Beruflich Dokumente
Kultur Dokumente
RasGas PLANT
HARMONICSSTUDY
HarmonicsMeasurement
Prof.LazharBenbrahim1,Prof.MohieddineBenammar1 ,
Eng.JesusRomero2
1
01/8/2010
[The increasing use of nonlinear loads, in modern industry is keeping harmonic
distortion in distribution networks on the rise. Keeping the level harmonics under the
standard limits is very crucial to the stability of the power networks. The objective of
this harmonic study of RasGas LNG plant is the measurement of harmonics and
investigationofcompliancewithIEEE519harmonicsstandards.]
Acknowledgment
We would like to acknowledge the help from RasGas Engineers and Technicians
for their help in carrying out the measurements at RasGas plant.
We would like also to thank all those who helped in this project.
Prof.LazharBenBrahim
Prof.MohieddineBenammar
Eng.JesusRomero
Abstract
The increasing use of power electronics equipment in modern industry is
keeping harmonic distortion in distribution networks on the rise. The most nonlinear
devices used in the gas processing industry are the VFDs. These and other devices
generate harmonics in the network of the plant. Keeping the level of these disturbances
under certain limits is very crucial to the stability of the power networks. The objective of
this harmonic study of RasGas LNG plant is the measurement of harmonics and
investigation of compliance with IEEE 519 harmonics standards.
Measurements of harmonics at various points of the plant have been carried out
using dedicated power quality analyzers. The results of these measurements have been
thoroughly analyzed. The measurements and interpretation of the results indicate overall
compliance with IEEE 519 standard. All voltage harmonics (Total Harmonics Distortion
and individual harmonics) at the various PCC (33kV, 6.6kV and 415V) meet the
standard. Almost the same goes for the Total Demand Distortion (TDD) for the current.
However, in some cases, some concerns are noted for the 48th harmonic current around
the VSCF. The UPS and battery chargers exhibit high THDI but given their low power, in
many cases this translates to acceptable TDDI and in all cases the chargers have little
impact on the power network. It is noted also that some 415 buses are not balanced from
the point of view linear versus non-linear loads. It is recommended that this is taken into
consideration in future expansion, as significant unbalance may result in violations of
harmonics standards.
TABLE OF CONTENTS
1.
INTRODUCTION..................................................................................................5
ANALYSIS ...........................................................................................................18
REFERENCES.....................................................................................................24
APPENDIX.Appendix1
1. INTRODUCTION
1.1. Motivation
Power quality is a big concern to facility designers and operators. When the quality of
electrical power supplied to equipment is deficient, performance degradation results. A
good power quality necessitates a thorough study of several issues (Fig. 1) [1]. In its
quest to make sure that the power quality of its network is up to the international
standards, RasGas has launched several studies. Among these studies is the harmonics
study of their LNG plant.
LNG plants are relying more and more on modern electronic equipments which are
nonlinear loads that may cause harmonic distortion in distribution networks. The most
used nonlinear device in modern industry is perhaps the static power electronics
converter (e.g., UPS, battery chargers and drives), [1]. A situation that has raised
waveform distortion levels in distribution networks. Keeping the level of these
disturbances (also called harmonics) under certain limits is very crucial to the stability of
the power networks. Harmonic studies are effective way to keep networks and equipment
under acceptable operating conditions and to foresee potential problems with the
installation.
PowerQuality
POWER
FREQUENCY
DISTURBANCES
POWER
SYSTEM
TRANSIENTS
ELECTRO
MAGNETIC
INTERFERENCE
GROUNDING
AND
BONDING
POWER
SYSTEM
HARMONICS
ELECTRO
STATIC
DISCHARGE
POWER
FACTOR
2. The measurements and data collection in the plant was planned. All critical points
where potential generation of harmonics was suspected have been considered
(VFDs, UPSs, Battery Chargers etc.).
