ENGINEERING AIR HANDLING PRODUCT

January 2011

CATALOGUE MSA (A)

GENERAL INFORMATION

The achieved fan performances can differ from the test


performances shown on the subsequent due to two main
effects:Normal
Operation
Range

A.) The encroachment of irregular or abrupt changes within the


system close to the fan. If good design practice is followed,
then the fan will receive nearly uniform air into its inlet
and discharge its air flow in an almost ideal pattern.
If this is achieved the fan will perform to its expected level.
B.) Changes to the internal elements of the fan: e.g. large junction
boxes on motors, belt drive stacks or excessive blade tip
clearances.
Tests were conducted to assess these effects and the
generalised impact is shown below for fan selections made
within the normal operating region over a wide
blade-angle range.
Massive Fan Industries Sdn. Bhd. certifies that
the Axial Flow Fan-MSA series shown herein
are licensed to bear the AMCA Seal.
The ratings shown are based on tests and
procedures performed in accordance with
AMCA Publication 211 and AMCA Publication
311 and comply with the requirements of the
AMCA Certified Ratings Program.

Type of installation
The main difference between the below
Standards, is the installation Types A, B, C
and D such that, if a fan unit is designed

for use in any one of the arrangements,


the variation in performance should be
established and shown.

Type A
Free inlet
Free outlet

Type C

Ducted inlet
Free outlet

Ducted inlet
Ducted outlet

Type B
Free inlet
Ducted outlet

Type D

Forms of Running
The main series of test were conducted on Form B units and comparative tests were carried
out on Form A units.
Resultant performance differences occur mainly on the outlet side of the fan, as correct
practice should result in the presence of the duct inlet cone on the fan inlet.
* Fan performance with installation type D, Form B are licensed by AMCA International only.
Installation Form A

Installation Form B
Air flow variation
As show on
performance
curves

B&D

B&D

Air flow variation


As show on
performance
curves

A&C

Air flow variation


As show on
performance
curves

Air flow variation


A&C

qv x 1.02
PsF x 1.04

as compared
to type ' D'
performance

Direction Of Air Flow


The standard direction of
air flow is Form 'A','AD' or
'AU'. However, Form 'B', 'BD'
or 'BU' flow can be
supplied if required.
These forms of running
are as follows :

Form A

Form AD

Form AU

Form B

Form BD

Form BU

Tip Clearances

Windmilling Losses

The performance is shown for the standard


radial tip clearance/diameter percentage of
0.25. If tip clearances are increase then duty
conditions should be adjusted as follows prior
to selection on the applicable curve.

It is sometimes necessary to have two fans in


series so as to offer a run and standby
capability. In such a condition the windmilling
(or non energised fan/motor unit) creates a
relative pressure loss which is a function of its
blade angle.

Tip clearance/ = qv x 1.01, PsF x 1.02


diameter 0.5%

Blade angle
o

Up to 20

Tip clearance/ = qv x 1.04, PsF x 1.08


diameter 0.75%

Tip clearance/ = qv x 1.06, PsF x 1.12


diameter 1.0%

k'loss
6.0

20 ~ 30

3.0

Over 30o

2.0

Pressure loss
'k' x Pdf

* Performance for two fans in series are not licensed by


AMCA International.

* Performance adjusted with this factor for tip clearances


are not licensed by AMCA International.

Multi-Stage Axial Flow Fan


A two stage fan will develop approximately
two times the pressure of a single-stage fan of
equal diameter and speed.

A two-stage contra-ratating fan comprises


assembling in series two (or more single-stage)
non-guide-vane fans with impellers rotating in
opposite direction. The contra-rotation of the
impellers recovers rotational losses and
converts the rotational energy into fan
pressure.

This is an economical system because the


component stages are standard fans
independently driven by standard motors.

There are two ways to design a two-stage axial-flow fan:


with two fan wheels rotating in the same rotation

with two counter rotating fan wheels

Motor

Motor

Other Fan Arrangement

Standard Accessory Losses

Some required duty pressure should be


adjusted to account for the below gains /
losses before making a selection on the
standard performance curves.
Fan
Arrangement

Effect on
pressure
capability

Motor

k'loss
Low loss inlet cone

Effect on
Total
sound level

Single stage fan unit with


downstream guide vanes

x 1.25

Two stage fan unit with


intermediate straightener

x 2.00

+ 3dB

Contra-rotating two
stage fan unit

x 2.4

+ 8 to 10dB

Bifurcated fan unit

x 0.7

0.2 Form 'A'


0.38 Form B

k'loss

+ 1dB

Flat 'finger type' guard

0.75

k'loss
Coned motor side
guard

+ 2dB

0.4

k'loss

* Performance for single stage fan unit with downstream


guide vanes, two stage fan unit with intermediate
straightener, contra-retating two stage fan unit and
Bifurcated fan unit are not licensed by AMCA
International.

