Substation Automation
Products Training

Substation Automation Products 2007-09-11


1

REB 670
Busbar Protection IED

ABB LtdBangalore., 2007

REB 670 Training

Substation Automation Products 2007-09-11


2

Application Areas for REB 670

Centralized Busbar
Protection from 4 up to 24
CT inputs

Differential, BFP & Non-Dir


OC Protection for:
Busbars
Meshed corners,

ABB LtdBangalore., 2007

Substation Automation Products 2007-09-11


3

T-protection

Three-Phase Terminal; 4/8 Bays- Double Zone

REB 670; 3Ph


2 Zones (A & B);
8 Bays

Application Areas:
Smaller Buses (up to 8 CTs per zone)
Single Busbar Stations (with Transfer Bus)
1 Breaker Stations
Double Busbar Stations (with Transfer Bus)
Zone Interconnection included in the design

ABB LtdBangalore., 2007

No switching in CT secondary circuits

Substation Automation Products 2007-09-11


4

REB 670 3- Ph; BBP, BFP & EnFP for single buses

ZA

ZB

ZA

Single Bus with bus tie CB


up to 3/7 feeder bays on each side

Single Busbar
up to 4/8 feeder bays

ZA
ZA

ZB

ZB

ABB LtdBangalore., 2007

H type station with bus-section CB


or sectionalizing disconnector
Alternative CT Location

Substation Automation Products 2007-09-11


5

T connections

REB 670 3- Ph, BBP, BFP, EnFP for 1 CB stations


ZA

ZB

1 Breaker Stations
up to 4 diameters

ZA

.. .
ZB

ABB LtdBangalore., 2007

1 Breaker Stations
up to 8 diameters

Substation Automation Products 2007-09-11


6

REB 670 3- Ph; BBP, BFP & EnFP for Double CB stations

ZA

.. .
ZB

Double Breaker Station


up to 8 feeders

ABB LtdBangalore., 2007

Alternative CT Location

Substation Automation Products 2007-09-11


7

REB 670 3- Ph; BBP, BFP & EnFP for double buses
ZA

.. .

ZB

Double Bus with bus-coupler CB


and up to 6/7 feeder bays
ZA

.. .
ZB

.. .

Transfer Bay

Transfer Bus

ABB LtdBangalore., 2007

.. .

Isolator replica in REB 670*1.0


by CAP 531 Configuration

Double Busbars with bus coupler CB and Transfer Bus


up to 6/7 feeder bays
Substation Automation Products 2007-09-11
8

Optional Measuring Point

Scheme Layout for Double Busbar; 2 Zones/7 feeders


700

ABB

EQUIPMENT INCLUDED in the PANEL:

ABB LtdBangalore., 2007

1 pcs 3 phase, Busbar protection terminal REB 670*1.0


- two differential zones
- check zone
- eight BFP relays
- eight OC feeder backup protection (EnFP)
- internal disconnector replica logic
- internal individual bay tripping logic
- disconnector status supervision

Substation Automation Products 2007-09-11


9

Single-Phase Terminal; 12/24 Bays- Double Zone


REB 670; Ph-L1
2 Zones (A & B);
24 Bays

REB 670; Ph-L2


2 Zones (A & B);
24 Bays

REB 670; Ph-L3

ABB LtdBangalore., 2007

2 Zones (A & B);


24 Bays

Substation Automation Products 2007-09-11


10

Application Areas:
Bigger Buses (up to 12/24 bays per zone)
Single Busbar Stations (with Transfer Bus)
1 Breaker Stations
Double Busbar Stations (with Transfer Bus)
Load Transfer is included into the design
3 Terminals required for complete scheme
LDCM available to share binary IO

No switching in CT secondary circuits

REB 670 1- Ph; BBP, BFP & EnFP for single buses

ZA

.. .

ZA

Single Bus
up to 12/24 feeder bays

ABB LtdBangalore., 2007

ZA

.. .

.. .

11

.. .

Single Bus with bus-section disconnector


up to 12/24 feeder bays (i.e. 12+12; 16+8 etc.)

ZB

Single Bus with bus-section CB, up to


11/23 feeder bays (i.e. 12+11; 10+13 etc.)

Substation Automation Products 2007-09-11

.. .

ZB

ZA

.. .

.. .

ZB

Single Bus with bus-section CB


up to 11/23 feeder bays on each side

REB 670 1- Ph; BBP applications for 1 CB stations

ZA

ZA

.. .
ZB

ABB LtdBangalore., 2007

1 Breaker Stations
up to 6 / 12 diameters

Substation Automation Products 2007-09-11


12

.. .
ZB

1 Breaker Stations
up to 12 / 24 diameters

REB 670 1- Ph, Complete BBP, BFP & EnFP for 1 CB Stations!