Fig. 2: Harmonics Measurement Training: RasGas engineers and technicians in the training
about the PQA at the Power Electronics Laboratory of Qatar University on February 3rd 2009
2. BACKGROUND
2.1. Terminology
9 Point of Common Connection (PCC): A point of metering between the utility
and consumer. Within an industrial plant, the PCC is the point between the
nonlinear load and other loads. This implies that harmonic limits must be met
internally, in the consumers system. Many consultants, for example, use this
7
THD
h=2
V h2
V 22 + V 3 2 + V 42 + V 5 2 + ....
V1
V1
100 % (1)
where Vh is the rms of the hth harmonic voltage, in volt. V1 refers to the
fundamental frequency (50Hz) voltage. V2 refers to the second harmonic, or the
voltage at twice the fundamental frequency (100 Hz, if the fundamental is 50 Hz)
and so on.
9 Current THD (THDI): Total Harmonic Distortion of the current waveform. The
ratio of the rms value of the harmonic content of the current to the rms value of
the fundamental current:
THD
h=2
I1
I h2
=
I 22 + I 32 + I 42 + I 52 + ....
I1
100 % (2)
Where Ih is the rms of the hth harmonic current, in Amperes. I1 refers to the
fundamental frequency (50Hz) current. I2 refers to the second harmonic, or the
current at twice the fundamental frequency (100 Hz) and so on.
9 Current TDD (TDDI): Total Demand Distortion of the current waveform. The
ratio of the rms value of the harmonic content of the current to the maximum
demand load current:
TDD
h=2
I h2
=
I 22 + I 32 + I 42 + I 52 + ....
100 % (3)
9 Derating of cables due to additional eddy current heating and skin effect losses.
9 Inductive interference with telecommunication circuits.
9 Signal interference and relay malfunctions, particularly in solid-state and digitally
controlled systems.
9 Unstable operation of firing circuits relying on zero voltage crossing detection
and latching.
9 Interference with large motor controllers
Standards were developed to keep harmonics under some acceptable limits. These
limits are described by IEEE 519 harmonics standard which indicates the Recommended
Practice and Requirements for Harmonic Control in Electrical Power Systems (see Table
1&2). Note that voltage harmonics and current harmonics are assessed through the THD
and TDD respectively. The TDD is the total demand distortion and is identical to the
THD except that the maximum load current (IL) is used instead of the fundamental
current component (I1). The measured harmonics distortion of voltage and current levels
are therefore compared to the allowable limits recommended by IEEE-519 standards [2].
Table 1: IEEE 519-1992 Standard: Recommended Practices and Requirements for Harmonic
Control in Electrical Power Systems (Voltage Distortion Limits)
Bus Voltage
THD_V %
<= 69KV
3.0
5.0
69 - 161KV
1.5
2.5
>= 161 KV
1.0
1.5
10
h<11
11h<17
17h23
23h35
35h
TDD %
<20*
4.0
2.0
1.5
0.6
0.3
5.0
20-50
7.0
3.5
2.5
1.0
0.5
8.0
50-100
10.0
4.5
4.0
1.5
0.7
12.0
100-1000
12.0
5.5
5.0
2.0
1.0
15.0
>1000
15.0
7.0
6.0
2.5
1.4
20.0
69 kV < V 161kV
<20
2.0
1.0
0.75
0.3
0.15
2.5
20-50
3.5
1.75
1.25
0.5
0.25
4.0
50-100
5.0
2.25
2.0
0.75
0.35
6.0
100-1000
6.0
2.75
2.5
1.0
0.5
7.5
>1000
7.5
3.5
3.0
1.25
0.7
10.0
ISC is the maximum short circuit current at the PCC and IL is the maximum demand load current (Fundamental
frequency component) at PCC.
*All power generation equipment is limited to these values of current distortion, regardless of actual ISC/IL
11
12
3. MEASUREMENT
Following the acquisition of the two sets of PQA and the adequate training carried out
for RasGas engineers, the first measurement was conducted on March 2nd 2009, we have
recorded some data around a well know harmonics-generating equipment (SS53:TR5342,TR5343, TR5344 which includes VFDs installations and we also verified the
UPS units UPS5731A and UPS5731B) and the data confirmed the existence of harmonics
as expected. This initial test gave us trust on the technician measurement capability and a
confidence in the reliability of the PQA, and decided to proceed with a wide range of
measurements at various locations in the plant. Instructions were given by the chairs to
13
the measurement team composed of RasGas engineers and technicians (to check the
direction of connections of the current sensors and to increase the sampling frequency of
measurement as the data taken is two little).
