Page 1
Section 1 - Forward
This document provides technical information on wiring the Bristol Babcock line of
TeleFlow series products to an Invensys Auto-Adjust Turbo-Meter.
TeleFlow series (3530) units listed in Table 1-1 can be interconnected to an Invensys AutoAdjust Turbo-Meter. Interface requirements dictate the 3530 be equipped with at least two
Pulse (Counter) Inputs. The TeleFlow Plus (Model 3530-20B) is equipped with a TeleFlow
CPU Board and will require the use of a BBI Low Power I/O Expansion Board since the
CPU Board has only one Pulse Input. Units equipped with the TeleRTU CPU Board dont
require an additional Low Power I/O Expansion Board (unless an additional Pulse Input is
dictated) since the TeleRTU CPU Board is equipped with two Pulse Inputs.
Table 1-1 3530-XXX Organizational Overview & I/O Requirements
Model Number
Product Name
3530-15B - TeleRTU
3530-20B - TeleFlow Plus
3530-25B - TeleRTU Plus
3530-35B - TeleRTU Module
3539-45B - TeleRecorder
Expansion I/O
Required?
NO
YES
NO
NO
NO
Notes
Expansion Bd. Not Accommodated
Expansion Bd. Accommodated
Expansion Bd. Accommodated
Expansion Bd. Accommodated
Expansion Bd. Not Accommodated
This documents provides illustrations that show the recommended connections between
BBI Series 3530s and the Invensys Auto-Adjust Tubo-Meter in a Class I, Division 2
environment.
Section 2 - Definitions
The Auto-Adjust Turbo-Meter (AAT) meter referenced herein is manufactured by Invensys
Energy Metering, 805 Liberty Blvd. DuBois, PA 15801.
Control Amplifiers shown in the illustrations provided herein are manufactured by
Pepperl+Fuchs.
Abbreviations used within this document (text and illustrations) are provided below:
AAT
BTS
CPU
EXC
MR
SR
SS
Page 2
Auto-Adjust Turbo-Meter
Blade Tip Sensor
Central Processing Unit
Excitation (+12Vdc) from 3530-XXX CPU Bd.
AAT Main Rotor
AAT Sensor Rotor
Slot Sensor
TeleFlow/AATM
Section 3 - Wiring
Recommended wiring is shown for connection of a Bristol Babcock Series 3530-XXX unit to
an AAT. Figures 2 through 5 are provided for 3530s equipped with a TeleFlow CPU Board,
i.e., 3530-10B, -20B and 50B. These units require the use of a Low Power I/O Expansion
Board. The Low Power I/O Expansion Board provides a second counter input for the Sensor
Rotor. Figures 6 through 9 are provided for 3530s that utilize the TeleRTU CPU Board, i.e.,
3530-15B, -25B, -35B and -45B. Figure 1 shows and edge view of the BBI 3530-XXX circuit
boards utilized to interface to an AAT.
Page 3
Page 4
FIGURE
2
3
4
5
6
7
8
9
PAGE #
5
6
7
8
9
10
11
12
TeleFlow/AATM
Figure 2 - Slot Sensor AAT Meter to BBI 3530-20B (via 24 Vdc Control Amplifier)
TeleFlow/AATM
Page 5
Figure 3 - Slot Sensor AAT Meter to BBI 3530-20B (via 120 Vac Control Amplifier)
Page 6
TeleFlow/AATM
TeleFlow/AATM
Page 7
Page 8
TeleFlow/AATM
Figure 6 - Slot Sensor AAT Meter to BBI 3530-XXB (with TeleRTU CPU Bd.)
(via 24 Vdc Control Amplifier)
TeleFlow/AATM
Page 9
Figure 7 - Slot Sensor AAT Meter to BBI 3530-XXB (with TeleRTU CPU Bd.)
(via 120 Vac Control Amplifier)
Page 10
TeleFlow/AATM
Figure 8 - Blade Tip Sensor AAT Meter to BBI 3530-XXB (with TeleRTU CPU Bd.)
(via 24 Vdc Control Amplifier)
TeleFlow/AATM
Page 11
Figure 9 - Blade Tip Sensor AAT Meter to BBI 3530-XXB (with TeleRTU CPU Bd.)
(via 120 Vac Control Amplifier)
Page 12
TeleFlow/AATM
TeleFlow/AATM
Page 13