Non return dampers


(airstream) operated

0.3 ~ 0.4

* Performance for accessory losses are not licensed by


AMCA International.

M.S AXIAL FANS PRODUCT RANGE


Direct-Drive MSA Series
These fans are normally with short or long casing.
The motor leads (protected by a flexible conduit)
are taken to a weather-proof terminal box which
is welded to the fan casing.

Glass Reinforced Nylon Impeller


Massive Fan GRN blades the latest design for excellent performance
which compromised with safe operating temperature range from
-40oC to 100oC, higher strength and stiffness to accept high speed.
GRN blades are formulated to
resist creep and fatigue
under mechanical stress
and load.

Glass Reinforced Polypropylene Impeller


Glass Reinforced Polypropylene fan (GRP) blades resist chemical
attack & staining and are unaffected by aqueous solutions of
inorganics salts or mineral acids alkali and gases, such as
Chlorinated hydro-carbon, ketones, aromatic and Alcohols.
A limited heat resistance from
temperature -40oC to 70oC,
but heat-stabilized grades
are available for applications
requiring prolonged use
at elevated temperature.

Aluminium
Massive fan aluminium fan blades have greater strength, suitable
for higher fan tip speed up to 100m/sec, and temperature up to
200oC continuous operations. Proven for use in emergency smoke
spill operation and other
non corrosive fume
extraction.

SMOKE SPILL STANDARD

Our smoke spill fans have been tested to Standard AS 4429:1999 and has been
approved for use by the relevant Malaysia Authority (Jabatan Bomba dan Penyelamat).

SMOKE SPILL STANDARD

DIMENSIONS DATA
LONG CASING
D

MODEL
500

A
500

B
545

C
585

D
400

N
12

O
12

WEIGHT (KG)
18

560

560

604

640

500

12

12

22

630

630

676

710

500

12

12

24

710

710

756

795

500

16

12

40

800

800

845

885

560

16

12

49

900

900

960

1005

630

16

12

66

1000

1000

1056

1110

630

16

12

73

1120

1120

1176

1230

900

20

12

135

1250

1250

1315

1360

1000

20

12

170

SHORT CASING
D

MODEL
500

A
500

B
545

C
585

D
285

NO
12

O
12

WEIGHT (KG)
11

560

560

604

640

346

12

12

16

630

630

676

710

365

12

12

18

710

710

756

795

408

16

12

30

800

800

845

885

408

16

12

40

900

900

960

1005

495

16

12

51

1000

1000

1056

1110

550

16

12

57

1120

1120

1176

1230

650

20

12

96

1250

1250

1325

1360

700

20

12

147

M.S. AXIAL Model: 500 2P ( 2880RPM, TYPE D )


500/6

Fan Total Efficiency

Fan Absorbed Power, kW

Fan Static Pressure, Pa

2880 rpm

Performance certified is for installation type D- Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (Accessories).

SOUND DATA - 2880rpm


Blade Angle

25o

35o

50o

Ps [Pa]
0
185
347
466
0
189
367
473
0
249
398
474

63
102
102
104
106
101
101
104
106
105
105
107
110

125
105
105
107
109
104
104
107
109
108
108
110
113

Sound Power Level Lw, dB


250
500
1K
2K
103
92
90
87
103
92
90
88
103
95
91
89
106
102
97
94
104
93
90
88
105
92
91
89
103
95
92
91
107
103
97
94
108
95
92
96
108
95
93
95
108
95
93
97
109
95
94
98

4K
86
86
87
89
87
87
87
90
88
89
90
90

8K
83
83
83
84
83
83
83
84
85
86
86
86

LwA dB(A)
98
98
99
104
99
99
100
104
103
103
103
104

The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA International Standard 301. The A-weighted sound
ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D:
ducted inlet, ducted outlet. Ratings include the effects of duct end correction.

M.S. AXIAL Model: 500 4P ( 1450RPM, TYPE D )


500/6

Fan Total Efficiency

Fan Absorbed Power, kW

Fan Static Pressure, Pa

1450 rpm

Performance certified is for installation type D- Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (Accessories).