Extensive measurement has started on April 7th 2009, and due to periodic maintenance
at the RasGas plant several delays in the measurement occur. It is worth noting that we
were suspecting harmonics from nonlinear loads such as VFDs, UPSs, BCs and in a
lesser gravity from transformers that may operate in saturation or resonant conditions. As
data was received, the chairs and engineer Romero were checking for data that may
represent a threat to the grid. Depending on measurement results, in some cases further
measurements were carried out to verify the causes for some of the measured harmonics,
this is the case of the Variable Speed Constant Frequency (VSCF) generators. Therefore,
harmonics spectrum especially at the 6.6kV may change depending on the operating
conditions of the plant where VSCF is in service. This has caused some delays in order to
investigate more the causes of these harmonics. The last data collected were carried out
by mid-December 2009. The period of measurement lasted 8 months which were enough
to carry out measurement at various operating conditions.
Sample of measurement data are shown in the Appendix. For each measurement point the
followings are given:
1. A general information about the measurement point (Hioki DMM tables)
2. Voltages and currents waveforms as well as harmonics spectrum
3. Lists of harmonics and THDs for the voltages and currents
Note that all measured data are stored into a CD included with this report.
The plant is composed of several trains and several substations which are more or less
similar.
Measurements shown in this report were selected and represent all types of
loads within the plant. Focus is on the SubStation SS02 which contains the most critical
nonlinear loads of the plant. Measurements at other substations (SS01 & SS03) were
carried out for the validation of the results obtained in SS02.
14
A summary of the results obtained from measurements carried out in SS01, SS03 and
mainly in SS02 is given in Table 3 below. A detailed analysis of these results is given in
the section below.
TR 0221
(GT 051)
TR 5143
TR 5142
TR 5154-2
1950 KVA
TR 5141B
4/5 MVA
POWER
(MW)
(measured)
VOLTAGE(kV)
(atMeasurement
point)
Short Circuit
TotalHarmonic
Current Isc (kA)
DistortionTHDV
12.00
33
THDV=3.15%
11.96
33
THDV=2.67%
12.38
33
THDV=2.74%
1.13
6.6
Isc= 0.2
THDV=3.03%
0.67
6.6
CURRENT(A)
(atMeasurementpoint)
TotalHarmonicDistortionTHDI
TotalDemandDistortionTDDI
222.7
THDI=3.28%
228
THDI=1.8%
239
THDI=0.43%
99.7
THDI=4.46%
Isc /IL=1.2
69.7
THDI=6.8%
