This manual describes detail installation guide for Furutec Busduct System. Kindly ensure that the
installation manual is thoroughly studied prior to installation. This manual should be kept for future
references.
Content
1. Application Data
2. Storage Precaution
2.1. Storage
2.2. Preparation Prior to Installation
3. Installation Procedure
3.1. Jointing Procedure
3.2. Horizontal Hanger
3.3. Vertical Hanger
3.4. Connection between Equipment
3.5. Earthing of Housing
3.6. Tap Off Unit
3.7. Tap Box
3.8. Installation of Outdoor Type Busduct
3.9. Expansion Joint
4. Inspection
5. Maintenance
Page 1
: IEC 60439-Part 2
Ingress of Protection
: IP 40, IP 42, IP 54
Type of Busduct
Accessories
: Elbow, Flange End, Tap Off Unit, Flange End Box etc.
Materials
System
: 3P5W
Rating
Insulation
Plating
Earth System
Plug-In Openings
Fire Barriers
: Fire Barrier (Rock Wool or Nomex) provided per floor slap (Optional)
Busduct Weight
Page 2
Page 3
Leaf Spring
Page 4
M8
90 110
M 10
180 230
M 12
320 400
M 16
800 - 1000
2. Ensure that the blue surface of the Belleville Washer towards the inner side (conductor side)
Page 5
Plug In Hole
5. Installation complete.
2. Open the cover of the Tap Box and insert the tap bar through the opening of the tap box and fix
the box to the top hole flange by fastening the screws.
3. Fix the box to the busduct housing using hanger clamps.
4. Connect the tap bars to the flexible links using the attached bolts.
5. Fix the top cover of the box.
6. Installation complete.
Page 6
4.0 Inspection
1. Ensure busduct alignment is straight before energizing it.
2. Ensure all joints are tightened to recommended torque before energizing.
3. Measure the insulation resistance of the busduct before energizing. Under dry atmosphere, the
value of resistance should be 100 M (500V Megger). However, the resistance value could not
be specified due to different length of the busduct route and environmental condition.
4. In case of reading value less than 10 M, thorough examination is required as there exist factor
which decrease the insulation and energizing is not recommended.
5. Check for any water ingress due to leaks from the building piping or other facilities.
6. Check for adverse temperature rise after energizing the busduct.
7. If there is abnormal temperature in the joint areas, de-energize the busduct and examine the
tightness of the joint and if appropriate torque is used.
5.0 Maintenance
1. Periodic inspection should be performed to detect any problems with the busduct system.
2. During inspection, check for loosen joint bolts, busduct temperature and moisture or water
dripping from leakages.
Page 7