TECHNICAL COMPARISON BETWEEN M/S EMERSON NETWORK POWER (INDIA) PVT

ELECTRONICS PVT LTD .


SL NO.
I.

Parameter description

UPS Type /Capacity /Quantity:


a) Parallel Redundant UPS system (preferably with Criss-cross
facility) with current sharing in UPS, mains and battery mode.
b) Redundant By-pass line with 3-Phase to Single phase Isolation
transformer and SCVS etc.

II.
1
III
1
2
3

5
6
7
8
9
10
11
12
13
14

c) Static switches for transfer of load to stabilized by-pass supply.


d) Maintenance By pass switch.

e) Wall mounting type ACDB.


Design features of UPS systems:
Fully microprocessor controlled
Double conversion technology based
PWM inverter
IGBT based switching technology
Output Parameters
Output Voltage: 220 VAC
Output Voltage regulation: +/ (-) 1% or better
Output Voltage Waveform: Sinusoidal
THD at inverter output :
a. Less than 3% for 100% linear load or
better
b. Less than 5% for Non-linear load or
better
Output Voltage Waveform: Sinusoidal
Output Crest factor capability: 3:1
Output Power
Output Power factor
Output Frequency
Output Frequency Tolerance

Output Frequency sync. range


Frequency stability (Sync)
Frequency stability (Unsync)
Load Power factor range :
Overload rating
110% overload continuous

125% overload for 10 minutes


150% overload for 1 minute
200% overload for 30 secs
15

In-put harmonic filter

16
17

Transfer time
Inverter DC to AC efficiency: 90% on full load
Transient Recovery time after 100% to 0 to 100%
Load Change
DC parameters
Nominal DC Voltage
Permissible D.C voltage variation
DC bus over voltage trip
End discharge of DC bus
D.C Voltage regulation
Battery & Battery Charger
UPS Back-up time: 30 Minutes (minimum)
Battery Type: Sealed Maintenance Free
VRLA/NiCd
a) for 2X5 KVA UPS system (SMF battery)
Battery Make: Exide /Amara Raja
Temperature compensated (In-built) Battery charger
and support capability for the following types of
Battery.
a. SMF VRLA for 2X5 KVA UPS
Battery sizing calculations based on SMF (Main
offer)
No. of blocks of Batteries
AH capacity of Battery
Charging method
Charging time for charging of battery to its rated
capacity after complete discharge
(Rectifier/Charger)

18
IV
1
2
3
4
5
V
1
2
3
4

5
6
7
8
9

10
11

VI
VII

List of Battery accessories:


Battery protection:
a. Overload and short Circuit
b. Reverse polarity
c. Earth leakage protection
d. Others (Pl. specify)
List of status and system Parameters to be
displayed ( LED/LCD) on UPS system
Recommended spares required for 2 years
Operation and Maintenance

VIII

Input Power supplies to UPS systems

xiii

No. of feeders:
Incoming feeder I (Main) : For Rectifiers
Incoming feeder II (Alt.): For stabilized By pass
link
Input Voltage : 415V, 3 ph. 3/4 wire
Input Voltage Variation : +25% / (-) 30%
Input Frequency :50Hz
Input Frequency variation :+/ (-) 10%
Input Power at rated load :
Power walk in
Input Power Factor at rated load :
Galvanic isolation of UPS systems and stabilized By
pass lines from input power supply system
By pass parameters
Voltage: 220VAC
Overload: 10 times of rated current for 20 msec
Panels
Free standing Floor mounted type fabricated with
1.6mm/2 mm CRCA sheet steel
Enclosure protection: IP 31 as a minimum protection
Colour coded bus bars and shrouded live parts
Forced ventilation with 100% redundant fans
Specified UPS Power rating shall be the net output
after deduction of power required for fans.
Cabling from bottom:
Dimensions:
Recommended minimum clearances:
Technical catalogues for
a.UPS systems
b. Battery & Battery charger
c. Transformer
d. SCVS
e. Static transfer switch
f.Other accessories
Single line Configuration Diagram
a)for 2X5 KVA system
Bill of Materials

XIV.
1

a) for 2X5 KVA parallel redundant system


Reliability
MTBF, MTTR

IX
1
2
X
1
2
3
4

5
xi
xii

2
3
XV.
XVI.
1
2
3
4
5
6
XVII.
XVIII.

