Sie sind auf Seite 1von 2

Firetuf FTP 120 - Fire Resistant Armoured Power Cable

Draka Firetuf FTP120 is a fire resistant armoured power cable solution for all three categories of fire performance required by BS8519, Category 1,2 and 3.
FTP120 is third party approved by LPCB for 120 min classification in BS8491. This is the test for fire resistance that includes direct flame, direct impact and
water jet at 850C. FTP120 holds third party BASEC certification to BS7846, the construction requirements for fire resistant armoured cables. LU approved
cable (LU Approval ref 406).

Construction
Manufacturing standard:

BS 7846

Conductors:

Stranded plain annealed copper wire (Class 2) to BS EN 60228

Insulation:

Mica-glass fire resistant tapes, covered by an extruded layer of XLPE

Binder:

Polyester tape, glass tapes where perfromance requires

Bedding:

Zero Halogen, Low Smoke (OHLS)

Armour:

Galvanised Steel Wire Armour

Sheath:

Zero Halogen, Low Smoke (OHLS)

Core colours:

Two core: Brown and Blue


Three core: Brown, Black and Grey
Four core: Brown, Black, Grey and Blue

Physical Characteristics
Voltage rating (Uo/U):

600/1000V

Operating temp:

-25C to +90C
(the cable should not be installed when either the ambient or cable
temperature is below 0C)

Min, bending radius:

8 x overall diameter of cable

Curent rating:

Refer to tables 4E4A & 4E4B in BS7671 or ERA 69-30 Part V

Note: In the event of a fire, the increase in impedance may require consideration to the installation of larger
conductor sizes, to accommodate motor starting loads and the performance of protective conductors.

Performance Characteristics
Circuit integrity:

BS 7846 F120
BS 8491 30, 60 and 120mins

Smoke emission:

BS EN 61034-2

Acid gas emmision:

BS EN 50267-2-1

Flame propagation:

BS EN 60332-1-2
BS EN 60332-3-24

2 Core FTPP2H
Nominal
area of
conductor

Armour
wire
diameter

mm
4*
6*
10*
16*
25*
35*
50
70
95
120
150
185
240
300
400

mm
1.25
1.25
1.25
1.25
1.25
1.6
1.6
1.6
2.0
2.0
2.0
2.5
2.5
2.5
2.5

Approx.
diameter
under
armour
mm
14.7
14.7
15.9
17.2
20.2
22.5
23.5
25.5
26.7
30.1
32.6
36.1
40.7
44.6
49.8

Approx.
overall
diameter

Approx.
cable
weight

mm
20.2
20.2
21.7
22.9
26.1
29.3
29.5
33.0
34.9
38.5
41.1
46.0
50.8
54.9
60.4

kg/km
765
760
875
1020
1325
1820
2580
2045
3465
4150
4845
6235
7635
9155
11140

Approx.
diameter
under
armour
mm
14.7
14.8
17.0
18.3
21.8
24.0
25.1
28.2
31.4
34.5
38.4
42.2
46.9
51.8
57.6

Approx.
overall
diameter

Approx.
cable
weight

mm
20.2
20.3
22.7
24.2
28.5
31.0
32.1
35.4
39.8
43.1
48.1
52.1
57.1
62.3
68.4

kg/km
785
795
1020
1230
1795
2170
2615
3360
4605
5505
7010
8295
10330
14425
15270

Maximum conductor
resistance
DC at 20 C
/km

AC at 90 C
/km

4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.047

5.878
3.927
2.333
1.466
0.926
0.6685
0.494
0.3412
0.2471
0.1964
0.1597
0.1284
0.0989
0.0801
0.0641

Nominal
area of
armour
mm
19
22
26
42
42
60
68
80
113
125
138
191
215
235
265

Maximum
armour
resistance
at 20C
/km
7.9
7
6
3.7
3.7
2.6
2.3
2
1.4
1.3
1.2
0.82
0.73
0.67
0.59

3 Core FTPP3H
Nominal
area of
conductor

Armour
wire
diameter

mm
4*
6*
10*
16*
25*
35*
50
70
95
120
150
185
240
300
400

mm
1.25
1.25
1.25
1.25
1.6
1.6
1.6
1.6
2.0
2.0
2.5
2.5
2.5
2.5
2.5

Maximum conductor
resistance
DC at 20 C
/km
4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.047

AC at 90 C
/km
5.878
3.927
2.333
1.466
0.926
0.6685
0.494
0.3412
0.2471
0.1964
0.1597
0.1284
0.0989
0.0801
0.0641

Nominal
area of
armour
mm
20
23
39
45
62
68
78
90
128
141
201
220
250
269
304

Maximum
armour
resistance
at 20C
/km
7.5
6.7
4
3.5
2.5
2.3
2
1.8
1.3
1.2
0.78
0.71
0.63
0.58
0.52

4 Core FTPP4H

DrakaFTP12010112013

Nominal
area of
conductor

Armour
wire
diameter

Approx.
Approx.
diameter
overall
under
diameter
armour
mm
mm
mm
mm
4*
1.25
15.0
20.5
6*
1.25
16.2
22.0
10*
1.25
18.7
24.4
16*
1.25
20.2
26.1
25*
1.6
24.0
30.8
35*
1.6
26.6
33.6
50
1.6
29.0
36.2
70
2.0
31.9
40.2
95
2.0
35.4
43.9
120
2.5
39.4
49.1
150
2.5
43.3
53.2
185
2.5
48.1
58.4
240
2.5
53.6
64.0
300
2.5
58.7
69.4
400
3.15
65.6
78.1
*Circular conductors, all others are shaped conductors

Prysmian Group,
Chickenhall Lane,
Eastleigh,
SO50 6YU

Approx.
cable
weight
kg/km
795
930
1200
1460
2150
2635
3275
4555
5770
7380
8720
10535
13115
15805
20420

Maximum conductor
resistance
DC at 20C
/km
4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.047

AC at 90C
/km
5.878
3.927
2.333
1.466
0.926
0.6685
0.494
0.3412
0.2471
0.1964
0.1597
0.1284
0.0989
0.0801
0.0641

Sales Telephone

01332 345431

www.drakauk.com

Nominal
area of
armour
mm
22
36
42
50
70
78
90
131
147
206
230
255
289
319
452

Maximum
armour
resistance
at 20C
/km
6.8
4.3
3.7
3.1
2.3
2
1.8
1.2
1.1
0.76
0.68
0.61
0.54
0.49
0.35

Das könnte Ihnen auch gefallen