Fieldbus Solutions with PCS 7

Siemens AG 2014. All Rights Reserved.

Fieldbus Solutions with PCS 7

PROFIBUS DP
Active Field Distributor
PROFIBUS PA
FOUNDATION Fieldbus
PROFINET

Siemens AG 2014. All Rights Reserved.

Fieldbus Solutions with PCS 7


PROFIBUS DP
System bus and open communication system

Siemens AG 2014. All Rights Reserved.

Fieldbus solutions with SIMATIC PCS 7


PROFIBUS supports:
HART communication
Fail-safe technology (PROFIsafe)

Drive integration (PROFIdrive)


Device profiles
And much more

PROFIBUS is the No. 1 field bus system in the world


Page 4

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

Fieldbus solutions with SIMATIC PCS 7


Untertitel
Text erste Ebene
Text zweite Ebene

Page 5

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

Fieldbus solutions with SIMATIC PCS 7


PROFIBUS DP

PROFIBUS DP

Active Field
Distributor

System bus of PCS 7 and open communication system

PROFIBUS PA
FOUNDATION
Fieldbus
PROFINET

Link between PCS 7 and PROFIBUS PA and FOUNDATION Fieldbus

Connects field devices, process instruments, drives, pumps, remote I/O and analyzers
PROFIsafe integrates safety functionality
Supports HART protocol
Installed base of almost 43 million nodes

Used for more than 10 years already

Page 6

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

Technical Overview
S7-400
> 100km

PROFIBUS DP

PROFIBUS PA
FOUNDATION
Fieldbus

OLM
RS485

PROFIBUS DP

Active Field
Distributor

Fiber optic

RS485

Max. 125 DP slaves per single PROFIBUS DP master system

Electrical networks can be extended with repeaters (segments)


max. 31 DP slaves per segment

(Diagnose)
Repeater

OLMs (Optical Link Module) for long distances, also provide


greater EMC stability

RS485iS coupler for PROFIBUS DP in hazardous areas

Copper with RS485 and fiber optic use the same communication
protocol

Max. 1,000 m

PROFINET

Coupler RS485iS

PA/FF Link

PA / FF H1

Page 7

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

Physical Properties
PROFIBUS DP

PROFIBUS DP

Active Field
Distributor
PROFIBUS PA

PhysicalLayer

FOUNDATION
Fieldbus
PROFINET

Application

max. segment length


@ Baud rate
1200 m @ <93,75 kBit/s

PROFIBUS

RS 485

DP

RS 485iS

Remote IO

1000 m @ 187,5 kBit/s

Intelligent drives

400 m @ 500 kBit/s

Intelligent field devices

200 m @ 1,5 kBit/s

100 m @ 12 MBit/s

Remote IO EX

200m @ 1.5 Mbps

Fast Transmission
Fiber Optic

Wide distance

> 10,000m @ 12 Mbps

EMC stability

Page 8

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

PROFIBUS DP development steps


PROFIBUS DP

Functionality

Active Field
Distributor
PROFIBUS PA

DP-V2
Extensions:
Peer slave communication (Publisher/Subscriber)
Isochronous mode (equidistance)
Time-of-day management and time stamping
Upload and download

FOUNDATION
Fieldbus
PROFINET

DP-V1
Extensions:
Acyclic data exchange
Alarms
DP-V0
Cyclic data exchange
Diagnostics

Page 9

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

Central access to all connected devices


PROFIBUS DP
Active Field
Distributor
PROFIBUS PA
FOUNDATION
Fieldbus

PROFINET

OS

ES

PROFIBUS DP

PROFIBUS PA

Page 10

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

Fieldbus Solutions with PCS 7

PROFIBUS DP
Active Field Distributor
PROFIBUS PA
FOUNDATION Fieldbus
PROFINET

Siemens AG 2014. All Rights Reserved.

Fieldbus Solutions with PCS 7


AFD
Active Field Distributor

Siemens AG 2014. All Rights Reserved.

Active field distributors


Increasing availability

Page 13

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

Automatic bus termination enables


unique online changeability

DP Link / FF Link

Add new devices


Enhance line
Enhance ring

Bus termination
Automatic bus termination

AFD

PROFIBUS PA / FOUNDATION Fieldbus

AFD

AFD

AFD

AFD

There is no need to reserve spare ports of the AFDs !

