Table of contents
Solenoid valves for gas VAS . . . . . . . . . . . . . . . . .1
Table of contents . . . . . . . . . . . . . . . . . . . . . . . . . 2
Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Application examples . . . . . . . . . . . . . . . . . . . . . . . .4
Technical data. . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Maintenance cycles . . . . . . . . . . . . . . . . . . . . . . 25
Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Certication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
VAS..N, quick opening . . . . . . . . . . . . . . . . . . . . . . 9
VAS..L, slow opening . . . . . . . . . . . . . . . . . . . . . . 10
VAS..S, position indicator and visual indicator . . . . 11
VAS connection diagram . . . . . . . . . . . . . . . . . . . .12
Replacement possibility for solenoid valves
for gas with threaded connection . . . . . . . . . . 13
VG is to be replaced by VAS . . . . . . . . . . . . . . . . 13
Replacement possibility for MODULINE
solenoid valves for gas . . . . . . . . . . . . . . . . . . . 15
VS is to be replaced by VAS. . . . . . . . . . . . . . . . . .15
Flow rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
kv value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Example. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Project planning information . . . . . . . . . . . . . . .21
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Pressure switch for gas DG..C . . . . . . . . . . . . . . . .22
Bypass valve VAS 1 . . . . . . . . . . . . . . . . . . . . . . . .22
VAS Edition 9.04
= To be continued
VAS../N
Application
VAS../L
Solenoid valves for gas VAS for safeguarding and controlling the air and gas supply to gas burners and gas
appliances. For use in gas control and safety systems in
all sectors of the iron, steel, glass and ceramics industries, also in commercial heat generation, such as the
packaging, paper and foodstuffs industries.
VAS..S
VAS../N + DG..C
Application
Application examples
Solenoid valve for gas
VAS..N, quick opening
VAS..N
VAS..N VAS..L
Application
Application examples
DG..C
DG..C
VAS..N
DG..C
VAS..N
Application
Application examples
VAS..N
VAS 1
VAS..N
Gas solenoid valve with pilot gas valve and pressure switch
VAS..N, quick opening,
VAS 1 as pilot gas valve,
pressure switch DG..C
VAS 1 DG..C
Application
Application examples
VAS..N
VAS 1
Certication
Function
Function
VAS..L, slow opening
pa
pS
pa
fully damped t
Start gas
t
10
Function
VAS..S, position indicator and visual indicator
These devices are tted with a microswitch to supply
open and closed signals.
Opening: When the valve is opened the position indicator
is operated rst. This in turn activates the visual position
indicator. The open signal is marked in blue. Only then
does the double valve seat open to release the volume
of gas (overtravel principle).
Closing: The voltage supply is disconnected from the
solenoid and the closing spring presses the double
valve disc on to the valve seat. The position indicator is
then actuated and the visual position indicator jumps
to shut.
The actuator cannot be rotated on a gas solenoid valve
with a position indicator and a visual position indicator.
1 COM
3 NC
2 NO
11
Function
VAS connection diagram
L1 (+)
N ()
12
Replacement possibility for solenoid valves for gas with threaded connection
VG is to be replaced by VAS
VG
10/15
15
15/12
20
25
25/15
40/32
40
40/33
50
50/39
50/65
65
65/49
R
02
03
10
18
Size 1
DN 20
Size 1
DN 25
Size 2
DN 40
Size 2
DN 40
Size 3
DN 50
Size 3
DN 50
Size 3
DN 65
Rp internal thread
Max. inlet pressure pe max.:
500 mbar
500 mbar
VAS
110
115
120
125
240
240
350
350
365
13
Replacement possibility for solenoid valves for gas with threaded connection
Cont.
