Curves in this Family

70C1034 - Long Delay I2t, Short Delay Flat and I2t


Magnum, Magnum DS and Magnum SB Circuit Breakers

5000

Magnum, Magnum DS and Magnum SB Circuit Breakers


Response: Instantaneous Trip
This curve is for 50Hz or 60Hz applications.

4000
4

3000

70C1035 - Long Delay I t, Short Delay Flat


Magnum, Magnum DS and Magnum SB Circuit Breakers

2000

70C1038 - IEEE Moderately Inverse, Short Delay Flat


Magnum DS and Magnum SB Circuit Breakers

Notes:
1. There is a memory effect that can act to shorten the Long Delay. The memory
effect comes into play if a current above the Long Delay Pickup value exists for a
time and then is cleared by the tripping of a downstream device or the circuit
breaker itself. A subsequent overload will cause the circuit breaker to trip in
shorter time than normal. The amount of time delay reduction is inverse to the
amount of time that has elapsed since the previous overload. Approximately five
minutes is required between overloads to completely reset memory.

70C1039 - IEEE Very Inverse, Short Delay Flat


Magnum DS and Magnum SB Circuit Breakers
70C1040 - IEEE Extremely Inverse, Short Delay Flat
Magnum DS and Magnum SB Circuit Breakers

1000
900
800
700

70C1031 - IEC-A Normal Inverse, Short Delay Flat


Magnum Circuit Breakers

600

2. The end of the curve is determined by the application and the interrupting
rating of the circuit breaker.

70C1032 - IEC-B Very Inverse, Short Delay Flat


Magnum Circuit Breakers

3. This curve is shown as a multiple of the Rating Plug (In).

300

70C1033 - IEC-C Extremely Inverse, Short Delay Flat


Magnum Circuit Breakers

4. The Instantaneous settings have conventional 100% 10% as their pick up


points.

200

70C1043 - Instantaneous
Magnum, Magnum DS and Magnum SB Circuit Breakers

5. Total clearing times shown include the response times of the trip unit, the
circuit breaker opening and the interruption of the current.

70C1586 - Instantaneous
Magnum, MDSX / SBSE Circuit Breakers

6. The adjustable range of the instantaneous setting is 2xIn through 10xIn. The M1
setting can extend the range according to the rating plug value as shown below.
An OFF setting is available.

500
400

70C1498 - Maintenance Mode Trip


Magnum DS and Magnum SB Circuit Breakers

M1 setting
Narrow Frame:
200A through 1250A
1600A
2000A
Standard Frame:
200A through 1250A
1600A, 2000A, 2500A
3000A, 3200A
Double Wide Frame:
2000A, 2500A
3000A, 3200A, 4000A, 5000A
6000A, 6300A

70C1041 - Ground (Earth) Fault Flat and I t (LSIA style)


Magnum, Magnum DS and Magnum SB Circuit Breakers

60
50
40
30

20

10
9
8
7
6

Available Adjustable
INST PU
Setting 2 to 10x In 10%
With 0.5 Increments

M1=14x In
M1=12x In
M1=10x In
M1=14x In
M1=12x In
M1=10x In

8. For Magnum SB Narrow and Standard frames, and Magnum Narrow Frames
MDNC, a fixed Instantaneous is always provided. The level is set at 18 x rms
15%. This protection is functional even when the Instantaneous is set to the
OFF position.

See Notes 6, 7

9. These curves are comprehensive for the complete family of Magnum Circuit
Breakers, including all frame sizes, ratings and constructions. The total
Instantaneous clearing times shown are conservative and consider the
maximum response times of the trip unit, the circuit breaker opening and the
interruption of the current under factors that contribute to the worst case
conditions, like: maximum rated voltages, single phase interruption and
minimum power factor. Faster clearing times are possible depending on the
specific system conditions, the type of Magnum Circuit Breaker applied and if any
arc reduction settings are employed. Contact Eaton Corporation for additional
information.

1
.9
.8
.7
.6

Fixed
Instantaneous
See Note 8

.5
.4

Instantaneous Trip
at High Fault Currents

.3

.2

See
Note 7

.1
.09
.08
.07
.06
.05

.05
.04

.04

End of Curve
See Note 2

Current in Multiples of Rating ( In )

700
800
900
1000

500

600

400

300

200

70
80
90
100

50

60

50

60

40

30

20

6
7
8
9
10

.01

.01

.02

.02

.7
.8
.9
1

.03

.5

.03

Symmetrical RMS Current (kA)

Dwg. No.: 70C1043


July 2012

TIME IN SECONDS

.1
.09
.08
.07
.06

.6

TIME IN SECONDS

M1=14x In
M1=12x In
M1=12x In

7. For circuit breakers rated 3200A and less, of MDSC type, an additional High
Instantaneous Trip Module is provided in the circuit breaker set to trip at a
170kA instantaneous peak current level. This protection is functional even
when the Instantaneous is set to the OFF position.

40

1 MINUTE

100
90
80
70

30

1 HOUR

Circuit Breaker Time / Current Curves


(Phase Current)

70C1030 - Envelope Information for 1150 Family of Curves

6000

20

2 HOURS

.5

Digitrip 1150 / 1150i - Instantaneous Curve