Isc= 5.6
THDV=2.72%
Isc /IL=16
0.884
TR 5155-2
1550 KVA
TR 5151A
1600 KVA
TR 5151B
1600 KVA
15
TDDI=2.61%
(<5%)
6.6
Isc= 0.2
THDV=2.65%
0.330
0.415
Isc= 26
THDV=2.26%
0.047
0.415
Isc= 25.5
THDV=2.60%
I48/I1=3.7%
I48/IL=2.16%
(>0.3%)
I48/I1 =4.3%
TDDI=1.35%
(<5%)
I48/IL=0.86%
(>0.3%)
TDDI=3.82%
(<5%)
I48/I1=3.9%
I48/IL=2.24%
(>0.3%)
TDDI=0.36%
(<5%)
I48=0.9%
I48/IL=0.22%
(<0.3%)
TDDI=0.19%
(<5%)
I48/I1=0.89%
I48/IL=0.04%
(<0.3%)
77.88
THDI=6.65%
Isc /IL=1.5
540.8
THDI=1.52%
Isc /IL=11
97.6
THDI=4.36%
Isc /IL=11
TR 5152E
400 KVA
TR 5153A
1250 KVA
UPS
5171A
100 KVA
0.047
0.415
Isc= 24.6
THDV=1.53%
0.248
0.415
Isc= 24.8
THDV=2.83%
0.016
0.415
90.23
THDI=30.73%
Isc /IL=44
Isc /IL=14
TR 5241A
25/30
MVA
0.407
6.6
39.2
THDV=0.94%
THDI=0.54%
TR 5241B
25/30
MVA
0.748
66
72.8
THDV=0.92%
THDI=0.72%
0.415
13.99
THDI=14.81%
TR 5342
16 MVA
Isc= 37.4
THDV=0.91%
10.49
33
Isc= 33.3
THDV=2.78%
TR 5343
12.84
(LCI VFD
+filter)
TR 5344
7.12
(LCI
VFD+filter
)
0.524
TR 5341A
4/5 MVA
Isc= 5.6
Isc /IL=67
Isc /IL=118
THDV=2.62%
THDI=1.75%
33
125
THDV=2.68%
THDI=2.89%
6.6
57.3
THDI=6.66%
6.6
TR 5341B
4/5 MVA
Isc= 5.6
THDV=2.90%
TR 5354-2
0.674
6.6
I5/I1=5.77%
I5/IL=1.65%
(<4.0%)
TDDI=9.47%
(<15%)
Isc /IL=16
TDDI=0.37%
(<12%)
I5/I1=7.42%
I5/IL=0.18%
(<10.0%)
TDDI=1.98%
(<15%)
I11/I1=2.52%
I11/IL=1.63%
(<5.50%)
TDDI=1.09%
(<5%)
I48/I1=5.27%
I48/IL=0.86%
(>0.30%)
TDDI=1.09%
(<5%)
I48/I1=4.69%
I48/IL=0.82%
(>0.30%)
61.3
THDI=6.66%
Isc /IL=16
73.7
I5/I1=34.94%
I5/IL=1.65%
(<12.0%)
I48/I1=0.04%
I48/I1=0.02%
181.2
THDI=3.07%
242
0.561
16
Isc /IL=177
33
THDV=2.98%
TDDI=1.98%
(<5%)
33.78
THDI=38.98%
THDV=2.15%
0.008
I5/I1=28.52%
I5/IL=4.64%
(<7.0%)
499.3
THDI=6.9%
Isc= 24.6
TR 5252E
400 KVA
TDDI=5.0%
(<8%)
1950 KVA
TR 5355-2
1550 KVA
TR 5351A
1600 KVA
TR 5351B
1600 KVA
TR 5352E
400 KVA
TR 5353A
1250 KVA
TR 5353B
1250 KVA
THDI=4.26%
Isc= 0.2
THDV=2.94%
0.733
6.6
Isc= 0.2
THDV=2.79%
0.366
0.415
Isc= 26
THDV=2.02%
0.065
0.415
Isc= 24.4
THDV=3.0%
0.049
0.415
Isc= 30.1
THDV=2.02%
0.257
0.415
Isc= 24.8
THDV=2.96%
0.137
0.415
Isc /IL=1.2
Isc /IL=1.5
TDDI=2.38%
(<5%)
I48/IL=3.56%
I48/IL=2.00%
(>0.30%)
563
THDI=2.17%
Isc /IL=11
TDDI=0.55%
(<5%)
140
THDI=4.32%
Isc /IL=11
Isc /IL=54
TDDI=0.27%
(<5%)
TDDI=0.65%
(<12%)
I5/I1=28.41%
I5/IL=0.18%
(<10.0%)
TDDI=2.08%
(<5%)
I5/I1=5.86%
I5/IL=1.72%
(<4.0%)
TDDI=1.41%
(<5%)
I5/I1=7.52%
I5/IL=1.3%
(<4.0%)
512.7
THDI=7.06%
Isc /IL=14
289.4
THDI=8.51%
UPS
5371A
100 KVA
0.0154
0.415
Isc= 30.1
THDV=2.27%
TR 5441A
25/30
MVA
TR 5441B
25/30
MVA
2.22
6.6
218
THDV=0.87%
THDI=0.97%
6.6
553
THDV=0.83%