XIX

XX.

There shall not be any common equipment


/component shared by main and redundant UPS
Availability
Provision for interfacing with Purchasers PLC
Environmental parameters :
Operating Temperature Variations
Storage Temperature
Relative Humidity
Temperature Derating
Altitude derating
Acoustic noise level at 1m from UPS under rated
load shall be less than 55dBA
FAT and SAT procedure
List of installations for similar items
List of Drawings/Documents to be submitted by
the successful vendor for approval and /or
reference
a.Single line configuration diagram
b. Updated Bill of materials
c.Technical datasheets
d. Panel General view diagrams for PR and
Hot Stand-by UPS systems and ACDBs
e. Wiring diagram for individual UPS
system
f.Panel interconnection diagrams
g. List of components with specification
and `Make
h. QAP and Test certificates
Conformance to relevant IEC and IS standardfor
various components/features

ON NETWORK POWER (INDIA) PVT. LTD. & M/S HITACHI HI- REL POWER
ELECTRONICS PVT LTD .
M/s Emerson Network Power (INDIA )
PVT. LTD .
2X5 KVA Parallel redundant Mode( model
S400D)

M/s Hitachi Hi-Rel Power


Electronics Pvt.Ltd.

Confirmed .

complied with 01 No - SCVS

Confirmed .
Confirmed .
Confirmed .

complied with one no . 63 A DP MCB as


Incomer and 5 nos . 16 A , DP MCB in the
outgoing side -01 Nos .

complied

complied
complied
complied

complied

Sinusoidal
complied
5kVA/ 4 Kw ( actual 10 KA / 8 KW )
0.8
50 Hz
+/- 1 HZ
50 hz , with 3 % tol in pos / neg
+/- 0.1%
+/- 0.2%
> 0.5

Confirmed .

Confirmed .
Confirmed .
Confirmed .
Confirmed .
Confirmed .
Confirmed .
Confirmed .
Confirmed .
Confirmed .
Confirmed .
Confirmed .
Confirmed .
Confirmed .
Confirmed .
5KVA /4KW
0.8
50Hz
+/-0.1%
3 Hz
3 Hz
3Hz
0. to Unity
110 % for Minutes

complied

complied

Confirmed
Confirmed
200 % for 4ms for Fuse Blown

Not Provided
0 millisecond ( synchronized )
complied

Confirmed .
4ms in Sync mode and 20 Sec in Async
Mode
Confirmed .
98 % WITHHI 20 MS.

+/- 10%
356 V
260V-410V
410V
260V
+/- 1%
complied

348 VDC
+/-12v
10.5V
10.5-13.5
CONFIRMED
12 V SMF VRLA

complied ( SMF Battery )


Amara Raja - Quanta / Excide / Rocket

CONFIRMED
CONFIRMED
ROOM TEMP.

Optional

ROOM TEMP.
CONFIRMED

Enclosed
26 blocks for each UPS
12V/ 18 AH
CVCC

TWO
17
FCBC
8-10 HOURS

10-hour
1. Battery Racks
2. Cable connectors with lugs .
Our battery protections are as below : DC
Over voltage , DC Under voltage , Battery
under voltage , Battery deep discharge ,
Black start on low charge of batteries ,
battery current limit , battery over
temperature alarm

RACK, LINK

CONFIRMED
CONFIRMED
CONFIRMED
NA
CONFIRMED

complied
CONFIRMED

Enclosed

complied
complied
complied
complied
complied
5 Kva ( actual 10 Kva )
Progressive over 10 Secs .
1
complied; input isolation transformer is
included in the BOM

