OMICRON - Asia-Pacific Protection & Testing Conference


105

15

16

Univ.-Prof. DI Dr. L. Fickert


Singapore, October 15th - 16th, 2014

Projects (per year) ~ 60


3

Short Circuits and Earth Faults

Short Circuits and Earth Faults

electricity industry
authorities (AT, EU)
private industry AT, IT, DE, CZ, TR, BLG, FYROM, TR, GB, CH, RO
corporations

Partners/ contacts

Guest lecturers

Student-employees

Univ.-Ass. + Univ.Project-Ass. 3 + 13 =

Univ.-Prof + Ao. Univ.-Prof + Senior Scientist

truth
objectivity
neutrality

Philosophy and Activities

Singapore, October 15th - 16th, 2014

We are obliged to:

Institut fr Elektrische Anlagen

Univ.-Prof. DI Dr. L. Fickert

Institute of Electrical Power Systems


University of Technology Graz

Dipl.-Ing. Thomas Mallits

Dipl.-Ing. Dr. Ernst Schmautzer

Univ.-Prof. Dipl.-Ing. Dr. Lothar Fickert

Consequences Concerning Safety of People

Protection, Application and Judging Fault

Short Circuits and Earth Faults: Calculation for

Institut fr Elektrische Anlagen

Univ.-Prof. DI Dr. L. Fickert

Institut fr Elektrische Anlagen

Univ.-Prof. DI Dr. L. Fickert

Institut fr Elektrische Anlagen

Singapore, October 15th - 16th, 2014

earth faults

short circuit

Typical faults in power grids

Singapore, October 15th - 16th, 2014

Short Circuits and Earth Faults

Short Circuits and Earth Faults

Presentation 12.1

OMICRON - Asia-Pacific Protection & Testing Conference

Univ.-Prof. DI Dr. L. Fickert

Institut fr Elektrische Anlagen

Univ.-Prof. DI Dr. L. Fickert

Institut fr Elektrische Anlagen

Petersen
coil 1)

Cable

Singapore, October 15th - 16th, 2014

Relay

Landline

1)Petersen

coil (1917):

arc suppression coil

Short Circuits and Earth Faults

Waldemar Petersen

Univ.-Prof. DI Dr. L. Fickert

XPet0 = 3*UN/IPet

R0 = 3*Rtrans

impedance

Neutral

network

Healthy

Singapore, October 15th - 16th, 2014

Relay

Short Circuits and Earth Faults

XCE0 = 3*UN/ICE

= (IPet ICE)/3

Short Circuits and Earth Faults

I0 = IE/3

Fault calculation in symmetrical components

Singapore, October 15th - 16th, 2014

Theory and Reality of Earth Faults

Institut fr Elektrische Anlagen

Univ.-Prof. DI Dr. L. Fickert

Symmetrical Components (2)

Short Circuits and Earth Faults

faults

method for earth

Simplified calculation

Symmetrical Components (1)

Singapore, October 15th - 16th, 2014

High voltage OHL on ground

Line to ground fault

Institut fr Elektrische Anlagen

Presentation 12.2

XNetwork,cap

OMICRON - Asia-Pacific Protection & Testing Conference

Univ.-Prof. DI Dr. L. Fickert

Institut fr Elektrische Anlagen

Univ.-Prof. DI Dr. L. Fickert

Short Circuits and Earth Faults

Singapore, October 15th - 16th, 2014

= (UN/3) / Isc

1%

11

Short Circuits and Earth Faults

2/3* 60A / 4000A

Xresidual

2/3Z1 /

2/3*(m*ICE) / Ik

Xresidual)

(UN/3) / (2/3Z1 +

IF = 3*(UN/3) / (2 Z1 + 3*Xresidual)

Xresonant = (UN/3) / (m* ICE)

Z1

IF = UN/ Rtrans2+ Xresidual2

Xresidual

Rtrans

accuracy, e.g. for Rtrans = 0:

Univ.-Prof. DI Dr. L. Fickert

Singapore, October 15th - 16th, 2014

IF = UPhase / [(RStp // Xresidual) + ZL(1+kE) + Rtrans ]

k0*ZL

ZL

Rtrans

12

Short Circuits and Earth Faults

10

Short Circuits and Earth Faults

Step 3 neutral with arc suppression coil (ASC) and neutral resistor

Singapore, October 15th - 16th, 2014

Step 2 neutral with arc suppression coil (ASC)

Institut fr Elektrische Anlagen

Univ.-Prof. DI Dr. L. Fickert

Simplified Calculation (3)

IF = UN/ Rtrans2+ Xresidual2

Xresidual = (UN/3) / (m* ICE)

Simplified Calculation (2)

Singapore, October 15th - 16th, 2014

IF = UN/ Rtrans2+ XNetwork,cap2

Xresidual

Rtrans

Step 2 neutral with arc suppression coil (ASC)

Step 1 isolated neutral

Rtrans

Simplified Calculation (2)

Institut fr Elektrische Anlagen

Simplified Calculation (1)

XNetwork,cap = (UN/ 3) / I

Institut fr Elektrische Anlagen

Presentation 12.3

OMICRON - Asia-Pacific Protection & Testing Conference

Univ.-Prof. DI Dr. L. Fickert

Singapore, October 15th - 16th, 2014

Singapore, October 15th - 16th, 2014

System

Global Earthing

Institut fr Elektrische Anlagen

Univ.-Prof. DI Dr. L. Fickert

15

Short Circuits and Earth Faults

13

Short Circuits and Earth Faults

Questions: Influence of the length to ground? Soil resistivity? Grass etc?

= R(I)*I = U(I)

U = 800V + 120*I

Resistance of a line to ground fault

Institut fr Elektrische Anlagen

Univ.-Prof. DI Dr. L. Fickert

Institut fr Elektrische Anlagen

Univ.-Prof. DI Dr. L. Fickert

Voltage in V

Singapore, October 15th - 16th, 2014

Duration in ms

Tolerable Touching Voltage

Danger

Singapore, October 15th - 16th, 2014

2,000

4,000

6,000

8,000

10,000

12,000

14,000

50

100

150

200

250

300

Resistance of trees

U[Volt]
R[/m]

Institut fr Elektrische Anlagen

10

16

Short Circuits and Earth Faults

14

Short Circuits and Earth Faults

10

H[m]

H[m]

Presentation 12.4

OMICRON - Asia-Pacific Protection & Testing Conference

Univ.-Prof. DI Dr. L. Fickert

IEarth

Singapore, October 15th - 16th, 2014

Principally wrong!!

Ground Current (3)

IEarth

1 /r

IEarth

19

Short Circuits and Earth Faults

17

Short Circuits and Earth Faults

UE 1m / r12 1/ r2

Utouch, max = UE [1 - r1 /(r1 + 1m)]

(r) = UEarth

Singapore, October 15th - 16th, 2014

UEarth = IEarth REarth

Utouching, max REarth = / (2r1)

Ground Current (1)

Institut fr Elektrische Anlagen

Univ.-Prof. DI Dr. L. Fickert

Institut fr Elektrische Anlagen

IEarth

Ground Current (4)

Top view

Univ.-Prof. DI Dr. L. Fickert

Singapore, October 15th - 16th, 2014

20

Short Circuits and Earth Faults

Return path follows its conductor closely

18

Short Circuits and Earth Faults

Lateral view

IEarth

Impact on current distribution


Inductance conductor-earth-loop
Impedance-relations of whole setup (parallel conductors)

Like This!

