigerant and air. Device controls maximise the chiller energy efficiency and the reliability.
A sophisticated software with predictive logic, select the most energy efficient combination of compressors, EEXV
and condenser fans to keep stable operating conditions and maximise energy efficiency. The compressors are
automatically rotated to ensure equal operating hours. MicroTech II C Plus protects critical components in response
to external signals from its system sensors measuring: motor temperatures, refrigerant gas and oil pressures,
correct phase sequence and evaporator.
Control section - main features

Management of the compressor capacity, Inverter, slide and fans modulation.

Chillers enabled to work in partial failure condition.

Full routine operation at condition of:

high ambient temperature value,

high thermal load,

high evaporator entering water temperature (start-up).

Display of evaporator entering/leaving water temperature.

Display of condensing-evaporating temperature and pressure, suction and discharge superheat for each
circuit.

Leaving water cooled temperature regulation. Temperature tolerance = 0,1C.

Compressors and evaporator pumps hours counter.

Display of Status Safety Devices.

Start up numbers and compressors working hours equalization.

Optimized management of compressors load.

Fans management according to condensing pressure.

Automatic re-start in case of power supply interruption (adjustable).

Soft Load.

Start at high evaporator water temperature.

Return Reset.

AOT Reset (optional).

Set point Reset (optional).

Safety device / logic for each refrigerant circuit

High pressure (pressure switch).

Low pressure (transducer).

Condensation fan Magneto-thermal.

High Discharge Temperature on the compressor.

Phase Monitor.

Low pressure ratio.

High oil pressure drop.

KPMHP00511-09EN page 6/60

Low oil pressure.

System security

Phase monitor.

Freeze protection.

Regulation type
Proportional + integral + derivative regulation on the leaving water evaporator output probe.
Condensing pressure
The condensation can be carried out according to temperature or pressure or pressure ratio. The fans can be
managed according to a 0/10 V modulating signal.
Intelligent Compressor Start Mode
Control software includes an intelligent compressor start mode that unloads the first compressor to 75% during
the start of the second one, in order to reduce inrush current.
MicroTech II C Plus terminal
MicroTech II C Plus built-in terminal has the following features.

4-lines by 20-character liquid crystal display back lighting.

Key-pad consisting of 6 keys.

Memory to protect the data.

General faults alarm relays.

Password access to modify the setting.

Service report displaying all running hours and general conditions.

Alarm history memory to allow an easy fault analysis.

Supervising systems (on request)


MicroTech II C Plus remote control
MicroTech II C Plus is able to communicate to BMS (Building Management System) based on the most
common protocols as:

CARELNative

ModbusRTU

LonWorks, now also based on the international 8040 Standard Chiller Profile and LonMark Technology

BacNet BTP certifief over IP and MS/TP (class 4)

Ethernet TCP/IP and SNM.

Standard accessories (supplied on basic unit)


Inverter compressor starter For low inrush current and reduced starting torque.
Double set-point Dual leaving water temperature set-points.
Fans thermal overload relays Safety devices against fan motor overloading in addition to the normal protection
envisaged by the electrical windings.
Phase monitor The phase monitor controls that phases sequence is correct and controls phase loss.
Evaporator Victaulic kit on water connection Hydraulic joint with gasket for an easy and quick water connection.
10mm evaporator insulation
Evaporator electric heater Electric heater controlled by a thermostat to protect the evaporator from freezing down to 28C ambient temperature, providing the power supply is on.
Electronic expansion valve
Discharge line shut off valves Installed on the discharge port of the compressor to facilitate maintenance operation.
Suction line shut off valve Installed on the suction port of the compressor to facilitate maintenance operation.
Low pressure side manometers
Compressor hour run meter

KPMHP00511-09EN page 7/60

General fault Alarm relay.


Main switch interlock door
Emergency stop
Fans circuit breakers Safety device against motor overloading and short circuit

Options (on request)


Partial heat recovery Produced with plate to plate heat exchangers installed between the compressor discharge and
the condenser coil, allowing to produce hot water.
Brine version Allows the unit to operate down to -8C leaving liquid temperature (antifreeze required).
Under/Over Voltage This device control the voltage value of power supply and stop the chiller if the value exceeds the
allowed operating limits.
Energy Meter This device allows to measure the energy absorbed by the chiller during its life. It is installed inside the
control box mounted on a DIN rail and show on a digital display: Line-to-Line Voltage, Phase and Average Current,
Active and Reactive Power, Active Energy, Frequency.
Current limit To limit maximum absorbed current of the unit whenever is required
20mm evaporator insulation
Fan Silent Mode - The microprocessor clock switches the fan at low speed according to the client setting (i.e. Night &
Day), providing that the ambient temperature/condensing pressure is allowing the speed change. It allows a perfect
condensing control down to 10C.
Fan speed regulation To control the fan speed revolution for smooth operating control of the unit. This option
improves the sound level of the unit during low ambient temperature operation.
Condenser coil guards
Cu-Cu condensing coils To give better protection against corrosion by aggressive environments.
Cu-Cu-Sn condensing coils To give better protection against corrosion in aggressive environments and by salty air.
Alucoat condensing coils Fins are protected by a special acrylic paint with a high resistance to corrosion.
Evaporator Flow switch Supplied separately to be wired and installed on the evaporator water piping (by the
customer).
High pressure side manometers
Set-point reset The leaving water temperature set-point can be overwritten with the following options: 4-20mA from
external source (by user); outside ambient temperature; evaporator water temperature t.
Demand limit User can limit the load of the unit by 4-20mA signal or by network system
Alarm from external device Microprocessor is able to receive an alarm signal from an external device (pump etc).
User can decide if this alarm signal will stop or not the unit.
Outside ambient temperature sensor and reset of leaving water temperature set-point
Kit container
Rubber type antivibration mounts Supplied separately, these are positioned under the base of the unit during
installation. Ideal to reduce the vibrations when the unit is floor mounted.
Spring type antivibration mounts Supplied separately, these are positioned under the base of the unit during
installation. Ideal for dampening vibrations for installation on roofs and metallic structures.
Water circulation pump (low or high lifting) Not available for McEnergy HPI Extension SE 072.2167.3 LN.
Hydronic kit consists of: single direct driven centrifugal pump, water filling system with pressure gauge, safety valve,
drain valve. The motor pump is protected by a circuit breaker installed in control panel. The kit is assembled and wired to
the control panel. The pipe and pump are protected from freezing with an additional electrical heater.
Two water circulation pumps (low or high lifting) Not available for McEnergy HPI Extension SE 072.2167.3 LN.
Hydronic kit consists of: twin direct driven centrifugal pumps, water filling system with pressure gauge, safety valve, drain
valve. The motor pump is protected by a circuit breaker installed in control panel. The kit is assembled and wired to the
control panel. The pipe and pumps are protected from freezing with an additional electrical heater.
Witness test Every unit is always tested at the test bench prior to the shipment. On request, a second test can be
carried out, at customers presence, in accordance with the procedures indicated on the test form. (Not available for units
with glycol mixtures).
Double pressure relief valve with diverter

KPMHP00511-09EN page 8/60

Nomenclature
McEnergy HPI "Extension"

-A

SE

072

.2

ST

Machine type
McEnergy HPI "Extension"

= Airto Water Heat Pump Inverter

Model series
Letter A,B,: major modification
Efficiency level
SE

= Standard Efficiency

Unit size
072 167
Always 3-digit code
Number of compressors
23
Nloise configuration
ST
LN

= Standard Noise
= Low Noise

KPMHP00511-09EN page 9/60

Specifications McEnergy HPI Extension SE-ST


TECHNICAL SPECIFICATIONS
Capacity (1) (2)
Capacity control
Unit power input (1) (2)

Version SE - ST

Cooling
Heating
Type
Minimum capacity
Cooling
Heating

EER (1)
COP (2)
ESEER
IPLV
Casing

Colour
Material

Dimensions

Unit

Weight

Water heat exchanger

Unit
Operating Weight
Type
Water volume
Nominal water flow rate
Nominal water flow rate
Nominal Water pressure drop
Nominal Water pressure drop
Insulation material

Air heat exchanger

Type

Fan

Type
Drive
Diameter
Nominal air flow
Model

Height
Width
Length

Cooling
Heating
Cooling
Heating

Quantity
Speed
Motor input

Sound level
Sound Pressure (3)

Refrigerant circuit
Piping connections

Safety devices

Notes (1)
Notes (2)
Notes (3)

079.2

083.2

093.2

096.2

254
270

273
297

292
324
Stepless

324
333

339
349

13
90.3
90.4
2.81
2.98
4.05
4.58

13
100
99.3
2.74
2.99
4.04
4.62

----mm
l/s
No.
rpm
W

Cooling
Heating
Cooling
Heating

l
No.
dB(A)
dB(A)
dB(A)
dB(A)
--kg.
No.
mm

13
13
109
116
107
117
2.69
2.79
3.03
2.84
4.01
4.07
4.62
4.75
Ivory White
Galvanized and painted steel sheet
2335
2254
3547
3500
3640

13
124
124
2.74
2.80
4.01
4.64

2335
2254
3547
3410
3550

2335
2254
3547
3455
3595

2335
2254
4381
3870
4010

2335
2254
4381
3870
4010

138
12.12
12.89
37
42

Single Pass Shell&Tube


138
138
133
13.03
13.94
15.46
14.18
15.49
15.89
42
48
53
49
58
55
Closed cell

133
16.21
16.66
58
60

High efficiency fin and tube type


with integral subcooler
Direct propeller type
DOL
800
31728
6
920
1.75

800
31728
6
920
1.75

800
31728
6
920
1.75

800
42304
8
920
1.75

800
42304
8
920
1.75

Semi-hermetic single screw


compressor Inverter driven

---

Oil charge
Quantity
Sound Power

072.2

---

Type
Compressor

kW
kW
--%
kW
kW
------------mm
mm
mm
kg
kg
--l
l/s
l/s
kPa
kPa

26
2
100.5
100.5
82.1
82.1
R-134a
88
2
139.7

26
2
100.5
100.5
82.1
82.1
R-134a
94
2
139.7

26
2
100.5
100.5
82.1
82.3
R-134a
100
2
139.7

26
2
101.2
101.2
82.3
82.3
R-134a
118
2
139.7

26
2
101.2
101.2
82.3
82.3
R-134a
118
2
139.7

Refrigerant type
Refrigerant charge
N. of circuits
Evaporator water inlet/outlet
High discharge pressure (pressure switch)
High discharge pressure (pressure transducer)
Low suction pressure (pressure transducer)
Compressor overload (Kriwan)
High discharge temperature
Low oil pressure
Low pressure ratio
High oil filter pressure drop
Phase monitor
Cooling capacity, unit power input in cooling and EER are based on the following conditions: evaporator 12/7C; ambient
35C, unit at full load operation.
Heating capacity, unit power input in heating and COP are based on the following conditions: condenser 40/45C; ambient
7C DB, unit at full load operation.
The values are according to ISO 3744 and are referred to: evaporator 12/7C, ambient 35C, full load operation.

KPMHP00511-09EN page 10/60

TECHNICAL SPECIFICATIONS
Capacity (1)
Capacity control
Unit power input (1)

Version SE - ST

Cooling
Heating
Type
Minimum capacity
Cooling
Heating

EER (1)
COP (2)
ESEER
IPLV
Casing

Colour
Material

Dimensions

Unit

Weight

Water heat exchanger

Height
Width
Length

Unit
Operating Weight
Type
Water volume
Nominal water flow rate
Nominal Water pressure drop

Cooling
Heating
Cooling
Heating

kW
kW
--%
kW
kW
------------mm
mm
mm
kg
kg
--l
l/s
l/s
kPa
kPa

103.2

109.2

117.2

124.2

130.3

365
379

382
410

413
443
Stepless

436
463

457
475

13
134
132
2.73
2.87
4.02
4.71

13
142
141
2.68
2.90
3.94
4.67

13
13
152
163
155
165
2.72
2.68
2.85
2.81
4.03
4.01
4.73
4.69
Ivory White
Galvanized and painted steel sheet

9
161
164
2.83
2.90
4.31
4.85

2335
2254
4381
3940
4068

2335
2335
2335
2254
2254
2254
4381
5281
5281
4010
4390
4390
4138
4518
4518
Single Pass Shell&Tube

2335
2254
6583
5015
5255

128
17.42
18.11
53
57

128
18.25
19.57
57
65

240
21.83
22.68
61
66

128
19.72
21.15
46
52
Closed cell

Insulation material
Air heat exchanger

Type

Fan

Type
Drive
Diameter
Nominal air flow
Model

Quantity
Speed
Motor input

Type
Compressor

Sound Power
Sound Pressure (3)

Refrigerant circuit
Piping connections

Safety devices

Notes (1)
Notes (2)
Notes (3)

Refrigerant type
Refrigerant charge
N. of circuits
Evaporator water inlet/outlet

Direct propeller type


DOL
800
42304
8
920
1.75

Cooling
Heating
Cooling
Heating

l
No.
dB(A)
dB(A)
dB(A)
dB(A)
--kg.
No.
mm

800
42304
8
920
1.75

800
52880
10
920
1.75

800
52880
10
920
1.75

800
63456
12
920
1.75

Semi-hermetic single screw


compressor Inverter driven

---

Oil charge
Quantity

Sound level

High efficiency fin and tube type


with integral subcooler

------mm
l/s
No.
rpm
W

128
20.81
22.14
51
57

26
2
101.2
101.2
82.3
82.3
R-134a
121
2
139.7

26
2
101.2
101.2
82.3
82.5
R-134a
124
2
139.7

26
2
101.8
101.8
82.5
82.5
R-134a
148
2
139.7

26
2
101.8
101.8
82.5
83.7
R-134a
148
2
139.7

39
3
103.6
103.6
83.7
83.7
R-134a
177
3
219.1

High discharge pressure (pressure switch)


High discharge pressure (pressure transducer)
Low suction pressure (pressure transducer)
Compressor overload (Kriwan)
High discharge temperature
Low oil pressure
Low pressure ratio
High oil filter pressure drop
Phase monitor
Cooling capacity, unit power input in cooling and EER are based on the following conditions: evaporator 12/7C; ambient
35C, unit at full load operation.
Heating capacity, unit power input in heating and COP are based on the following conditions: condenser 40/45C; ambient
7C DB, unit at full load operation.
The values are according to ISO 3744 and are referred to: evaporator 12/7C, ambient 35C, full load operation.

KPMHP00511-09EN page 11/60

TECHNICAL SPECIFICATIONS
Capacity (1)
Capacity control
Unit power input (1)

Version SE - ST

Cooling
Heating
Type
Minimum capacity
Cooling
Heating

EER (1)
COP (2)
ESEER
IPLV
Casing

Colour
Material

Dimensions

Unit

Weight

Water heat exchanger

Height
Width
Length

Unit
Operating Weight
Type
Water volume
Nominal water flow rate
Nominal Water pressure drop

Cooling
Heating
Cooling
Heating

kW
kW
--%
kW
kW
------------mm
mm
mm
kg
kg
--l
l/s
l/s
kPa
kPa

144.3

153.3

167.3

505
530

522
558
Stepless

583
615

9
178
176
2.83
3.02
4.13
4.89

9
9
186
215
184
205
2.81
2.71
3.04
3.00
4.13
4.05
4.85
4.78
Ivory White
Galvanized and painted steel sheet
2335
2335
2335
2254
2254
2254
6583
6583
6583
5495
5735
5735
5724
5964
5953
Single Pass Shell&Tube
229
24.11
25.33
50
55

229
24.92
26.65
53
60
Closed cell

Insulation material
Air heat exchanger

Type

Fan

Type
Drive
Diameter
Nominal air flow
Model

---

Quantity
Speed
Motor input

Type
Compressor

Sound Power
Sound Pressure (3)

Refrigerant circuit
Piping connections

Safety devices

Notes (1)
Notes (2)
Notes (3)

---

Oil charge
Quantity

Sound level

Refrigerant type
Refrigerant charge
N. of circuits
Evaporator water inlet/outlet

----mm
l/s
No.
rpm
W

Cooling
Heating
Cooling
Heating

l
No.
dB(A)
dB(A)
dB(A)
dB(A)
--kg.
No.
mm

218
27.87
29.39
65
71

High efficiency fin and tube type


with integral subcooler
Direct propeller type
DOL
800
63456
12
920
1.75

800
63456
12
920
1.75

800
63456
12
920
1.75

Semi-hermetic single screw


compressor Inverter driven
39
3
103.6
103.6
83.7
83.7
R-134a
183
3
219.1

39
3
103.6
103.6
83.7
83.7
R-134a
186
3
219.1

39
3
103.6
103.6
83.7
83.7
R-134a
186
3
219.1

High discharge pressure (pressure switch)


High discharge pressure (pressure transducer)
Low suction pressure (pressure transducer)
Compressor overload (Kriwan)
High discharge temperature
Low oil pressure
Low pressure ratio
High oil filter pressure drop
Phase monitor
Cooling capacity, unit power input in cooling and EER are based on the following conditions:
evaporator 12/7C; ambient 35C, unit at full load operation.
Heating capacity, unit power input in heating and COP are based on the following conditions:
condenser 40/45C; ambient 7C DB, unit at full load operation.
The values are according to ISO 3744 and are referred to: evaporator 12/7C, ambient 35C, full
load operation.

KPMHP00511-09EN page 12/60

Version SE - ST

ELECTRICAL SPECIFICATIONS

Power Supply

Phase
Frequency
Voltage
Voltage Tolerance

Minimum
Maximum

Maximum starting current


Nominal running current cooling
Nominal running current heating
Maximum running current
Maximum current for wires sizing
Nominal running current in cooling
Nominal running current in heating
Phase
Voltage

Unit

Fans

Compressor

Voltage Tolerance

Minimum
Maximum

Maximum running current


Starting method

Version SE - ST

ELECTRICAL SPECIFICATIONS

Power Supply

Phase
Frequency
Voltage
Voltage Tolerance

Minimum
Maximum

Maximum starting current


Nominal running current cooling
Nominal running current heating
Maximum running current
Maximum current for wires sizing
Nominal running current in cooling
Nominal running current in heating
Phase
Voltage

Unit

Fans

Compressor

Voltage Tolerance

Minimum
Maximum

Maximum running current


Starting method

Phase
Frequency
Voltage
Voltage Tolerance

Minimum
Maximum

Maximum starting current


Nominal running current cooling
Nominal running current heating
Maximum running current
Maximum current for wires sizing
Nominal running current in cooling
Nominal running current in heating
Phase
Voltage

Unit

Fans

Compressor

Voltage Tolerance
Maximum running current
Starting method

--Hz
V
%
%
A
A
A
A
A
A
A
No.
V
%
%
A
---

Version SE - ST

ELECTRICAL SPECIFICATIONS

Power Supply

--Hz
V
%
%
A
A
A
A
A
A
A
No.
V
%
%
A
---

Minimum
Maximum

--Hz
V
%
%
A
A
A
A
A
A
A
No.
V
%
%
A
---

072.2

079.2

083.2

093.2

096.2

3
50
400
-10%
+10%
217
150
153
238
262
4
4
3
400
-10%
+10%
107+107

3
50
400
-10%
+10%
217
167
167
238
262
4
4
3
400
-10%
+10%
107+107

3
50
400
-10%
+10%
217
181
178
238
262
4
4
3
400
-10%
+10%
107+107
VFD

3
50
400
-10%
+10%
264
196
197
285
314
4
4
3
400
-10%
+10%
107+146

3
50
400
-10%
+10%
296
209
210
324
356
4
4
3
400
-10%
+10%
146+146

103.2

109.2

117.2

124.2

130.3

3
50
400
-10%
+10%
296
224
222
324
356
4
4
3
400
-10%
+10%
146+146

3
50
400
-10%
+10%
296
237
235
324
356
4
4
3
400
-10%
+10%
146+146

3
50
400
-10%
+10%
334
255
260
362
398
4
4
3
400
-10%
+10%
146+176
VFD

3
50
400
-10%
+10%
358
273
276
392
431
4
4
3
400
-10%
+10%
176+176

3
50
400
-10%
+10%
328
271
275
369
406
4
4
3
400
-10%
+10%

144.3

153.3

167.3

3
50
400
-10%
+10%
398
300
296
447
492
4
4
3
400
-10%
+10%

3
50
400
-10%
+10%
430
313
309
486
535
4
4
3
400
-10%
+10%

3
50
400
-10%
+10%
430
357
342
486
535
4
4
3
400
-10%
+10%

107+107+107

146+146+107 146+146+146 146+146+146

VFD

Allowed voltage tolerance 10%. Voltage unbalance between phases must be within 3%.
Maximum starting current: starting current of biggest compressor + current of the compressor at 75% maximum load + fans current for
the circuit at 75%.
Notes

Nominal current in cooling mode is referred to installation with 25kA short circuit current and is based on the following conditions:
evaporator 12C/7C; ambient 35C.compressor + fans current.
Nominal current in heating mode is referred to installation with 25kA short circuit current and is based on the following conditions:
condenser 40C/45C; ambient 7C DB/6C WB + fans current.
Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current
Maximum current for wires sizing: (compressors full load ampere + fans current) x 1,1.

KPMHP00511-09EN page 13/60

Specifications McEnergy HPI Extension SE-LN


Version SE - LN

TECHNICAL SPECIFICATIONS
Capacity (1) (2)
Capacity control
Unit power input (1) (2)

Cooling
Heating
Type
Minimum capacity
Cooling
Heating

EER (1)
COP (2)
ESEER
IPLV
Casing

Colour
Material

Dimensions

Unit

Weight

Water heat exchanger

Height
Width
Length

Unit
Operating Weight
Type
Water volume
Nominal water flow rate
Nominal Water pressure drop

Cooling
Heating
Cooling
Heating

kW
kW
--%
kW
kW
------------mm
mm
mm
kg
kg
--l
l/s
l/s
kPa
kPa

072.2

079.2

083.2

093.2

096.2

248
270

266
297

291
324
Stepless

316
333

331
349

13
88.5
90.4
2.80
2.98
4.18
4.84

13
98
99
2.70
2.99
4.16
4.86

13
13
109
113
107
117
2.66
2.79
3.03
2.84
4.11
4.29
4.80
4.97
Ivory White
Galvanized and painted steel sheet

13
122
124
2.72
2.80
4.18
4.87

2335
2254
3547
3750
3888

2335
2335
2335
2254
2254
2254
3547
3547
4381
3795
3840
4210
3933
3978
4343
Single Pass Shell&Tube

2335
2254
4381
4210
4343

138
11.83
12.89
36
42

138
12.70
14.18
40
49

133
15.83
16.66
55
60

138
13.89
15.49
48
58
Closed cell

Insulation material
Air heat exchanger

Type

Fan

Cooling
Heating
Quantity
Speed - Cooling (Heating)
Motor input - Cooling (Heating)

Nominal air flow

Model

Type
Compressor

Sound level
Sound Pressure (3)

Piping connections

Safety devices

Notes (1)
Notes (2)
Notes (3)

Refrigerant type
Refrigerant charge
N. of circuits
Evaporator water inlet/outlet

----mm
l/s
l/s
No.
rpm
W

Direct propeller type


DOL
800
24432
31728
6
715 (920)
0.78 (1.75)

Cooling
Heating
Cooling
Heating

l
No.
dB(A)
dB(A)
dB(A)
dB(A)
--kg.
No.
mm

800
24432
31728
6
715 (920)
0.78 (1.75)

800
24432
31728
6
715 (920)
0.78 (1.75)

800
32576
42304
8
715 (920)
0.78 (1.75)

800
32576
42304
8
715 (920)
0.78 (1.75)

Semi-hermetic
single screw compressor

---

Oil charge
Quantity
Sound Power

Refrigerant circuit

High efficiency fin and tube type


with integral subcooler

---

Type
Drive
Diameter

133
15.12
15.89
51
55

26
2
94.0
94.9
75.6
76.5
R-134a
88
2
139.7

26
2
94.0
94.9
75.6
76.5
R-134a
94
2
139.7

26
2
94.0
94.9
75.6
76.5
R-134a
100
2
139.7

26
2
94.7
96.1
75.8
77.2
R-134a
118
2
139.7

26
2
94.7
96.1
75.8
77.2
R-134a
118
2
139.7

High discharge pressure (pressure switch)


High discharge pressure (pressure transducer)
Low suction pressure (pressure transducer)
Compressor overload (Kriwan)
High discharge temperature
Low oil pressure
Low pressure ratio
High oil filter pressure drop
Phase monitor
Cooling capacity, unit power input in cooling and EER are based on the following conditions: evaporator 12/7C; ambient
35C, unit at full load operation.
Heating capacity, unit power input in heating and COP are based on the following conditions: condenser 40/45C; ambient
7C DB, unit at full load operation.
The values are according to ISO 3744 and are referred to: evaporator 12/7C, ambient 35C, full load operation.

