Beruflich Dokumente
Kultur Dokumente
sure; Dual-window energy ratio; Mathematical Morphology; Generalized multi-resolution morphological gradient.
I. INTRODUCTION
utoreclosure schemes applied to EHV systems have been
an effective method to improve the stability and synchronism of power systems. However the present
auto-reclosure technique normally employs a prescribed reclosure time, that is, the breaker is re-closed after a fixed period
following a tripping operation. Main problems with the conventional reclosure scheme are: (a) the risk of a fault restrike,
due to insufficient arc deionization time, (b) the risk of a second shock to the system in the case of a permanent fault, (c)
possibility of greater power oscillations. These problems could
threaten the system stability and reliability and cause expensive
damage. Therefore, a fault identification method, which can
distinguish between a permanent fault and a transient fault and
can determine when the secondary arc being extinguished, is
very important for improving the performance of the reclosure
techniques.
SE1( nT ) =
n + N1 1
I 2 ( k T )T
(2)
k =n
SE 2( nT ) =
n + N1 + N 2 1
I 2 ( k T )T
(3)
k = n + N1
ER( nT ) = SE 2( nT ) SE1( nT )
(4)
n=1,2,N-N1-N2
Where T is the sampling time interval, and N1 and N2 are the
lengths of the time-windows of SE1 and SE2. The choice of the
time-window length follows the criterion as below: Firstly, it
can make sure that ER has the steady output when the power
systems operate during steady state. Secondly, the length of the
time window should be less than the time interval of any two
neighboring singular outputs, which correspond to the arc features, of the mode 1 current. By means of this design, the ER
can focus on the intensive changes of the HF signal accurately.
Consequently, the ER output during a transient fault can be
evaluated as the successive pulses. In contrast, the ER output
during a permanent fault will appear as a flat line approximately except at the time of fault occurrence and breaker
opening. At present we are not able to determine the optimal
length of the time window in theory. In virtue of the sufficient
simulation tests, above requirements can be satisfied when N1
and N2 are both set to 1/8 power-frequency cycle. The design
of the time windows of SE1 and SE2 is shown in Fig.1.
SE2
{
{
SE1
N1
N2
340km
F
35GVA
5GVA
X1=0.2783/km
R 1=0.027/km
C1 =0.0127 F/km
X0 =0.6494/km
R0 =0.1948/km
C 0= 0.009 F/km
t3
0.05
0.1
0.15
Time,s
(a)
0.2
0.25
t3
t2
t1
0
0.05
0.1
Digital Level,A
0.15
Time,s
(b)
10
0.2
0.05
0.1
t3
t2
t1
0.05
0.1
Time,s
(c)
0.15
0.2
0.05
0.1
Time,s
(d)
0.15
0.2
-200
t2
t1
0
0.05
0.1
Time,s
(a)
0.15
0.2
0.25
200
0
-200
t2
t1
0
0.05
0.1
10
Time,s
(b)
0.15
0.2
0.25
0.15
0.2
0.25
-10
t2
t1
0
0.05
0.1
10
Time,s
(c)
5
Threshold
t2
t1
0
0.05
0.1
Time,s
0.15
0.2
(d)
0.25
0.25
Time,s
(b)
0.15
0.2
0.25
Time,s
(c)
0.15
0.2
0.25
0.15
0.2
0.25
0.15
0.2
0.25
t2
0.05
0.1
Time,s
(d)
5
0
-5
-10
0.25
0.2
-1
t3 Threshold
t2
t1
10
5
0
x 10
t1
0.25
10
0.15
Current,A
0
-5
Energy Ratio ER
0.1
15
Current,A
0.05
-200
0
0.25
-10
Mode Current,A
-200
0
Time,s
(a)
Current,A
-200
Digital Level,A
0.1
200
200
Energy Ratio ER
0.05
Digital Level
Mode Current,A
t2
t1
-5000
200
0
-200
5000
Current,A
Energy Ratio ER
Current,A
200
Current,A
t1
t2
0.05
t1
0
0
t2
0.1
10
Time,s
(e)
0.05
Threshold
0.1
Time,s
(f)
0.15
0.2
0.25
is a recommendable choice.