THDI=1.05%
0.013
0.415
TR 5452E
400 KVA
17.22
THDI=14.75%
Isc= 36.4
THDV=0.8%
TR 5542
3.47
33
Isc /IL=14
35.0
THDI=42%
Isc /IL=216
Isc /IL=65
62.4
I48/I1=1.19%
I48/IL=0.301
%
(>0.30%)
I48/I1=0.45%
I48/IL=0.03%
(<0.30%)
97.18
THDI=3.72%
THDV=3.02%
17
I48/I1=3.64%
I48/IL=1.57%
(>0.30%)
76.38
THDI=4.24%
Isc= 24.4
5.66
TDDI=1.84%
(<5%)
TDDI=10.5%
(<15%)
I5/I1=36.0%
I5/IL=9.1%
(<12.0%)
I48/I1=0.09%
I48/I1=0.02%
TDDI=0.46%
(<15%)
I5=6.54%
I5/IL=0.21%
(<12.0%)
11.5/2-5.75
MVA
Isc= 31.4
THDV=2.66%
TR 50142
12.0
0.0017
33
THDV=1.23%
33
THDV=1.24%
33
THDV=1.30%
0.415
Isc= 30.0
THDV=1.87%
0.0136
415
TR 50143
TR 50144
BC
50181A
44 KVA
UPS
50171A
100 KVA
TR 50342
11.5/2-5.75
MVA
BC 0181B
70 KVA
UPS
0171A
30 KVA
THDI=8.87%
10.7
3.24
Isc= 30.0
THDV=1.23%
0.308
33
Isc /IL=156
TDDI=2.75%
(<15%)
I11/I1=7.03%
I11/IL=2.18%
(<5.5%)
TDDI=5.32%
(<15%)
I5/I1=34.4%
I5/IL=3.24%
(<12.0%)
TDDI=13.5%
(<15%)
I5/I1=40.8%
I5/IL=10.1%
(<12.0%)
210.7
THDI=2.82%
198.2
THDI=1.99%
70.8
THDI=3.25%
5.76
THDI=56.51%
Isc /IL=490
34.5
THDI=52.66%
Isc /IL=215
5.4
THDI=66.5%
Isc= 19.9
THDV=1.23%
0.003
0.415
Isc= 29.2
THDV=0.48%
0.0042
0.415
Isc= 29.2
THDV=0.45%
Isc /IL=99
I11/I1=46.71%
TDDI=1.78%
(<12%)
I11/IL=1.25%
(<4.5%)
TDDI=5.17%
(<15%)
I5/I1=35.6%
I5/IL=3.43%
(<12.0%)
TDDI=16.9%
(>15%)
I5/I1=43.14%
I5/IL=12.9%
(>12.0%)
9.4
THDI=53.33%
Isc /IL=299
12.5
THDI=56.75%
Isc /IL=699
4. ANALYSIS
4.1. Introduction
Harmonics analysis was based on measurements collected for both currents and
voltages. The measurements were carried out as follows:
1. Voltage harmonics measurement data measured at the PCC of the following
buses:
18
4.2. Analysis
4.2.1.
This is the most critical information in the analysis of harmonics. The acceptance criteria
for the harmonic study according with the IEEE 519 standard (Table 1) are:
1. Maximum total voltage distortion THDV : 5%;
2. Maximum voltage distortion for each harmonic Vh : 3%;
Summary of all harmonics measurement data are given in Table 3. The study showed that
all the measured voltage harmonics at the plant comply with the IEEE 519 standard; the
highest THDV was only 3.03% and it is well below the 5% limit of the standard; this
maximum THD was recorded at the PCC SB5141A (TR5154-2, in train#4 Substation
SS51 at the 6.6kV level). It is worth to note that this distortion is at the point of coupling
with the Variable Speed Constant Frequency (VSCF) and was recorded on November
25th 2009. This VSCF indicated some concerns in the current harmonics compliance, and
is further discussed below.