N
L
K
Q
T
3
6
1
3
4
6
D
Quick opening
Slow opening
Mains voltage:
24 V DC
120 V AC
220/240 V AC
Electrical connection via terminals
Electrical connection via socket
Screw plug at the inlet
Screw plug at the inlet and outlet
Pressure test point at the inlet
Pressure test point at the inlet and outlet
Flow adjustment
Position indicator
M
Suitable for biologically produced methane
V
Viton valve disc seal
VG 25R02NT31DM
Example
Quick opening
Slow opening
Mains voltage:
/N
/L
K
Q
W
24 V DC
120 V AC
230 V AC
Electrical connection via terminals
Electrical connection via socket
Screw plug at the inlet and outlet
Flow adjustment
Example
VAS 125R/NW
standard, available
* Pressure test points may be attached at the left
and/or right-hand side.
14
VS
1
1
1
1
2
38
115
125
230
240
350
ML
02
N
L
D
VAS
110
115
120
125
225
240
340
350
R
/N
/L
15
Mains voltage: 24 V DC
120 V AC
220/240 V AC
Electrical connection via terminals
Electrical connection via socket
Pressure test point at the inlet
Position indicator
M
Suitable for biologically produced methane
V
Viton valve disc seal
VS 240ML02LT3
Example
with Rp 1 connection anges
Mains voltage: 24 V DC
K
120 V AC
Q
230 V AC
W
Electrical connection via terminals
Example
VAS 240R/LW
with test points
standard, available
* Pressure test points may be attached at the left and/or
right-hand side.
16
VA
50
65
S3
VA
,V
40
VA
S2
VA 25
AS
S2
25
32
0
VA
S3
40
15
VA
S1
VA 20
S1
25
60
VA
S1
80
S1
10
100
VA
p [mbar]
S3
50
Flow rate
40
30
S2
= Natural gas
= LPG
= Air
VA
20
10
8
6
5
4
3
1 1
2
3
7 8
6
4
5
10
5
6
6
7 8
20
7 8
10
30
10
40
20
20
30
50 60
80 100
30
50 60
40
40
50 60
200
300
80 100
80 100
200
200
300
300
400
400 500
17
Flow rate
kv value
kv =
V(n)
514
n T
p pa
p pa
n T
V(n) = 514 kv
p =
V(n)
kv
p
pa
n
T
V(n)
514 kv
n T
pa
Type
kV
m3/h
VAS 110
VAS 115
VAS 120
VAS 125
VAS 225
VAS 232
VAS 240
VAS 250
VAS 340
VAS 350
VAS 365
5.5
6.9
10.6
12.4
22
27
30
30
40
47
51
Example
We want to nd the size and nominal ange width for a
gas solenoid valve VAS.
We have the maximum ow rate V(n) max, the inlet pressure pe and the natural gas temperature T.
V(n) max = 60 m3/h
pe = 70 mbar = 0,07 bar
pe absolute = 0,07 bar + 1 bar = 1,07 bar
pmax = 0,01 bar (desired)
pa absolute = pe absolute pmax
pa absolute = 1,07 bar 0,01 bar = 1,06 bar
T = 27 C
Tabsolute = 27 + 273 K = 300 K
kv =
60
514
0,83 300
0,01 1,06
= 17,9
18
Selection
-0 10 15 20 25 32 40 50 65 / /0 /10 /15 /20 /25 /32 /40 /50 /65 R
VAS 1
VAS 2
VAS 3
Inlet ange nominal size
= no inlet ange
-0 = dummy ange
Outlet ange nominal size
= no outlet ange
/0 = dummy ange
Specication may be omitted if outlet = inlet
Rp internal thread = R
Quick opening, quick closing = /N
Slow opening, quick closing = /L
Mains voltage: 24 V DC
=K
120 V AC; 50/60 Hz = Q
230 V AC; 50/60 Hz = W
Position indicator and visual indicator: attached at the right-hand side
= SR*
with gold contacts, attached at the right-hand side = GR*
attached at the left-hand side
= SL*
with gold contacts, attached at the left-hand side = GL*
/N
/L K Q W
SR
GR
SL
GL
19
Selection
VAS 1
VAS 2
VAS 3
Electrical connection:
M20 cable gland
Plug with socket
Plug without socket
Attached to the left side of the connection box:
Not tted
Plug for valve
Plug for position indicator
Attached to the right side of the connection box:
Not tted
Plug for valve
Plug for position indicator
Accessories attached at the right-hand side:
2 screw plugs
2 test points pe and pa
Pressure switch for gas DG..C (see table) at the inlet
Pressure switch for gas DG..C (see table) at the outlet
Bypass valve VAS 1*
Accessories attached at the left-hand side:
2 screw plugs
2 test points pe and pa
Pressure switch for gas DG..C (see table) at the inlet
Pressure switch for gas DG..C (see table) at the outlet
Bypass valve VAS 1*
* Position indicator and bypass valve cannot be installed together on one side.