g + ( x ) = ( 1 g + )( x ) ( 1 g + )( x )
(10)
g ( x ) = (1 g )( x ) (1 g )( x )
(11)
(f
g )( x ) = min{ f ( x + y ) g ( y )}
y
(6)
Where f(x) and g(x) denote a 1-D input signal and a SE (also a
signal) respectively and x D f , y Dg . (5) and (6) show
that these two operations, dilation and erosion, are the combinations of simple addition operations (both subtraction and
comparison can be regarded as addition operations). For a dilation or an erosion of f by a flat lines SE g, whose lengths are k
and m respectively, there would only be (m-1)(k-2m-2) addition
operations. All the operations in the proposed scheme in this
paper are based on these two operations, the computational
complexity, therefore, is quite low.
B. The theory and analysis of GMMG
g ( x ) = g + ( x ) + g ( x )
(12)
g = {g1 , g 2 ,..., g l1 , g l }
(9) will have an arc across the reduced air insulation. Therefore it
is not practical to differentiate between a permanent fault and a
+
where g is the SE used for extracting the ascending edges and transient fault by the presence or absence of an arc in the primary fault. However, the characteristic due to the secondary
g is for the descending edges of the transient arc still exists after the faulty phase is isolated. Therefore, the
criterion can be designed to monitor the mode current after
1
waves, l = 2 l1 , where indicates the level of MMG to be
fault clearance. It means that a transient fault exists if ER is
processed, l1 is the primary length of g at level 1. The under- equably intermittently larger than TL in 2~3 cycles. Therefore,
+
lined samples, g , in g and g , show their origins. Based the breaker should not be re-closed. The fault can be regards as
a permanent one if ER is below TL steadily for 2~3 cycles after
on the definition of MG in (7) and scalable flat SE in (8) and breaker opens. After the fault is identified as a transient one,
Digital Level
10
5
10
Digital Level
t1
-10
Energy Ratio ER
t2
0.05
0.1 Time,s
-5
0.05
0.1 Time,s
(a)
0.2
0.25
Digital Level
t1
0
t3 Threshold
t2
0.05
0.1
0.15
Time,s
(b)
0.2
0.25
0.05
Threshold
0.1
Digital Level
10
0
t1
0
0.05
0.1
Energy Ratio ER
Time,s
(a)
0.15
0.2
0.25
Threshold
t2
t1
0
0.05
0.1
Time,s
(b)
0.15
0.2
0.25
Fig.6 shows that the GMMG can clearly localize the arc resulting in singularity. In the mean time the higher harmonics
can be restrained effectively. ERs associated with the chopping
effect of the arc are greater than 5, and at other periods ER is
equal to 1 steadily approximately even accompanied by intensive noises.
Fig.7 illustrates the simulation results of a permanent fault,
of which the fault conditions are identical to those of above
transient fault. From Fig.7 it is presented that ER is below TL
steadily except at the moments of fault occurrence and breaker
opening. It demonstrates that the scheme is reliable to identify
the permanent fault. A variety of simulations tests in the condition of different fault types and locations, etc are carried out to
validate this method. Several typical scenarios are given in
Fig.8~ Fig.10. Fig.8 illustrates the analytical results of a
high-impedance permanent fault. Fig.9 illustrates the analytical
results of a transient fault occurred on the transmission line at a
distance of 2 km from substation M. Fig.10 illustrates the analytical results of a high-impedance transient fault.