Page 14

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

Architectures with Active Field Distributor


Line architecture
Automatic bus termination by the last AFD
Line architecture with redundant couplers

AFS connects a bus line segment to two feeding


field device coupler FDC 157
Ring architecture with bus coupler and media
redundancy
Advantages
Automatic bus termination
Ease and safe installation
Reduce unplanned plant downtimes
Extendable and repairable during operation
Page 15

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

Active Field Distributor for PROFIBUS PA & FF-H1


New Mechanical Design

PROFIBUS PA / FF-H1

AFD4 (01/2013)

Bigger connectors (M12 M16)

All connectors relocated to bottom side

Screw terminal instead of spring terminal

Revised version of 4 channel field distributor with automatic


bus termination

8 channel version for most competitive channel price

6 channel field barrier for intrinsically safe applications

(6ES71570AG810XA0)

AFD8 (01/2013)
(6ES71570AG820XA0)

AFDiS
(6ES71570AG830XA0)

Page 16

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

Active Field Distributor


Comparison
Current version
PROFIBUS DP

Feature

Active Field
Distributor

AFS

Spurs

AFD4

AFD8

01 / 2013

01/2013

60mA

60mA

60mA

40mA / 60mA

AFD

Grounding bar

FOUNDATION
Fieldbus

Automatic bus termination


Coupler redundancy

PROFINET

AFS
(redesign)

Direct grounding

PROFIBUS PA

New product line

Ring redundancy
Short-circuit-proof spurs

Electronic chatter suppression


Status LEDs

Trunk cover with auto switch-off


Degree of protection
Operating temperature range
Approved for hazardous area
(Device / Spurs)

Integrated repeater

Page 17

2014-08-13

Thomas Bartsch

AFDiS

IP65

IP65

IP66

IP66

IP66

IP66

- 25 70

- 25 70

- 40 70

- 40 70

- 40 70

- 40 70

zone 2 / Ex e

zone 2 / Ex e

zone 2 / Ex ic

zone 2 / Ex ic

zone 1 / Ex ia

Siemens AG 2014. All Rights Reserved.


Industry Sector

SIMATIC Fieldbus Calculator


PROFIBUS DP

Planning of Fieldbus Segments

Active Field
Distributor

PROFIBUS PA

PROFIBUS PA
FOUNDATION
Fieldbus

FOUNDATION Fieldbus H1
http://support.automation.siemens.com/WW/view/en/53842953

PROFINET

Page 18

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

Fieldbus Solutions with PCS 7

PROFIBUS DP
Active Field Distributor
PROFIBUS PA
FOUNDATION Fieldbus
PROFINET

Siemens AG 2014. All Rights Reserved.

Fieldbus Solutions with PCS 7


PROFIBUS PA

Siemens AG 2014. All Rights Reserved.

PROFIBUS PA
Overview
PROFIBUS DP

PROFIBUS DP

123 devices
64
devices
PROFIBUS PA (Ex)

Active Field
Distributor
PROFIBUS PA

9 devices

Max. 7872 Devices

FOUNDATION
Fieldbus

PROFIBUS PA

31 devices

PROFINET

DP Interface module IM153-2 (12Mbps to 31.25 kbps)


Slave on PROFIBUS DP (one address), Master on PROFIBUS PA
Can be used redundant (H-System)
Max.. 244 bytes of I/O data (1 AI Value = 5 Byte)
Up to 64 PA devices
DP/PA coupler for PROFIBUS PA segment

DP/PA coupler
Interface module
IM153-2

Integrated Power supply - (Ex Option: Class 1, Div. 1, ZONE 0)


Up to 31 (9 Ex) PA devices
Max 5 couplers per link
Total number of devices on one PROFIBUS Master system
Up to 123 DP Slaves
Page 21

DP/PA Link is one DPThomas


Slave ->Bartsch
123 x 64 = max. 7872 PA devices
2014-08-13

DP/PA Link

Siemens AG 2014. All Rights Reserved.


Industry Sector

PROFIBUS PA features
PROFIBUS DP
Active Field
Distributor
PROFIBUS PA
FOUNDATION
Fieldbus

Cost and space savings


Less instruments using multivariable devices
Less wiring
Less I/O cards

Less controller logic

PROFINET

420mA

PROFIBUS PA

PROFIBUS PA
420mA
Digital

Page 22

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

PROFIBUS PA features
PROFIBUS DP
Active Field
Distributor
PROFIBUS PA
FOUNDATION
Fieldbus

Free choice of devices due to open standard

Interchangeability
Devices can be operated in device manufacturer independent
mode according PA Profiles e.g.
counting

PROFINET

pressure
flow
level

Interoperability
Universal device description independent from DCS or device
Download from
manufacturer
parameterize
manufacturer
GSD
EDD

Page 23

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

PROFIBUS PA features
PROFIBUS DP
Active Field
Distributor
PROFIBUS PA
FOUNDATION
Fieldbus
PROFINET