KPMHP00511-09EN page 14/60

Version SE - LN

TECHNICAL SPECIFICATIONS
Capacity (1) (2)
Capacity control
Unit power input (1) (2)

Cooling
Heating
Type
Minimum capacity
Cooling
Heating

EER (1)
COP (2)
ESEER
IPLV
Casing

Colour
Material

Dimensions

Unit

Weight

Water heat exchanger

Height
Width
Length

Unit
Operating Weight
Type
Water volume
Nominal water flow rate
Nominal Water pressure drop

Cooling
Heating
Cooling
Heating

kW
kW
--%
kW
kW
------------mm
mm
mm
kg
kg
--l
l/s
l/s
kPa
kPa

103.2

109.2

117.2

124.2

130.3

355
379

372
410

403
443
Stepless

425
463

448
475

13
132
132
2.68
2.87
4.16
4.87

13
142
141
2.62
2.90
4.13
4.84

13
13
149
161
155
165
2.71
2.64
2.85
2.81
4.19
4.14
4.91
4.86
Ivory White
Galvanized and painted steel sheet

9
156
164
2.87
2.90
4.31
5.04

2335
2254
4381
4280
4408

2335
2335
2335
2254
2254
2254
4381
5281
5281
4350
4730
4730
4478
4858
4858
Single Pass Shell&Tube

2335
2254
6583
5525
5765

128
16.98
18.11
50
57

128
17.77
19.57
55
65

240
21.39
22.68
59
66

128
19.28
21.15
44
52
Closed cell

Insulation material
Air heat exchanger

Type

Fan

Cooling
Nominal air flow
Heating
Quantity
Model
Speed - Cooling (Heating)
Motor input - Cooling (Heating)
Type

Compressor

Sound level
Sound Pressure (3)

Refrigerant circuit
Piping connections

Safety devices

Notes (1)
Notes (2)
Notes (3)

Refrigerant type
Refrigerant charge
N. of circuits
Evaporator water inlet/outlet

----mm
l/s
l/s
No.
rpm
W

Direct propeller type


DOL
800
32576
42304
8
715 (920)
0.78 (1.75)

Cooling
Heating
Cooling
Heating

l
No.
dB(A)
dB(A)
dB(A)
dB(A)
--kg.
No.
mm

800
32576
42304
8
715 (920)
0.78 (1.75)

800
40720
52880
10
715 (920)
0.78 (1.75)

800
40720
52880
10
715 (920)
0.78 (1.75)

800
48864
63456
12
715 (920)
0.78 (1.75)

Semi-hermetic
single screw compressor

---

Oil charge
Quantity
Sound Power

High efficiency fin and tube type


with integral subcooler

---

Type
Drive
Diameter

128
20.30
22.14
48
57

26
2
94.7
96.1
75.8
77.2
R-134a
121
2
139.7

26
2
94.7
96.1
75.8
77.2
R-134a
124
2
139.7

26
2
95.3
96.7
76.0
77.4
R-134a
148
2
139.7

26
2
95.3
96.7
76.0
77.4
R-134a
148
2
139.7

39
3
97.0
98.4
77.2
78.6
R-134a
177
3
219.1

High discharge pressure (pressure switch)


High discharge pressure (pressure transducer)
Low suction pressure (pressure transducer)
Compressor overload (Kriwan)
High discharge temperature
Low oil pressure
Low pressure ratio
High oil filter pressure drop
Phase monitor
Cooling capacity, unit power input in cooling and EER are based on the following conditions: evaporator 12/7C; ambient
35C, unit at full load operation.
Heating capacity, unit power input in heating and COP are based on the following conditions: condenser 40/45C; ambient
7C DB, unit at full load operation.
The values are according to ISO 3744 and are referred to: evaporator 12/7C, ambient 35C, full load operation.

KPMHP00511-09EN page 15/60

Version SE - LN

TECHNICAL SPECIFICATIONS
Capacity (1)
Capacity control
Unit power input (1)

Cooling
Heating
Type
Minimum capacity
Cooling
Heating

EER (1)
COP (2)
ESEER
IPLV
Casing

Colour
Material

Dimensions

Unit

Weight

Water heat exchanger

Height
Width
Length

Unit
Operating Weight
Type
Water volume
Nominal water flow rate
Nominal Water pressure drop

Cooling
Heating
Cooling
Heating

kW
kW
--%
kW
kW
------------mm
mm
mm
kg
kg
--l
l/s
l/s
kPa
kPa

144.3

153.3

167.3

493
530

510
558
Stepless

567
615

9
174
176
2.83
3.02
4.29
5.01

9
9
183
214
184
205
2.79
2.65
3.04
3.00
4.23
4.10
4.96
4.83
Ivory White
Galvanized and painted steel sheet
2335
2335
2335
2254
2254
2254
6583
6583
6583
6005
6245
6245
6234
6474
6463
Single Pass Shell&Tube
229
23.56
25.33
48
55

229
24.34
26.65
51
60
Closed cell

Insulation material
Air heat exchanger

Type

---

Type
Drive
Diameter
Fan

Cooling
Nominal air flow
Heating
Quantity
Model
Speed - Cooling (Heating)
Motor input - Cooling (Heating)
Type

Compressor

Sound level
Sound Pressure (3)

Refrigerant circuit
Piping connections

Safety devices

Notes (1)
Notes (2)
Notes (3)

---

Oil charge
Quantity
Sound Power

Refrigerant type
Refrigerant charge
N. of circuits
Evaporator water inlet/outlet

----mm
l/s
l/s
No.
rpm
W

Cooling
Heating
Cooling
Heating

l
No.
dB(A)
dB(A)
dB(A)
dB(A)
--kg.
No.
mm

218
27.11
29.39
62
71

High efficiency fin and tube type


with integral subcooler
Direct propeller type
DOL
800
48864
63456
12
715 (920)
0.78 (1.75)

800
48864
63456
12
715 (920)
0.78 (1.75)

800
48864
63456
12
715 (920)
0.78 (1.75)

Semi-hermetic
single screw compressor
39
3
97.0
98.4
77.2
78.6
R-134a
183
3
219.1

39
3
97.0
98.4
77.2
78.6
R-134a
186
3
219.1

39
3
97.0
98.4
77.2
78.6
R-134a
186
3
219.1

High discharge pressure (pressure switch)


High discharge pressure (pressure transducer)
Low suction pressure (pressure transducer)
Compressor overload (Kriwan)
High discharge temperature
Low oil pressure
Low pressure ratio
High oil filter pressure drop
Phase monitor
Cooling capacity, unit power input in cooling and EER are based on the following conditions:
evaporator 12/7C; ambient 35C, unit at full load operation.
Heating capacity, unit power input in heating and COP are based on the following conditions:
condenser 40/45C; ambient 7C DB, unit at full load operation.
The values are according to ISO 3744 and are referred to: evaporator 12/7C, ambient 35C, full
load operation.

KPMHP00511-09EN page 16/60

Version SE - LN

ELECTRICAL SPECIFICATIONS

Power Supply

Phase
Frequency
Voltage
Voltage Tolerance

Minimum
Maximum

Maximum starting current


Nominal running current cooling
Nominal running current heating
Maximum running current
Maximum current for wires sizing
Nominal running current in cooling
Nominal running current in heating
Phase
Voltage

Unit

Fans

Compressor

Voltage Tolerance

Minimum
Maximum

Maximum running current


Starting method

Version SE - LN

ELECTRICAL SPECIFICATIONS

Power Supply

Phase
Frequency
Voltage
Voltage Tolerance

Minimum
Maximum

Maximum starting current


Nominal running current cooling
Nominal running current heating
Maximum running current
Maximum current for wires sizing
Nominal running current in cooling
Nominal running current in heating
Phase
Voltage

Unit

Fans

Compressor

Voltage Tolerance

Minimum
Maximum

Maximum running current


Starting method

Phase
Frequency
Voltage
Voltage Tolerance

Minimum
Maximum

Maximum starting current


Nominal running current cooling
Nominal running current heating
Maximum running current
Maximum current for wires sizing
Nominal running current in cooling
Nominal running current in heating
Phase
Voltage

Unit

Fans

Compressor

Voltage Tolerance
Maximum running current
Starting method

--Hz
V
%
%
A
A
A
A
A
A
A
No.
V
%
%
A
---

Version SE - LN

ELECTRICAL SPECIFICATIONS

Power Supply

--Hz
V
%
%
A
A
A
A
A
A
A
No.
V
%
%
A
---

Minimum
Maximum

--Hz
V
%
%
A
A
A
A
A
A
A
No.
V
%
%
A
---

072.2
3
50
400
-10%
+10%
208
149
153
238
262
3
4
3
400
-10%
+10%
107+107

103.2
3
50
400
-10%
+10%
285
178
222
324
356
3
4
3
400
-10%
+10%
146+146

079.2

083.2

093.2

3
3
3
50
50
50
400
400
400
-10%
-10%
-10%
+10%
+10%
+10%
208
208
252
160
147
153
167
178
197
238
238
285
262
262
314
3
3
3
4
4
4
3
3
3
400
400
400
-10%
-10%
-10%
+10%
+10%
+10%
107+107
107+107
107+146
Wye Delta type (Y )
109.2

117.2

124.2

3
3
3
50
50
50
400
400
400
-10%
-10%
-10%
+10%
+10%
+10%
284
319
343
192
200
219
235
260
276
324
362
392
356
398
431
3
3
3
4
4
4
3
3
3
400
400
400
-10%
-10%
-10%
+10%
+10%
+10%
146+146
146+176
176+176
Wye Delta type (Y )

144.3

153.3

167.3

3
50
400
-10%
+10%
380
255
296
447
492
3
4
3
400
-10%
+10%

3
50
400
-10%
+10%
412
269
309
486
535
3
4
3
400
-10%
+10%

3
50
400
-10%
+10%
412
311
342
486
535
3
4
3
400
-10%
+10%

096.2
3
50
400
-10%
+10%
284
167
210
324
356
3
4
3
400
-10%
+10%
146+146

130.3
3
50
400
-10%
+10%
310
232
275
369
406
3
4
3
400
-10%
+10%
107+107+107

146+146+107 146+146+146 146+146+146

Wye Delta type (Y )

Allowed voltage tolerance 10%. Voltage unbalance between phases must be within 3%.
Maximum starting current: starting current of biggest compressor + current of the compressor at 75% maximum load + fans current for
the circuit at 75%.
Notes

Nominal current in cooling mode is referred to installation with 25kA short circuit current and is based on the following conditions:
evaporator 12C/7C; ambient 35C.compressor + fans current.
Nominal current in heating mode is referred to installation with 25kA short circuit current and is based on the following conditions:
condenser 40C/45C; ambient 7C DB/6C WB + fans current.
Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current
Maximum current for wires sizing: (compressors full load ampere + fans current) x 1,1.

KPMHP00511-09EN page 17/60

Sound Levels
Cooling Mode - McEnergy HPI Extension SE ST
-5

Rated
072.2083.2

093.2109.2

117.2124.2

130.3167.3

Power

Sound pressure level at 1 m from the unit in semispheric free field (rif. 2 x 10 Pa)

Unit size

63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

dB(A)

dB(A)

77.0

75.6

75.8

74.9

81.1

69.3

60.7

51.9

82.1
75.9
83.1

100.5
94.4
101.5

82.3
76.1
84.2
82.5
76.3
84.4
83.7
77.5
85.6

101.2
95.0
103.1
101.8
95.7
103.7
103.6
97.4
105.4

Min

77.0

75.1

73.8

74.0

72.2

66.2

58.9

49.5

Boost

77.4

78.6

79.1

80.7

79.5

74.7

66.5

58.0

Rated

77.2

75.8

76.0

75.1

81.3

69.5

60.9

52.1

Min

77.2

75.3

74.0

74.2

72.4

66.4

59.1

49.7

Boost

78.5

79.7

80.2

81.8

80.6

75.8

67.6

59.1

Rated

77.4

76.0

76.2

75.3

81.5

69.7

61.1

52.3

Min

77.4

75.5

74.2

74.4

72.6

66.6

59.3

49.9

Boost

78.7

79.9

80.4

82.0

80.8

76.0

67.8

59.3

Rated

78.6

77.2

77.4

76.5

82.7

70.9

62.3

53.5

Min

78.6

76.7

75.4

75.6

73.8

67.8

60.5

51.1

Boost

79.9

81.1

81.6

83.2

82.0

77.2

69.0

60.5

Rated (nominal frequency)


Min (minimum frequency)
Boost (maximum frequency)

Cooling Mode - McEnergy HPI Extension SE LN


-5

072.2083.2

093.2109.2

117.2124.2

130.3167.3

Power

Sound pressure level at 1 m from the unit in semispheric free field (rif. 2 x 10 Pa)

Unit size

63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

dB(A)

dB(A)

Rated

76.1

72.4

70.9

69.6

74.2

63.9

55.5

46.3

Min

76.1

72.5

70.5

69.8

68.6

62.8

55.1

45.7

Boost

76.2

73.6

72.8

73.7

72.6

67.7

59.5

50.8

75.6
72.3
76.2

94.0
90.7
94.6

Rated

76.3

72.6

71.1

69.8

74.4

64.1

55.7

46.5

Min

76.3

72.7

70.7

70.0

68.8

63.0

55.3

45.9

Boost

76.4

73.8

73.0

73.9

72.8

67.9

59.7

51.0

Rated

76.5

72.8

71.3

70.0

74.6

64.3

55.9

46.7

Min

76.5

72.9

70.9

70.2

69.0

63.2

55.5

46.1

Boost

76.6

74.0

73.2

74.1

73.0

68.1

59.9

51.2

Rated

77.7

74.0

72.5

71.2

75.8

65.5

57.1

47.9

Min

77.7

74.1

72.1

71.4

70.2

64.4

56.7

47.3

Boost

77.8

75.2

74.4

75.3

74.2

69.3

61.1

52.4

75.8
72.5
76.4
76.0
72.7
76.6
77.2
73.9
77.8

94.7
91.4
95.3
95.3
92.0
95.9
97.0
93.7
97.6

Rated (nominal frequency)


Min (minimum frequency)
Boost (maximum frequency)

KPMHP00511-09EN page 18/60

Heating Mode - McEnergy HPI Extension SE ST


-5

Rated
072.2083.2

093.2109.2

117.2124.2

130.3167.3

Power

Sound pressure level at 1 m from the unit in semispheric free field (rif. 2 x 10 Pa)

Unit size

63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

dB(A)

dB(A)

77.0

75.6

75.8

74.9

81.1

69.3

60.7

51.9

82.1
75.9
83.1

100.5
94.4
101.5

82.3
76.1
84.2
82.5
76.3
84.4
83.7
77.5
85.6

101.2
95.0
103.1
101.8
95.7
103.7
103.6
97.4
105.4

Min

77.0

75.1

73.8

74.0

72.2

66.2

58.9

49.5

Boost

77.4

78.6

79.1

80.7

79.5

74.7

66.5

58.0

Rated

77.2

75.8

76.0

75.1

81.3

69.5

60.9

52.1

Min

77.2

75.3

74.0

74.2

72.4

66.4

59.1

49.7

Boost

78.5

79.7

80.2

81.8

80.6

75.8

67.6

59.1

Rated

77.4

76.0

76.2

75.3

81.5

69.7

61.1

52.3

Min

77.4

75.5

74.2

74.4

72.6

66.6

59.3

49.9

Boost

78.7

79.9

80.4

82.0

80.8

76.0

67.8

59.3

Rated

78.6

77.2

77.4

76.5

82.7

70.9

62.3

53.5

Min

78.6

76.7

75.4

75.6

73.8

67.8

60.5

51.1

Boost

79.9

81.1

81.6

83.2

82.0

77.2

69.0

60.5

Rated (nominal frequency)


Min (minimum frequency)
Boost (maximum frequency)

Heating Mode - McEnergy HPI Extension SE LN


-5

072.2083.2

093.2109.2

117.2124.2

130.3167.3

Power

Sound pressure level at 1 m from the unit in semispheric free field (rif. 2 x 10 Pa)

Unit size

63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

dB(A)

dB(A)

Rated

78.1

74.1

72.3

70.8

74.8

65.1

56.8

47.5

Min

78.1

74.1

71.8

70.9

69.9

64.2

56.4

46.9

Boost

78.1

74.9

73.7

74.1

73.2

68.2

60.0

51.2

76.5
73.5
76.7

94.9
91.9
95.1

Rated

79.5

75.5

74.1

71.5

75.1

67.6

59.6

51.0

Min

78.3

74.3

72.0

71.1

70.1

64.4

56.6

47.1

Boost

78.3

75.1

73.9

74.3

73.4

68.4

60.2

51.4

Rated

79.7

75.7

74.3

71.7

75.3

67.8

59.8

51.2

Min

78.5

74.5

72.2

71.3

70.3

64.6

56.8

47.3

Boost

78.5

75.3

74.1

74.5

73.6

68.6

60.4

51.6

Rated

80.9

76.9

75.5

72.9

76.5

69.0

61.0

52.4

Min

79.7

75.7

73.4

72.5

71.5

65.8

58.0

48.5

Boost

79.7

76.5

75.3

75.7

74.8

69.8

61.6

52.8

77.2
73.7
76.9
77.4
73.9
77.1
78.6
75.1
78.3

96.1
92.6
95.8
96.7
93.2
96.4
98.4
94.9
98.1

Rated (nominal frequency)


Min (minimum frequency)
Boost (maximum frequency)

Sound pressure level correction factors for different distances - McEnergy HPI Extension SE ST/LN
Unit size

Distance
1m

5m

10m

15m

20m

25m

50m

072.2

0.0

6.2

10.3

13.0

15.1

16.8

22.2

079.2

0.0

6.2

10.3

13.0

15.1

16.8

22.2

083.2

0.0

6.2

10.3

13.0

15.1

16.8

22.2

093.2

0.0

5.9

9.9

12.6

14.7

16.4

21.8

096.2

0.0

5.9

9.9

12.6

14.7

16.4

21.8

103.2

0.0

5.9

9.9

12.6

14.7

16.4

21.8

109.2

0.0

5.9

9.9

12.6

14.7

16.4

21.8

117.2

0.0

5.7

9.6

12.3

14.3

16.0

21.4

124.2

0.0

5.7

9.6

12.3

14.3

16.0

21.4

130.3

0.0

5.4

9.3

11.9

13.9

15.6

20.9

144.3

0.0

5.4

9.3

11.9

13.9

15.6

20.9

153.3

0.0

5.4

9.3

11.9

13.9

15.6

20.9

167.3

0.0

5.4

9.3

11.9

13.9

15.6

20.9

KPMHP00511-09EN page 19/60

Operating limits
McEnergy HPI Extension SE-ST/LN
Cooling Mode
50

CondenserInletAirTemp.(C)

40

30
OperationwithGlycol
(below4CEvapLWT)

20

10

FanSpeedRegulationrequired
(below10CAmb.Temp)

10

20
10

10

12

14

16

EvaporatorLeavingWaterTemp.(C)

Heating Mode
25

20

EvaporatorInletAirTemp.(C)

15

10

10

15
30

32

34

36

38

40

42

44

46

48

CondenserLeavingWaterTemp.(C)

KPMHP00511-09EN page 20/60

50

52

54

56

58

60

Table 1 Evaporator minimum and maximum water t


Max evaporator water T
Min evaporator water T

Note:
(1) Table referred to Cooling and Heating Mode

Table 2 Evaporator fouling factors


Fouling factors
m2C / kW

Cooling capacity
correction factor

Power input
correction factor

EER
correction factor

0.0176
0.0440
0.0880
0.1320

1.000
0.978
0.957
0.938

1.000
0.986
0.974
0.962

1.000
0.992
0.983
0.975

Note:
(1) Table referred to Cooling and Heating Mode

Table 3 Air heat exchanger - Altitude correction factors


Elevation above sea level (m)
0
300
Barometric pressure (mbar)
Cooling capacity correction factor
Power input correction factor

1013
1.000
1.000

977
0.993
1.005

600

900

1200

1500

1800

942
0.986
1.009

908
0.979
1.015

875
0.973
1.021

843
0.967
1.026

812
0.960
1.031

Notes:
(1) Table referred to Cooling Mode only
(2) Maximum operating altitude is 2000 m above sea level
(3) Contact factory in case the unit has to be installed at altitudes between 1000 and 2000 m above sea level

Table 4 Minimum glycol percentage for low water temperature


Evaporator Leaving Water Temperatue C
2
0
Ethylene glycol (%)
Propylene glycol (%)

10
10

20
20

-2

-4

-6

-8

20
20

20
30

30
30

30
30

Notes:
(1) Table referred to Cooling Mode only
(2) Minimum glycol percentage to be used with evaporator leaving water temperature below 4C to prevent freezing of water circuit.