3
2
1
CONFIRMED
+/-15 %
CONFIRMED
+/-6 %
5KVA/4KW
15 SEC
0.8
CONFIRMED

Complied
complied

CONFIRMED
CONFIRMED

complied; only the ACDB shall be wall mounted type


IP 20 as standard
RAL 7021

RITTAL MAKE PS SERIES


CONFIRMED
CONFIRMED
CONFIRMED

complied
complied
HXDXW = 1150 mm x 650 mm x 450 mm
500 mm

CONFIRMED
AS PER DESIGN STADARD
UPS CATALOG ATTACHED

Enclosed catalogue for UPS System


Enclosed
AFTER LOI RECEIPT

BOM : 1. UPS - 5 KVA X2 2. Batt : 12V18AH


- 52 Nos 3. Input isolation Trf- 01 No. 4.
SCVS : 01 no. 5. Paralleling Kit - 01 no . 6.
Battery rack : 02 Nos . ( with cables & lugs )
0.2 million hours

CONFIMRED

complied
99.99 %

optional
0-45 Deg C .
0-70 Deg C.
95%
1.5 % per Deg C between 40-50 Deg C .
1% per 100m between 1000m-2000m

NA
50 DEGREE
95 % NC
NA
NA
65 dB

Enclosed .
Enclosed .

NOT APPLICABLE
SHALL BE PROVIDED LATER.
CONFIMRED

Enclosed .

complied

TC AFTER UPS PANEL TEST.


62040-3

DATA SHEET
SL NO. a) Parallel
Parameter
description
Redundant UPS
system
I.

(preferably with Criss-cross facility) with


UPS Type
/Capacity
/Quantity:
current
sharing
in UPS,
mains and battery
mode.

Vendor to fill

CONFIRMED

b) Redundant By-pass line with 3-Phase to


Single phase Isolation transformer and SCVS
etc.
CONFIRMED
c) Static switches for transfer of load to
stabilized by-pass supply.
CONFIRMED
d) Maintenance By pass switch.

CONFIRMED

e) Wall mounting type ACDB.

CONFIRMED

II.

Design features of UPS systems:


Fully microprocessor controlled

CONFIRMED

Double conversion technology based


PWM inverter

CONFIRMED

IGBT based switching technology

CONFIRMED

III
1

Output Parameters
Output Voltage: 220 VAC

CONFIRMED
CONFIRMED

Output Voltage regulation: +/ (-) 1% or


better
CONFIRMED

Output Voltage Waveform: Sinusoidal

CONFIRMED

CONFIRMED

THD at inverter output :


a. Less than 3% for 100% linear load or CONFIRMED
better
CONFIRMED

b. Less than 5% for Non-linear load or


better

Output Voltage Waveform: Sinusoidal

CONFIRMED

Output Crest factor capability: 3:1

CONFIRMED

Output Power

5KVA /4KW

8
9
10
11
12
13
14

15

Output Power factor


Output Frequency

0.8
50Hz

Output Frequency Tolerance

Output Frequency sync. range


Frequency stability (Sync)
Frequency stability (Unsync)
Load Power factor range :

+/-0.1%
3 Hz
3 Hz
3Hz
0. TO UNITY

Overload rating
110% overload continuous
125% overload for 10 minutes
150% overload for 1 minute

110 % FOR MINUTES


CONFIRMED
CONFIRMED

200% overload for 30 secs

200 % FOR 4MS FOR


FUSE BLOWN

In-put harmonic filter

CONFIRMED

17

4MS IN SYNC MODE AND


Transfer time
20 SEC IN ASYNC MODE
Inverter DC to AC efficiency: 90% on
full load
CONFIRMED
Transient Recovery time after 100% to
0 to 100%
98 % WITHHI 20 MS.

18
IV
1
2

Load Change
DC parameters
Nominal DC Voltage
Permissible D.C voltage variation

16

348 VDC
+/-12v

DC bus over voltage trip

End discharge of DC bus

10.5V

5
V

D.C Voltage regulation


Battery & Battery Charger

10.5-13.5

UPS Back-up time: 30 Minutes


(minimum)

CONFIRMED

Battery Type: Sealed Maintenance Free 12 V SMF VRLA

2
3

VRLA/NiCd
a) for 2X5 KVA UPS system (SMF
battery)
Battery Make: Exide /Amara Raja

CONFIRMED
CONFIRMED

Temperature compensated (In-built)


Battery charger

ROOM TEMP.

and support capability for the following


types of
Battery.
4

a. SMF VRLA for 2X5 KVA UPS

ROOM TEMP.