Higher Accuracy
Less conversions

32 bit resolution, digital transmission


No application specific measuring ranges
Conventional 420mA
technology

0...50 bar

0...10 bar
A

420mA

8.9
0...10 bar

PROFIBUS PA
0...50 bar

8.928
A

PAInterface

8.928
PROFIBUS PA

Page 24

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

PROFIBUS PA features
PROFIBUS DP

Central configuration, parameterization and diagnostics

Active Field
Distributor
PROFIBUS PA
FOUNDATION
Fieldbus

PROFINET

OS

ES

PROFIBUS DP

PROFIBUS PA

Page 25

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

Seamless integration into PCS 7 asset management

PROFIBUS DP
Active Field
Distributor
PROFIBUS PA
FOUNDATION
Fieldbus
PROFINET

Device status OK
IH alarm
IH warning
IH requirement

Asset
Management
Replacement value

Simulation

Detailed diagnostics
via device manager

Out of order
passivated
Config. changed
Status unknown
Operator reaction

Page 26

2014-08-13

Thomas Bartsch

Available views:
I&M
Alarm
Diagnostic
Parameters
Change Report
Maintenance
Siemens AG 2014. All Rights Reserved.
Industry Sector

PROFIBUS PA features
PROFIBUS DP
Active Field
Distributor
PROFIBUS PA

High performance for fast control loops


SIMATIC PDM

Engineering
Station

ES

Simple calculation formula for PROFIBUS PA


cycle time = app. 10 ms x number of devices
Industrial Ethernet
+ 1.3 ms (for each additional cyclic value)
+ 10 to 20ms (for acyclic class-2 master services)

FOUNDATION
Fieldbus
PROFINET

S7 41x

PROFIBUS DP up to 12 MBit/s
0,5ms

0,5ms

2 msec

0,5ms

0,5ms

DP up-link

PA
Coupler

cyclic

Acyclic
20ms

DP/PA Link

acyclic

PROFIBUS PA 31,25 kBit/s

80 msec
10ms

15ms
10ms

Page 27

2014-08-13

Thomas Bartsch

10ms

15ms

Siemens AG 2014. All Rights Reserved.


Industry Sector

PROFIBUS PA features
PROFIBUS DP
Active Field
Distributor
PROFIBUS PA

Process safety support with PROFISafe

IEC 61508/11:

The whole communication path to the field device is failsafe now!

No fail-safe-I/Os required, less cabling

FOUNDATION
Fieldbus
PROFINET

S7 41x

S7 41x

F_PA_DI
F_PA_AI

ET200M
420 mA

PROFIsafe on PROFIBUS DP
Page 28

2014-08-13

Thomas Bartsch

DP/PA-Link

PROFIsafe on PROFIBUS DP and PA


Siemens AG 2014. All Rights Reserved.
Industry Sector

Conventional setup for high available and fail-safe applications


PROFIBUS DP
Active Field
Distributor

High available and fail-safe


measurement (e.g. 2 out of 3)

Todays architecture

PROFIBUS PA

S7 41x HF

FOUNDATION
Fieldbus

2oo3
PROFIBUS DP

PROFINET

F-Remote I/O

Safe communication up to the I/O card


Safety and high availability requires multiple I/O cards
Page 29

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

Cost saving architecture for high available and fail-safe applications


S7 41x HF

Active Field
Distributor
PROFIBUS PA
FOUNDATION
Fieldbus

PROFIBUS DP

PROFIBUS DP

Tomorrows architecture

DP/PA Link, redundant

PROFINET

2oo3

1oo2

Safe communication down to the field device


Safety and high availability on one segment
Page 30

2014-08-13
Allows

Thomas of
Bartsch
combination
standard and PROFISafe devices

Siemens AG 2014. All Rights Reserved.


Industry Sector

PROFIBUS PA enables
PROFIBUS DP
Active Field
Distributor
PROFIBUS PA
FOUNDATION
Fieldbus
PROFINET

Fast and easy installation because of bus-powering and automatic bus termination
Prevention of unexpected plant downtimes due to scalable redundancy concept
Early fault recognition and preventive maintenance due to enhanced diagnostics and asset management
support
Cost- and space saving configurations as a real alternative to conventional technologies (4 20mA,
HART, fail-safe etc.)
Complete hardware configuration change in run without production downtimes (including modifications on
trunk line)

PROFIBUS and PROFIBUS PA are state-of-the-art and fit for the future
Page 31

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

Fieldbus Solutions with PCS 7

PROFIBUS DP
Active Field Distributor
PROFIBUS PA
FOUNDATION Fieldbus
PROFINET

Siemens AG 2014. All Rights Reserved.