Table 5 Minimum glycol percentage for low air ambient temperature


Air Ambient Temperatue C
-3
10%

Ethylene glycol (%)

Air Ambient Temperatue C


Propylene glycol (%)

-8

-15

-20

-3

20%

30%

40%

10%

-3

-7

-12

-20

-3

10%

20%

30%

40%

10%

Notes:
(1) Minimum glycol percentage to prevent freezing of water circuit at indicated air ambient temperature
(2) Air ambient temperature do exceed the operating limits of the unit, as protection of water circuit may be needed in winter season at nonworking conditions

Table 6 Correction factors for low evaporator leaving water temperature


Evaporator Leaving Water Temperatue C
2
0
-2
Cooling Capacity
Compressor Power Input

0.842
0.950

0.785
0.940

0.725
0.920

-4

-6

-8

0.670
0.890

0.613
0.870

0.562
0.840

Notes:
(1) Table referred to Cooling Mode only
(2) Correction factors have to be applied at working conditions: evaporator leaving water temperature 7C

Table 7 Correction factors for water and glycol mixture


Ethylene Glycol %
Ethylene Glycol

Propylene Glycol

10%

20%

30%

40%

50%

Cooling Capacity
Compressor Power Input
Flow Rate (same T)
Evaporator Pressure Drop

0.991
0.996
1.013
1.070

0.982
0.992
1.04
1.129

0.972
0.986
1.074
1.181

0.961
0.976
1.121
1.263

0.946
0.966
1.178
1.308

PropyleneGlycol %

0.985

0.964

0.932

0.889

0.846

Cooling Capacity
Compressor Power Input
Flow Rate (same T)
Evapoarator Pressure Drop

0.993
1.017
1.120
0.985

0.983
1.032
1.272
0.964

0.969
1.056
1.496
0.932

0.948
1.092
1.792
0.889

0.929
1.139
2.128
0.846

Notes:
(1) Table referred to Cooling Mode only
(2) In Heating mode correction factor is 1 at water temperature beetween operating limits
(3) Contact factory for water temperature out of operating limits

KPMHP00511-09EN page 21/60

How to use the Correction factors proposed in the previous tables


A) Mixture Water and Glycol --- Evaporator leaving water temperature > 4C
- depending from the type and percentage (%) of glycol filled in the circuit (see table 4.2 and 6)
- multiply the Cooling Capacity, the Compressor Power Input by the Correction factor of Table 6
- starting from this new value of Cooling Capacity, calculate the Flow Rate (l/s) and the Evaporatore Pressure Drop (kPa)
- now multiply the new Flow Rate and the new Evaporator Pressure Drop by the Correction Factors of Table 6
Example
Unit Size:

McEnergy HPI Extension 072.2 ST

Mixture:

Water

Working condition:
- Cooling capacity:
- Power input:
- Flow rate (t 5C):
- Evaporator pressure drop:

ELWT 12/7C Condenser inlet air temperature 35C


254 kW (rated Conditions)
90.3 kW (Rated Conditions)
12.12 l/s
37 kPa

Mixture:

Water + Ethylene Glycol 30% (for a winter air temperature up to -15C)

Working condition:
- Cooling capacity:
- Power input:
- Flow rate (t 5C):
- Evaporator pressure drop:

ELWT 12/7C Condenser inlet air temperature 35C


254 x 0.972 = 247 kW
90.3 x 0.986 = 89.0 kW
11.80 (referred to 247 kW) x 1.074 = 12.67 l/s
40 (referred to 12.67 l/s) x 1.181 = 47 kPa

B) Mixture Water and Glycol --- Evaporator leaving water temperature < 4C
- depending from the type and percentage (%) of glycol filled in the circuit (see table 4.1 and 4.2 and table 6)
- depending from the evaporator leaving water temperature (see table 5)
- multiply the Cooling Capacity, the Compressor Power Input by the Correction factor of Table 5 and Table 6
- starting from this new value of Cooling Capacity, calculate the Flow Rate (l/s) and the Evaporatore Pressure Drop (kPa)
- now multiply the new Flow Rate and the new Evaporator Pressure Drop by the Correction Factors of Table 6
Example
Unit Size:

McEnergy HPI Extension 072.2 ST

Mixture:

Water

Standard working condition


- Cooling capacity:
- Power input:
- Flow rate (t 5C):
- Evaporator pressure drop:

ELWT 12/7C Condenser inlet air temperature 30C


265 kW (Rated conditions)
83.3 kW (Rated conditions)
12.66 l/s
40 kPa

Mixture:

Water + Glycol 30% (for a low evaporator leaving temperature of -1/-6C)

Working condition:
- Cooling capacity:
- Power input:
- Flow rate (t 5C):
- Evaporator pressure drop:

ELWT -1/-6C Condenser inlet air temperature 30C


265 x 0.613 x 0.972 = 158 kW
83.3 x 0.870 x 0.986 = 71.5 kW
7.54 l/s (referred to 158 kW) x 1.074 = 8.10 l/s
18 kPa (referred to 8.10 l/s) x 1.181 = 21 kPa

KPMHP00511-09EN page 22/60

Below 150

Below 50

[mgCaCO3/l]

[mgSiO2/l]

[mgFe/l]

[mgCu/l]

Calcium harness

Silca ion

Iron

Copper

[mgCO2/l]

Cooling Water

---

Below 4.0

Below 0.3

Below 0.1

Not detectable

Below 0.1

Below 0.3

Below 30

Below 50

Below 70

Below 50

Below 50

Below 50

(Below 300)

Below 30

6.0 ~ 8.0

Supply water (4)

---

Below 4.0

Below 0.3

Below 1.0

Not detectable

Below 1.0

Below 1.0

Below 30

Below 50

Below 70

Below 50

Below 50

Below 50

(Below 400)

Below 40

6.0 ~ 8.0

Flowing water

Once Flow

---

Below 4.0

Below 0.3

Below 1.0

Not detectable

Below 1.0

Below 1.0

Below 30

Below 50

Below 70

Below 50

Below 50

Below 50

(Below 400)

Below 40

6.0 ~ 8.0

[Below 20C]

Circulating water

---

Below 0.4

Below 0.25

Below 0.3

Not detectable

Below 1.0

Below 1.0

Below 30

Below 50

Below 70

Below 50

Below 50

Below 50

(Below 300)

Below 30

7.0 ~ 8.0

[20C ~ 60C]

Circulating water

4 Supply water is considered drink water, industrial water and ground water except for genuine water, neutral water and soft water.
5 The above mentioned items are representable items in corrosion and scale cases.

3 In the cooling water using hermetic cooling tower, close circuit water is according to heated water standard, and scattered water is according to cooling water standard.

---

Below 4.0

Below 0.3

Below 0.1

Not detectable

Below 0.1

Below 0.3

Below 30

Below 50

Below 70

Below 50

Below 50

Below 50

(Below 300)

Below 30

7.0 ~ 8.0

---

Below 0.4

Below 0.1

Below 0.1

Not detectable

Below 1.0

Below 1.0

Below 30

Below 50

Below 70

Below 50

Below 30

Below 30

(Below 300)

Below 30

7.0 ~ 8.0

[60C ~ 80C]

---

Below 4.0

Below 0.3

Below 0.1

Not detectable

Below 0.1

Below 0.3

Below 30

Below 50

Below 70

Below 50

Below 30

Below 30

(Below 300)

Below 30

7.0 ~ 8.0

Supply water (4)

High temperature
Circulating water

Heated water (2)

Supply water (4)

Low temperature

Especially when the iron materials is in direct contact with water without any protection shields, it is desireable to give the valid measure for corrosion. E.g. chemical measure

2 In case of using heated water (more than 40C), corrosion is generally noticeable.

---

Below 4.0

Below 0.3

Below 0.1

Not detectable

Below 1.0

Below 0.3

Below 30

Below 50

Below 70

Below 50

Below 50

Below 50

(Below 300)

Below 30

6.0 ~ 8.0

Supply water (4)

Cooled Water

1 Names, definitions and units are according to JIS K 0101. Units and figures between brackets are old units published as reference only.

Stability index

6.0 ~ 7.0

Below 4.0

[mgCL/l]

Free carbide

Below 0.3

[mgNH 4/l]

Remaining chloride

Below 1.0

Not detectable

Below 0.3

Ammonium ion

[mgS /l]

2-

Below 200

[mgCaCO3/l]

Total hardness

Sulfite ion

Below 100

[mgCaCO3/l]

M-alkalinity (pH4.8)

Below 1.0

Below 200

[mgSO 4/l]

2-

[mgCl /l]

Below 200

(Below 800)

(S/cm) at 25C

2-

Below 80

6.5 ~ 8.2

[mS/m] at 25C

at 25C

Circulating water

Sulfate ion

Chloride ion

Electrical conductivity

pH

Items (1) (5)

Items to be controlled:

Items to be referred to

Circulating System

Corrosion + Scale

Corrosion

Corrosion

Corrosion

Corrosion

Corrosion

Corrosion + Scale

Scale

Scale

Scale

Scale

Corrosion

Corrosion

Corrosion + Scale

Corrosion + Scale

Corrosion + Scale

Tendency if out of criteria

Water charge, flow and quality

KPMHP00511-09EN page 23/60

Water content in cooling circuits


The cooled water distribution circuits should have minimum water content to avoid excessive compressors start and
stop.
In fact, each time the compressor starts up, an excessive quantity of oil goes from the compressor sump and
simultaneously there is a rise in the temperature of the compressor motors stator due to the inrush current during the
start-up. To prevent damage to the compressors, McQuay has envisaged the application of a device to limit frequent
stops and restarts.
During the span of one hour there will be no more than 6 starts of the compressor. The plant side should therefore
ensure that the overall water content allows a more constant functioning of the unit and consequently greater
environmental comfort. The minimum water content per unit should be calculated with a certain approximation using this
simplified formula:
For 2 compressors unit
M (liters) = ( 0.1595 x T(C) + 3.0825 ) x P(kW)

For 3 compressors unit


M (liters) = (0.0443 x T(C) + 1.6202) x P(kW)

where:
M
= minimum water content per unit expressed in litres
P
= cooling capacity of the unit expressed in kW
T
= evaporator entering / leaving water temperature difference expressed in C
This formula is valid for:
- standard microprocessor parameters
For more accurate determination of quantity of water, it is advisable to contact the designer of the plant.

KPMHP00511-09EN page 24/60

Automatic and Manual Boost - Cooling Mode


Manual Boost
Max frequency

Boost conditions

Boost conditions

Nominal frequency

Automatic Boost

Frequency(Hz)

Rated conditions

20

22.5

25

27.5

30

32.5

35

37.5

40

CondenserInletAirTemp.(C)

Automatic and Manual Boost - Heating Mode


Boost conditions

Max frequency

Manual Boost

Automatic Boost

Nominal frequency

Rated conditions

Frequency(Hz)

Boost conditions

12

10

10

12

EvaporatorInletAirTemp.(C)

Automatic boost: unit standard configuration


Manual boost: customized configuration by different settings
Rated conditions: compressors are running at nominal frequency
Boost conditions: compressors are running at the maximum frequency

KPMHP00511-09EN page 25/60

Heating Capacity correction factors for different evaporator inlet air temperature and relative
humidity conditions
1.05

1.00

Ambient Temp. <0C

CorrectionFactor

0.95

0.90
Ambient Temp. 0C
Ambient Temp. 4C
0.85
Ambient Temp. 7C
Ambient Temp. 10C
0.80
Ambient Temp. 12C

0.75
40%

45%

50%

55%

60%

65%

70%

75%

80%

85%

90%

RelativeHumidity(%)

Integrated Heating Capacity - Automatic Boost


1.05

1.00

CorrectionFactor

0.95

Power Input
0.90

0.85

Heating Capacity
0.80

0.75
12

10

10

12

EvaporatorInletAirTemp.(C)

Correction factors to be applied to Standard Ratings in Heating Mode (Relative Humidity: 85% with evaporator inlet air temperature
above 0C ; 100% with evaporator inlet air temperature below 0C)

KPMHP00511-09EN page 26/60

14

Integrated Heating Capacity - Manual Boost


1.05

1.00

CorrectionFactor

0.95

Power Input
0.90

0.85

Heating Capacity
0.80

0.75
12

10

10

12

14

EvaporatorInletAirTemp.(C)

Correction factors to be applied to Standard Ratings in Heating Mode (Relative Humidity: 85% with evaporator inlet air temperature
above 0C ; 100% with evaporator inlet air temperature below 0C)

KPMHP00511-09EN page 27/60

KPMHP00511-09EN page 28/60

093.2

083.2

079.2

072.2

Rated
Cc (kW)
Pi (kW)
263
68.3
271
69.1
279
69.9
287
70.9
295
71.8
303
72.7
312
73.6
320
74.6
329
75.6
338
76.5
347
77.6
356
78.6
283
74.8
291
75.8
300
76.7
309
77.7
317
78.7
326
79.8
335
80.8
344
81.9
353
82.9
363
84.0
372
85.2
382
86.3
304
81.4
312
82.5
321
83.5
330
84.6
340
85.7
349
86.8
358
88.0
368
89.1
378
90.3
388
91.5
397
92.7
407
94.0
335
87.6
345
88.7
355
89.7
365
90.8
375
91.9
386
93.0
396
94.2
407
95.3
418
96.5
429
97.7
440
98.9
451
100

20

Boost
Cc (kW)
Pi (kW)
358
114
368
116
378
118
388
119
398
121
409
122
419
124
430
126
440
128
451
130
462
131
473
133
377
124
386
124
397
126
406
126
415
127
424
128
433
128
444
130
453
131
462
131
471
132
481
133
397
133
405
132
416
134
423
133
431
133
439
133
446
132
457
134
465
134
473
133
480
133
488
132
452
145
465
147
475
148
486
149
499
151
510
152
521
153
532
154
543
155
557
157
568
158
577
157

Rated
Cc (kW)
Pi (kW)
253
74.1
261
75.0
268
75.9
276
76.8
284
77.8
293
78.7
301
79.7
309
80.7
318
81.7
327
82.7
335
83.8
344
84.9
273
81.4
281
82.4
289
83.4
297
84.4
306
85.4
315
86.5
323
87.6
332
88.7
341
89.8
350
91.0
360
92.1
369
93.3
292
88.7
301
89.8
309
90.9
318
92.0
327
93.1
336
94.3
346
95.5
355
96.7
365
97.9
374
99.2
384
100
394
102
322
95
332
96
342
97
352
98
362
100
372
101
383
102
393
103
404
104
415
106
425
107
437
108

25
Boost
Cc (kW)
Pi (kW)
343
125
353
127
363
129
373
130
383
132
393
134
400
133
408
133
415
133
422
132
433
134
440
133
355
129
363
130
372
130
382
132
391
133
399
133
407
133
416
133
423
133
430
132
439
133
448
134
366
133
374
133
381
132
391
134
398
133
406
133
413
132
423
134
430
133
437
132
444
132
455
134
427
154
437
155
449
157
459
157
468
157
477
156
487
157
498
157
507
157
515
156
526
157
537
158

Notes:
Cc (cooling capacity) - Pi (unit power input) ELWT (evaporator leaving water temperature t 5C).
Data are referred to 0,0176 m2 C/kW evaporator fouling factor
Rated conditions are for compressors running at nominal frequency.
Boost conditions are for compressors running at maximum frequency.
10% glycol is recommend for shaded area conditions

4
5
6
7
8
9
10
11
12
13
14
15
4
5
6
7
8
9
10
11
12
13
14
15
4
5
6
7
8
9
10
11
12
13
14
15
4
5
6
7
8
9
10
11
12
13
14
15

ELWT (C)
Rated
Cc (kW)
Pi (kW)
242
80.4
250
81.4
258
82.3
265
83.3
273
84.2
281
85.3
289
86.3
298
87.3
306
88.4
314
89.5
323
90.5
332
91.7
261
88.5
269
89.5
277
90.6
285
91.6
294
92.7
302
93.8
311
95.0
320
96.1
328
97.3
337
98.5
346
100
355
101
280
96.5
288
97.7
297
98.8
306
100
314
101
323
102
332
104
341
105
351
106
360
107
370
109
379
110
309
103
319
105
328
106
338
107
348
108
358
109
368
110
378
112
389
113
400
114
410
116
421
117

30
Boost
Cc (kW)
Pi (kW)
326
134
333
134
339
133
346
133
353
133
360
132
370
134
377
133
383
133
390
132
400
134
407
133
318
133
326
133
334
134
341
133
347
133
354
132
363
134
370
133
376
132
384
133
392
133
399
133
336
133
342
132
352
134
359
133
366
133
372
132
382
133
389
133
395
132
405
134
412
133
418
132
396
157
404
157
412
156
423
158
431
157
440
157
450
157
459
158
468
157
478
157
485
156
495
157

Rated
Cc (kW)
Pi (kW)
231
87.3
239
88.4
246
89.3
254
90.3
261
91.4
269
92.4
277
93.4
285
94.5
293
95.6
301
96.7
310
97.8
318
99.0
249
96.2
257
97.3
265
98.4
273
100
281
101
289
102
297
103
306
104
315
105
323
107
332
108
341
109
267
105
275
106
283
107
292
109
300
110
309
111
318
112
327
114
336
115
345
116
354
118
364
119
295
112
305
113
314
115
324
116
333
117
343
118
353
120
363
121
373
122
383
124
394
125
404
126

Boost
Cc (kW)
Pi (kW)
295
132
304
134
311
133
317
133
323
132
333
134
339
133
345
133
352
132
361
133
367
133
374
132
300
132
309
134
315
133
322
132
330
133
337
133
343
133
351
133
357
132
365
133
373
133
379
132
305
132
314
134
320
133
326
132
336
134
342
133
348
132
357
134
363
133
369
131
379
133
385
132
361
157
369
157
378
157
387
158
395
157
404
157
411
156
421
157
430
157
437
156
447
157
456
157

Condenser Inlet Air Temperature (C)


35
Rated
Cc (kW)
Pi (kW)
290
132
299
134
305
133
311
133
318
132
326
134
333
133
340
133
346
132
355
133
361
133
367
132
295
132
303
134
310
133
316
132
324
133
331
133
337
133
345
133
351
132
359
132
367
133
373
132
299
132
308
134
315
133
321
132
329
133
336
133
342
132
351
134
357
133
363
131
372
133
378
132
354
157
362
156
371
157
380
157
388
157
397
157
405
156
413
157
423
157
430
156
439
156
449
157

36
Boost
Cc (kW)
Pi (kW)
290
132
299
134
305
133
311
133
318
132
326
134
333
133
340
133
346
132
355
133
361
133
367
132
295
132
303
134
310
133
316
132
324
133
331
133
337
133
345
133
351
132
359
132
367
133
373
132
299
132
308
134
315
133
321
132
329
133
336
133
342
132
351
134
357
133
363
131
372
133
378
132
354
157
362
156
371
157
380
157
388
157
397
157
405
156
413
157
423
157
430
156
439
156
449
157

Rated
Cc (kW)
Pi (kW)
270
134
276
133
282
133
288
132
296
134
302
133
308
132
317
134
323
133
329
132
338
134
343
133
273
134
279
133
287
133
292
133
300
133
307
133
313
132
322
134
327
133
333
132
342
133
347
132
253
114
261
116
269
117
277
118
286
119
294
121
303
122
311
123
320
125
329
126
338
128
347
129
327
157
334
156
344
158
351
157
360
157
368
157
377
158
384
156
392
157
401
157
408
156
419
158

40
Boost
Cc (kW)
Pi (kW)
270
134
276
133
282
133
288
132
296
134
302
133
308
132
317
134
323
133
329
132
338
134
343
133
273
134
279
133
287
133
292
133
300
133
307
133
313
132
322
134
327
133
333
132
342
133
347
132
277
133
283
132
292
134
297
133
303
132
312
133
317
132
326
134
332
133
337
131
346
133
351
132
327
157
334
156
344
158
351
157
360
157
368
157
377
158
384
156
392
157
401
157
408
156
419
158

Rated
Cc (kW)
Pi (kW)
230
122
238
123
243
122
251
124
256
123
261
122
269
123
274
122
282
123
287
122
295
124
300
123
232
122
240
123
245
122
253
123
258
122
264
123
270
123
277
123
283
123
290
123
296
123
303
123
235
122
242
123
247
122
255
123
260
122
268
123
272
122
280
123
285
122
293
123
297
121
306
123
281
147
289
147
296
147
304
147
310
145
319
147
325
146
335
147
341
146
350
147
356
146
366
147

45
Boost
Cc (kW)
Pi (kW)
230
122
238
123
243
122
251
124
256
123
261
122
269
123
274
122
282
123
287
122
295
124
300
123
232
122
240
123
245
122
253
123
258
122
264
123
270
123
277
123
283
123
290
123
296
123
303
123
235
122
242
123
247
122
255
123
260
122
268
123
272
122
280
123
285
122
293
123
297
121
306
123
281
147
289
147
296
147
304
147
310
145
319
147
325
146
335
147
341
146
350
147
356
146
366
147

Standard ratings

Cooling Mode - McEnergy HPI Extension SE-ST

KPMHP00511-09EN page 29/60

117.2

109.2

103.2

096.2

Rated
Cc (kW)
Pi (kW)
351
93.4
362
94.5
372
95.6
383
96.8
393
98.0
404
99.2
415
100
426
102
438
103
449
104
461
106
472
107
378
100
389
102
401
103
412
104
424
106
435
107
447
108
459
110
471
111
484
113
496
114
509
116
397
107
409
108
420
109
432
111
444
112
456
114
468
115
481
117
493
118
506
120
519
121
532
123
427
114
440
116
452
117
465
118
478
120
491
121
504
123
518
124
531
126
545
127
559
129
573
131

20

Boost
Cc (kW)
Pi (kW)
472
156
485
158
498
160
511
163
524
165
537
167
551
169
564
171
578
174
592
176
606
178
616
178
504
167
518
170
530
170
542
171
554
172
566
173
580
175
592
176
604
177
615
176
625
176
639
178
522
176
537
178
547
178
557
177
567
177
577
176
592
178
602
178
612
177
622
177
632
176
647
178
572
191
588
193
603
195
617
196
628
196
642
197
653
196
664
195
678
196
689
196
703
197
714
196

Rated
Cc (kW)
Pi (kW)
339
102
349
103
359
104
369
105
380
106
390
108
401
109
412
110
423
111
434
113
445
114
457
116
364
109
375
111
386
112
397
113
409
115
420
116
432
118
443
119
455
120
467
122
480
123
492
125
382
116
393
118
405
119
416
120
428
122
440
123
452
125
464
127
477
128
489
130
502
131
514
133
412
124
424
126
436
127
449
129
461
130
474
132
487
133
500
135
514
136
527
138
541
140
555
141

25
Boost
Cc (kW)
Pi (kW)
453
171
466
174
478
176
491
178
501
177
510
177
519
176
533
178
542
178
551
177
560
176
574
178
475
175
486
176
499
179
509
178
519
177
528
176
540
177
551
178
561
177
570
176
582
177
594
178
483
177
492
176
506
179
515
178
525
177
534
176
548
179
557
178
567
177
576
176
590
178
599
177
534
196
545
195
557
196
570
197
581
196
591
195
607
197
617
196
628
196
640
196
654
197
664
196

Notes:
Cc (cooling capacity) - Pi (unit power input) ELWT (evaporator leaving water temperature t 5C).
Data are referred to 0,0176 m2 C/kW evaporator fouling factor
Rated conditions are for compressors running at nominal frequency.
Boost conditions are for compressors running at maximum frequency.
10% glycol is recommend for shaded area conditions

4
5
6
7
8
9
10
11
12
13
14
15
4
5
6
7
8
9
10
11
12
13
14
15
4
5
6
7
8
9
10
11
12
13
14
15
4
5
6
7
8
9
10
11
12
13
14
15

ELWT (C)
Rated
Cc (kW)
Pi (kW)
325
110
335
112
345
113
355
114
365
115
375
117
386
118
397
119
407
121
418
122
429
124
440
125
349
119
360
120
370
122
381
123
392
124
404
126
415
127
427
129
438
131
450
132
462
134
474
135
366
126
377
128
388
129
400
131
411
132
423
134
435
136
446
137
459
139
471
141
483
142
496
144
395
135
407
137
419
138
431
140
444
141
456
143
469
144
482
146
495
148
508
149
522
151
535
153

30
Boost
Cc (kW)
Pi (kW)
424
178
433
177
442
176
454
179
463
178
472
177
480
177
493
179
502
178
510
177
519
176
532
178
438
177
447
176
458
177
468
178
477
177
486
176
497
177
508
177
517
176
528
177
539
178
547
177
443
177
452
176
465
178
473
178
482
177
491
176
504
178
513
177
521
176
535
178
543
177
551
176
491
197
501
196
511
195
525
197
535
196
545
195
560
198
569
196
579
195
594
198
603
196
613
195

Rated
Cc (kW)
Pi (kW)
310
120.1
320
121.4
329
122.6
339
124.0
349
125.3
359
126.7
370
128.1
380
129.5
391
130.9
401
132.4
412
133.8
423
135.3
333
129.4
343
130.8
354
132.2
365
133.7
375
135.2
386
136.7
397
138.3
409
139.9
420
141.5
431
143.1
443
144.8
455
146.5
349
137.8
360
139.3
371
140.8
382
142.4
393
144.0
405
145.6
416
147.3
428
149.0
439
150.7
451
152.5
463
154.3
476
156.1
377
147
389
149
401
150
413
152
425
153
437
155
450
157
462
158
475
160
488
162
501
164
514
165

Boost
Cc (kW)
Pi (kW)
388
178
397
177
405
176
416
179
425
178
433
177
441
176
453
178
461
177
469
176
481
178
489
177
399
177
409
177
419
178
428
177
438
178
446
176
456
177
467
178
475
176
485
177
495
177
503
176
403
176
415
178
423
177
431
176
444
178
452
177
460
176
472
178
480
177
488
175
501
178
508
176
449
197
458
196
469
196
480
197
489
195
501
196
512
196
521
195
535
197
544
196
553
195
567
197

Condenser Inlet Air Temperature (C)


35
Rated
Cc (kW)
Pi (kW)
381
178
389
177
398
177
409
178
417
177
426
177
434
176
445
178
453
177
461
176
473
178
481
177
392
177
402
177
411
178
420
177
430
178
439
177
448
177
459
178
467
177
476
177
487
177
495
176
396
177
407
178
415
177
424
176
435
178
444
177
452
176
464
178
472
177
479
176
492
178
500
176
437
194
447
194
458
194
469
195
478
193
489
194
500
194
509
193
523
195
532
194
541
193
554
194

36
Boost
Cc (kW)
Pi (kW)
381
178
389
177
398
177
409
178
417
177
426
177
434
176
445
178
453
177
461
176
473
178
481
177
392
177
402
177
411
178
420
177
430
178
439
177
448
177
459
178
467
177
476
177
487
177
495
176
396
177
407
178
415
177
424
176
435
178
444
177
452
176
464
178
472
177
479
176
492
178
500
176
437
194
447
194
458
194
469
195
478
193
489
194
500
194
509
193
523
195
532
194
541
193
554
194