Digital Level
5
0
-5
Energy Ratio ER
0.25
t1
0
t2
0.05
0.1
Time,s
(a)
0.15
0.2
0.15
0.2
0.25
Threshold
t2
t1
0
0
0.05
0.1
t1
Time,s
(b)
t2
0.05
0.1
10
Time,s
(a)
0.15
0.2
0.15
0.2
0.25
t1
0
0
Threshold
t2
0.05
0.1
Time,s
(b)
0.25
t2
10
Time,s
(b)
-1
-10
0.2
t2
t1
0
0
Energy Ratio ER
Energy Ratio ER
10
0.15
0.15
0.25
t3
t2
t1
0
0.2
-10
0.15
(a)
10
0.25
From Fig.8 to Fig. 10, the transient fault can always be identified from the permanent fault by means of the proposed criterion no matter how the fault location and fault resistance
change. In the event of the permanent fault, ER is always below TL during the period of fault existence no matter how the
fault conditions change. As for the transient fault, the change of
the fault location has minor impact on the criterion. In the event
of the high-impedance transient fault, the magnitude of HF
signal output of the mode current modulated by GMMG decreases compared with the general case. However, the change
of ER is minor, which demonstrates that this scheme is well
adaptive. As a consequence, the proposed adaptive
auto-reclosure scheme based on GMMG can identify arc signal
correctly and has higher reliability compared with the scheme
using conventional filter.
As for the scenario of the transmission line having shunt reactor and a neutral reactor, we set up a corresponding model as
shown in Fig.11. The undercompensation mode is adopted,
which leads to the parameters in Fig11. With this model, we
simulate a full process of the occurrence, isolation, and recovery of a transient fault which can be seen in Fig. 12.
According to the analysis in [14], the residual voltage of the
isolated phase consists of both the residual voltage coupled
with the sound phases and the free oscillation frequency component due to electromagnet induction capacitance and the
compensated reactors. Therefore, the compound residual voltage on the isolated phase will appear as a swing behavior. As
seen in Fig. 12, the swing frequency is about 10Hz. The above
characteristic concerning voltage can be reflected in the mode
current, which is shown in Fig. 13. However, in this condition,
the changes resulting from the secondary arc are far lower than
those due to the oscillation effect. As seen in Fig. 13 only the
changes corresponding to the phase change of oscillation can
be identified.
Therefore, the proposed criterion cannot be directly applied
to the transmission line with reactor compensation. This scenario should be investigated in more details.
35GVA
XL
XL
XL =1447
XN
5GVA
XN
XN =444
X 1=0.2783/km
R 1=0.027/km
C 1=0.0127 F/km
X0=0.2783/km
R0 =0.1948/km
C0 = 0.009 F/km
[7] Chen Z., Lin X. Bo Z. etc, "Adaptive optimal reclosure using wavelet
transform analysis on fault transients", in Proceedings of Sixth International
Conference on Advances in Power System Control, Operation and Management - Proceedings, , Hong Kong , 2003 , vol. 1, pp. 268-273
[8] Redfern, M.A. Terry, S.C.; Robinson, F.V.P. et. al. The application of distribution system current transformers for high frequency transient based protection, IEE Conference Publication, Eighth IEE International Conference on
Developments in Power System Protection, Vol.1, 2004, pp. 108-111
U/kV
250
0
[9] A.T. Johns, R.K. Aggarwal, Y.H. Song. Improved techniques for modelling
fault arcs on faulted EHV transmission systems, IEE Proc-Gener, Transm.
Distrib, Vol.141, No.2, 1994, pp. 282-289
-250
0.2
0.4
0.6
0.8
Time,s
Fig. 12 The faulty phase voltage when a transient fault occurring, being isolated and recovering on a transmission line with shunt reactor compensation
Energy Ratio ER
2000
1000
0.2
0.4
0.6
0.8
Time,s
[10] P. Sun, J. F. Zhang, D. J. Zhang, and Q. H. Wu, "Morphological identification of transformer magnetizing inrush current," Inst. Elect. Eng. Electron.
Lett., vol. 38, No. 9, 2002, pp. 437-438,.
[11] J. Serra, Image analysis and mathematical morphology, London: Academic, 1982.