Fieldbus Solutions with PCS 7


FOUNDATION Fieldbus

Siemens AG 2014. All Rights Reserved.

FOUNDATION Fieldbus
Seamless system integration (such as PROFIBUS PA, HART, I/O)
via high speed system backbone
Central configuration & parameterization
Complete asset management support via
PCS 7 Maintenance Station / PDM

Control In The Field


Redundancy on all levels
Redundant controller
Redundant backbone
Redundant linking device / Link Master
FF-H1 coupler / ring redundancy

Page 34

2014-08-13

Thomas Bartsch

Engineering
Station

Maintenance /
OS Server

AS 41x HF

FF Link
Drives

FOUNDATION Fieldbus
PROFIBUS DP System backbone

H.I.S.T (Host Interoperability Test) certified


Host according FF-569
Device tag & address assignment
Configuration of Link Master devices
Block tag configuration
Standard & enhanced Blocks
Function block linkage configuration
Device description service

Multi Client

ET200M HF
ET200iSP

PA Link
PROFIBUS PA

Siemens AG 2014. All Rights Reserved.


Industry Sector

Linking device hardware platform


The FF Linking device is based on the same hardware
platform as the well proven SIMATIC PA Link
Link = IM153-2 + Field Device Coupler
PA Link
IM 153-2
DP Link

FF Link

Field Device Coupler


FDC 157

IM 153-2 FF
FF Link

Field Device Coupler


FDC 157

+
FF Stack

DP Slave
PA Master

Page 35

Manchester encoding
Bus powering

2014-08-13

Thomas Bartsch

Manchester encoding
DP Slave
FF Link Master Bus powering

Siemens AG 2014. All Rights Reserved.


Industry Sector

FF Link quantity structures

Property

Value / Comment

Links per DP master system

123 (typ. 30 to 40)

Link Master per link

1 LAS (1 backup link master in redundant configuration)

Segments per link

I/O channels per link

40AI, 40AO, 40DI, 40DO

I/O data per link

244 bytes input / 244 bytes output (AI,AO = 5 bytes, DI/DO = 2 bytes)

Bus power per segment

1000 mA at 30V

Devices per segment

31 (typ. 8 to 10 due to FF cycle time)

Page 36

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

No 3rd party components required


FF-H1 Link Master

Power conditioner

SIMATIC FF Link

SIMATIC NET
FF-H1 type A cable
(yellow and blue)

FOUNDATION
Fieldbus - H1

Active Field Distributor


(junction box with
automatic bus termination)

Field Devices

Page 37

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

Hardware configuration workflow


2
Add & configure
Configure FF Link

1
Add & configure devices

Import additional DDs


via PDM
Device Integration
Manager

4
Connect device I/O data
to process image of
controller

Page 38

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

APL fieldbus channel drivers

Connect process image


with application via
generic fieldbus channel
driver included in
PCS 7 APL
FbAnIn
FbAnOu

FbDiIn
FbDiOu
Module drivers can be
generated automatically

Page 39

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

FF communication schedule generation


FF-blocks connected to process image are automatically managed by the system

In addition FF-blocks can be manually interconnected to establish Control In The


Field loops (PDM Connection Editor)
Macro cycle

FOUNDATION Fieldbus H1

2
AO

PID

AO_1

PID_1

AI
BKCAL_IN

OUT

CAS_IN

OUT

AI_1
OUT

Page 40

2014-08-13

30

31

Additional devices
configured for
cyclic data exchange
with the controllers
process image

BKCAL_OUT

IN

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

Fieldbus parameter settings

Timing settings for


address and device tag
change procedure

Automatic or
custom settings

Retry Factor

Page 41

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

Macrocycle configuration
Schedule and macro cycle are
automatically determined by the system
according the following conditions:
Interconnections (process image and
CIF)
Device type specific timings

Acyclic portion
(70% = 280ms)

Fieldbus communication parameters


settings
User defined conditions (max cycle time,
ratio between cyclic and acyclic
communication)

Reserve
(64ms)
Cyclic
communication
(56ms)

Macro cycle
(400 ms)

Page 42

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

Link master assignment


DP/FF-Link is implicitly loaded as primary link master at default
Master IM153-2 is Link Active Scheduler (LAS)
Standby IM153-2 is backup LM (in redundant configuration)

Optionally, field devices can be assigned to be backup link master as well

Control In The Field applications keep on running without controller or linking device !