Rated
Cc (kW)
Pi (kW)
352
177.7
360
176.7
371
178.8
379
177.7
386
176.7
398
178.7
405
177.6
413
176.4
424
178.5
431
177.2
439
176.0
450
178.0
362
177.2
372
177.6
379
176.5
389
177.0
398
177.3
408
177.8
416
176.5
427
178.6
435
177.2
442
175.8
454
177.9
462
176.4
366
178.1
374
176.8
382
175.5
393
177.5
401
176.1
412
178.1
420
176.7
431
178.7
439
177.2
446
175.7
458
177.7
465
176.1
393
185.7
403
186.2
411
184.7
424
186.7
432
185.2
442
185.2
452
185.6
462
185.6
473
186.0
483
186.0
493
186.3
501
184.6

40
Boost
Cc (kW)
Pi (kW)
352
178
360
177
371
179
379
178
386
177
398
179
405
178
413
176
424
178
431
177
439
176
450
178
362
177
372
178
379
176
389
177
398
177
408
178
416
176
427
179
435
177
442
176
454
178
462
176
366
178
374
177
382
175
393
177
401
176
412
178
420
177
431
179
439
177
446
176
458
178
465
176
393
186
403
186
411
185
424
187
432
185
442
185
452
186
462
186
473
186
483
186
493
186
501
185

Rated
Cc (kW)
Pi (kW)
307
461.0
314
466.5
324
478.3
331
483.7
337
489.0
348
500.9
354
506.1
365
518.2
371
523.1
382
535.5
388
540.3
398
552.7
313
166.1
323
167.9
330
166.4
341
168.2
347
166.7
356
166.9
364
166.9
373
167.1
381
167.1
390
167.2
399
167.2
407
167.3
315
166.3
326
168.0
332
166.4
343
168.1
349
166.5
360
168.2
366
166.5
377
168.2
383
166.4
394
168.1
400
166.3
411
168.0
352
186.0
360
184.3
371
186.2
378
184.4
390
186.3
397
184.5
409
186.3
416
184.4
428
186.3
435
184.4
448
186.2
457
186.0

45
Boost
Cc (kW)
Pi (kW)
307
168
314
166
324
168
331
167
337
166
348
167
354
166
365
168
371
166
382
168
388
166
398
168
313
166
323
168
330
166
341
168
347
167
356
167
364
167
373
167
381
167
390
167
399
167
407
167
315
166
326
168
332
166
343
168
349
166
360
168
366
166
377
168
383
166
394
168
400
166
411
168
352
186
360
184
371
186
378
184
390
186
397
185
409
186
416
184
428
186
435
184
448
186
457
186

KPMHP00511-09EN page 30/60

167.3

153.3

144.3

130.3

124.2

Rated
Cc (kW)
Pi (kW)
452
122
465
124
478
125
491
127
505
128
519
130
533
132
547
133
561
135
575
137
590
138
605
140
472
122
486
124
500
125
514
127
529
128
544
130
559
131
574
133
590
134
605
136
621
138
637
139
522
135
537
136
553
138
569
140
585
141
602
143
619
145
636
147
653
149
670
151
688
153
706
155
540
140
556
142
572
144
589
145
605
147
622
149
639
151
657
153
674
155
692
157
710
159
729
161
606
161
624
163
642
166
660
168
679
170
698
172
717
174
736
177
755
179
775
182
795
184
815
186

20

Boost
Cc (kW)
Pi (kW)
602
206
618
209
634
211
646
211
658
210
675
213
687
212
699
211
710
211
722
210
739
213
751
212
640
201
658
203
675
206
688
205
701
205
714
204
727
203
745
206
758
205
771
205
783
204
796
203
708
225
726
226
746
229
764
231
782
233
801
235
819
238
838
240
857
242
878
245
893
244
912
247
730
235
750
238
770
241
791
244
812
247
833
251
854
254
875
258
897
261
918
265
934
264
956
268
802
267
817
266
833
265
848
265
864
264
886
268
902
267
917
266
933
265
948
264
971
268
986
267

Rated
Cc (kW)
Pi (kW)
435
133
448
135
461
136
474
138
487
139
501
141
514
143
528
145
542
146
556
148
570
150
585
152
455
133
468
134
482
136
496
137
511
139
525
140
540
142
555
144
570
145
585
147
601
149
617
150
503
146
518
148
533
150
549
152
565
153
581
155
597
157
614
159
631
161
648
163
665
165
682
167
520
152
536
154
552
156
568
158
584
160
601
162
617
164
634
166
652
168
669
170
687
172
705
174
583
176
601
178
618
180
636
182
654
185
673
187
691
189
710
192
729
194
749
197
768
199
788
202

25
Boost
Cc (kW)
Pi (kW)
562
211
573
211
584
210
600
212
611
211
622
210
638
213
649
212
660
211
671
210
687
213
698
212
592
203
609
206
621
205
633
204
650
206
662
206
674
205
685
204
703
206
715
205
726
204
738
204
672
240
689
242
707
244
724
246
738
245
754
246
768
245
786
247
799
246
815
246
829
245
843
244
701
257
721
261
741
264
761
267
776
266
790
265
805
264
825
268
840
267
855
266
869
265
883
264
734
264
755
268
769
266
784
265
798
264
819
268
834
266
848
265
862
264
884
267
898
266
912
265

Notes:
Cc (cooling capacity) - Pi (unit power input) ELWT (evaporator leaving water temperature t 5C).
Data are referred to 0,0176 m2 C/kW evaporator fouling factor
Rated conditions are for compressors running at nominal frequency.
Boost conditions are for compressors running at maximum frequency.
10% glycol is recommend for shaded area conditions

4
5
6
7
8
9
10
11
12
13
14
15
4
5
6
7
8
9
10
11
12
13
14
15
4
5
6
7
8
9
10
11
12
13
14
15
4
5
6
7
8
9
10
11
12
13
14
15
4
5
6
7
8
9
10
11
12
13
14
15

ELWT (C)
Rated
Cc (kW)
Pi (kW)
417
145
430
147
443
148
455
150
468
152
482
153
495
155
508
157
522
159
536
160
550
162
564
164
436
144
450
146
463
147
477
149
491
150
506
152
520
154
535
155
549
157
564
159
580
161
595
162
482
159
497
161
512
163
527
164
543
166
559
168
575
170
591
172
607
174
624
176
641
178
658
180
499
166
514
168
530
169
545
171
561
173
578
175
594
177
611
179
627
181
644
184
662
186
679
188
559
191
576
193
593
196
611
198
628
200
646
203
664
205
683
208
701
210
720
213
739
216
759
218

30
Boost
Cc (kW)
Pi (kW)
517
212
528
211
538
210
553
213
563
212
573
211
589
213
599
212
609
211
624
213
635
212
645
211
544
205
555
204
571
206
582
205
593
204
609
206
620
205
631
204
647
206
658
205
669
204
686
206
623
246
638
246
651
245
664
244
680
246
695
246
708
245
721
244
740
247
752
245
765
244
784
247
656
267
670
266
683
265
697
264
716
268
730
266
743
265
757
264
777
267
790
266
804
264
824
268
678
268
692
267
705
266
718
264
738
268
752
266
765
265
785
268
799
266
812
265
832
268
845
266

Rated
Cc (kW)
Pi (kW)
398
158
411
159
423
161
436
163
448
165
461
166
474
168
487
170
501
172
514
174
528
176
542
178
417
156
430
158
443
160
457
161
471
163
485
165
499
166
513
168
527
170
542
172
557
174
572
175
460
173
475
174
490
176
505
178
520
180
535
182
551
184
567
186
583
188
599
190
615
193
632
195
476
180
491
182
506
184
522
186
537
188
553
190
569
192
585
194
602
196
618
199
635
201
652
203
533
208
549
210
566
213
583
215
601
218
618
220
636
223
654
225
672
228
690
231
709
233
728
236

Boost
Cc (kW)
Pi (kW)
472
212
482
210
496
213
505
212
515
210
529
213
539
212
548
210
563
213
572
211
581
210
596
212
495
204
505
203
520
206
530
204
540
203
556
205
566
204
582
206
592
205
601
203
617
205
627
204
569
246
582
246
595
245
610
246
624
246
636
245
647
244
665
247
677
245
691
245
707
246
719
245
600
267
613
266
626
265
644
268
656
267
669
266
682
264
700
267
713
266
725
264
744
267
757
266
616
266
628
265
647
268
660
267
672
265
691
268
703
266
715
264
735
268
747
266
759
264
778
267

Condenser Inlet Air Temperature (C)


35
Rated
Cc (kW)
Pi (kW)
460
209
471
209
484
210
494
210
503
209
517
210
527
210
536
208
550
211
559
209
569
208
583
210
485
204
496
204
510
205
521
205
531
203
545
205
556
204
571
206
581
205
591
203
606
205
617
204
558
246
571
246
584
245
599
246
612
246
625
245
637
244
654
246
666
245
679
245
695
246
707
245
589
267
601
266
615
265
632
268
644
266
658
266
670
265
688
267
701
266
714
264
731
267
744
266
604
266
617
265
634
268
648
267
660
265
678
267
691
266
703
265
722
268
734
266
745
264
765
267

36
Boost
Cc (kW)
Pi (kW)
460
209
471
209
484
210
494
210
503
209
517
210
527
210
536
208
550
211
559
209
569
208
583
210
485
204
496
204
510
205
521
205
531
203
545
205
556
204
571
206
581
205
591
203
606
205
617
204
558
246
571
246
584
245
599
246
612
246
625
245
637
244
654
246
666
245
679
245
695
246
707
245
589
267
601
266
615
265
632
268
644
266
658
266
670
265
688
267
701
266
714
264
731
267
744
266
604
266
617
265
634
268
648
267
660
265
678
267
691
266
703
265
722
268
734
266
745
264
765
267

Rated
Cc (kW)
Pi (kW)
414
200
427
202
436
200
449
203
457
201
465
199
479
201
487
200
500
202
508
200
522
202
530
200
446
204
461
206
470
204
484
206
494
205
503
203
517
206
527
204
541
206
550
204
559
203
574
205
516
246
527
245
542
246
554
246
566
245
582
247
593
246
606
245
621
247
632
245
644
245
660
246
544
266
556
265
573
268
585
267
596
265
614
268
626
266
637
265
655
268
667
266
678
264
696
267
554
264
571
267
583
265
601
268
612
266
623
264
641
267
652
265
671
268
682
266
693
263
711
266

40
Boost
Cc (kW)
Pi (kW)
414
200
427
202
436
200
449
203
457
201
465
199
479
201
487
200
500
202
508
200
522
202
530
200
446
204
461
206
470
204
484
206
494
205
503
203
517
206
527
204
541
206
550
204
559
203
574
205
516
246
527
245
542
246
554
246
566
245
582
247
593
246
606
245
621
247
632
245
644
245
660
246
544
266
556
265
573
268
585
267
596
265
614
268
626
266
637
265
655
268
667
266
678
264
696
267
554
264
571
267
583
265
601
268
612
266
623
264
641
267
652
265
671
268
682
266
693
263
711
266

Rated
Cc (kW)
Pi (kW)
373
202
381
200
393
202
401
200
413
202
421
200
433
202
441
200
454
202
461
200
474
202
481
200
379
188
391
190
399
188
412
190
419
188
433
189
440
188
453
189
460
187
474
189
488
191
495
189
445
231
455
229
469
231
479
229
490
229
503
230
515
229
528
230
539
229
552
230
564
229
580
232
473
251
484
249
499
252
510
250
520
248
536
251
546
249
562
251
572
249
588
252
598
250
615
252
481
251
490
248
506
251
516
249
532
251
542
249
558
251
568
249
584
251
593
249
610
251
619
248

45
Boost
Cc (kW)
Pi (kW)
373
202
381
200
393
202
401
200
413
202
421
200
433
202
441
200
454
202
461
200
474
202
481
200
379
188
391
190
399
188
412
190
419
188
433
189
440
188
453
189
460
187
474
189
488
191
495
189
445
231
455
229
469
231
479
229
490
229
503
230
515
229
528
230
539
229
552
230
564
229
580
232
473
251
484
249
499
252
510
250
520
248
536
251
546
249
562
251
572
249
588
252
598
250
615
252
481
251
490
248
506
251
516
249
532
251
542
249
558
251
568
249
584
251
593
249
610
251
619
248

093.2

083.2

079.2

072.2

Rated
Cc (kW)
Pi (kW)
258
65.5
266
66.4
274
67.4
282
68.4
290
69.4
298
70.4
306
71.5
314
72.5
323
73.6
331
74.7
340
75.8
349
77.0
278
72.6
286
73.7
294
74.8
303
75.9
311
77.0
320
78.1
328
79.3
337
80.5
346
81.7
355
82.9
364
84.2
373
85.4
305
80.8
314
82.0
323
83.2
332
84.5
341
85.8
351
87.1
360
88.5
370
89.8
380
91.2
389
92.6
400
94.1
410
95.6
329
83.7
339
84.9
349
86.0
359
87.2
369
88.5
379
89.7
389
91.0
400
92.2
410
93.6
421
94.9
432
96.2
443
97.6

20

Boost
Cc (kW)
Pi (kW)
348
116
358
118
367
120
377
122
387
124
397
125
407
127
414
127
422
127
429
127
436
126
446
128
361
121
371
123
379
124
388
125
396
125
405
126
413
127
422
128
430
127
437
127
444
127
452
127
382
126
393
128
400
128
407
128
415
127
422
127
429
126
440
128
447
128
454
127
462
127
469
126
436
144
448
146
459
147
469
148
479
149
490
150
498
150
509
150
518
150
526
149
535
149
545
150

Rated
Cc (kW)
Pi (kW)
248
71.5
256
72.5
263
73.5
271
74.6
279
75.6
287
76.7
295
77.8
303
78.9
311
80.0
320
81.2
328
82.3
337
83.5
267
79.4
275
80.5
283
81.6
291
82.8
299
84.0
308
85.1
316
86.4
325
87.6
334
88.9
342
90.1
351
91.4
360
92.8
293
88.3
301
89.6
310
90.9
319
92.2
328
93.5
337
94.9
347
96.3
356
97.7
365
99.2
375
101
385
102
395
104
317
91.6
326
92.8
336
94.0
345
95.2
355
96.5
365
97.8
375
99.1
386
100
396
102
406
103
417
105
428
106

25
Boost
Cc (kW)
Pi (kW)
333
127
340
127
347
127
354
126
363
128
370
128
377
127
384
127
391
127
400
129
407
128
414
128
340
128
347
127
354
127
360
127
369
127
377
128
384
127
390
127
397
126
407
128
413
128
420
127
354
128
361
128
368
127
374
126
385
128
391
128
398
127
405
126
415
128
422
128
428
127
435
126
409
150
417
150
427
150
435
150
444
149
452
149
463
151
472
150
480
149
487
149
499
151
507
150

Notes:
Cc (cooling capacity) - Pi (unit power input) ELWT (evaporator leaving water temperature t 5C).
Data are referred to 0,0176 m2 C/kW evaporator fouling factor
Rated conditions are for compressors running at nominal frequency.
Boost conditions are for compressors running at maximum frequency.
10% glycol is recommend for shaded area conditions

4
5
6
7
8
9
10
11
12
13
14
15
4
5
6
7
8
9
10
11
12
13
14
15
4
5
6
7
8
9
10
11
12
13
14
15
4
5
6
7
8
9
10
11
12
13
14
15

ELWT (C)
Rated
Cc (kW)
Pi (kW)
237
78.1
245
79.2
252
80.2
260
81.3
267
82.4
275
83.5
283
84.6
291
85.8
299
86.9
307
88.1
315
89.4
324
90.6
255
86.8
263
87.9
271
89.1
279
90.3
287
91.5
295
92.8
303
94.0
312
95.3
320
96.6
329
98.0
338
99.3
346
101
280
96.4
288
97.8
297
99.1
305
100
314
102
323
103
332
105
341
106
351
108
360
109
369
111
379
112
303
100
313
101
322
103
331
104
341
105
351
107
361
108
371
109
381
111
391
112
401
114
412
115

30
Boost
Cc (kW)
Pi (kW)
306
127
312
127
321
128
328
128
334
128
341
127
347
127
356
129
363
128
369
127
375
127
385
129
312
127
318
127
327
129
333
128
339
127
346
127
354
127
361
128
367
127
375
128
381
127
389
128
322
127
332
128
338
128
345
127
351
126
360
128
367
127
373
127
383
128
389
128
395
127
405
129
375
150
383
149
392
150
400
149
408
149
419
151
426
150
434
149
443
149
452
150
460
149
469
150

Rated
Cc (kW)
Pi (kW)
226
85.3
233
86.3
240
87.4
248
88.5
255
89.7
263
90.8
270
92.0
278
93.2
286
94.4
294
95.7
302
96.9
310
98.2
243
94.8
250
96.0
258
97.2
266
98.4
274
100
282
101
290
102
298
104
306
105
314
106
323
108
331
109
266
105
274
107
282
108
291
109
299
111
308
112
317
114
326
115
335
117
344
119
353
120
362
122
289
109
298
111
307
112
316
113
326
115
335
116
345
117
355
119
365
120
374
122
385
123
395
125

Boost
Cc (kW)
Pi (kW)
281
129
287
128
293
128
299
127
305
126
314
128
320
128
326
127
332
126
340
128
346
127
352
126
285
128
291
128
297
127
305
128
310
127
318
127
325
128
331
127
336
126
345
128
351
127
358
128
294
127
300
126
309
128
315
127
320
126
330
128
335
127
341
126
350
128
356
127
361
126
371
128
343
150
350
150
357
149
366
150
375
150
382
149
391
149
399
150
406
149
415
149
424
150
431
149

Condenser Inlet Air Temperature (C)


35
Rated
Cc (kW)
Pi (kW)
274
127
280
126
286
125
291
125
298
125
306
126
312
126
318
125
323
124
332
126
338
125
343
124
278
126
284
126
289
125
297
126
303
125
310
125
317
126
322
125
328
124
337
126
342
125
349
125
286
125
292
124
300
126
306
125
312
125
321
126
327
125
332
124
341
126
347
125
352
124
361
126
334
148
341
147
349
147
357
147
366
148
373
147
381
147
389
148
396
147
405
147
414
148
421
147

36
Boost
Cc (kW)
Pi (kW)
274
127
280
126
286
125
291
125
298
125
306
126
312
126
318
125
323
124
332
126
338
125
343
124
278
126
284
126
289
125
297
126
303
125
310
125
317
126
322
125
328
124
337
126
342
125
349
125
286
125
292
124
300
126
306
125
312
125
321
126
327
125
332
124
341
126
347
125
352
124
361
126
334
148
341
147
349
147
357
147
366
148
373
147
381
147
389
148
396
147
405
147
414
148
421
147

Rated
Cc (kW)
Pi (kW)
245
118
250
118
255
117
260
116
268
118
273
117
281
118
286
117
291
116
300
118
304
117
309
116
246
117
253
118
258
117
265
117
271
117
277
118
284
118
289
117
295
117
301
117
308
117
313
116
254
117
259
116
267
118
272
117
280
118
285
117
293
118
298
117
302
116
311
117
315
116
324
118
299
140
305
139
314
140
320
139
328
139
336
140
342
139
350
139
357
139
365
139
373
139
381
139

40
Boost
Cc (kW)
Pi (kW)
245
118
250
118
255
117
260
116
268
118
273
117
281
118
286
117
291
116
300
118
304
117
309
116
246
117
253
118
258
117
265
117
271
117
277
118
284
118
289
117
295
117
301
117
308
117
313
116
254
117
259
116
267
118
272
117
280
118
285
117
293
118
298
117
302
116
311
117
315
116
324
118
299
140
305
139
314
140
320
139
328
139
336
140
342
139
350
139
357
139
365
139
373
139
381
139

Rated
Cc (kW)
Pi (kW)
218
117
225
118
230
117
235
116
242
118
247
117
254
118
259
117
264
116
271
117
276
116
283
118
220
117
227
118
232
117
238
117
243
117
250
117
255
117
262
117
266
116
274
117
278
116
286
118
226
117
230
116
238
117
242
116
250
117
254
116
262
117
266
116
274
117
278
116
286
117
290
116
268
141
274
139
281
139
288
140
296
140
303
140
310
140
316
138
325
140
330
138
339
140
345
139

45
Boost
Cc (kW)
Pi (kW)
218
117
225
118
230
117
235
116
242
118
247
117
254
118
259
117
264
116
271
117
276
116
283
118
220
117
227
118
232
117
238
117
243
117
250
117
255
117
262
117
266
116
274
117
278
116
286
118
226
117
230
116
238
117
242
116
250
117
254
116
262
117
266
116
274
117
278
116
286
117
290
116
268
141
274
139
281
139
288
140
296
140
303
140
310
140
316
138
325
140
330
138
339
140
345
139

Cooling Mode - McEnergy HPI Extension SE-LN

KPMHP00511-09EN page 31/60

KPMHP00511-09EN page 32/60

117.2

109.2

103.2

096.2

Rated
Cc (kW)
Pi (kW)
345
89.9
356
91.2
366
92.4
376
93.7
386
95.1
397
96.4
408
97.8
418
99.2
429
101
440
102
452
104
463
105
371
97.6
382
99.0
393
100
404
102
415
103
427
105
438
106
450
108
462
110
474
111
486
113
498
115
389
104
401
106
412
107
423
109
435
111
447
112
459
114
471
115
483
117
495
119
508
121
520
123
420
110
432
111
445
113
457
114
470
116
482
118
495
119
508
121
522
122
535
124
549
126
562
128

20

Boost
Cc (kW)
Pi (kW)
460
159
472
162
484
164
497
166
510
169
522
172
532
171
541
171
550
170
560
170
569
169
582
172
485
167
496
168
507
169
518
170
528
169
539
170
551
171
560
171
570
170
579
169
588
169
600
170
497
171
506
171
516
170
525
170
535
169
544
168
558
171
567
170
576
170
585
169
595
168
608
171
535
174
547
175
559
176
571
177
586
180
598
181
611
182
623
183
638
185
651
186
663
187
674
186

Rated
Cc (kW)
Pi (kW)
332
98.4
342
100
352
101
362
102
372
104
383
105
393
107
404
108
414
110
425
111
436
113
447
114
357
107
367
108
378
110
389
111
400
113
411
114
422
116
434
118
445
119
457
121
469
123
480
125
374
114
385
116
396
117
407
119
419
121
430
122
442
124
454
126
466
128
478
129
490
131
502
133
404
120
416
122
428
123
440
125
453
127
465
128
478
130
491
132
504
133
517
135
530
137
543
139

25
Boost
Cc (kW)
Pi (kW)
437
171
446
171
455
170
464
170
473
169
481
169
494
171
502
171
511
170
520
169
532
172
541
171
452
171
461
170
470
170
479
169
490
170
500
171
509
170
518
170
529
170
538
170
549
170
557
170
458
171
467
170
475
170
484
169
497
171
506
171
515
170
523
169
536
171
545
170
553
169
562
168
502
183
514
184
525
185
539
187
549
187
559
186
573
188
583
187
593
186
605
187
617
188
627
187

Notes:
Cc (cooling capacity) - Pi (unit power input) ELWT (evaporator leaving water temperature t 5C).
Data are referred to 0,0176 m2 C/kW evaporator fouling factor
Rated conditions are for compressors running at nominal frequency.
Boost conditions are for compressors running at maximum frequency.
10% glycol is recommend for shaded area conditions

4
5
6
7
8
9
10
11
12
13
14
15
4
5
6
7
8
9
10
11
12
13
14
15
4
5
6
7
8
9
10
11
12
13
14
15
4
5
6
7
8
9
10
11
12
13
14
15

ELWT (C)
Rated
Cc (kW)
Pi (kW)
318
108
328
109
337
110
347
112
357
113
367
115
377
116
388
118
398
119
409
121
419
122
430
124
341
117
352
118
362
120
373
121
383
123
394
125
405
126
416
128
427
130
439
132
450
133
462
135
358
125
368
127
379
128
390
130
401
132
413
133
424
135
435
137
447
139
459
141
471
143
483
145
387
131
399
133
411
135
422
136
435
138
447
140
459
142
472
143
484
145
497
147
510
149
523
151

30
Boost
Cc (kW)
Pi (kW)
402
171
411
170
419
170
427
169
435
169
447
171
455
170
463
170
471
169
483
171
491
170
499
169
414
170
423
169
433
170
441
169
451
170
459
169
470
170
478
169
488
170
498
171
506
170
514
168
419
170
427
169
439
171
447
170
455
169
463
168
476
171
484
170
492
169
504
171
512
170
520
169
465
187
477
188
486
187
495
186
507
187
516
186
527
187
539
188
548
186
556
185
570
188
579
186