= standard
= available
Order example
VAS 232R/NW
Electrical connection via M20 cable gland, not tted,
with 2 screw plugs attached at the right-hand side and
2 test points attached at the left-hand side
20
Selection
Pressure switch for gas DG..C
Type
Adjusting range [mbar]
DG 17/VC
2 17
DG 40/VC
5 40
DG 110/VC
30 110
DG 300/VC
100 300
21
pa
pe
Installation
> 20
mm
VAS
GFK
> +80 C
Ensure that there is sufcient installation space around the ange screws
and the actuator.
22
Accessories
Scope of delivery:
1 x pressure switch for gas,
2 x retaining screws,
2 x sealing rings.
pe
pa
23
Auswahl
Bypass valve VAS 1
2
3
4
5
24
Technical data
Power consumption:
Type
24 V DC
[W]
VAS 1
29
VAS 2
46
VAS 3
53
120 V AC
[W]
30
54
55
230 V AC
[W]
30
53
63
Enclosure: IP 65.
Duty cycle: 100%.
Power factor of the solenoid coil:
cos = 1.
Valve housing: Aluminium,
Valve seal: NBR.
Connection anges with internal thread: Rp to ISO 7-1.
Position indicator:
Contact rating: 125 250 V, 50/60 Hz, max. 2 A (resistive load).
Switching frequency:
VAS..N: Arbitrary.
VAS..L: There must be a period of 20 seconds between
switching off and on again so that the damping is fully
effective.
Short circuit-proof: with quick-acting fuse up to 6.3 A.
For 24 V DC order a position indicator with gold-plated contacts.
Contact rating at 24 V DC:
max. 40 mA.
25
Technical data
E
E
E
H5
H3
H1
H4
H2
F
F
F
F
VAS..N
Type
Connection
VAS 110
VAS 115
VAS 120
VAS 125
VAS 225
VAS 232
VAS 240
VAS 250
VAS 340
VAS 350
VAS 365
Rp
3/8
1/2
3/4
1
1
11/4
11/2
2
11/2
2
21/2
DN
10
15
20
25
25
32
40
50
40
50
65
E
mm
75
75
75
75
88
88
88
88
88
88
88
F
mm
15
15
23
23
29
29
29
29
36
36
36
H1
mm
140
140
140
140
164
164
164
164
174
174
174
H2
mm
32
32
32
32
47
47
47
47
59
59
59
H3
mm
204
204
204
204
228
228
228
228
238
238
238
H4
mm
154
154
154
154
183
183
183
183
193
193
193
H5
mm
217
217
217
217
245
245
245
245
256
256
256
.
V
p = 1 mbar
Air
m3/h
4.4
5.5
8.5
10.6
17,5
21,5
23,5
24,6
33
41
43
F
F
VAS..N..S
Dimensions
L
mm
75
75
91
91
127
127
127
127
155
155
155
H2
F
F
VAS..L
Dimensions
H2
VAS..L..S
Weight
kv
m3/h
5.5
6.9
10.6
12.4
22
27
30
30
40
47
51
kg
1.4
1.4
1.5
1.4
3.8
3.7
3.8
3.6
5.1
4.9
4.7
21,5
79
48
H2
36
DG..C
26
Maintenance cycles
27
Contact
G. Kromschrder AG
Strotheweg 1
D-49504 Lotte (Bren)
Tel.: +49 (0)5 41 / 12 14 - 0
Fax: +49 (0)5 41 / 12 14 - 370
info@kromschroeder.com
The current addresses of our international agents are available on the Internet:
www.kromschroeder.com information contacts