19
Figure 3: Voltage & current waveforms at 6.6kV PCC : TR5154-2 with THDV= 3.03%
(while the VSCF is connected to the PCC and generating power to the network).
4.2.2.
Methodology:
Unlike the voltage harmonic limits of the IEEE 519 standard, the current harmonic limits
depend on the short circuit level of the system they are being injected into. The limit for
the current harmonics according with the IEEE 519 (Table2) depends on (Isc/IL): ratio of
the short circuit current (Isc) available at the PCC to the maximum load current (IL).
In the current harmonics study, we should be selective as it is impractical to measure at
all loads. Sometimes current harmonic distortion can be assessed through simple
inspection of the types of loads. All this requires is familiarity with the characteristic
harmonic spectrum of each type of common nonlinear load. However, harmonics
measurement is essential to verify their compliance with the IEEE519 standards. These
current harmonic measurement data are useful for some of these nonlinear loads that may
need designing suitable harmonic filters. This involves direct measurements at selected
locations for example, the point of common coupling (PCC) and the node where
nonlinear loads are connected.
20
We started the measurements by emphasis on the nonlinear high power loads which
consist of the Mega- drives called VDFs, AFDs or simply drives. Given that the power
quality analyzer (PQA) instruments provide measurement of the THD for both current
and voltage quantities, and in order to compare results against the IEEE standard, it was
necessary to compute the TDDI from the THDI, IL, I1, and Isc. Since the TDDI is always
less or equal than THDI, the followings procedure for current harmonics analysis is
adopted and applied in Table 3:
Case 1. THDI and all individual harmonics are less than the minimum of the
standard limits (for the strictest limit applicable to ISC/IL<20). In this case,
compliance with the standards is surely met and no further analysis is
needed.
Case 2. The measured load current is close to the rated current (I1IL which means
that TDDITHDI). If THDI or/and individual harmonic(s) are larger than
the maximum of the standard limits (for the limit applicable to
ISC/IL>1000), then there is violation of the IEEE 519 standards and no
further calculation is needed.
Case 3. Above cases are not applicable. In this case, we proceed as follows:
i. The ratio ISC/IL is determined to identify the appropriate row in
Table 2.
ii. TDDI is determined: TDDI= THDI(I1/IL).
iii. Determine harmonic current distortion in percent of IL from (Ih/I1)
which is PQA-measured value: Ih/IL= (Ih/I1)(I1/IL).
iv. Use the computed values in (ii) and (iii) to compare distortion to
the IEEE limits (Table 2). The example shown below illustrates the
applied method.
Analysis:
As illustrated in Table 3 the measurements show that the mega drives, whether VSI type
(without filters) or LCI type (with filters) used for the helper motors of the compressors,
are complying with the IEEE519 standards. This is a reassuring result as these drives are,
currently, the largest non-linear loads. From the table, we note for example that the THDI
21
values for VFDs connected to TR5342, TR5343 and TR5344 are 3.07%, 1.75% and
2.89% respectively. These values are complying even with the strictest limits of the TDDI
(<5%). However we note that the 11th harmonics (I11/I1=2.52% ) of the TR5342 drive is
larger than the strictest limit (<2%). In order to verify the compliance with the IEEE 519
standards we proceed as explained in case 3 above. At the 33kV PCC SB0221 where this
VFD drive is connected, Isc=33.3kA [4], assuming a typical power factor of 0.85, the
value of IL is estimated from the rated power as follows:
12
3
cos
33.3 10
247
33
10
10
0.85
247
135
Given the actual value of Isc/IL, the 4th row of the IEEE519 standards Table 2 should be
used. The THDI is well below the 15% limit for TDDI and the 11th harmonic of the
current is also well below the 5.5% limit. It is obvious that this drive is complying with
the standards. Similar analysis for other two drives (connected through TR5343 &
TR5344) and the compliance with the IEEE 519 standards is confirmed. The same
method was applied to all measured points; the results confirmed compliance with the
standards except for the following VSCF case discussed below. Other remarks are given
below for the UPS.