Rated
Cc (kW)
Pi (kW)
303
118
312
119
322
120
331
122
341
123
351
125
361
126
371
128
381
130
391
131
402
133
412
135
325
128
335
129
345
131
355
132
366
134
376
136
387
138
398
139
409
141
420
143
431
145
442
147
340
137
351
138
361
140
372
142
383
144
394
145
405
147
416
149
427
151
439
153
450
155
462
157
369
144
380
145
392
147
403
149
415
151
427
152
439
154
451
156
464
158
476
160
486
160
495
160

Boost
Cc (kW)
Pi (kW)
367
170
375
170
383
169
394
171
401
170
409
169
417
168
428
171
435
170
443
169
454
171
461
170
378
170
386
169
395
170
405
171
413
170
422
170
432
171
439
170
447
169
459
171
466
170
473
168
383
171
391
170
398
169
410
171
417
170
425
169
437
171
444
170
451
169
463
171
470
169
477
168
424
186
434
187
445
188
453
187
462
185
474
188
483
186
494
187
504
187
515
188
523
187
531
185

Condenser Inlet Air Temperature (C)


35
Rated
Cc (kW)
Pi (kW)
358
168
366
167
374
167
384
169
392
168
400
168
407
167
418
168
426
168
433
167
444
169
451
168
368
168
377
168
386
168
395
168
403
168
412
168
422
169
429
168
437
167
448
169
456
168
463
167
373
169
381
168
389
167
399
169
407
168
415
167
426
169
433
168
441
167
452
168
460
168
467
166
416
187
426
187
436
187
445
187
453
185
466
187
474
187
485
187
495
187
506
188
514
187
523
185

36
Boost
Cc (kW)
Pi (kW)
358
168
366
167
374
167
384
169
392
168
400
168
407
167
418
168
426
168
433
167
444
169
451
168
368
168
377
168
386
168
395
168
403
168
412
168
422
169
429
168
437
167
448
169
456
168
463
167
373
169
381
168
389
167
399
169
407
168
415
167
426
169
433
168
441
167
452
168
460
168
467
166
416
187
426
187
436
187
445
187
453
185
466
187
474
187
485
187
495
187
506
188
514
187
523
185

Rated
Cc (kW)
Pi (kW)
323
160
330
159
340
161
347
160
354
159
364
161
371
159
377
158
388
160
394
159
405
161
411
159
330
159
340
161
347
159
354
158
365
160
371
159
382
161
388
159
397
160
406
160
415
160
423
160
333
159
343
161
350
159
357
158
367
160
374
158
384
160
391
159
402
161
408
159
419
161
425
159
385
188
393
187
401
186
413
188
421
186
431
187
441
187
451
187
458
186
471
188
478
186
489
187

40
Boost
Cc (kW)
Pi (kW)
323
160
330
159
340
161
347
160
354
159
364
161
371
159
377
158
388
160
394
159
405
161
411
159
330
159
340
161
347
159
354
158
365
160
371
159
382
161
388
159
397
160
406
160
415
160
423
160
333
159
343
161
350
159
357
158
367
160
374
158
384
160
391
159
402
161
408
159
419
161
425
159
385
188
393
187
401
186
413
188
421
186
431
187
441
187
451
187
458
186
471
188
478
186
489
187

Rated
Cc (kW)
Pi (kW)
291
161
298
160
304
159
313
160
320
159
329
161
336
160
342
158
351
160
357
158
367
160
373
159
296
159
306
161
312
160
320
160
328
160
334
158
344
160
350
159
358
159
366
159
374
159
385
161
298
159
308
161
314
159
324
161
330
160
335
158
345
160
351
158
361
160
367
158
377
159
388
161
343
186
352
186
361
187
371
187
378
185
389
187
399
187
408
187
418
188
424
186
436
188
443
186

45
Boost
Cc (kW)
Pi (kW)
291
161
298
160
304
159
313
160
320
159
329
161
336
160
342
158
351
160
357
158
367
160
373
159
296
159
306
161
312
160
320
160
328
160
334
158
344
160
350
159
358
159
366
159
374
159
385
161
298
159
308
161
314
159
324
161
330
160
335
158
345
160
351
158
361
160
367
158
377
159
388
161
343
186
352
186
361
187
371
187
378
185
389
187
399
187
408
187
418
188
424
186
436
188
443
186

KPMHP00511-09EN page 33/60

167.3

153.3

144.3

130.3

124.2

Rated
Cc (kW)
Pi (kW)
444
118
457
120
469
122
482
123
496
125
509
127
522
129
536
130
550
132
564
134
578
136
592
138
465
116
478
117
492
119
506
120
521
122
535
124
550
125
565
127
580
129
595
131
610
133
626
134
513
129
529
131
544
133
560
135
575
136
591
138
608
140
624
142
641
144
658
147
675
149
692
151
531
135
546
137
562
139
578
141
594
143
611
145
628
147
644
149
662
151
679
153
696
156
714
158
595
158
612
160
629
162
647
165
665
167
683
170
701
172
720
175
739
178
758
180
777
183
797
186

20

Boost
Cc (kW)
Pi (kW)
578
203
589
203
600
202
611
201
623
200
638
203
649
203
660
202
671
201
682
200
698
203
709
203
617
194
629
194
641
193
653
193
670
195
682
195
694
194
706
193
718
193
729
192
747
195
759
194
686
224
703
226
720
229
737
231
755
233
774
237
788
236
802
235
815
235
829
234
843
233
859
234
711
239
731
242
750
246
770
250
789
253
810
257
824
257
839
256
853
255
868
255
882
254
897
253
755
255
770
255
784
254
799
253
819
257
834
256
848
255
862
254
877
253
898
257
912
256
926
255

Rated
Cc (kW)
Pi (kW)
427
130
439
131
452
133
465
135
477
137
490
139
504
140
517
142
531
144
544
146
558
148
572
150
447
126
461
128
474
130
488
131
502
133
516
135
531
137
545
138
560
140
575
142
590
144
605
146
494
141
508
143
524
145
539
147
554
149
570
151
586
153
602
155
618
157
635
159
651
162
668
164
510
148
526
149
541
151
557
154
573
156
589
158
605
160
621
162
638
164
655
167
672
169
690
171
571
173
588
175
605
178
622
180
640
183
657
185
675
188
693
191
712
193
730
196
749
199
768
202

25
Boost
Cc (kW)
Pi (kW)
534
203
545
203
555
202
566
201
580
204
591
203
601
202
611
201
626
204
637
203
647
202
657
201
564
192
580
195
592
194
603
193
614
192
630
195
641
194
652
193
663
192
680
195
691
194
702
193
646
236
659
236
672
235
685
234
698
234
713
234
729
236
742
235
755
234
770
234
782
233
799
235
676
257
690
256
704
256
718
255
732
254
745
253
764
257
778
256
791
255
805
254
818
253
838
256
695
254
708
253
728
257
741
256
755
255
768
254
781
252
801
256
815
255
828
254
840
252
861
256

Notes:
Cc (cooling capacity) - Pi (unit power input) ELWT (evaporator leaving water temperature t 5C).
Data are referred to 0,0176 m2 C/kW evaporator fouling factor
Rated conditions are for compressors running at nominal frequency.
Boost conditions are for compressors running at maximum frequency.
10% glycol is recommend for shaded area conditions

4
5
6
7
8
9
10
11
12
13
14
15
4
5
6
7
8
9
10
11
12
13
14
15
4
5
6
7
8
9
10
11
12
13
14
15
4
5
6
7
8
9
10
11
12
13
14
15
4
5
6
7
8
9
10
11
12
13
14
15

ELWT (C)
Rated
Cc (kW)
Pi (kW)
409
142
421
144
433
145
445
147
458
149
471
151
484
153
497
155
510
157
523
159
537
161
550
163
429
138
442
140
455
142
469
143
482
145
496
147
510
149
524
151
539
152
553
154
568
156
583
158
473
154
487
156
502
158
517
160
532
162
547
164
563
166
578
169
594
171
610
173
626
175
643
178
489
161
504
163
519
165
534
167
549
170
565
172
581
174
597
176
613
179
630
181
647
184
663
186
546
189
562
191
579
194
596
196
613
199
630
202
647
205
665
207
683
210
701
213
720
216
738
219

30
Boost
Cc (kW)
Pi (kW)
490
203
500
202
510
201
524
204
533
203
543
201
552
200
567
203
576
202
586
200
600
203
610
202
517
192
532
195
542
194
553
193
568
195
578
194
589
193
604
195
614
194
624
193
640
195
650
194
592
236
605
235
617
234
629
233
643
233
658
236
670
234
684
234
696
233
712
235
726
235
738
234
622
257
635
256
648
255
660
254
673
253
691
257
704
256
717
254
729
253
748
256
760
255
773
254
640
257
653
256
665
254
678
253
696
257
709
255
721
254
740
257
752
256
764
254
776
252
796
256

Condenser Inlet Air Temperature (C)


35
Rated
Boost
Cc (kW)
Pi (kW)
Cc (kW)
Pi (kW)
389
155
446
201
401
157
459
204
413
159
468
203
425
161
477
202
437
163
486
200
450
165
500
203
462
167
508
201
475
169
522
204
488
171
531
203
501
173
540
201
514
175
553
204
527
178
562
202
409
151
474
195
422
153
483
193
435
154
493
192
448
156
507
195
461
158
517
193
475
160
526
192
488
162
541
194
502
164
550
193
516
166
565
195
530
168
574
194
545
170
584
192
559
172
599
195
450
168
539
235
464
170
551
234
479
172
563
234
493
174
578
236
508
176
589
234
523
179
602
234
538
181
613
233
553
183
628
235
569
186
641
234
584
188
652
233
600
190
669
236
616
193
680
234
465
176
567
255
480
178
579
254
495
180
591
253
510
183
608
257
525
185
620
255
540
187
632
254
555
189
644
252
571
192
661
256
587
194
673
254
603
197
684
253
619
199
702
256
636
202
714
254
519
206
579
254
535
209
597
257
551
211
608
256
567
214
620
254
584
217
631
252
601
220
649
256
618
223
661
254
635
226
679
257
653
229
690
255
670
232
701
253
688
235
719
257
706
238
730
255
Rated
Cc (kW)
Pi (kW)
435
199
448
201
457
201
466
199
476
199
488
201
498
200
510
202
519
200
528
199
541
201
550
200
460
191
470
190
480
190
493
191
503
190
512
189
527
191
536
190
551
192
560
191
568
189
583
192
530
236
541
234
555
235
569
236
580
235
593
236
604
234
619
236
631
235
643
234
659
237
670
235
553
252
565
251
578
251
593
253
605
252
618
251
629
250
646
253
658
252
669
250
687
253
698
251
565
251
581
253
594
253
605
251
617
250
633
252
644
250
662
254
673
252
685
251
702
253
714
252

36
Boost
Cc (kW)
Pi (kW)
435
199
448
201
457
201
466
199
476
199
488
201
498
200
510
202
519
200
528
199
541
201
550
200
460
191
470
190
480
190
493
191
503
190
512
189
527
191
536
190
551
192
560
191
568
189
583
192
530
236
541
234
555
235
569
236
580
235
593
236
604
234
619
236
631
235
643
234
659
237
670
235
553
252
565
251
578
251
593
253
605
252
618
251
629
250
646
253
658
252
669
250
687
253
698
251
565
251
581
253
594
253
605
251
617
250
633
252
644
250
662
254
673
252
685
251
702
253
714
252

Rated
Cc (kW)
Pi (kW)
394
192
402
190
414
192
422
191
434
193
442
191
455
194
462
192
470
190
483
192
490
191
503
193
407
178
415
177
428
179
436
177
450
179
457
178
471
180
478
178
492
180
500
178
507
176
521
179
495
239
505
238
521
241
531
239
542
238
558
241
568
239
583
241
593
239
605
239
620
240
630
238
498
239
509
238
524
241
535
239
545
238
561
241
572
239
588
242
598
240
608
238
624
241
634
239
508
240
518
238
534
241
544
238
560
241
570
239
579
237
596
240
605
237
622
240
632
238
649
241

40
Boost
Cc (kW)
Pi (kW)
394
192
402
190
414
192
422
191
434
193
442
191
455
194
462
192
470
190
483
192
490
191
503
193
407
178
415
177
428
179
436
177
450
179
457
178
471
180
478
178
492
180
500
178
507
176
521
179
495
239
505
238
521
241
531
239
542
238
558
241
568
239
583
241
593
239
605
239
620
240
630
238
498
239
509
238
524
241
535
239
545
238
561
241
572
239
588
242
598
240
608
238
624
241
634
239
508
240
518
238
534
241
544
238
560
241
570
239
579
237
596
240
605
237
622
240
632
238
649
241

Rated
Cc (kW)
Pi (kW)
353
193
361
191
372
193
380
191
391
193
399
191
410
194
417
191
429
194
436
192
448
194
455
191
365
179
372
178
384
179
391
178
404
179
411
178
424
179
430
177
443
179
450
177
463
179
469
177
446
241
456
240
466
238
481
241
490
239
504
240
515
240
528
241
538
239
549
238
563
240
572
237
448
241
458
239
468
237
483
240
492
238
507
241
517
239
532
242
542
239
551
237
566
240
575
237
453
240
463
238
478
240
487
238
502
241
511
238
526
241
535
238
551
241
559
238
575
241
583
238

45
Boost
Cc (kW)
Pi (kW)
353
193
361
191
372
193
380
191
391
193
399
191
410
194
417
191
429
194
436
192
448
194
455
191
365
179
372
178
384
179
391
178
404
179
411
178
424
179
430
177
443
179
450
177
463
179
469
177
446
241
456
240
466
238
481
241
490
239
504
240
515
240
528
241
538
239
549
238
563
240
572
237
448
241
458
239
468
237
483
240
492
238
507
241
517
239
532
242
542
239
551
237
566
240
575
237
453
240
463
238
478
240
487
238
502
241
511
238
526
241
535
238
551
241
559
238
575
241
583
238

KPMHP00511-09EN page 34/60

083.2

079.2

072.2

Boost
Hc (kW)
Pi (kW)
230
107
231
109
231
111
231
113
232
115
232
117
232
120
233
122
233
125
234
127
234
130
234
132
232
133
230
134
225
132
223
133
253
116
253
118
254
121
254
123
252
124
251
125
248
126
247
128
246
129
244
130
242
132
240
132
237
133
235
134
231
133
226
133
275
123
276
126
276
129
277
132
275
133
272
134
267
133
265
134
259
132
256
133
251
132
248
133
245
134
239
132
236
133
233
133

-10 (RH 100%)

Rated
Hc (kW)
Pi (kW)
230
107
231
109
231
111
231
113
232
115
232
117
232
120
233
122
233
125
234
127
234
130
234
132
232
133
230
134
225
132
223
133
253
116
253
118
254
121
254
123
252
124
251
125
248
126
247
128
246
129
244
130
242
132
240
132
237
133
235
134
231
133
226
133
275
123
276
126
276
129
277
132
275
133
272
134
267
133
265
134
259
132
256
133
251
132
248
133
245
134
239
132
236
133
233
133

Boost
Hc (kW)
Pi (kW)
268
108
269
111
269
113
270
115
270
117
270
120
271
122
271
124
272
127
272
130
272
132
270
133
267
134
262
132
259
133
257
134
296
119
296
121
295
123
294
124
291
125
290
127
287
127
286
129
284
130
281
131
280
133
277
133
273
133
268
133
265
133
262
134
323
127
323
130
324
133
321
134
315
133
312
134
306
133
303
133
298
133
295
133
292
134
285
133
282
133
278
134
271
132
268
133

-5 (RH 100%)
Rated
Hc (kW)
Pi (kW)
247
96.0
247
97.9
247
100
247
102
247
104
247
106
247
108
248
110
248
112
248
114
248
117
248
119
248
121
248
124
249
126
249
128
271
105
272
107
272
109
272
112
272
114
272
116
273
118
273
121
271
122
270
124
268
125
265
126
263
127
262
128
260
130
256
130
296
113
297
115
297
117
297
120
297
122
297
125
298
127
298
130
298
133
295
133
292
134
285
133
282
133
278
134
271
132
268
133

Notes:
Hc (heating capacity) - Pi (unit power input) CLWT (condenser leaving water temperature t 5C)
Data are referred to 0,0176 m2 C/kW evaporator fouling factor
Rated conditions are for compressors running at nominal frequency
Boost conditions are for compressors running at maximum frequency
Refer to Operating limit chapter for Integrated Heating Capacity

35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50

CLWT (C)
Rated
Hc (kW)
Pi (kW)
261
87.4
261
89.0
261
90.6
260
92.2
260
93.9
260
95.6
260
97.3
260
99.1
260
101
260
103
259
105
259
107
259
109
259
111
259
113
259
115
287
95.9
287
97.6
287
99.4
287
101
287
103
286
105
286
107
286
109
286
111
286
113
286
115
286
118
285
120
285
122
283
123
279
124
314
103
314
105
313
107
313
109
313
111
313
113
313
115
313
117
312
120
312
122
312
124
312
127
312
129
312
132
308
132
303
133

Boost
Hc (kW)
Pi (kW)
311
112
311
114
311
116
311
118
312
120
312
123
313
125
313
128
313
130
314
133
311
134
305
132
302
133
299
134
293
133
290
133
342
123
339
123
338
125
335
125
333
127
332
128
328
129
327
131
323
131
322
133
318
133
313
133
308
133
305
133
300
133
296
133
374
132
371
133
367
133
361
132
358
133
354
134
348
133
344
134
337
132
333
133
330
134
322
132
318
133
314
133
310
134
306
134

Eavaporator Inlet Air Temperature (C)


0 (RH 85%)
Boost
Hc (kW)
Pi (kW)
381
119
381
121
381
123
381
126
381
128
381
130
381
133
378
133
374
134
367
132
364
133
360
133
356
134
352
134
345
133
341
133
407
126
405
127
403
129
401
130
397
130
395
132
392
133
388
133
384
134
378
133
372
133
367
133
363
133
358
134
352
133
347
133
438
132
434
133
429
133
425
134
417
132
412
133
408
133
403
134
398
134
389
132
384
132
379
133
374
133
369
133
364
133
359
134

7 (RH 85%)
Rated
Hc (kW)
Pi (kW)
274
75.9
274
77.2
273
78.6
273
80.0
272
81.4
272
82.8
272
84.3
271
85.8
271
87.3
270
88.8
270
90.4
269
92.0
269
93.6
268
95.2
268
96.9
267
98.6
302
83.2
301
84.7
301
86.2
300
87.8
300
89.3
299
90.9
299
92.6
298
94.2
298
95.9
297
97.6
297
99.3
296
101
296
103
295
105
295
107
294
108
329
89
329
91
328
93
328
94
327
96
327
98
326
100
326
101
325
103
325
105
324
107
324
109
323
111
322
113
322
115
321
117

Boost
Hc (kW)
Pi (kW)
439
126
439
128
439
130
439
133
435
133
431
134
428
134
419
133
415
133
411
133
407
134
402
134
394
132
389
133
384
133
379
133
451
130
447
130
444
131
441
133
437
133
432
133
428
134
421
133
416
133
411
134
404
133
399
133
392
132
387
132
381
132
376
133
491
133
486
134
476
132
471
133
466
133
460
133
455
133
449
134
444
134
433
132
427
132
421
132
415
132
409
132
403
132
397
132

12 (RH 85%)
Rated
Hc (kW)
Pi (kW)
317
79.3
317
80.7
316
82.0
316
83.5
315
84.9
315
86.3
314
87.8
313
89.3
313
90.9
312
92.4
312
94.0
311
95.6
310
97.3
310
98.9
309
101
308
102
349
87.1
348
88.6
348
90.1
347
91.7
346
93.3
346
94.9
345
96.6
345
98.2
344
100
343
102
342
103
342
105
341
107
340
109
340
111
339
113
381
94
380
95
380
97
379
99
378
100
378
102
377
104
376
106
375
107
375
109
374
111
373
113
372
115
372
117
371
119
370
121

Heating Mode - McEnergy HPI Extension SE-ST

KPMHP00511-09EN page 35/60

103.2

096.2

093.2

Rated
Hc (kW)
Pi (kW)
278
134
278
137
279
140
280
143
277
146
275
147
271
150
270
151
270
153
269
155
269
157
267
157
264
157
262
158
257
156
255
157
281
142
281
146
282
149
280
152
283
155
285
159
287
162
289
166
291
170
293
173
295
177
294
178
290
177
289
178
284
177
282
178
302
152
304
155
306
159
309
162
311
166
311
168
310
169
308
170
308
173
307
174
306
176
305
178
301
177
298
177
296
178
290
177

Boost
Hc (kW)
Pi (kW)
278
134
278
137
279
140
280
143
277
146
275
147
271
150
270
151
270
153
269
155
269
157
267
157
264
157
262
158
257
156
255
157
281
142
281
146
282
149
280
152
283
155
285
159
287
162
289
166
291
170
293
173
295
177
294
178
290
177
289
178
284
177
282
178
302
152
304
155
306
159
309
162
311
166
311
168
310
169
308
170
308
173
307
174
306
176
305
178
301
177
298
177
296
178
290
177

-10 (RH 100%)


Rated
Hc (kW)
Pi (kW)
299
122
299
125
300
127
300
130
300
133
300
136
300
138
301
141
301
144
296
146
296
148
296
150
294
151
293
153
293
155
290
156
302
130
302
132
300
135
302
138
303
141
305
144
307
147
308
150
310
153
311
157
313
160
314
163
316
167
317
170
318
174
320
177
328
138
329
141
331
144
332
147
334
150
335
154
336
157
338
160
339
163
341
167
338
168
337
170
334
171
334
173
333
175
331
177

Boost
Hc (kW)
Pi (kW)
326
137
326
140
327
143
324
146
318
148
316
150
311
151
311
154
310
155
310
157
307
157
304
157
301
157
297
157
295
158
291
157
329
146
329
149
330
152
327
156
326
159
328
163
331
166
333
170
335
173
337
177
336
178
332
177
331
178
326
177
324
178
320
177
351
155
353
159
355
162
357
166
356
167
356
170
355
171
355
173
353
174
353
177
349
177
347
178
343
178
339
177
335
177
331
177

-5 (RH 100%)

Notes:
Hc (heating capacity) - Pi (unit power input) CLWT (condenser leaving water temperature t 5C)
Data are referred to 0,0176 m2 C/kW evaporator fouling factor
Rated conditions are for compressors running at nominal frequency
Boost conditions are for compressors running at maximum frequency
Refer to Operating limit chapter for Integrated Heating Capacity

35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50

CLWT (C)
Rated
Hc (kW)
Pi (kW)
317
111
317
114
317
116
316
118
316
120
316
123
316
125
313
128
313
130
314
133
315
136
315
138
316
141
317
144
317
146
316
148
319
118
320
120
321
123
322
125
323
128
324
130
325
133
326
136
327
139
328
141
329
144
330
147
331
150
332
153
333
156
334
159
351
126
352
128
353
131
354
133
355
136
356
139
356
142
357
145
358
147
359
150
360
153
360
157
361
160
362
163
362
166
361
168

Boost
Hc (kW)
Pi (kW)
378
141
374
144
371
146
365
148
361
150
355
152
354
153
354
156
352
157
349
157
346
157
342
157
340
157
335
156
332
157
329
158
381
150
378
153
375
156
371
160
373
163
375
167
378
170
380
174
382
178
378
177
377
178
373
177
371
178
366
176
364
177
361
178
404
160
406
163
406
165
407
168
405
169
405
171
403
173
403
175
401
176
399
177
397
178
391
177
388
178
384
178
378
177
374
177

Eavaporator Inlet Air Temperature (C)


0 (RH 85%)
Boost
Hc (kW)
Pi (kW)
442
147
438
148
434
150
429
152
423
153
423
156
421
157
417
157
415
158
409
156
407
157
403
157
400
157
396
158
389
156
386
157
446
157
443
160
445
163
447
167
450
170
452
174
454
178
450
177
449
178
444
177
442
178
437
177
434
178
432
179
425
177
422
178
486
166
486
168
484
169
484
171
481
172
481
174
480
176
477
177
473
177
470
178
466
178
460
178
455
177
451
178
446
177
439
177