Page 43

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

Complete Device Management support via


SIMATIC PDM

Maintenance
Station

Online views

Page 44

2014-08-13

PDM

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

Software Package
PCS 7 V8.0 Update 1 or higher
PDM V8.0 Servicepack 1 or higher

FF Communication is now integrated into PDM

Universal Solution for FF and PROFIBUS PA


Page 45

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

Fieldbus Solutions with PCS 7

PROFIBUS DP
Active Field Distributor
PROFIBUS PA
FOUNDATION Fieldbus
PROFINET

Siemens AG 2014. All Rights Reserved.

Fieldbus Solutions with PCS 7


PROFINET

Siemens AG 2014. All Rights Reserved.

Installation Base of PROFINET


Over 5.9 Mio nodes are already installed
Controller
Remote IO

Drives
Displays

Page 48

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

PROFINET in Process Automation


Imagine: a PROFIBUS installation with
a higher availability
a higher scalability of the redundancy
more than one master in the network
Webserver functionality
electrical ring installation
more than 126 connections / devices on the same network
graphic visualization and automatic identification of the topology
complete commissioning with automatic addressing and naming
easy and fast device exchange
100% investment protection for the future by integration of existing fieldbus technologies (proxy technology)
very high data rate over high distances without need of separate repeaters
flexible topologies, which follows the installation of your plant (Line, Star, Tree and Ring)
wireless communication (also high available)
big data rates (e.g. data base, pictures, printer, webcam) over the same cable

PROFINET has the answers to all these requirements!


Page 49

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

PROFINET in Process Automation


Architectures
PROFIBUS DP
Active Field
Distributor
PROFIBUS PA
FOUNDATION
Fieldbus

Topologies
Line
Ring

Ringstruktur

Sternstruktur
Wireless

Tree
Mixed

Linienstruktur

Glas/POF

PROFINET

Media and cable length


Copper

Baumstruktur

PROFINET

max. 100m between two devices


Fiber optics
50 m 16 km
Wireless

Industrial WLAN (IEEE 802.11)


Bluetooth (IEEE 802.15.2)
Page 50

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

PROFINET in Process Automation


Comparison of the addressing

Individual and manual


addressing of each
station

Easy addressing by controller


with support of engineering
system

Automatic detection of the


topology
Visualization of the topology
Easy device exchange
Fast commissioning
Prevention of address conflicts

Page 51

2014-08-13

Thomas Bartsch

Automatic addressing of the station by


the controller
Engineering of stations by the
engineering station

Siemens AG 2014. All Rights Reserved.


Industry Sector

Standardization
Key features of PROFINET in the Process Automation
Complete fieldbus integration

Configuration in Run (CiR)

DCS

DCS
DeviceNet

Proxy

Remote I/O
PROFIBUS DP

Released

Already standardized
PROFIBUS PA

PROFINET

HART

FF H1

Time synchronization & stamping

PROFINET IO System Redundancy

System Master Clock


(GPS, DCF77, )

Backup

System Redundancy

Primary
Redundant Controller
Controller 1

In PI Review

Controller 2

Released

Controller 3

Redundant Network

Backup
Clock Master

PNIO Media Redundancy


Proxy

Page 52

Device

2014-08-13

Device

Thomas Bartsch

Device with
redundant
connectivity

Device with
Released
Sept. 2012
singular

connectivity
Siemens AG 2014.
All Rights Reserved.
Industry Sector

PROFINET in Process Automation


Integration of existing fieldbus technologies

DCS

AS-Interface

PROFINET

PROFIBUS DP

PROFIBUS PA

HART

FF H1

Page 53

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

PROFINET in Process Automation


Integration of PROFIBUS-DP in PROFINET

PROFINET

Proxy

Transparent communication
between PROFINET und PROFIBUS-DP

PROFIBUS DP

IE/PB Link (Proxy) represents the


PROFIBUS-Devices on PROFINET at a single
controller
The IE/PB Link is a PROFINET device on
Ethernet and DP-Master on PROFIBUS
Cyclic and acyclic communication

IE/PB Link

100% Investment protection for the future


Step-by-step from PROFIBUS DP to
PROFINET
Siemens AG 2014. All Rights Reserved.

Page 54

2014-08-13

Thomas Bartsch

Industry Sector

PROFINET in Process Automation


Integration of PROFIBUS-PA in PROFINET

PROFINET

Proxy

PROFIBUS DP

DP/PA Coupler for connection of


PROFIBUS-PA field devices
Connection of up to 31 PA field devices per
DP/PA Coupler

PROFIBUS PA

Cyclic and acyclic communication

Page 55

2014-08-13

Thomas Bartsch

DP/PA Coupler

Siemens AG 2014. All Rights Reserved.


