LV bushing cantilever strength analysis
Overview
Problem description
LV bushing force diagram
Review of manufacturer specifications
Discussion / Next actions
Problem description
p
LV bushing
g force diagram
g
Specifications summary
Cantilever strength
Manufacturer A
Manufacturer B
80 ft-lb
Manufacturer C
Not available
Standards on LV Bushing
g Cantilever
IEC 6013760137 2008.
2008 Ins
Insulated
lated b
bushings
shings for alternating
voltages above 1 000 V
Cantilever Load requirements:
300 N (67.4 lb) for Ir 800 A
1 000 N ((224.8 lb)) for Ir >800 A
Force Applied
pp
for Cantilever Test
Cantile er Load = Torq
Cantilever
Torque
e Applied
Cantilever Load = Force * Distance
Since Load
Si
L d is
i fixed,
fi d the
th torque
t
applied varies with the length of
the LV bushing and its terminal
Distance
Force
Distance
in/ft
Load
lb
Torque
ft-lb
6 / 0.5
224.8
112.4
8 / 0.75
224.8
168.6
10 / 0.833
224.8
187.2
Standards on LV Bushing
g Cantilever
Most LV Bushing Manufacturers specify the cantilever
torque used on their certification testing
The following
g is a sample
p of the cantilever torque
q values that
are published for LV Bushings:
Stud diam.
(in)
Max. Current
(Amp)
Bush. Torque
ft-lb
5/8
830
250
13.34 / 1.11
1500
280 to 375
2200
320
17.1 / 1.42
Standards on LV Bushing
g Cantilever
Conclusions:
No current IEEE Std. Covers LV Bushing requirements
IEC 60137 Standard provides cantilever requirements for LV
Bushings
Most LV Bushing manufacturers provide cantilever torque test
values that would meet IEC 60137 requirements
q
for std.
dimensions of bushing-terminal assemblies
Concerns would raise on larger terminals that would cause torque
distances above 12
12 , where mechanical support may be required
Findings may suggest to review any reported issues, to determine
whether a LV bushing standardization is needed