7 (RH 85%)
Rated
Hc (kW)
Pi (kW)
332
97.8
332
100
332
101
332
103
332
105
332
107
333
109
333
111
333
113
333
115
333
117
333
119
332
121
332
123
332
126
332
128
347
103
347
105
347
107
347
109
348
111
348
113
348
116
348
118
348
120
349
122
349
124
349
127
349
129
349
131
349
134
349
136
379
110
379
112
379
114
379
116
379
118
379
121
379
123
379
125
379
127
379
130
379
132
379
134
379
137
379
139
379
142
379
145

Boost
Hc (kW)
Pi (kW)
496
151
491
153
482
154
481
156
479
157
475
157
471
156
468
157
465
158
458
156
455
157
451
157
446
157
442
157
437
158
431
157
508
165
510
169
512
172
514
175
513
177
512
178
507
177
505
178
503
179
497
177
494
178
492
179
485
177
481
178
477
178
469
176
552
169
551
171
551
173
547
174
546
176
545
178
538
177
535
178
530
177
526
178
520
178
513
177
509
177
502
177
498
177
493
178

12 (RH 85%)
Rated
Hc (kW)
Pi (kW)
384
102
384
104
384
106
384
107
384
109
384
111
384
113
384
115
384
117
383
119
383
122
383
124
383
126
383
128
382
130
382
133
401
108
401
110
401
112
401
114
401
116
401
118
401
120
402
122
402
125
401
127
402
129
401
131
401
134
401
136
401
139
401
141
438
115
438
117
438
119
438
121
438
123
438
125
437
128
437
130
437
132
437
135
437
137
437
139
436
142
436
144
436
147
435
150

KPMHP00511-09EN page 36/60

124.2

117.2

109.2

Boost
Hc (kW)
Pi (kW)
332
162
334
166
336
170
338
173
339
177
338
179
333
178
328
176
326
178
321
176
319
177
316
178
310
177
308
178
305
179
298
177
370
179
371
183
372
187
373
191
375
195
372
197
368
197
364
197
359
197
355
197
350
196
345
196
342
197
337
197
332
196
326
196
388
191
389
195
390
199
392
204
393
208
395
213
388
211
386
213
380
211
377
213
370
211
367
212
364
213
357
211
354
212
346
210

-10 (RH 100%)


Rated
Hc (kW)
Pi (kW)
332
162
334
166
336
170
338
173
339
177
338
179
333
178
328
176
326
178
321
176
319
177
316
178
310
177
308
178
305
179
298
177
370
179
371
183
372
187
373
191
375
195
372
197
368
197
364
197
359
197
355
197
350
196
345
196
342
197
337
197
332
196
326
196
388
191
389
195
390
199
392
204
393
208
395
213
388
211
386
213
380
211
377
213
370
211
367
212
364
213
357
211
354
212
346
210

Boost
Hc (kW)
Pi (kW)
387
167
389
170
390
174
392
178
387
177
386
178
380
177
378
178
372
177
371
179
364
177
361
178
354
176
351
177
347
178
344
179
410
182
412
186
413
190
415
195
414
196
410
196
406
197
402
196
398
196
394
196
391
197
386
196
381
196
378
197
373
196
368
196
428
194
429
198
432
203
434
207
436
212
430
210
428
212
423
211
421
212
415
210
413
212
407
211
404
212
401
213
394
211
391
212

-5 (RH 100%)
Rated
Hc (kW)
Pi (kW)
359
148
361
151
362
154
363
158
364
161
366
164
367
168
368
171
369
175
371
179
364
177
361
178
354
176
351
177
347
178
344
179
380
162
381
165
383
169
384
173
386
176
387
180
388
184
390
187
391
191
391
194
391
197
386
196
381
196
378
197
373
196
368
196
396
172
398
176
399
180
401
184
403
187
404
191
406
195
408
200
410
204
411
208
413
212
407
211
404
212
401
213
394
211
391
212

Notes:
Hc (heating capacity) - Pi (unit power input) CLWT (condenser leaving water temperature t 5C)
Data are referred to 0,0176 m2 C/kW evaporator fouling factor
Rated conditions are for compressors running at nominal frequency
Boost conditions are for compressors running at maximum frequency
Refer to Operating limit chapter for Integrated Heating Capacity

35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50

CLWT (C)
Rated
Hc (kW)
Pi (kW)
384
135
385
137
385
140
386
143
387
146
387
149
388
152
388
155
389
158
390
161
390
164
391
167
391
171
392
174
392
178
388
178
399
147
400
150
401
153
403
156
404
159
405
162
407
166
408
169
410
173
411
176
412
180
413
183
415
187
416
190
417
194
416
197
414
156
415
159
417
162
419
166
420
169
422
173
424
176
425
180
427
183
429
187
430
191
432
195
434
199
435
203
437
207
438
211

Boost
Hc (kW)
Pi (kW)
445
171
447
175
446
177
444
178
438
177
436
178
430
177
427
178
420
177
417
178
414
179
406
177
403
178
399
179
392
178
388
178
457
186
459
190
462
195
461
196
458
197
455
197
450
196
449
197
443
196
441
197
435
195
433
196
430
197
423
195
420
196
416
197
473
198
476
203
479
207
482
212
481
213
476
212
472
211
470
212
465
211
464
212
458
211
456
212
454
213
447
211
444
212
441
213

Eavaporator Inlet Air Temperature (C)


0 (RH 85%)
Boost
Hc (kW)
Pi (kW)
534
177
532
178
526
177
523
178
515
177
512
177
508
178
500
177
496
177
492
178
487
179
478
177
473
177
468
178
463
178
452
176
543
194
544
196
543
197
540
196
538
197
536
197
533
197
529
197
526
196
521
196
516
196
513
196
510
197
501
195
497
196
493
196
559
206
563
210
563
212
560
211
561
213
557
212
554
211
553
212
548
211
547
212
541
210
539
212
536
213
528
210
524
211
521
212

7 (RH 85%)
Rated
Hc (kW)
Pi (kW)
411
117
411
120
411
122
411
124
411
126
411
129
410
131
410
134
410
136
410
139
410
141
409
144
409
146
409
149
409
152
408
154
439
121
440
123
440
126
441
128
441
130
441
132
442
135
442
137
442
140
442
142
443
145
443
147
443
150
443
153
443
155
443
158
457
137
458
140
458
142
459
145
460
148
461
150
461
153
462
156
462
159
463
162
463
165
464
168
464
171
465
174
465
177
465
181

Boost
Hc (kW)
Pi (kW)
598
177
595
178
592
178
583
177
579
178
574
178
564
176
560
177
554
177
549
178
544
178
532
176
526
176
520
177
514
177
507
177
621
196
620
196
617
196
615
196
613
198
608
196
605
197
600
197
594
196
591
197
584
196
579
197
574
197
569
198
560
196
551
195
641
212
639
211
640
212
637
211
637
213
633
211
632
213
626
211
624
212
621
213
613
211
609
212
604
212
600
213
589
210
583
211

12 (RH 85%)
Rated
Hc (kW)
Pi (kW)
475
123
475
125
475
127
474
129
474
132
474
134
474
136
473
139
473
141
472
144
472
147
472
149
471
152
471
154
470
157
470
160
513
126
513
128
513
131
514
133
514
135
514
138
514
140
514
143
514
145
514
148
513
150
513
153
513
155
513
158
513
161
512
164
534
143
535
146
535
149
535
151
536
154
536
157
536
160
537
163
537
166
537
169
537
172
537
175
537
178
538
181
537
184
537
188

KPMHP00511-09EN page 37/60


167.3

153.3

144.3

130.3

Boost
Hc (kW)
Pi (kW)
391
185
393
189
394
194
396
198
397
202
399
206
392
205
390
204
383
205
381
204
374
205
371
204
368
205
360
206
357
204
346
205
428
200
430
204
433
209
435
213
437
218
439
223
441
227
440
230
440
233
440
237
439
241
440
245
435
245
432
247
425
246
420
246
455
209
457
214
459
219
461
223
463
228
465
233
466
238
468
243
470
248
472
254
473
259
475
264
472
266
468
268
460
266
456
267
493
234
496
239
499
245
501
250
504
256
507
261
510
267
503
266
500
268
493
266
490
268
482
266
478
267
470
265
466
266
462
268

-10 (RH 100%)


Rated
Hc (kW)
Pi (kW)
391
185
393
189
394
194
396
198
397
202
399
206
392
205
390
204
383
205
381
204
374
205
371
204
368
205
360
206
357
204
346
205
428
200
430
204
433
209
435
213
437
218
439
223
441
227
440
230
440
233
440
237
439
241
440
245
435
245
432
247
425
246
420
246
455
209
457
214
459
219
461
223
463
228
465
233
466
238
468
243
470
248
472
254
473
259
475
264
472
266
468
268
460
266
456
267
493
234
496
239
499
245
501
250
504
256
507
261
510
267
503
266
500
268
493
266
490
268
482
266
478
267
470
265
466
266
462
268

Boost
Hc (kW)
Pi (kW)
440
191
443
195
445
199
448
203
446
205
441
204
439
205
433
204
431
205
425
204
422
205
415
204
411
205
408
206
400
204
396
204
501
206
503
210
505
215
507
219
509
224
510
228
511
232
510
235
511
239
510
242
510
246
505
247
498
246
493
246
485
245
481
246
533
216
535
220
537
225
539
230
541
235
542
240
544
245
546
250
548
255
549
261
551
266
547
268
538
266
534
267
524
265
520
267
575
241
578
246
581
251
584
257
586
263
584
265
581
267
574
265
571
267
562
265
559
267
550
265
546
267
536
264
531
266
527
267

-5 (RH 100%)
Rated
Hc (kW)
Pi (kW)
411
170
413
173
414
177
416
181
417
184
419
188
421
192
422
196
424
200
425
204
422
205
415
204
411
205
408
206
400
204
396
204
466
183
467
187
469
191
470
195
471
199
472
203
474
207
475
211
476
216
477
220
478
224
478
228
478
232
476
234
475
238
474
242
494
191
495
195
497
200
498
204
499
208
500
212
501
217
502
221
503
226
504
230
505
235
506
240
507
245
508
249
509
254
510
260
536
214
538
218
539
223
542
228
543
233
545
238
547
243
549
248
551
253
553
258
554
264
550
265
546
267
536
264
531
266
527
267

Notes:
Hc (heating capacity) - Pi (unit power input) CLWT (condenser leaving water temperature t 5C)
Data are referred to 0,0176 m2 C/kW evaporator fouling factor
Rated conditions are for compressors running at nominal frequency
Boost conditions are for compressors running at maximum frequency
Refer to Operating limit chapter for Integrated Heating Capacity

35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50

CLWT (C)
Rated
Hc (kW)
Pi (kW)
442
156
443
159
444
162
444
165
445
168
446
171
447
175
448
178
448
182
449
185
450
189
451
192
451
196
452
200
452
204
448
205
500
168
500
171
501
174
501
178
501
181
502
184
502
188
503
192
503
195
504
199
504
203
505
207
505
211
505
215
506
219
506
223
529
176
529
179
530
183
530
186
530
190
530
193
530
197
531
200
531
204
531
208
532
212
532
217
532
221
532
225
533
229
533
234
575
195
576
199
576
203
577
207
578
211
579
215
580
220
581
224
582
229
583
233
584
238
585
243
586
248
587
252
587
257
588
263

Boost
Hc (kW)
Pi (kW)
509
197
511
201
514
206
508
205
506
206
500
205
498
206
491
205
488
206
480
204
477
205
473
206
464
204
460
205
456
206
448
205
580
213
582
217
584
221
586
226
587
230
586
233
587
237
586
240
586
244
581
245
577
246
567
244
563
246
558
247
548
245
543
246
618
223
619
228
621
232
623
237
625
242
626
247
628
253
630
258
632
263
627
265
623
267
613
265
608
266
603
268
592
265
587
266
663
248
666
254
669
259
672
265
669
267
661
265
658
267
649
266
645
267
635
265
631
267
626
268
615
266
610
267
605
268
592
265

Eavaporator Inlet Air Temperature (C)


0 (RH 85%)
Boost
Hc (kW)
Pi (kW)
613
206
607
204
604
205
597
204
594
205
590
206
581
204
577
205
573
206
568
206
558
204
553
205
547
205
542
206
536
206
524
203
711
228
711
231
711
235
710
238
710
241
708
244
703
245
697
245
692
246
683
245
676
245
670
246
664
247
653
245
645
245
638
246
757
240
758
245
760
249
761
254
762
259
764
263
758
265
753
266
748
267
736
265
730
266
723
267
717
268
704
265
697
266
690
267
810
265
806
267
797
265
793
267
789
268
778
266
774
267
762
265
756
266
750
267
744
268
731
265
724
266
717
267
710
268
694
264

7 (RH 85%)
Rated
Hc (kW)
Pi (kW)
476
137
476
140
476
142
476
145
476
147
476
150
475
153
475
155
475
158
475
161
475
164
474
167
474
170
474
173
474
176
473
179
534
147
534
150
533
153
533
155
533
158
532
161
532
164
531
167
531
170
531
173
530
176
530
179
529
182
529
185
528
189
527
192
563
154
562
157
562
159
561
162
561
165
560
168
560
171
559
174
559
177
558
181
558
184
557
187
556
190
556
194
555
197
554
201
617
171
617
174
617
177
616
181
616
184
616
187
616
191
616
194
616
198
615
202
615
205
615
209
614
213
614
217
614
221
613
225

Boost
Hc (kW)
Pi (kW)
690
206
682
205
678
205
673
206
663
204
658
205
653
206
648
206
636
204
630
204
623
204
617
205
610
205
603
205
596
206
588
206
816
238
815
241
814
244
807
245
802
246
797
247
785
244
779
245
772
246
766
247
757
247
744
245
737
245
729
246
721
246
713
247
874
254
875
259
877
264
871
265
865
266
859
267
846
265
839
266
832
267
825
267
817
268
802
265
794
266
786
266
777
267
768
267
908
266
904
267
892
265
887
266
881
267
868
264
861
265
854
266
847
267
840
268
824
265
815
265
807
266
798
266
789
267
780
267

12 (RH 85%)
Rated
Hc (kW)
Pi (kW)
551
144
551
146
551
149
551
151
550
154
550
157
549
159
549
162
549
165
548
168
548
171
547
174
547
177
546
180
546
183
545
186
618
154
618
157
617
159
617
162
616
165
616
168
615
171
614
174
613
177
613
180
612
183
611
186
610
189
609
193
609
196
608
199
652
161
651
164
650
167
650
170
649
173
648
176
647
179
646
182
645
185
645
188
644
192
643
195
642
198
641
202
640
205
639
209
714
179
713
182
713
185
712
189
712
192
712
196
711
199
711
203
710
206
710
210
709
214
708
218
708
221
707
225
707
229
706
233

KPMHP00511-09EN page 38/60

083.2

079.2

072.2

Boost
Hc (kW)
Pi (kW)
230
107
231
109
231
111
231
113
232
115
232
117
232
120
233
122
233
125
234
127
234
130
234
132
232
133
230
134
225
132
223
133
253
116
253
118
254
121
254
123
252
124
251
125
248
126
247
128
246
129
244
130
242
132
240
132
237
133
235
134
231
133
226
133
275
123
276
126
276
129
277
132
275
133
272
134
267
133
265
134
259
132
256
133
251
132
248
133
245
134
239
132
236
133
233
133

-10 (RH 100%)

Rated
Hc (kW)
Pi (kW)
230
107
231
109
231
111
231
113
232
115
232
117
232
120
233
122
233
125
234
127
234
130
234
132
232
133
230
134
225
132
223
133
253
116
253
118
254
121
254
123
252
124
251
125
248
126
247
128
246
129
244
130
242
132
240
132
237
133
235
134
231
133
226
133
275
123
276
126
276
129
277
132
275
133
272
134
267
133
265
134
259
132
256
133
251
132
248
133
245
134
239
132
236
133
233
133

Boost
Hc (kW)
Pi (kW)
268
108
269
111
269
113
270
115
270
117
270
120
271
122
271
124
272
127
272
130
272
132
270
133
267
134
262
132
259
133
257
134
296
119
296
121
295
123
294
124
291
125
290
127
287
127
286
129
284
130
281
131
280
133
277
133
273
133
268
133
265
133
262
134
323
127
323
130
324
133
321
134
315
133
312
134
306
133
303
133
298
133
295
133
292
134
285
133
282
133
278
134
271
132
268
133

-5 (RH 100%)
Rated
Hc (kW)
Pi (kW)
247
96.0
247
97.9
247
100
247
102
247
104
247
106
247
108
248
110
248
112
248
114
248
117
248
119
248
121
248
124
249
126
249
128
271
105
272
107
272
109
272
112
272
114
272
116
273
118
273
121
271
122
270
124
268
125
265
126
263
127
262
128
260
130
256
130
296
113
297
115
297
117
297
120
297
122
297
125
298
127
298
130
298
133
295
133
292
134
285
133
282
133
278
134
271
132
268
133

Notes:
Hc (heating capacity) - Pi (unit power input) CLWT (condenser leaving water temperature t 5C)
Data are referred to 0,0176 m2 C/kW evaporator fouling factor
Rated conditions are for compressors running at nominal frequency
Boost conditions are for compressors running at maximum frequency
Refer to Operating limit chapter for Integrated Heating Capacity

35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50

CLWT (C)
Rated
Hc (kW)
Pi (kW)
261
87.4
261
89.0
261
90.6
260
92.2
260
93.9
260
95.6
260
97.3
260
99.1
260
101
260
103
259
105
259
107
259
109
259
111
259
113
259
115
287
95.9
287
97.6
287
99.4
287
101
287
103
286
105
286
107
286
109
286
111
286
113
286
115
286
118
285
120
285
122
283
123
279
124
314
103
314
105
313
107
313
109
313
111
313
113
313
115
313
117
312
120
312
122
312
124
312
127
312
129
312
132
308
132
303
133

Boost
Hc (kW)
Pi (kW)
311
112
311
114
311
116
311
118
312
120
312
123
313
125
313
128
313
130
314
133
311
134
305
132
302
133
299
134
293
133
290
133
342
123
339
123
338
125
335
125
333
127
332
128
328
129
327
131
323
131
322
133
318
133
313
133
308
133
305
133
300
133
296
133
374
132
371
133
367
133
361
132
358
133
354
134
348
133
344
134
337
132
333
133
330
134
322
132
318
133
314
133
310
134
306
134

Eavaporator Inlet Air Temperature (C)


0 (RH 85%)
Boost
Hc (kW)
Pi (kW)
381
119
381
121
381
123
381
126
381
128
381
130
381
133
378
133
374
134
367
132
364
133
360
133
356
134
352
134
345
133
341
133
407
126
405
127
403
129
401
130
397
130
395
132
392
133
388
133
384
134
378
133
372
133
367
133
363
133
358
134
352
133
347
133
438
132
434
133
429
133
425
134
417
132
412
133
408
133
403
134
398
134
389
132
384
132
379
133
374
133
369
133
364
133
359
134

7 (RH 85%)
Rated
Hc (kW)
Pi (kW)
274
75.9
274
77.2
273
78.6
273
80.0
272
81.4
272
82.8
272
84.3
271
85.8
271
87.3
270
88.8
270
90.4
269
92.0
269
93.6
268
95.2
268
96.9
267
98.6
302
83.2
301
84.7
301
86.2
300
87.8
300
89.3
299
90.9
299
92.6
298
94.2
298
95.9
297
97.6
297
99.3
296
101
296
103
295
105
295
107
294
108
329
89.5
329
91.1
328
92.8
328
94.4
327
96.1
327
97.9
326
100
326
101
325
103
325
105
324
107
324
109
323
111
322
113
322
115
321
117

Boost
Hc (kW)
Pi (kW)
439
126
439
128
439
130
439
133
435
133
431
134
428
134
419
133
415
133
411
133
407
134
402
134
394
132
389
133
384
133
379
133
462
130
458
130
455
131
452
133
448
133
443
133
438
134
432
133
427
133
422
134
414
133
409
133
401
132
396
132
391
132
385
133
491
133
486
134
476
132
471
133
466
133
460
133
455
133
449
134
444
134
433
132
427
132
421
132
415
132
409
132
403
132
397
132

12 (RH 85%)
Rated
Hc (kW)
Pi (kW)
317
79.3
317
80.7
316
82.0
316
83.5
315
84.9
315
86.3
314
87.8
313
89.3
313
90.9
312
92.4
312
94.0
311
95.6
310
97.3
310
98.9
309
101
308
102
349
87.1
348
88.6
348
90.1
347
91.7
346
93.3
346
94.9
345
96.6
345
98.2
344
100
343
102
342
103
342
105
341
107
340
109
340
111
339
113
381
93.6
380
95.2
380
96.9
379
98.6
378
100
378
102
377
104
376
106
375
107
375
109
374
111
373
113
372
115
372
117
371
119
370
121

Heating Mode - McEnergy HPI Extension SE-LN

KPMHP00511-09EN page 39/60

103.2

096.2

093.2

Boost
Hc (kW)
Pi (kW)
278
134
278
137
279
140
280
143
277
146
275
147
271
150
270
151
270
153
269
155
269
157
267
157
264
157
262
158
257
156
255
157
281
142
281
146
282
149
280
152
283
155
285
159
287
162
289
166
291
170
293
173
295
177
294
178
290
177
289
178
284
177
282
178
302
152
304
155
306
159
309
162
311
166
311
168
310
169
308
170
308
173
307
174
306
176
305
178
301
177
298
177
296
178
290
177

-10 (RH 100%)


Rated
Hc (kW)
Pi (kW)
278
134
278
137
279
140
280
143
277
146
275
147
271
150
270
151
270
153
269
155
269
157
267
157
264
157
262
158
257
156
255
157
281
142
281
146
282
149
280
152
283
155
285
159
287
162
289
166
291
170
293
173
295
177
294
178
290
177
289
178
284
177
282
178
302
152
304
155
306
159
309
162
311
166
311
168
310
169
308
170
308
173
307
174
306
176
305
178
301
177
298
177
296
178
290
177

Boost
Hc (kW)
Pi (kW)
326
137
326
140
327
143
324
146
318
148
316
150
311
151
311
154
310
155
310
157
307
157
304
157
301
157
297
157
295
158
290
156
329
146
329
149
330
152
327
156
326
159
328
163
331
166
333
170
335
173
337
177
336
178
332
177
331
178
326
177
324
178
320
177
351
155
353
159
355
162
357
166
356
167
356
170
355
171
355
173
353
174
353
177
349
177
347
178
343
178
339
177
335
177
331
177

-5 (RH 100%)
Rated
Hc (kW)
Pi (kW)
299
122
299
125
300
127
300
130
300
133
300
136
300
138
301
141
301
144
296
146
296
148
296
150
294
151
293
153
293
155
290
156
302
130
302
132
300
135
302
138
303
141
305
144
307
147
308
150
310
153
311
157
313
160
314
163
316
167
317
170
318
174
320
177
328
138
329
141
331
144
332
147
334
150
335
154
336
157
338
160
339
163
341
167
338
168
337
170
334
171
334
173
333
175
331
177

Notes:
Hc (heating capacity) - Pi (unit power input) CLWT (condenser leaving water temperature t 5C)
Data are referred to 0,0176 m2 C/kW evaporator fouling factor
Rated conditions are for compressors running at nominal frequency
Boost conditions are for compressors running at maximum frequency
Refer to Operating limit chapter for Integrated Heating Capacity

35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50

CLWT (C)
Rated
Hc (kW)
Pi (kW)
317
111
317
114
317
116
316
118
316
120
316
123
316
125
313
128
313
130
314
133
315
136
315
138
316
141
317
144
317
146
316
148
319
118
320
120
321
123
322
125
323
128
324
130
325
133
326
136
327
139
328
141
329
144
330
147
331
150
332
153
333
156
334
159
351
126
352
128
353
131
354
133
355
136
356
139
356
142
357
145
358
147
359
150
360
153
360
157
361
160
362
163
362
166
361
168