CONFIRMED

Battery sizing calculations based on


SMF (Main
offer)

6
7
8

No. of blocks of Batteries


AH capacity of Battery
Charging method

TWO
17
FCBC

Charging time for charging of battery


to its rated

8-10 HOURS

capacity after complete discharge


(Rectifier/Charger)
10

List of Battery accessories:

11

Battery protection:

VI

RACK, LINK

a. Overload and short Circuit

CONFIRMED

b. Reverse polarity

CONFIRMED

c. Earth leakage protection


d. Others (Pl. specify)

CONFIRMED
NA

List of status and system


Parameters to be

CONFIRMED

displayed ( LED/LCD) on UPS system


Recommended spares required for
2 years
CONFIRMED

VII

VIII

Operation and Maintenance


Input Power supplies to UPS
systems
No. of feeders:

Incoming feeder I (Main) : For Rectifiers

Incoming feeder II (Alt.): For stabilized


By pass
link

Input Voltage : 415V, 3 ph. 3/4 wire


Input Voltage Variation : +25% / (-)
30%

CONFIRMED

Input Frequency :50Hz

CONFIRMED

Input Frequency variation :+/ (-) 10%

+/-6 %

Input Power at rated load :

5KVA/4KW

+/-15 %

Power walk in

15 SEC

Input Power Factor at rated load :

0.8

Galvanic isolation of UPS systems and


stabilized By

CONFIRMED

pass lines from input power supply


system
IX

By pass parameters

Voltage: 220VAC

2
X

Overload: 10 times of rated current for


20 msec
CONFIRMED
Panels

Free standing Floor mounted type


fabricated with

CONFIRMED

RITTAL MAKE PS SERIES

1.6mm/2 mm CRCA sheet steel

Enclosure protection: IP 31 as a
minimum protection

CONFIRMED

Colour coded bus bars and shrouded


live parts
Forced ventilation with 100%
redundant fans

5
xi

Specified UPS Power rating shall be the


net output
after deduction of power required for
fans.
Cabling from bottom:
CONFIRMED
Dimensions:

Recommended minimum clearances:

CONFIRMED
CONFIRMED

AS PER DESIGN STADARD


UPS CATALOG

xii

Technical catalogues for


a.UPS systems
b. Battery & Battery charger
c. Transformer
d. SCVS
e. Static transfer switch
f.Other accessories
Single line Configuration Diagram
a)for 2X5 KVA system

ATTACHED

xiii

Bill of Materials

XIV.

a) for 2X5 KVA parallel redundant


system
Reliability

MTBF, MTTR

There shall not be any common


equipment
/component shared by main and
redundant UPS

Availability

AFTER LOI RECEIPT

CONFIMRED

99.99 %

XV.
XVI.

Provision for interfacing with


Purchasers PLC
Environmental parameters :

Operating Temperature Variations

NA

2
3
4
5

Storage Temperature
Relative Humidity
Temperature Derating
Altitude derating

50 DEGREE
95 % NC
NA
NA

Acoustic noise level at 1m from UPS


under rated

65 dB

load shall be less than 55dBA


XVII.

FAT and SAT procedure

NOT APPLICABLE

XVIII.

List of installations for similar


items

SHALL BE PROVIDED
LATER.

List of Drawings/Documents to be
submitted by

CONFIMRED

the successful vendor for approval


and /or
reference
a.Single line configuration diagram
b. Updated Bill of materials
c.Technical datasheets
d. Panel General view diagrams for PR
and
Hot Stand-by UPS systems and ACDBs
e. Wiring diagram for individual UPS

system
f.Panel interconnection diagrams
g. List of components with specification
and `Make
XIX

XX.

h. QAP and Test certificates

TC AFTER UPS PANEL


TEST.

Conformance to relevant IEC and


62040-3
IS standardfor various
components/features