Singapore, October 15th - 16th, 2014

Ground Current (2)

Institut fr Elektrische Anlagen

Univ.-Prof. DI Dr. L. Fickert

Institut fr Elektrische Anlagen

Presentation 12.5

Singapore, October 15th - 16th, 2014

Current flow in power grid (1)

OMICRON - Asia-Pacific Protection & Testing Conference

Univ.-Prof. DI Dr. L. Fickert

conductor
Singapore, October 15th - 16th, 2014

23

Short Circuits and Earth Faults

substation is part of system with multi earthed high voltage neutral

feeding extended industrial areas

many outgoing earth electrodes

many nearby substations

protective earth conductors of low voltage system

substation with many distributed earth electrodes interconnected by

city centre or densely built up areas

interconnected earthing systems

substation surrounded by buildings with foundation earth electrodes and

verification by typical measurements or calculations

short fault duration

suitable cable sheath reduction factor or earth wire reduction factor

low fault current level

low overall resistance is helpful, but is not a guarantee

Typical situations

21

Short Circuits and Earth Faults

Global earthing system: Typical applications

Institut fr Elektrische Anlagen

Univ.-Prof. DI Dr. L. Fickert

Source

Institut fr Elektrische Anlagen

3%

Singapore, October 15th - 16th, 2014

Earth fault current

Current flow in power grid (2)

Univ.-Prof. DI Dr. L. Fickert

Singapore, October 15th - 16th, 2014

24

Short Circuits and Earth Faults

(EPR F UTP: cement mixer in the backyard with extension line)

Connection of l.v. earth (TN) and m.v. earth and und transferred potentials

Installations at the fringes of densely use areas

Outlying Buildings (Sausage stand in the woods)

Outlying RMUs (recreation home)

Cable riser poles (m.v.)

Outliers:

Situations at the fringes of settlements

Example:

Mitigation

Measurements (Calculations)

Exceptions/ critical situations

22

Short Circuits and Earth Faults

Global earthing system critical situations

Institut fr Elektrische Anlagen

Univ.-Prof. DI Dr. L. Fickert

Source

Institut fr Elektrische Anlagen

Presentation 12.6

Singapore, October 15th - 16th, 2014

OMICRON - Asia-Pacific Protection & Testing Conference

Univ.-Prof. DI Dr. L. Fickert

30 Volt

27

Short Circuits and Earth Faults

200 Volt for <0,5s

1000A

for <0,4s

25

Short Circuits and Earth Faults

Transformer station

ZTrans 30 m

300 Volt

Singapore, October 15th - 16th, 2014

Worst case: 6 times worse

With global earthing system

linear scaling 300A

typ 60A 60 Volt

Typical touch voltages

traditionally:

Summary:

Institut fr Elektrische Anlagen

Univ.-Prof. DI Dr. L. Fickert

Global earthing system

Global earthing system: reality (1)

Institut fr Elektrische Anlagen

Summary

Singapore, October 15th - 16th, 2014

Singapore, October 15th - 16th, 2014

Critical situations s.a. outliers: mitigation

28

Short Circuits and Earth Faults

An earth current of 100A causes a neglectable touching


voltage

26

Short Circuits and Earth Faults

UW

Only a small fraction of the fault current flows through


earth

Touching voltage relation is time-dependent

Univ.-Prof. DI Dr. L. Fickert

Institut fr Elektrische Anlagen

Univ.-Prof. DI Dr. L. Fickert

Example for critical points

Global earthing system: reality (2)

Institut fr Elektrische Anlagen

Presentation 12.7

Univ.-Prof. DI Dr. L. Fickert


Singapore, October 15th - 16th, 2014

www.ifea.tugraz.at

Institute of Electrical Power Systems


University of Technology Graz

Dipl.-Ing. Thomas Mallits

Dipl.-Ing. Dr. Ernst Schmautzer

Univ.-Prof. Dipl.-Ing. Dr. Lothar Fickert

29

Short Circuits and Earth Faults

Consequences Concerning Safety of People

Protection, Application and Judging Fault

Short Circuits and Earth Faults: Calculation for

Institut fr Elektrische Anlagen

Presentation 12.8

OMICRON - Asia-Pacific Protection & Testing Conference