Boost
Hc (kW)
Pi (kW)
378
141
374
144
371
146
365
148
361
150
355
152
354
153
354
156
352
157
349
157
346
157
342
157
340
157
335
156
332
157
329
158
381
150
378
153
375
156
371
160
373
163
375
167
378
170
380
174
382
178
378
177
377
178
373
177
371
178
366
176
364
177
361
178
404
160
406
163
406
165
407
168
405
169
405
171
403
173
403
175
401
176
399
177
397
178
391
177
388
178
384
178
378
177
374
177

Eavaporator Inlet Air Temperature (C)


0 (RH 85%)
Boost
Hc (kW)
Pi (kW)
442
147
438
148
434
150
429
152
423
153
423
156
421
157
417
157
415
158
409
156
407
157
403
157
400
157
396
158
389
156
386
157
446
157
443
160
445
163
447
167
450
170
452
174
454
178
450
177
449
178
444
177
442
178
437
177
434
178
432
179
425
177
422
178
486
166
486
168
484
169
484
171
481
172
481
174
480
176
477
177
473
177
470
178
466
178
460
178
455
177
451
178
446
177
439
177

7 (RH 85%)
Rated
Hc (kW)
Pi (kW)
332
97.8
332
100
332
101
332
103
332
105
332
107
333
109
333
111
333
113
333
115
333
117
333
119
332
121
332
123
332
126
332
128
347
103
347
105
347
107
347
109
348
111
348
113
348
116
348
118
348
120
349
122
349
124
349
127
349
129
349
131
349
134
349
136
379
110
379
112
379
114
379
116
379
118
379
121
379
123
379
125
379
127
379
130
379
132
379
134
379
137
379
139
379
142
379
145

Boost
Hc (kW)
Pi (kW)
496
151
491
153
482
154
481
156
479
157
475
157
471
156
468
157
465
158
458
156
455
157
451
157
446
157
442
157
437
158
431
157
508
165
510
169
512
172
514
175
513
177
512
178
507
177
505
178
503
179
497
177
494
178
492
179
485
177
481
178
477
178
469
176
552
169
551
171
551
173
547
174
546
176
545
178
538
177
535
178
530
177
526
178
520
178
513
177
509
177
502
177
498
177
493
178

12 (RH 85%)
Rated
Hc (kW)
Pi (kW)
384
102
384
104
384
106
384
107
384
109
384
111
384
113
384
115
384
117
383
119
383
122
383
124
383
126
383
128
382
130
382
133
401
108
401
110
401
112
401
114
401
116
401
118
401
120
402
122
402
125
401
127
402
129
401
131
401
134
401
136
401
139
401
141
438
115
438
117
438
119
438
121
438
123
438
125
437
128
437
130
437
132
437
135
437
137
437
139
436
142
436
144
436
147
435
150

KPMHP00511-09EN page 40/60

124.2

117.2

109.2

Boost
Hc (kW)
Pi (kW)
332
162
334
166
336
170
338
173
339
177
338
179
333
178
328
176
326
178
321
176
319
177
316
178
310
177
308
178
305
179
298
177
370
179
371
183
372
187
373
191
375
195
372
197
368
197
364
197
359
197
355
197
350
196
345
196
342
197
337
197
332
196
326
196
388
191
389
195
390
199
392
204
393
208
395
213
388
211
386
213
380
211
377
213
370
211
367
212
364
213
357
211
354
212
346
210

-10 (RH 100%)


Rated
Hc (kW)
Pi (kW)
332
162
334
166
336
170
338
173
339
177
338
179
333
178
328
176
326
178
321
176
319
177
316
178
310
177
308
178
305
179
298
177
370
179
371
183
372
187
373
191
375
195
372
197
368
197
364
197
359
197
355
197
350
196
345
196
342
197
337
197
332
196
326
196
388
191
389
195
390
199
392
204
393
208
395
213
388
211
386
213
380
211
377
213
370
211
367
212
364
213
357
211
354
212
346
210

Boost
Hc (kW)
Pi (kW)
387
167
389
170
390
174
392
178
387
177
386
178
380
177
378
178
372
177
371
179
364
177
361
178
354
176
351
177
347
178
344
179
410
182
412
186
413
190
415
195
414
196
410
196
406
197
402
196
398
196
394
196
391
197
386
196
381
196
378
197
373
196
368
196
428
194
429
198
432
203
434
207
436
212
430
210
428
212
423
211
421
212
415
210
413
212
407
211
404
212
401
213
394
211
391
212

-5 (RH 100%)
Rated
Hc (kW)
Pi (kW)
359
148
361
151
362
154
363
158
364
161
366
164
367
168
368
171
369
175
371
179
364
177
361
178
354
176
351
177
347
178
344
179
380
162
381
165
383
169
384
173
386
176
387
180
388
184
390
187
391
191
391
194
391
197
386
196
381
196
378
197
373
196
368
196
396
172
398
176
399
180
401
184
403
187
404
191
406
195
408
200
410
204
411
208
413
212
407
211
404
212
401
213
394
211
391
212

Notes:
Hc (heating capacity) - Pi (unit power input) CLWT (condenser leaving water temperature t 5C)
Data are referred to 0,0176 m2 C/kW evaporator fouling factor
Rated conditions are for compressors running at nominal frequency
Boost conditions are for compressors running at maximum frequency
Refer to Operating limit chapter for Integrated Heating Capacity

35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50

CLWT (C)
Rated
Hc (kW)
Pi (kW)
384
135
385
137
385
140
386
143
387
146
387
149
388
152
388
155
389
158
390
161
390
164
391
167
391
171
392
174
392
178
388
178
399
147
400
150
401
153
403
156
404
159
405
162
407
166
408
169
410
173
411
176
412
180
413
183
415
187
416
190
417
194
416
197
414
156
415
159
417
162
419
166
420
169
422
173
424
176
425
180
427
183
429
187
430
191
432
195
434
199
435
203
437
207
438
211

Boost
Hc (kW)
Pi (kW)
445
171
447
175
446
177
444
178
438
177
436
178
430
177
427
178
420
177
417
178
414
179
406
177
403
178
399
179
392
178
388
178
457
186
459
190
462
195
461
196
458
197
455
197
450
196
449
197
443
196
441
197
435
195
433
196
430
197
423
195
420
196
416
197
473
198
476
203
479
207
482
212
481
213
476
212
472
211
470
212
465
211
464
212
458
211
456
212
454
213
447
211
444
212
441
213

Eavaporator Inlet Air Temperature (C)


0 (RH 85%)
Boost
Hc (kW)
Pi (kW)
534
177
532
178
526
177
523
178
515
177
512
177
508
178
500
177
496
177
492
178
487
179
478
177
473
177
468
178
463
178
452
176
543
194
544
196
543
197
540
196
538
197
536
197
533
197
529
197
526
196
521
196
516
196
513
196
510
197
501
195
497
196
493
196
559
206
563
210
563
212
560
211
561
213
557
212
554
211
553
212
548
211
547
212
541
210
539
212
536
213
528
210
524
211
521
212

7 (RH 85%)
Rated
Hc (kW)
Pi (kW)
411
117
411
120
411
122
411
124
411
126
411
129
410
131
410
134
410
136
410
139
410
141
409
144
409
146
409
149
409
152
408
154
439
121
440
123
440
126
441
128
441
130
441
132
442
135
442
137
442
140
442
142
443
145
443
147
443
150
443
153
443
155
443
158
457
137
458
140
458
142
459
145
460
148
461
150
461
153
462
156
462
159
463
162
463
165
464
168
464
171
465
174
465
177
465
181

Boost
Hc (kW)
Pi (kW)
598
177
595
178
592
178
583
177
579
178
574
178
564
176
560
177
554
177
549
178
544
178
532
176
526
176
520
177
514
177
507
177
621
196
620
196
617
196
615
196
613
198
608
196
605
197
600
197
594
196
591
197
584
196
579
197
574
197
569
198
560
196
551
195
641
212
639
211
640
212
637
211
637
213
633
211
632
213
626
211
624
212
621
213
613
211
609
212
604
212
600
213
589
210
583
211

12 (RH 85%)
Rated
Hc (kW)
Pi (kW)
475
123
475
125
475
127
474
129
474
132
474
134
474
136
473
139
473
141
472
144
472
147
472
149
471
152
471
154
470
157
470
160
513
126
513
128
513
131
514
133
514
135
514
138
514
140
514
143
514
145
514
148
513
150
513
153
513
155
513
158
513
161
512
164
534
143
535
146
535
149
535
151
536
154
536
157
536
160
537
163
537
166
537
169
537
172
537
175
537
178
538
181
537
184
537
188

KPMHP00511-09EN page 41/60


167.3

153.3

144.3

130.3

Boost
Hc (kW)
Pi (kW)
391
185
393
189
394
194
396
198
397
202
399
206
392
205
390
204
383
205
381
204
374
205
371
204
368
205
360
206
357
204
346
205
428
200
430
204
433
209
435
213
437
218
439
223
441
227
440
230
440
233
440
237
439
241
440
245
435
245
432
247
425
246
420
246
455
209
457
214
459
219
461
223
463
228
465
233
466
238
468
243
470
248
472
254
473
259
475
264
472
266
468
268
460
266
456
267
493
234
496
239
499
245
501
250
504
256
507
261
510
267
503
266
500
268
493
266
490
268
482
266
478
267
470
265
466
266
462
268

-10 (RH 100%)


Rated
Hc (kW)
Pi (kW)
391
185
393
189
394
194
396
198
397
202
399
206
392
205
390
204
383
205
381
204
374
205
371
204
368
205
360
206
357
204
346
205
428
200
430
204
433
209
435
213
437
218
439
223
441
227
440
230
440
233
440
237
439
241
440
245
435
245
432
247
425
246
420
246
455
209
457
214
459
219
461
223
463
228
465
233
466
238
468
243
470
248
472
254
473
259
475
264
472
266
468
268
460
266
456
267
493
234
496
239
499
245
501
250
504
256
507
261
510
267
503
266
500
268
493
266
490
268
482
266
478
267
470
265
466
266
462
268

Boost
Hc (kW)
Pi (kW)
440
191
443
195
445
199
448
203
446
205
441
204
439
205
433
204
431
205
425
204
422
205
415
204
411
205
408
206
400
204
396
204
501
206
503
210
505
215
507
219
509
224
510
228
511
232
510
235
511
239
510
242
510
246
505
247
498
246
493
246
485
245
481
246
533
216
535
220
537
225
539
230
541
235
542
240
544
245
546
250
548
255
549
261
551
266
547
268
538
266
534
267
524
265
520
267
575
241
578
246
581
251
584
257
586
263
584
265
581
267
574
265
571
267
562
265
559
267
550
265
546
267
536
264
531
266
527
267

-5 (RH 100%)
Rated
Hc (kW)
Pi (kW)
411
170
413
173
414
177
416
181
417
184
419
188
421
192
422
196
424
200
425
204
422
205
415
204
411
205
408
206
400
204
396
204
466
183
467
187
469
191
470
195
471
199
472
203
474
207
475
211
476
216
477
220
478
224
478
228
478
232
476
234
475
238
474
242
494
191
495
195
497
200
498
204
499
208
500
212
501
217
502
221
503
226
504
230
505
235
506
240
507
245
508
249
509
254
510
260
536
214
538
218
539
223
542
228
543
233
545
238
547
243
549
248
551
253
553
258
554
264
550
265
546
267
536
264
531
266
527
267

Notes:
Hc (heating capacity) - Pi (unit power input) CLWT (condenser leaving water temperature t 5C)
Data are referred to 0,0176 m2 C/kW evaporator fouling factor
Rated conditions are for compressors running at nominal frequency
Boost conditions are for compressors running at maximum frequency
Refer to Operating limit chapter for Integrated Heating Capacity

35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50

CLWT (C)
Rated
Hc (kW)
Pi (kW)
442
156
443
159
444
162
444
165
445
168
446
171
447
175
448
178
448
182
449
185
450
189
451
192
451
196
452
200
452
204
448
205
500
168
500
171
501
174
501
178
501
181
502
184
502
188
503
192
503
195
504
199
504
203
505
207
505
211
505
215
506
219
506
223
529
176
529
179
530
183
530
186
530
190
530
193
530
197
531
200
531
204
531
208
532
212
532
217
532
221
532
225
533
229
533
234
575
195
576
199
576
203
577
207
578
211
579
215
580
220
581
224
582
229
583
233
584
238
585
243
586
248
587
252
587
257
588
263

Boost
Hc (kW)
Pi (kW)
509
197
511
201
514
206
508
205
506
206
500
205
498
206
491
205
488
206
480
204
477
205
473
206
464
204
460
205
456
206
448
205
580
213
582
217
584
221
586
226
587
230
586
233
587
237
586
240
586
244
581
245
577
246
567
244
563
246
558
247
548
245
543
246
618
223
619
228
621
232
623
237
625
242
626
247
628
253
630
258
632
263
627
265
623
267
613
265
608
266
603
268
592
265
587
266
663
248
666
254
669
259
672
265
669
267
661
265
658
267
649
266
645
267
635
265
631
267
626
268
615
266
610
267
605
268
592
265

Eavaporator Inlet Air Temperature (C)


0 (RH 85%)
Boost
Hc (kW)
Pi (kW)
613
206
607
204
604
205
597
204
594
205
590
206
581
204
577
205
573
206
568
206
558
204
553
205
547
205
542
206
536
206
524
203
711
228
711
231
711
235
710
238
710
241
708
244
703
245
697
245
692
246
683
245
676
245
670
246
664
247
653
245
645
245
638
246
757
240
758
245
760
249
761
254
762
259
764
263
758
265
753
266
748
267
736
265
730
266
723
267
717
268
704
265
697
266
690
267
810
265
806
267
797
265
793
267
789
268
778
266
774
267
762
265
756
266
750
267
744
268
731
265
724
266
717
267
710
268
694
264

7 (RH 85%)
Rated
Hc (kW)
Pi (kW)
476
137
476
140
476
142
476
145
476
147
476
150
475
153
475
155
475
158
475
161
475
164
474
167
474
170
474
173
474
176
473
179
534
147
534
150
533
153
533
155
533
158
532
161
532
164
531
167
531
170
531
173
530
176
530
179
529
182
529
185
528
189
527
192
563
154
562
157
562
159
561
162
561
165
560
168
560
171
559
174
559
177
558
181
558
184
557
187
556
190
556
194
555
197
554
201
617
171
617
174
617
177
616
181
616
184
616
187
616
191
616
194
616
198
615
202
615
205
615
209
614
213
614
217
614
221
613
225

Boost
Hc (kW)
Pi (kW)
690
206
682
205
678
205
673
206
663
204
658
205
653
206
648
206
636
204
630
204
623
204
617
205
610
205
603
205
596
206
588
206
816
238
815
241
814
244
807
245
802
246
797
247
785
244
779
245
772
246
766
247
757
247
744
245
737
245
729
246
721
246
713
247
874
254
875
259
877
264
871
265
865
266
859
267
846
265
839
266
832
267
825
267
817
268
802
265
794
266
786
266
777
267
768
267
908
266
904
267
892
265
887
266
881
267
868
264
861
265
854
266
847
267
840
268
824
265
815
265
807
266
798
266
789
267
780
267

12 (RH 85%)
Rated
Hc (kW)
Pi (kW)
551
144
551
146
551
149
551
151
550
154
550
157
549
159
549
162
549
165
548
168
548
171
547
174
547
177
546
180
546
183
545
186
618
154
618
157
617
159
617
162
616
165
616
168
615
171
614
174
613
177
613
180
612
183
611
186
610
189
609
193
609
196
608
199
652
161
651
164
650
167
650
170
649
173
648
176
647
179
646
182
645
185
645
188
644
192
643
195
642
198
641
202
640
205
639
209
714
179
713
182
713
185
712
189
712
192
712
196
711
199
711
203
710
206
710
210
709
214
708
218
708
221
707
225
707
229
706
233

Evaporator water pressure drops


McEnergy HPI ExtensionSE-ST
Cooling Capacity (kW)
Water Flow (l/s)
Pressure Drops (kPa)

072.2

079.2

083.2

093.2

096.2

103.2

109.2

117.2

124.2

130.3

144.3

153.3

167.3

254

273

292

324

339

365

382

413

436

457

505

522

583

12.12

13.03

13.94

15.46

16.21

17.42

18.25

19.72

20.81

21.83

24.11

24.92

27.87

37

42

48

53

58

53

57

46

51

61

50

53

65

Water flow and pressure drop referred to nominal codition: evaporator water in/out: 12/7C condenser air inlet: 35C

Heating Capacity (kW)


Water Flow (l/s)
Pressure Drops (kPa)

072.2

079.2

083.2

093.2

096.2

103.2

109.2

117.2

124.2

130.3

144.3

153.3

167.3

270

297

324

333

349

379

410

443

463

475

530

558

615

12.89

14.18

15.49

15.89

16.66

18.11

19.57

21.15

22.14

22.68

25.33

26.65

29.39

42

49

58

55

60

57

65

52

57

66

55

60

71

Water flow and pressure drop referred to nominal codition: condenser water in/out: 40/45C evaporator air inlet: 7C DB / 6C WB

McEnergy HPI ExtensionSE-LN


Cooling Capacity (kW)
Water Flow (l/s)
Pressure Drops (kPa)

072.2

079.2

083.2

093.2

096.2

103.2

109.2

117.2

124.2

130.3

144.3

153.3

167.3

248

266

291

316

331

355

372

403

425

448

493

510

567

11.83

12.70

13.89

15.12

15.83

16.98

17.77

19.28

20.30

21.39

23.56

24.34

27.11

36

40

48

51

55

50

55

44

48

59

48

51

62

Water flow and pressure drop referred to nominal codition: evaporator water in/out: 12/7C condenser air inlet: 35C

Heating Capacity (kW)


Water Flow (l/s)
Pressure Drops (kPa)

072.2

079.2

083.2

093.2

096.2

103.2

109.2

117.2

124.2

130.3

144.3

153.3

167.3

270

297

324

333

349

379

410

443

463

475

530

558

615

12.89

14.18

15.49

15.89

16.66

18.11

19.57

21.15

22.14

22.68

25.33

26.65

29.39

42

49

58

55

60

57

65

52

57

66

55

60

71

Water flow and pressure drop referred to nominal codition: condenser water in/out: 40/45C evaporator air inlet: 7C DB / 6C WB

To determinate the pressure drop for different versions or at different working condition, please refer to the following
formula:
PD2 (kPa) = PD1 (kPa) x
where:
PD2
Pressure drop to be determinate (kPa)
PD1
Pressure drop at nominal condition (kPa)
Q2
water flow at new working condition (l/s)
Q1
water flow at nominal condition (l/s)
How to use the formula: Example
The unit McEnergy HPI Extension SE 072.2 ST has been selected for working at the following conditions:
- evaporator water in/out : 11/6C
- condenser air inlet: 30C
The cooling capacity at these working conditions is: 265 kW (Rated conditions)
The water flow at these working conditions is: 12.68 l/s (Rated conditions)
The unit McEnergy HPI Extension SE 072.2 ST at nominal working conditions has the following data:
- evaporator water in/out : 12/7C
- condenser air inlet: 35C
The cooling capacity at these working conditions is: 254 kW
The water flow at these working conditions is: 12.12 l/s
The pressure drop at these working conditions is: 37 kPa
The pressure drop at the selected working condition will be:
PD2 (kPa) = 37 (kPa) x
PD2 (kPa) = 40 (kPa)
NOTE
If the calculated evaporator water pressure drop is below 10 kPa or above 100 kPa please contact the factory for
dedicated evaporator.

KPMHP00511-09EN page 42/60

Options
Partial Heat Recovery
Ratings Pressure Drops
McEnergy HPI ExtensionSE-ST/LN
Partial Heat Recovery Leaving Water Temperature (C)

Partial Heat Rrecovery LWT 45C

55 (t=5C)

Water Flow

Pressure Drops

Hc (kW)

Hc (kW)

Hc (kW)

l/s

kPa

072.2

74.3

67.8

57.9

3.55

079.2

80.9

76.1

65.4

3.87

083.2

88.5

85.2

73.5

4.23

93.5

88.2

75.7

4.47

99.4

91.9

78.6

4.75

106

100

85.7

5.06

115

109

94.2

5.49

117

107

96.0

5.60

22

125

113

102

5.95

24

133

128

110

6.34

15

144.3

144

135

115

6.86

18

153.3

149

138

118

7.12

14

167.3

173

164

141

8.24

18

093.2
096.2
103.2
109.2
117.2
124.2
130.3

Condenser Inlet Air 35C

50 (t=5C)

Evaporator Leaving
Temperature 7C - t 5C

45 (t=5C)

To determinate the pressure drop for different versions or at different working condition, please refer
to the following formula:
PD2 (kPa) = PD1 (kPa) x

where:
PD2
PD1
Q2
Q1

Pressure drop to be determinate (kPa)


Pressure drop at nominal condition (kPa)
water flow at new working condition (l/s)
water flow at nominal condition (l/s)

How to use the formula: Example


The unit McEnergy HPI Extension SE 072.2 ST has been selected for working at the following conditions:
- Partial heat recovery leaving water temperature 50/55C
The heating capacity at these working conditions is: 57.9 kW
The water flow at these working conditions is: 2.77 l/s
The unit McEnergy HPI Extension SE 072.2 ST at nominal working conditions has the following data:
- Partial heat recovery leaving water temperature 40/45C
- condenser air inlet: 35C
The heating capacity at these working conditions is: 74.3 kW
The water flow at these working conditions is: 3.55 l/s
The pressure drop at these working conditions is: 5 kPa

The pressure drop at the selected working condition will be:

PD2 (kPa) = 5 (kPa) x

PD2 (kPa) = 3 (kPa)

KPMHP00511-09EN page 43/60

Water Pump Kit


Single Pump (2 poles) - Low Available external static pressure
300

Available External Static Pressure (kPa)

280
260
240
220
200
180
160

SPK 4

140
120
100

SPK 3

80

SPK 1

60

SPK 2

40
20
0
0

10

12

14

16

18

20

22

24

26

28

30

32

34

36

38

40

Water Flow (l/s)

Single Pump (2 poles) - Low Available external static pressure


300

Available External Static Pressure (kPa)

280
260
240
220
200
180

SPK 8

160

SPK 9

140

SPK 5

120

SPK 10

100
80

SPK 6

60
40

SPK 7

20
0
0

10

12

14

16

18

20

22

24

26

28

30

32

34

36

38

40

Water Flow (l/s)

Pump Kit

SPK1

SPK2

SPK3

SPK4

SPK5

Unit size SE-ST

072.2

079.2

083.2

093.2

096.2

103.2

Unit size SE-LN

072.2

079.2

083.2

093.2

096.2

103.2

SPK7

SPK8

SPK9

109.2

117.2

124.2

130.3

144.3

153.3

167.3

109.2

117.2

124.2

130.3

144.3

153.3

167.3

Note
- when using mixture of water and glycol please contact the factory as above specification can change

KPMHP00511-09EN page 44/60

SPK10

SPK6

Single Pump (2 poles) - High Available external static pressure


425

Available External Static Pressure (kPa)

400
375
350
325
300
275
250
225
200
175
150

SPK 4

125

SPK 1

100
75

SPK 3

SPK 2

50
25
0
0

10

12

14

16

18

20

22

24

26

28

30

32

34

36

38

40

Water Flow (l/s)

Single Pump (2 poles) - High Available external static pressure


425

Available External Static Pressure (kPa)

400
375

SPK 10

350
325
300
275

SPK 9

250
225

SPK 7

200
175
150
125

SPK 5

100

SPK 8

75
50

SPK 6

25
0
0

10

12

14

16

18

20

22

24

26

28

30

32

34

36

38

40

Water Flow (l/s)

Pump Kit

SPK1

SPK2

SPK3

SPK4

Unit size SE-ST

072.2

079.2

083.2

093.2

Unit size SE-LN

072.2

079.2

083.2

093.2

SPK7

SPK5

SPK6

096.2

103.2

109.2

117.2

096.2

103.2

109.2

117.2

SPK10

SPK8

SPK9

124.2

130.3

144.3

153.3

167.3

124.2

130.3

144.3

153.3

167.3

Note
- when using mixture of water and glycol please contact the factory as above specification can change

KPMHP00511-09EN page 45/60

Twin Pump (2 poles) - Low Available external static pressure


300

Available External Static Pressure (kPa)