Industry Sector

PROFINET in Process Automation


Combination of PROFINET and PROFIBUS
PROFIBUS and PROFINET in the Controller

Coexistence of PROFIBUS and PROFINET

Flexible system design with PROFIBUS and


PROFINET
PROFIBUS and PROFINET extend each
other
Coexistence of both technologies
Routing via PROFIBUS interface

Coexistence of PROFIBUS and PROFINET

No additional CPs for PROFIBUS


Easy migration from PROFIBUS to
PROFINET
Migrate step by step

PROFINET and PROFIBUS can be used at the same time on the Controller
Less Hardware required!

Page 56

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

PROFINET in Process Automation


Redundancy

Primary

Redundant Controller

57

Backup

Redundant Network

Device with
redundant
connectivity

Device with
singular
connectivity

Functionality
Support of system
redundancy is mandatory for
PA PROFINET devices in
CC-B(PA).

High Scalability
High Availability

Page 57

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

PROFINET in Process Automation


Terms

Page 58

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

PROFINET in Process Automation


Terms and Meanings
What means System Redundancy
We need to know first some terms to understand

PN IO Controller (IOC)
can be a single or redundant AS 400
Application Relation (AR)
Describes the relationship between IOC and the Remote IO or PN devices
Network Access Point (NAP)
Means the number of interface in a PN IO Device
S1/S2 Devices
S1 only one AR
S2 two AR possible

R1/R2 Device
two AR possible per interface (NAP)
Page 59

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

PROFINET in Process Automation


Single System

Controller
CPU

IOC
AR 1 Application Relation
AR

Single NAP
1 Interface

Network Access Point

NAP
PN IO

Page 60

2014-08-13

S1 Device

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

PROFINET in Process Automation


Redundant System and System Redundancy
Redundant Automation System

Controller 1
CPU

Controller 2

IOC

CPU

IOC

AR 1 Application Relation
1 Interface

AR 1

S2 Device
Supports System Redundancy

AR 2

Single NAP
Network Access Point

AR 2 Application Relation

NAP
PN IO

Page 61

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

PROFINET in Process Automation


System Redundancy Redundant System
Redundant Automation System

Controller 1
CPU

AR 2.1

AR 1.1

Controller 2

IOC

CPU

NAP 1

AR 2.1

IOC

AR 1.1
AR 1.2

AR 1.2

AR 2.2

AR 2.1

2 Interfaces

Redundant NAP

NAP 2
R2 Device

PN IO

Page 62

2014-08-13

Thomas Bartsch

Each NAP has 2 AR

Siemens AG 2014. All Rights Reserved.


Industry Sector

PROFINET in Process Automation


Media Redundancy Protocol (MRP)

MRP Media Redundancy Protocol

Architecture

IEC 61158-5-10 Edition 1.0 2007-12


Part of the PROFINET standardization
Based on ring topology - The basic concepts of MRP and HSR (High
Speed Redundancy) are identical
Max. 50 nodes in the ring
PROFINET IO-Controller
PROFINET IO-Devices
Components of the network infrastructure (IE switches, CPs)
Configuration and diagnostics in STEP7
200 ms reconfiguration time
MRP manages Ethernet Ring architecture, independent of the
connected participants and there communication relation

Page 63

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

PROFINET in Process Automation


Media Redundancy Protocol (MRP)

Innovation for simplification of the


system architecture

PROFINET devices are supporting


MRP functionality
data

One device or controller is RingMaster

PROFINET
Industrial Ethernet

Other devices or masters can take


over Ring-Master functionality in case
of a failure

MRP on integrated
PROFINET ports
Page 64

2014-08-13

Improved plant availability


More flexibility
Less costs, because of less required components
Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

PROFINET in Process Automation


Media Redundancy Protocol (MRP)

In case of a failure in the network or of


a device the communication resume
The Ring-Manager will initiate a
second communication path on the
network
The communication is now managed
over the alternative path