[12] D. Wang and D. C. He, "Fast implementation of 1-D grayscale morphological filters," IEEE Trans. Circuits Syst. I, vol. 41, No. 9, pp. 634-636, 1994
[13] D. Zhang, Q. Li, J. Zhang, et al. Improving the accuracy of single-ended
transient fault locators using mathematical morphology, IEEE/CSEE International Conference on Power System Technology, Kunming, China, 2002 pp.
1456-1459.
[14] Li Bin, Li Yong-li, Sheng Kun, et al. The study on single-pole adaptive
reclosure of EHV transmission lines with the shunt reactor, Proceedings of
CSEE, Vol.24, No.5, 2004, pp. 52-56.
Fig. 13 The ER evaluated by GMMG of the mode current of the fault in Fig. 12
BIOGRAPHIES
V. CONCLUSION
The adaptive reclosure technique is of importance for improving the stability of power systems. The key point lies with
the identification of transient fault from permanent fault. A
criterion of DWTER based on the mode current is proposed in
this paper. The redundancy of setting of the criterion can be
improved compared with the criterion of single-window transient voltages energy. And the requirement on the transducer
can be lowered by means of this scheme. To effectively extract
the HF energy of the mode current, a novel concept of GMMG
is put forward. EMTP based simulation results show that the
GMMG based auto-reclosure scheme improves the discrimination reliability of the transient current based criterion.
REFERENCES
[1] Y Z Ge, F H Sui, Y Xiao, "Prediction Methods for Preventing Single-phase
Reclosing on Permanent Fault", IEEE Transactions on Power Delivery, Vol.4,
No.1, 1989, pp114-121.
[2] R K Aggarwal, A T Johns, Y H Song, etc., "Neural-network based adaptive
single-pole autoreclosure technique for EHV transmission systems", IEE
Proc-Gener. Transm. Distrib., Vol.141, No.2, 1994, pp243-250
[3] M B Djuric, V V Terzija, "A New Approach to the Arcing Faults Detection
for Fast Autoreclsoure in transmission Systems", IEEE Transaction on Power
Delivery, Vol.10, No.4, 1995, pp1793-1798.
[4] Z Q Bo, A T Johns, "Transient Based Protection - A New Concept in Power
System Protection", IPST'97, International Conference on Power System Transients, University of Washington, Seattle, Washington, USA, 1997,
pp1345-1352.
Xiangning Lin received a Master and a Ph.D degree from the Huazhong University of Science & Technology (HUST), Wuhan, China in 1996 and 1999
respectively in the Electrical Engineering. He is currently an associated professor in Huazhong University of Science and Technology. His research interests are modern signal processing and its applications in the power systems,
power system protective relaying and control.
Haifeng Liu received a Bachelor degree from the Hohai University, Nanjing,
China in 2003 in the Electrical Engineering. He is currently pursuing his Master degree in Huazhong University of Science and Technology. His research
interests are power system protective relaying and control.
Hanli Weng received a Bachelor degree from the Huazhong University of
Science & Technology (HUST), Wuhan, China in 2002 in the Electrical Engineering. She is currently pursuing his Ph. D degree in Huazhong University of
Science and Technology. Her research interests are power system protective
relaying and control.
Wenjun Lu received a Bachelor and a Master degree from the Hunan University, Changsha, China in 1993 and 1996 respectively in the Electrical Engineering. He is currently pursuing his Ph. Ddegree in Huazhong University of
Science and Technology. His research interests are power system protective
relaying and control.
Pei Liu received M.S. from HUST in China. She is presently a professor at the
department of Electrical Power Engineering in HUST. Her research interests
include digital protection relaying, power quality analysis and wavelet applications in power systems.
Zhiqian BO (M'92. SM'95) received BSc degree from the Northeastern University, China and PhD degree Thc Queen's University of Belfast, UK. From
1989 to 1997, he worked at the Power System Group at the University of Bath.
During this time he published numerous papers and contributed to significant
innovations in the field. Presently, he is with ARREVA T&D Protection &
Control Ltd. His main research interests are power system protection and control.