280
260
240
220
200
180
160

DPK 2

140
120
100

DPK 4

DPK 1

80

DPK 3

60
40
20
0
0

10

12

14

16

18

20

22

24

26

28

30

32

34

36

38

40

34

36

38

40

Water Flow (l/s)

Twin Pump (2 poles) - Low Available external static pressure


300

Available External Static Pressure (kPa)

280
260
240
220
200

DPK 8

180

DPK 9

160
140

DPK 5

120
100

DPK 6

80
60
40

DPK 7

20
0
0

10

12

14

16

18

20

22

24

26

28

30

32

Water Flow (l/s)

Pump Kit

DPK1

DPK2

DPK3

DPK4

DPK5

DPK6

DPK7

DPK9

Unit size SE-ST

072.2

079.2

083.2

093.2

096.2

103.2

109.2

117.2

124.2

130.3

144.3

153.3

167.3

Unit size SE-LN

072.2

079.2

083.2

093.2

096.2

103.2

109.2

117.2

124.2

130.3

144.3

153.3

167.3

DPK8

Note
- when using mixture of water and glycol please contact the factory as above specification can change

KPMHP00511-09EN page 46/60

Twin Pump (2 poles) - High Available external static pressure


425

Available External Static Pressure (kPa)

400
375
350
325
300
275

SPK 4

250
225
200
175

SPK 3

150
125

DPK 1

100
75

DPK 2

50
25
0
0

10

12

14

16

18

20

22

24

26

28

30

32

34

36

38

40

34

36

38

40

Water Flow (l/s)

Twin Pump (2 poles) - High Available external static pressure


425

Available External Static Pressure (kPa)

400
375
350
325

DPK 8

300
275
250
225
200

DPK 6

175
150

DPK 5

125
100

DPK 7

75
50
25
0
0

10

12

14

16

18

20

22

24

26

28

30

32

Water Flow (l/s)

Pump Kit

DPK1

DPK2

Unit size SE-ST

072.2

079.2

Unit size SE-LN

072.2

079.2

DPK5

DPK6

DPK8

DPK3

DPK4

DPK7

083.2

093.2

096.2

103.2

109.2

117.2

124.2

130.3

144.3

153.3

167.3

083.2

093.2

096.2

103.2

109.2

117.2

124.2

130.3

144.3

153.3

167.3

Note
- when using mixture of water and glycol please contact the factory as above specification can change

KPMHP00511-09EN page 47/60

Water Pump Kit - Technical Information

Double Pump
Hihg Available Static Pressure

Double Pump
Low Available Static Pressure

Single Pump
High Available Static Pressure

Single Pump
Low Available Static Pressure

Pump Motor Power


(kW)

Pump Motor Current


(A)

Power supply
(V-ph-Hz)

PN

Motor
Protection

Insulation
(Class)

Working Temp.
(C)

SPK 1

2.2

5.0

400V-3ph-50hz

10

IP55

Class F

-10 130

SPK 2

3.0

6.3

400V-3ph-50hz

10

IP55

Class F

-10 130

SPK 3

4.0

7.7

400V-3ph-50hz

10

IP55

Class F

-10 130

SPK 4

4.0

7.7

400V-3ph-50hz

10

IP55

Class F

-10 130

SPK 5

4.0

7.7

400V-3ph-50hz

10

IP55

Class F

-10 130

SPK 6

4.0

7.7

400V-3ph-50hz

10

IP55

Class F

-10 130

SPK 7

5.5

10.4

400V-3ph-50hz

10

IP55

Class F

-10 130

SPK 8

5.5

10.4

400V-3ph-50hz

10

IP55

Class F

-10 130

SPK 9

5.5

10.4

400V-3ph-50hz

10

IP55

Class F

-10 130

SPK 10

7.5

13.9

400V-3ph-50hz

10

IP55

Class F

-10 130

SPK 1

3.0

6.3

400V-3ph-50hz

10

IP55

Class F

-10 130

SPK 2

4.0

7.7

400V-3ph-50hz

10

IP55

Class F

-10 130

SPK 3

5.5

10.4

400V-3ph-50hz

10

IP55

Class F

-10 130

SPK 4

5.5

10.4

400V-3ph-50hz

10

IP55

Class F

-10 130

SPK 5

5.5

10.4

400V-3ph-50hz

10

IP55

Class F

-10 130

SPK 6

7.5

13.9

400V-3ph-50hz

10

IP55

Class F

-10 130

SPK 7

7.5

13.9

400V-3ph-50hz

10

IP55

Class F

-10 130

SPK 8

7.5

13.9

400V-3ph-50hz

10

IP55

Class F

-10 130

SPK 9

7.5

13.9

400V-3ph-50hz

10

IP55

Class F

-10 130

SPK 10

11.0

20.2

400V-3ph-50hz

10

IP55

Class F

-10 130

Pump Motor Power


(kW)

Pump Motor Current


(A)

Power supply
(V-ph-Hz)

PN

Motor
Protection

Insulation
(Class)

Working Temp.
(C)

DPK 1

3.0

6.3

400V-3ph-50hz

10

IP55

Class F

-10 130

DPK 2

4.0

7.7

400V-3ph-50hz

10

IP55

Class F

-10 130

DPK 3

4.0

7.7

400V-3ph-50hz

10

IP55

Class F

-10 130

DPK 4

4.0

7.7

400V-3ph-50hz

10

IP55

Class F

-10 130

DPK 5

5.5

10.4

400V-3ph-50hz

10

IP55

Class F

-10 130

DPK 6

5.5

10.4

400V-3ph-50hz

10

IP55

Class F

-10 130

DPK 7

5.5

10.4

400V-3ph-50hz

10

IP55

Class F

-10 130

DPK 8

5.5

10.4

400V-3ph-50hz

10

IP55

Class F

-10 130

DPK 9

7.5

13.9

400V-3ph-50hz

10

IP55

Class F

-10 130

DPK 1

4.0

7.7

400V-3ph-50hz

10

IP55

Class F

-10 130

DPK 2

5.5

10.4

400V-3ph-50hz

10

IP55

Class F

-10 130

DPK 3

5.5

10.4

400V-3ph-50hz

10

IP55

Class F

-10 130

DPK 4

7.5

13.9

400V-3ph-50hz

10

IP55

Class F

-10 130

DPK 5

7.5

13.9

400V-3ph-50hz

10

IP55

Class F

-10 130

DPK 6

7.5

13.9

400V-3ph-50hz

10

IP55

Class F

-10 130

DPK 7

7.5

13.9

400V-3ph-50hz

10

IP55

Class F

-10 130

DPK 8

11.0

20.2

400V-3ph-50hz

10

IP55

Class F

-10 130

DPK 9

11.0

20.2

400V-3ph-50hz

10

IP55

Class F

-10 130

Note
- when using mixture of water and glycol please contact the factory as above specification can change

KPMHP00511-09EN page 48/60

1 - Air heat exchanger (condenser evaporator)


2 - Water heat exchanger (evaporator condenser)
3 - Evaporator water inlet
4 - Evaporator water outlet
5 - Victaulic connection
6 - Electrical control panel
7 - Slot for power and control connection
8 - Fan
9 - Compressor

Legend

2254
2254
2254
2254
2254
2254
2254
2254
2254
2254
2254
2254

2254

072.2
079.2
083.2
093.2
096.2
103.2
109.2
117.2
124.2
130.3
144.3
153.3
167.3

Size

3547
3547
4381
4381
4381
4381
5281
5281
6583
6583
6583
6583

3547

2335
2335
2335
2335
2335
2335
2335
2335
2335
2335
2335
2335

2335

288
288
290
290
290
290
290
290
290
451
451
451

288

Dimensions

2000
2000
2000
2000
2000
2000
2000
2000
2000
1973
1973
1973

2000

449
449
449
449
449
449
449
449
449
503
503
503

449

852
852
852
852
852
852
852
852
852
809
809
809

852

6
6
8
8
8
8
10
10
12
12
12
12

Fans

Dimensions McEnergy HPI Extension SE ST / LN

KPMHP00511-09EN page 49/60

Installation notes
Warning
Installation and maintenance of the unit must to be performed only by qualified personnel who have knowledge with local
codes and regulations, and experience with this type of equipment. Must be avoided the unit installation in places that
could be considered dangerous for all the maintenance operations.

Handling
Care should be taken to avoid rough handling or shock due to dropping the unit. Do not push or pull the unit from
anything other than the base frame. Never allow the unit to fall during unloading or moving as this may result in serious
damage. To lift the unit, rings are provided in the base frame of the unit. Spreader bar and cables should be arranged to
prevent damage to the condenser coil or unit cabinet.

Location
The units are produced for outside installation on roofs, floors or below ground level on condition that the area is free
from obstacles for the passage of the condenser air. The unit should be positioned on solid foundations and perfectly
level; in the case of installation on roofs or floors, it may be advisable to arrange the use of suitable weight distribution
beams. When the units are installed on the ground, a concrete base at least 250 mm wider and longer than the units
footprint should be laid. Furthermore, this base should withstand the unit weight mentioned in the technical data table.

Space requirements
The units are air-cooled, then it is important to respect the minimum distances which guarantee the best ventilation of the
condenser coils. Limitations of space reducing the air flow could cause significant reductions in cooling capacity and an
increase in electricity consumption.
To determinate unit placement, careful consideration must be given to assure a sufficient air flow across the condenser
heat transfer surface. Two conditions must be avoided to achieve the best performance: warm air recirculation and coil
starvation.
Both these conditions cause an increase of condensing pressures that result in reductions in unit efficiency and capacity.
Moreover the unique microprocessor has the ability to calculate the operating environment of the air cooled chiller and
the capacity to optimize its performance staying on-line during abnormal conditions.
Each side of the unit must be accessible after installation for periodic service. Fig.1 shows you minimum recommended
clearance requirements.
Vertical condenser air discharge must be unobstructed because the unit would have its capacity and efficiency
significantly reduced.
If the units are positioned in places surrounded by walls or obstacles of the same height as the units, the units should be
at least 2500 mm from obstacles (Fig.2). In the event the obstacles are higher than the units, the units should be at least
3000 mm from the obstacle (Fig.3). Units installed closer than the minimum recommended distance to a wall or other
vertical riser may experience a combination of coil starvation and warm air recirculation, thus causing reduction in unit
capacity and efficiency reductions. The microprocessor control is proactive in response of design condition. In the case
of single or compounded influences restricting airflow to the unit, the microprocessor will act to keep the compressor(s)
running (at reduced capacity) rather than allowing a shut-off on high discharge pressure.
When two or more units are positioned side by side it is recommended that the condenser coils are at least 3600 mm
distance from one another (Fig.4); strong wind could be the cause of air warm recirculation.
For other installation solutions, consult our technicians.
The above recommended information are representative of general installation. A specific evaluation should be done by
contractor depending on the case.

KPMHP00511-09EN page 50/60

Fig.1 Minimum recommended installation clearances

Fig.2

Fig.3

Fig.3

KPMHP00511-09EN page 51/60

Acoustic protection
When noise level must meet special requirements, it is necessary to pay the maximum attention to ensure the perfect
insulation of the unit from the support base by applying appropriate vibration-dampening devices on the unit, on the
water pipes and on the electrical connections.

Storage
The environment conditions have to be in the following limits:
Minimum ambient temperature:
Maximum ambient temperature:
Maximum R.H.:

KPMHP00511-09EN page 52/60

-20C
+57C
95% not condensing

Technical Specification for Air to Water Heat Pump


GENERAL
The Air to Water Heat Pump will be designed and manufactured in accordance with following European
directives:
Rating of chillers
EN 12055
Construction of pressure vessel
97/23/EC (PED)
Machinery Directive
98/37/EC as modified
Low Voltage
2006/95/EC
Electromagnetic Compatibility
2004/108/EC
Electrical & Safety codes
EN 602041 / EN 60335-2-40
Manufacturing Quality Stds
UNI EN ISO 9001:2000
Rating of chillers
EN 12055
The unit will be tested at full load in the factory at the nominal working conditions and water temperatures.
Before shipment a full test will be held to avoid any losses.
Heat Pump will be delivered to the job site completely assembled and charged with right refrigerant and oil
quantity.
Comply with the manufacturer instructions for rigging and handling equipment.
The unit will be able to start up and operate as standard at full load and outside air temperature from . C
to . C with an evaporator leaving fluid temperature between . C and 15 C
All units published performances have to be certified by Eurovent.
REFRIGERANT
Only HFC 134a will be accepted.
PERFORMANCE
3 Number of air to water heat pumps: ...............
3 Cooling capacity for single air to water heat pump: ............... kW
3 Power input for single air to water heat pump in cooling mode: ............... kW
3 Shell & tube heat exchanger entering water temperature in cooling mode: ............... C
3 Shell & tube heat exchanger leaving water temperature in cooling mode: ............... C
3 Shell & tube heat exchanger water flow: ............... l/s
3 Nominal outside working ambient temperature in cooling mode: ............... C
3
3
3
3
3
3

Heating capacity for single air to water heat pump: ............... kW


Power input for single air to water heat pump in heating mode: ............... kW
Shell & tube heat exchanger entering water temperature in heating mode: ............... C
Shell & tube heat exchanger leaving water temperature in heating mode: ............... C
Shell & tube heat exchanger water flow: ............... l/s
Nominal outside working ambient temperature in heating mode: ............... C

The unit should work with electricity in range 400 V 10%, 3ph, 50Hz without neutral and shall only
have one power connection point. The control circuit voltage shall be 24 V maximum, supplied by a
factory-installed transformer.

UNIT DESCRIPTION
The unit shall include as standard not less than: two or three independent refrigerant circuits, semi-hermetic
rotary single screw compressors, aircooled variable electrical frequency driver for each compressor (VFD),
electronic expansion device (EEXV), refrigerant direct expansion shell & tube heat exchanger, air-cooled
condenser section, R134a refrigerant, lubrication system, motor starting components, suction line shut-off

KPMHP00511-09EN page 53/60

valve, discharge line shut-off valve, control system and all components necessary for safe and stable unit
operation.
The unit will be factory assembled on a robust base-frame made of zinc coated steel, protected by an epoxy
paint.
NOISE LEVEL AND VIBRATIONS
Sound pressure level at 1 meter distance in free field, semispheric conditions, shall not exceed dB(A).
The sound pressure levels must be rated in accordance to ISO 3744.
Other types of rating unacceptable. Vibration level should not exceed 2 mm/s.
DIMENSIONS
Unit dimensions shall not exceed following indications:
3 unit length ............... mm,
3 unit width ............... mm,
3 unit height ............... mm.
HEAT PUMP COMPONENTS
Compressors
9 Semi-hermetic, single-screw type with one main helical rotor meshing with gaterotor. The gaterotor
will be constructed of a carbon impregnated engineered composite material. The gaterotor supports
will be constructed of cast iron.
9 The oil injection shall be used in order to get high EER (Energy Efficiency Ratio) also at high
condensing pressure and low sound pressure levels in each load condition.
9 Refrigerant system differential pressure shall provide oil flow throught service replaceble, 0.5 micron,
full flow, cartridge type oil filter internal to compressor.
Refrigerant system differential pressure shall provide oil injection on all moving compressor parts to
correctly lubricate them. Electrical oil pump lubricating system is not acceptable.
9 The compressors oil cooling must be realized, when necessary, by refrigerant liquid injection.
External dedicated heat exchanger and additional piping to carry the oil from the compressor to heat
exchanger and viceversa will be not accepted.
9 The compressor shall be provided with an integrated, high efficiency, cyclonic type oil separator and
with built-in oil filter, cartridge type.
9 The compressor shall be direct electrical driven, without gear transmission between the screw and
the electrical motor.
9 The compressor casing shall be provided with ports to realize economized refrigerant cycles.
9 Shall be present two thermal protection realized by a thermistor for high temperature protection: one
temperature sensor to protect electrical motor and another sensor to protect unit and lubricating oil
from high discharge gas temperature.
9 The compressor shall be equipped with an electric oil-crankcase heater.
9 Compressor shall be fully field serviceable. Compressor that must be removed and returned to the
factory for service shall be unacceptable.
Cooling capacity control system
9 Each unit will have a microprocessor for the control of compressor inverter position and the
instantaneous RPM value of the motor.
9 The unit capacity control shall be infinitely modulating, both in cooling and in heating mode, from
100% down to 30% for each compressor (from 100% down to 13% of full load for units with 2
compressors and 9% of full load for units with 3 compressors).
9 Step unloading unacceptable because of evaporator leaving water temperature fluctuation and low
unit efficiency at partial load.

KPMHP00511-09EN page 54/60

9
9

9
9

The system shall stage the unit based on the leaving evaporator water temperature that shall be
controlled by a PID (Proportional Integral Derivative) loop.
Unit control logic shall to manage frequency level of the compressor electric motor to exactly match
plant load request in order to keep constant the set point for delivered chilled or hot water
temperature.
In this operating condition unit control logic shall modulate electrical frequency level in a range lower
and upper the nominal electrical network value fixed at 50 Hz.
The microprocessor unit control shall detect conditions that approach protective limits and take selfcorrective action prior to an alarm occurring. The system shall automatically reduce chiller capacity
when any of the following parameters are outside their normal operating range:
o High condenser pressure
o Low evaporation refrigerant temperature
o High compressor motor amps
Ait ro water heat pump shall be able to deliver heating capacity (with -5C outside ambient
temperature) close to its nominal cooling capacity related at +35C outside ambient temperature with
+7C for set-point of the leaving evaporator chilled water. In this condition unit shall be able to deliver
45C hot water.

Unit-Mounted Variable Frequency Driver (VFD) and Electrical Requirement


9 All interconnecting wiring between the VFD and the chiller shall be factory-installed. Customer
electrical connection for compressor motor power shall be limited to main power leads to the single
point power connection located into electrical panel.
9 The VFD shall be air cooled type. Water cooled design or refrigerant cooled design are not
acceptable.
9 The VFD full load efficiency shall meet or exceed 97% at 100% VFD rated ampacity.
9 Base motor frequency shall permit motor to be utilized at nameplate voltage. Adjustable frequency
range, monitored by units microprocessor control, shall permit a stable unit capacity control down to
13% (9% with 3 compressor unit) without hot-gas bypass.
9 Starting current for the compressor shall not exceed nominal compressor load amps.
9 Unit power factor shall be not less than 0.95 on entire unit capacity range, from 100% down to 13%
(9% with 3 compressor unit).
Evaporator
9 The units shall be supplied with shell and tubes counter-flow heat exchanger with single refrigerant
pass. It will be refrigerant direct expansion type with refrigerant inside the tubes and water outside
(shell side). It will include carbon steel tube sheets, with straight copper tubes internally wound for
higher efficiencies, expanded on the tube plates.
9 The external shell shall be linked with an electrical heater to prevent freezing down to -28C ambient
temperature, commanded by a thermostat and shall be insulated with flexible, closed cell
polyurethane insulation material (10-mm thick).
9 The evaporator will have 2 circuits, one for each compressor and shall be single refrigerant pass.
9 The water connections shall be VICTAULIC type connections as standard to ensure quick
mechanical disconnection between the unit and the hydronic network.
9 Evaporator is manufactured in accordance to PED approval.
Condenser coil
9 The condenser coils are constructed with internally finned seamless copper tubes having a "W"
configuration and arranged in a staggered row pattern and mechanically expanded into lanced and
rippled aluminium fins with full fin collars for higher efficiencies. The space between the fins are
given by a collar that will increase the surface area in connection with the tubes, protecting them
from ambient corrosion.
9 The coils will have an integral subcooler circuit that provides sufficient subcooling to effectively
eliminate the possibility of liquid flashing and increase the unit's efficiency of 5-7% without increasing
in power absorption.
9 The condenser coil shall be leak-tested and submitted to a pressure test with dry air.
KPMHP00511-09EN page 55/60

Condenser fans
9 The fans used in conjunction with the condenser coils, shall be helical type with aerofoil blades for
higher efficiencies and lower noise. Each fan shall be protected by a fan guard.
9 The air discharge shall be vertical and each fan must be coupled to the electrical motor, supplied as
standard to IP54 and capable to work to ambient temperatures of - 20C to + 55C.
9 They shall have individual overload protection via a disconnect switch.
Refrigerant circuit
9 The unit must have refrigerant circuits completely independent of each other with one compressor
and one variable electrical frequency driver per circuit (VFD).
9 Each circuit shall include as standard: electronic expansion device piloted by units microprocessor
control, compressor discharge shut-off valve, suction line shut-off valve, 4-way valve to reverse
refrigerant cycle into the unit, liquid line shut-off valve with charging connection, replaceable core
filter-drier, sight glass with moisture indicator and insulated suction line.
Condensation control
9 The units will be provided with an automatic control for condensing pressure which ensures the
working at low external temperatures down to +10 C, thanks the ON/OFF of the condenser fans, to
maintain condensing pressure. Fan speed control, to allow units operation with very low ambient
temperature (-18C), should be available as option.
9 Automatic compressor unloading when abnormal high condensing pressure is detected to prevent
the shutdown of the refrigerant circuit (shutdown of the unit) due to a high-pressure fault.
Low Noise unit options (on request)
9 The unit compressors shall be connected with units metal baseframe by rubber antivibration
supports to prevent the transmission of vibrations to all metal unit structure and so to control the unit
noise.
9 The discharge and suction lines shall be provided with mufflers to eliminate vibration and so to
reduce the noise unit emission.
9 The chiller shall be provided with an acoustically compressor enclosure. This enclosure shall be
realized with a light, corrosion resisting aluminium structure and metal panels. The compressors
sound-proof enclosure shall be internally fitted with flexible, multi layer, high density materials. The
middle layer is 3 mm, very high density and high efficiency noise reduction material. The enclosure
shall be carefully assembled to avoid decreasing of its noise reduction power.
9 The chiller shall be provided with very low speed condenser fans and with an improved condenser
section.
Control panel
9 Field power connection, control interlock terminals, and unit control system should be centrally
located in an electric panel (IP 54). Power and starting controls should be separate from safety and
operating controls in different compartments of the same panel.
9 Starting will be star/delta type.
9 Power and starting controls should include fuses and contactors for each compressor winding and
fan motors. Operating and safety controls should include energy saving control; emergency stop
switch; overload protection for compressor motor; high and low pressure cut-out switch (for each
refrigerant circuit); anti-freeze thermostat; cut-out switch for each compressor.
9 All of the information regarding the unit will be reported on a display and with the internal built-in
calendar and clock that will switch the unit ON/OFF during day time all year long.
9 The following features and functions shall be included:
- resetting chilled water temperature by controlling the return water temperature or by a remote
4-20 mA DC signal or by controlling the external ambient temperature;
- soft load function to prevent the system from operating at full load during the chilled fluid
pulldown period;
- password protection of critical parameters of control;

KPMHP00511-09EN page 56/60

- start-to-start and stop-to-star timers to provide minimum compressor off-time with maximum
motor protection;
- communication capability with a PC or remote monitoring;
- discharge pressure control through intelligent cycling of condenser fans;
- lead-lag selection by manual or automatically by circuit run hours;
- double set point for brine unit version;
- scheduling via internal time clock to allow programming of a yearly start-stop schedule
accommodating weekends and holidays.
Optional High Level Communications Interface
The controller as a minimum shall be capable of providing the data shown in the above list and document
entitled McQuaycomms, using the following options:
Option A
Option B
Option C
Option D

RS485 Serial card


RS232 Serial card
LonWorks interface to FTT10A Transceiver
Bacnet Compatible

KPMHP00511-09EN page 57/60

KPMHP00511-09EN page 58/60

KPMHP00511-09EN page 59/60

The present publication is drawn up by of information only and does not constitute an offer binding upon McQuay. McQuay has compiled the content of this
publication to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose
of its content, and the products and services presented therein. Specification are subject to change without prior notice. McQuay explicitly rejects any
liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or interpretation of this publication. All content is
copyrighted by McQuay.

McQuay partecipa al programma di


Certificazione Eurovent.
I prodotti interessati figurano nella Guida
Eurovent dei Prodotti Certificati.

McQuay is participating in the Eurovent


Certification Programme
Product are as listed in the Eurovent
Directory of Certified Products

McQuay Italia S.P.A.


Via Piani di Santa Maria, 72 00040 Ariccia (Roma) Italia Tel. (06) 937311 Fax (06) 9374014
www .mcquayeurope. com

KPMHP00511-09EN page 60/60