The VSCF is driven by a hydraulic turbine to generate power. This turbine operates on
recovered heat from the wasted heat recovery unit; this recovered heat supply depends on
plant operating condition, and therefore the VSCF is not continuously synchronized with
the network. During the data collection, the VSCF was operating and delivering power
through a transformer to the 6.6kV bus. As was shown in the voltage harmonics study
section, the dominant harmonic of the generated voltage from the VSCF at the PCC is the
48th harmonic which is a relatively high frequency component (Figure 3). This highest
voltage harmonic component (2.66%) was recorded on November 25th 2009. Although
this component is below the 3% limit of the IEEE standard, this was an unexpected
phenomenon that has led the team to investigate the sources of these harmonics by
22
carrying more measurements where VSCF are not connected to the bus. This has pointed
out to the fact that the 48th harmonic was not load-injected distortion but rather VSCFgenerated. This voltage harmonic component induced a current with the similar
harmonics content where the dominant harmonic was the 48th (see Figure 3). The IEEE
standard stipulates that the first row of Table 2 must be applied for all generators
regardless of the actual value of Isc/IL. As shown in Table 3 and after processing all the
data, the results indicate no violation at the TDDI level. However, the 48th harmonic
component of the current is beyond the limits for TR5154-2 (I48/IL=2.16%>0.3%) and
TR5155-2 (I48/IL=2.24%>0.3%), both of which are connected to the VSCF generators.
This harmonic component is most likely caused by the VSCF; this may be substantiated
by the following reasons: (a) the non-linear loads at the plant are not expected to inject
this 2.4 kHz component (48th harmonic); (b) measurements at substations where no
VSCF are connected show no presence of such harmonic (see data for TR5241A,
TR5241B, TR5441A and TR5441B in Table 3). This could be further confirmed by
measurement using the PQA, as this is capable distinguishing the outflow and inflow
harmonics. Unfortunately, many of the measurements taken including these taken around
the VSCF have been carried out by technicians without proper training. Thus the
collected data is adequate for evaluating harmonics but could not be used to precisely
determine source of injected harmonics.
We note that, although not violating the TDDI limits of the IEEE standard in all cases
except for one (UPS0171A in SS01), the UPS and battery chargers used in the plant are
exhibiting very high THDI (in some cases around 50%). The reason the TDDI limits are
not generally violated is because these units are operating well below their rated power.
Care must be taken in future in case the load of these units is increased, as this would
raise the TDDI to levels that may violate IEEE limits.
Harmonics Distortion and individual harmonics) at the various PCC (33kV, 6.6kV and
415V) meet the standard. Almost the same goes for the Total Demand Distortion (TDD)
for the current. However we note that, in some cases, the individual harmonic current
violates the IEEE limit especially around the VSCF. From harmonics point of view, this
VSCF generator is the weakest unit in the studied network; it is recommended that
solutions to mitigate harmonics generated by these units be considered. Although so far
this did not cause any problem to the LNG plant as the generated harmonics are
intermittent and therefore the better way to deal with it is to report findings to the
manufacturer in order to fix this within the equipment itself. The UPS and battery
chargers exhibit high THDI (in some cases around 50%). The reason the TDDI limits are
not generally violated is because these units are operating well below their rated power.
Care must be taken in future in case the load of these units is increased, as this would
raise the TDDI to levels that may violate IEEE limits.
It is noted that some 415 buses are not balanced from the point of view linear versus nonlinear loads. It is recommended that this is taken into consideration in future expansion,
as significant unbalance may result in violations harmonics standards.
6. REFERENCES
[1] Francisco C. De La Rosa, Harmonics and Power Systems Taylor & Francis
Group, LLC CRC Press, 2006.
[2] IEEE 519 Standard : Reference Standard
[3] Mohan, Undeland and Robbins Power Electronics: Converters, Application and
Design,. Published by John Wiley & Sons, 1989, 667 pages.
[4] RGX-S-91-2181-020Rev2- Electrical Network Studies-Short Circuit
24