ZA

.. .
ZB

ABB LtdBangalore., 2007

Bus Diff, CB Fail & EnFP


1 Breaker Stations
up to 4/8 diameters

Substation Automation Products 2007-09-11


13

REB 670 1- Ph; BBP, BFP & EnFP for Double CB stations

ZA

ZA

.. .

.. .

ZB

ZB

Double Breaker Station


up to 6 / 12 feeders

Double Breaker Station


up to 12 / 24 feeders

ABB LtdBangalore., 2007

Alternative CT Location

Substation Automation Products 2007-09-11


14

REB 670 1- Ph; BBP, BFP & EnFP for double buses

ZA

.. .

ZB

Double Bus with bus-coupler CB


up to 22/23 feeder bays

ABB LtdBangalore., 2007

Isolator replica in REB 670*1.0


by CAP 531 Configuration

Substation Automation Products 2007-09-11


15

Optional Measuring Point

REB 670 1- Ph; BBP, BFP & EnFP for double bus & transfer
ZA

.. .
ZB

.. .

Transfer Bus

.. .
Combined Bus-Coupler
& Transfer Bay

ZA

.. .
ZB

.. .

Bus-Coupler Bay
Transfer Bay

Transfer Bus

.. .

ABB LtdBangalore., 2007

Isolator replica in REB 670*1.0


by CAP 531 Configuration

Double Busbars with Transfer Bus


up to 22/23 feeder bays
Substation Automation Products 2007-09-11
16

Scheme Layout for Double Busbar; 2 Zones/22 feeders


700

ABB

EQUIPMENT INCLUDED in the PANEL:

ABB LtdBangalore., 2007

3 pcs 1 phase, Busbar protection terminal REB 670*1.0


- two differential zones
- check zone
- 24 BFP relays
- 24 OC feeder backup protection (EnFP)
- internal disconnector replica logic
- internal individual bay tripping logic
- disconnector status supervision

Substation Automation Products 2007-09-11


17

REB 670 1- Ph; BBP, BFP & EnFP for double buses
Main 2

Main 1

.. .
Reserve 1

.. .
Reserve 2

Four Zone Double Bus with two bus-coupler CBs and two
bus-section CBs and up to 20/21 feeder bays on each station side

Main 1

.. .

ABB LtdBangalore., 2007

Reserve 1

Main 2

.. .
Reserve 2

Four Zone Double Bus with two BC-CBs one BS-CB and one sectionalizing
disconnector with up to 18-20 feeder bays in the whole station
Substation Automation Products 2007-09-11
18

Optional Measuring Point

REB 670*1.0; 1-ph version Summation Principle

REB 670; 1 Ph
2 Zones (A & B);
24 Bays

+ N times

ABB LtdBangalore., 2007

N 8
Substation Automation Products 2007-09-11
19

Buses up to 24 bays per zone


Single Busbar
1 Breaker Systems
Double Busbar
Same applications possible as for 1Ph solution
Software Driven Zone Selection
Cost effective Solution

UserFriendliness

Pre-configured REB670 ready to use

ABB LtdBangalore., 2007

Substation Automation Products 2007-09-11


20

Single zone applications


Two zone applications without
need for any zone selection
(e.g. 1 CB stations)
Double busbar stations with zone
selection using busbar
disconnectors a & b aux contacts
Double busbar stations with zone
selection using only busbar
disconnectors b aux contact
Direct replacement for RED 521

ABB LtdBangalore., 2007

Available Configurations X01, X02 & X03

X01 = Just BBP for simple stations layouts (i.e. 1 CB, Double
Breaker, Single Breaker, or for double busbar-single breaker
stations where Zone Selection is done by using just b contacts).
Available for all five versions A20, A31, B20, B21 & B31.
Direct replacement for RED 521

X02 = Just BBP for double busbar-single breaker stations where


Zone Selection is done by using a&b contacts from disconnectors
and breakers. Available for versions A31, B21 & B31

X03 = BBP with BFP, EnFP & OCP for double busbar-single
breaker stations where Zone Selection is done by using a&b
contacts from disconnectors and breakers. Available for versions
A31, B21 & B31

For other station layouts or functionality CAP 531 configuration shall


be arranged by the end user.

Make country/end-customer specific solution

Substation Automation Products 2007-09-11