data

PROFINET
Industrial Ethernet

The failure is limited to a damaged


device

Page 65

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

PROFINET in Process Automation


Media Redundancy Protocol (MRP) Topologie Editor

Online check of ring configuration in the Topology Editor


Page 66

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

PROFINET in Process Automation


Media Redundancy Protocol (MRP) Topologie Editor
Flexibilitt

Effizienz

Performance

Mageschneiderte
Anlagenkonzepte

Optimale Nutzung von


Ressourcen

Hhere Produktivitt

Industrial Wireless LAN

Ein Kabel fr alles

Geschwindigkeit

Safety

Gerte-/ Netzdiagnose

Hohe Przision

Flexible Topologien

Easy cabling
Energieeffizienz

Groe Mengengerste

Offener Standard

Easy cabling
Einfache
Verkabelung

Hohe Datenrate

Web Tools

Schneller Gertetausch

Medienredundanz

Erweiterbarkeit

Robustheit/Stabilitt

Schneller Hochlauf

Detection of a lost connection in the Topology Editor


Page 67

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

PROFINET in Process Automation


PROFINET Diagnostic

Device failure

Maintenance
cable
Diagnostic information of Topology Editor

Page 68

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

PROFINET in Process Automation


System Architectures with S1 Devices and PCS 7 V8.1

Controller

Controller

With IOC

With IOC

MRP
S1 - Device

S1 - Device

S1 - Device

S1 - Device

S1 Devices
e.g. ET 200M, ET 200SP, IE/PB Link PNIO (MRP with Switch), Simocode, Sinamics
Page 69

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

PROFINET in Process Automation


System Architectures with S1 Devices and Switches and PCS 7 V8.1

Controller

Controller
With IOC

MRP

With IOC

S1 - Device

S1 - Device

S1 - Device

S1 - Device

S1 Devices
e.g. ET 200M, ET 200SP, IE/PB Link PNIO, Simocode, Sinamics
Page 70

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

PROFINET in Process Automation


System Architectures with S2 Devices and PCS 7 V8.1
Redundant Controller

Redundant Controller

With IOC

With IOC

MRP

S2 - Device

S2 - Device

S2 - Device

S2 - Device

S2 Devices
e.g. ET 200M, Simocode (new version 2014)
Page 71

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

PROFINET in Process Automation


System Architectures with S2 Devices and Switches and PCS 7 V8.1
Redundant Controller

Redundant Controller

With IOC

With IOC

MRP

S2 - Device

S2 - Device

S2 - Device

S2 - Device

S2 Devices
e.g. ET 200M, Simocode (new version 2014)
Page 72

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

PROFINET in Process Automation


Products

Siemens AG 2014. All Rights Reserved.

PROFINET in Process Automation


PROFINET as Fieldbus in PCS 7
PROFIBUS DP

PCS 7 Standard with PROFINET

Active Field
Distributor

AS 410

PROFIBUS PA
FOUNDATION
Fieldbus
PROFINET

AS 414-3IE and AS 416-3IE

PROFINET Interface integrated into CPU


AS 414-3, 416-2/4, 417-4
CP 443-1

Possible IO
ET 200SP Standard modules with PCS 7 V8.1
ET 200M with IM 153-4 PNIO HF
All modules

IE/PB Link PN IO with DP/PA - Link

Page 74

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

PROFINET in Process Automation


PROFINET as Fieldbus in PCS 7
PROFIBUS DP

PCS 7 High available and safety related automation systems

Active Field
Distributor

AS 410H,
AS 412H, AS 414H, AS 416H, AS 417H

PROFIBUS PA
FOUNDATION
Fieldbus
PROFINET

AS 410 F/FH,
AS 412F/FH, AS 414F/FH,
AS 416F/FH, AS 417F/FH
Integrated PN-Interface
Possible IO on PROFINET
ET 200SP Standard modules with PCS 7 V 8.1
ET 200M with IM 153-4 PNIO HF
F-DI Namur only on PROFIBUS

Architecture with Switches


Page 75

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

PROFINET in Process Automation


PROFINET in PCS 7 V8.02
Cost effective architecture for system
redundancy (Red. Controller, Single IM)

PCS 7 OS server

Industrial Ethernet, plant bus

Fault-tolerant
automation systems

Comprehensive diagnostics and easier


commissioning support via standard
Ethernet mechanisms (Plug & Play)

PCS 7
AS 410-5H

PROFINET, field bus


ET 200M PN

Zone 2

Zone 1

100% investment protection and


backward compatibility for fieldbus
installations (reuse of I/O modules)

SIMOCODE PN
Weighing systems

Improved performance due to higher bus


transmission rate (100 Mbit)
Improved robustness

PROFIBUS PA
IE/PB-Link

AFD
PROFIBUS DP

PAC 3200/4200 PN

SINAMICS PN

PA-Koppler

AFDiS

Free customizable flexible plant


topologies

PROFIBUS & PROFINET in one System

Page 76

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

PROFINET in Process Automation


PROFINET in PCS 7 V8.1

PCS 7 OS server

Second PROFINET IO Controller on


CPU410-5H
(without 443-1 -> optimized costs)

