Beruflich Dokumente
Kultur Dokumente
PROYECTO:
Fecha :
6/4/2015
Pagina:
de 7
A
REV
4-Jun-15
FECHA
273715415.xls
PARA APROBACION
DESCRIPCION
MFA
JUM
WM
EJECUT
REVIS
APROB
REVISION : A
Fecha:
Pagina:
PROYECTO:
AMPLIACIN Y MEJORAMIENTO DEL SISTEMA DE EMISORES Y TRATAMIENTO DE AGUAS RESIDUALES DE AREQUIPA METROPOLITANA, COMPONENTE 3 RELLENO DE SEGURIDAD - SOC
METODO DE WENNER
4 AR
=
1+
2A
2A
A 2 +( 2 B )2 ( 2 A )2 +( 2 B )2
LUGAR
DISTANCIA
A [m]
FACTOR
[INSTRUMENTO]
VALOR
LEIDO
DISTANCIA
B[m]
RESISTIVIDAD
[Ohm.m]
PROFUNDIDAD
d [m]
1
2
4
1
1
1
227
189
64.5
0.25
0.25
0.25
1568.4541
2438.4347
1632.0757
0.75
1.5
3
4.3
0.25
216.5104
16
13.73
0.25
1380.8796
12
2do Punto
469,429 mE
9'493,355 mS
1 : Resistividad max.
2438.4347 [ohms.m]
2 : Resistividad min.
216.5104 [ohms.m]
eq : Resistividad Equi.
6/4/2015
1er PUNTO
3000.0000
2500.0000
2000.0000
1500.0000
1000.0000
500.0000
0.0000
0
2
4
6
8 10
Profundidad [m]
12
14
1.5 [m]
502.9345 [ohms.m]
REVISION : A
Fecha:
Pagina:
PROYECTO:
AMPLIACIN Y MEJORAMIENTO DEL SISTEMA DE EMISORES Y TRATAMIENTO DE AGUAS RESIDUALES DE AREQUIPA METROPOLITANA, COMPONENTE 3 RELLENO DE SEGURIDAD - SOC
METODO DE WENNER
4 AR
2A
2A
1+
A 2+( 2 B )2 ( 2 A )2 +( 2 B )2
LUGAR
DISTANCIA
A [m]
FACTOR
[INSTRUMENTO]
VALOR
LEIDO
DISTANCIA
B[m]
RESISTIVIDAD
[Ohm.m]
PROFUNDIDAD
d [m]
1
2
4
1
1
1
227
189
64.5
0.25
0.25
0.25
1568.4541
2438.4347
1632.0757
0.75
1.5
3
4.3
0.25
216.5104
16
13.73
0.25
1380.8796
12
1er Punto
469,264 mE
9'493,455 mS
1 : Resistividad max.
2438.4347 [ohms.m]
2 : Resistividad min.
216.5104 [ohms.m]
eq : Resistividad equi.
R e s is t iv id a d [ O h m . m ]
6/4/2015
1er PUNTO
3000.0000
2500.0000
2000.0000
1500.0000
1000.0000
500.0000
0.0000
0
2
4
6
8
10
Profundidad [m]
12
14
1.5 [m]
502.9345 [ohms.m]
Fecha:
Pagina:
6/4/2015
PROYECTO:
AMPLIACIN Y MEJORAMIENTO DEL SISTEMA DE EMISORES Y TRATAMIENTO DE AGUAS RESIDUALES DE AREQUIPA METROPOLITANA, COMPONENTE 3 RELLENO DE SEGURIDAD - SOCIEDAD
17.36
Ancho [m] =
14.92
Lt [m]
At [m2]
If [A] =
s [ohms.m] =
e [ohms.m] =
t [seg] =
[ohms.m] =
0.6 :Profundidad de enterrado.
h [m]
=
CALCULO DE LONGITUD TERICA DE CONTRAPESO ENTERRADO
238.4711 Se requiere reticular el rea
LT [m] =
RTA [ohms] =
Divisiones =
N electrodos
Kp = 1.25
LT [m] =
CALCULO SECCION MINIMA DE CONTRAPESO - CALIBRE EN mm2
0. 9 KpI f t
LT =
116 +0 . 17 p e
a1 = a2 h
Log(
Tm - Ta
234 + Ta
33.t
LUGAR
Corriente F.
I [Amp]
Temp.
Tm [C]
Temp.
Ta [C]
Tiempo
t[seg]
Seccin Cond.
[CM]
Seccin Cond.
[mm2]
Seccin Conductor
Seleccionado
[mm2]
1000
5000
200
200
12
12
1
0.5
11569.1219
40903.0226
5.864
20.731
50
10000
200
12
0.3
63366.6901
32.117
El minimo calibre a considerar en las instalacionespor norma es 35 mm2, por la corrosin y perdidas.
* Los fabricantes de pararrayos requieren como mnimo 50mm2, calibre del conductor.
Rg=
R1 R2 R
m2
Rg [Ohms] =
20.7671
R1 + R2 2 Rm
4 Lr
2 k 1Lr
R2 =
ln
1+
2 n R Lr
b
At
R1 =
Rm=
( )
( nR 1 )
[( )
2 Lt
k 1Lt
ln
+
k2
Lt
a1
At
[ ( )
2 Lt
k 1Lt
ln
+
k 2 +1
Lt
Lr
At
nR
Seleccionamos
3
7
10
R1 [ohms] :
R2 [ohms] :
Rm [ohms] :
Lt [m] :
k1, k2:
0.069190 [m]
Lr [m] :
b [m] :
3 [m]
0.009555 [m]
nR
]
k1
k2
1.293
1.293
1.293
4.475
4.475
4.475
R1 [Ohms]
15.24194
15.24194
15.24194
R2 [Ohms]
56.86662
28.36351
22.38441
Rm [Ohms]
0.01649
0.01649
0.01649
Rg [Ohms]
12.02567
9.92174 OK
9.07558
3/4
Fecha:
Pagina:
6/4/2015
PROYECTO:
AMPLIACIN Y MEJORAMIENTO DEL SISTEMA DE EMISORES Y TRATAMIENTO DE AGUAS RESIDUALES DE AREQUIPA METROPOLITANA, COMPONENTE 3 RELLENO DE SEGURIDAD - SOCIEDAD
CONCLUSIONES Y RECOMENDACIONES
CONCLUSIONES
1.- La resistividad del terreno es alta en las reas de los equipos a proteger, razn por la cual se ha diseado el Sistema de Puesta a Tierra con Malla, con
los siguientes valores:
rea Administrativa:
eq : Resistividad min.
502.9345 [ohms.m]
2.- Los calculos de la malla de puesta a tierra para el Pararrayos de la Zona Administrativa, resultaron como sigue:
rea Administrativa:
-Cubrir un rea de 259,01m2, con una malla de PAT aproximadamente cuadrada, de dimensiones por lado
promedio 17,36m x 14,92m; todo con cable desnudo de cobre de 50 mm2, enterrado a 0,60m bajo el nivel
natural del terreno.
-De los clculos result que, con el permetro cubierto con un cable de 50mm2 enterrado a 0,60m bajo el
terreno natural; se consdiderar una instalacin de 7 varillas de cobre ubicadas en el rea a cubrir.
-Se reticular elrea de la malla en intervalos de 1,90m horizontal y 2,17m vertical; se han adicionado 7 varillas
de cobre en los vrtices del tramo de esta malla, resultando una longitud de malla 311,52m.
-La resistencia total de la malla result 9,92 Ohms.