Industrial Ethernet, plant bus

Fault-tolerant
automation systems

PCS 7
AS 410-5H

PROFINET, field bus

ET 200SP: The low-cost Remote I/O


ET 200M PN

Zone 2

Zone 1

ET 200SP PN
Weighing systems

PROFIBUS PA
IE/PB-Link

SIMOCODE PRO V PN Release 2014

AFD

with System Redundancy

PROFIBUS DP

SIMOCODE PN

PAC 3200/4200 PN

PA-Koppler

AFDiS

SINAMICS PN

Integration of Drives via PN

Page 77

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

PROFINET in Process Automation


SIMOCODE pro with PROFINET
Functionality

Integrated two port switch with support of MRP

In preparation: redundant connection on high available controller over PROFINET

Communication based on open industry standard OPC UA and diagnostic over integrated web
server

Expandable with failsafe module with PROFIsafe

Supply of energy measured value over PROFIenergy

Benefit

SIMOCODE pro
with PROFINET

Page 78

2014-08-13

In preparation: Higher availability with PROFINET redundancy functions

In preparation: No need of Y-Link for connection on redundant system

Simplified operation and monitoring

Client and location-independent diagnostic

Easy implementation of Safety- (PROFIsafe) and Energy management (PROFIenergy) concepts

More

Integration of SIMOCE pro PN with full functionality with PCS 7 V8 Advanced Process Library (APL)

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

PROFINET in Process Automation


ET 200SP
ET 200SP
50% smaller footprint

Power modules to create load groups


integrated into the system

New AI HART module

Tool-free connection system


due to push-in terminals

Reduced variety of parts


due to function compression

Enhanced product performance

Simple to use smaller in size stronger in performance


with PROFINET, replacing ET 200S
Page 79

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

PROFINET in Process Automation


CPU 410-5H
Technical Details
Flexible scalable PO (from 100 PO to 2600 PO)
Memory
48MB Load-, 16MB Code- and 16MB data memory

IO-Range
16.000 Byte Input and 16000 Byte Output

Performance
10ms cycle time

Functionality
HF-CPU (Process Safety & High Availability)
High precision time stamping

Interfaces
DP-Master with max. 96 DP-Slaves
Up to 10 additional external DP-Master
2x PN IO Controller with 250 Devices each
or 2x Ethernet
or 1x Ethernet & 1x PN IO Controller

Conformal Coating

Page 80

2014-08-13

Thomas Bartsch

Individual configurations possible

Siemens AG 2014. All Rights Reserved.


Industry Sector

PROFINET in Process Automation


Advantages

Siemens AG 2014. All Rights Reserved.

PROFINET in Process Automation


The way from PROFIBUS to PROFINET
PROFINET: The perfect combination of two
worlds with additional value

PROFIBUS is the most established fieldbus and PROFINET is the further


development based on standard Ethernet

PROFIBUS know-how can be easy used for


PROFINET

The low costs for the change from PROFIBUS to PROFINET are a investment
protection for the customer

PROFINET has advantages compared to


PROFIBUS

Flexible topologies, Scalable redundancy, Performance, Robust installation,


Wireless, Web, Multi-Master, Shared Device, Media redundancy and many more

New projects can already start today with


PROFINET

and using therefore the innovative concepts of the system architectures

Partly shift to PROFINET with a existing


PROFIBUS installation

Step-by-step change from PROFIBUS communication modules, whereby the cabling


of the I/O modules is still used. A proxy is used to connect the remaining devices.

PROFINET is a worldwide established and


reliable standard

which is accepted and used in all branches and markets

The time is ready for PROFINET!

Page 82

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

PROFINET in Process Automation


Advantages of PROFINET
PROFINET is a worldwide established
standard in the industry based on
standard Ethernet

100% investment protection for the future


due to integration of existing fieldbus
technologies (Proxies)

PROFINET is well proven since many of


years in factory automation and motion
control

Higher scalability of the system redundancy

Seamless Integration from ERP/MES level


to field level (horizontal integration)

Higher performance with higher data rate


(100Mbit)

Detailed diagnostic and easier


commissioning due to Ethernet mechanisms
(Plug & Play)

Higher robustness

Complete Commissioning by automatic


naming and addressing
Easier and faster device exchange

More flexible topologies (Line, Star, Tree


and Ring)

PROFINET is the future system backbone for PCS 7


Page 83

2014-08-13

Thomas Bartsch

Siemens AG 2014. All Rights Reserved.


Industry Sector

Thank you for your attention!

Thomas Bartsch
Marketing Manager
I IA AS S MP 7
Siemensallee 84
76187 Karlsruhe
Phone: +49 721 595-6745
Fax: +49 721 595-8487
Cellular: +49 173 707 4436

E-Mail: thomasbartsch@siemens.com

Siemens AG 2014. All Rights Reserved.

Das könnte Ihnen auch gefallen