SOUND DATA - 1450rpm


Blade Angle

25o

35o

50o

Ps [Pa]
0
47
88
118
0
48
93
120
0
63
101
120

63
90
90
92
94
89
89
92
94
93
93
95
98

125
88
88
88
91
89
90
88
92
93
93
93
94

Sound Power Level Lw, dB


250
500
1K
2K
77
75
72
71
77
75
73
71
80
76
74
72
87
82
79
74
78
75
73
72
77
76
74
72
80
77
76
72
88
82
79
75
81
80
77
73
80
80
78
74
82
80
78
75
83
80
79
75

4K
68
68
68
69
68
68
68
69
70
71
71
71

8K
60
60
61
62
60
60
62
63
64
66
67
67

LwA dB(A)
79
79
80
85
80
80
81
85
83
84
84
85

The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA International Standard 301. The A-weighted sound
ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D:
ducted inlet, ducted outlet. Ratings include the effects of duct end correction.

M.S. AXIAL Model: 500 6P ( 960RPM, TYPE D )


500/6

Fan Total Efficiency

Fan Absorbed Power, kW

Fan Static Pressure, Pa

960 rpm

Performance certified is for installation type D- Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (Accessories).

SOUND DATA - 960rpm


Blade Angle

25o

35o

50o

Ps [Pa]
0
21
39
52
0
21
41
53
0
28
44
53

63
80
80
81
83
80
81
81
84
84
84
85
87

125
74
74
76
80
75
75
76
81
79
78
79
80

Sound Power Level Lw, dB


250
500
1K
2K
67
64
62
60
67
65
63
60
69
66
64
61
75
71
67
62
67
65
63
61
67
66
64
61
69
68
65
61
75
71
68
62
71
69
66
62
71
70
67
63
72
70
67
64
72
71
68
64

4K
54
54
55
56
54
54
55
56
57
59
60
60

8K
46
46
48
49
46
46
49
50
51
54
56
56

LwA dB(A)
68
68
69
74
69
69
70
74
72
73
73
74

The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA International Standard 301. The A-weighted sound
ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D:
ducted inlet, ducted outlet. Ratings include the effects of duct end correction.

10

M.S. AXIAL Model: 560 2P ( 2880RPM, TYPE D )


560/6

Fan Total Efficiency

Fan Absorbed Power, kW

Fan Static Pressure, Pa

2880 rpm

Performance certified is for installation type D- Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (Accessories).

SOUND DATA - 2880rpm


Blade Angle

25o

35o

50o

Ps [Pa]
0
197
375
514
0
237
406
593
0
249
473
635

63
102
102
102
103
102
102
101
103
104
103
104
106

125
105
105
105
106
105
105
104
106
107
106
107
109

Sound Power Level Lw, dB


250
500
1K
2K
104
94
93
90
102
93
92
90
103
93
92
92
103
107
99
96
105
96
93
91
104
95
93
91
104
94
93
93
104
107
98
96
108
97
95
99
107
97
95
98
106
97
96
98
107
99
97
101

4K
88
88
90
92
89
89
90
92
91
92
93
95

8K
85
86
87
87
87
86
87
88
88
89
89
90

LwA dB(A)
100
99
100
106
101
100
100
106
104
103
104
105

The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA International Standard 301. The A-weighted sound
ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D:
ducted inlet, ducted outlet. Ratings include the effects of duct end correction.

11

M.S. AXIAL Model: 560 4P ( 1450RPM, TYPE D )


560/6

Fan Total Efficiency

Fan Absorbed Power, kW

Fan Static Pressure, Pa

1450 rpm

Performance certified is for installation type D- Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (Accessories).

SOUND DATA - 1450rpm


Blade Angle

25o

35o

50o

Ps [Pa]
0
50
95
130
0
60
103
150
0
63
120
161

63
90
90
90
91
90
90
89
91
92
91
92
94

125
89
87
88
88
90
89
89
89
93
92
91
92

Sound Power Level Lw, dB


250
500
1K
2K
79
78
75
73
78
77
75
73
78
77
77
75
92
84
81
77
81
78
76
74
90
78
76
74
79
78
77
75
92
83
81
77
84
82
80
76
83
82
80
77
83
82
81
78
86
84
82
80

4K
70
71
72
72
72
71
72
73
73
74
74
75

8K
60
62
63
64
63
63
64
66
67
68
69
70

LwA dB(A)
81
81
82
88
82
82
83
88
85
86
86
88

The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA International Standard 301. The A-weighted sound
ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D:
ducted inlet, ducted outlet. Ratings include the effects of duct end correction.

12

M.S. AXIAL Model: 560 6P ( 960RPM, TYPE D )


560/6

Fan Total Efficiency

Fan Absorbed Power, kW

Fan Static Pressure, Pa

960 rpm

Performance certified is for installation type D- Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (Accessories).

SOUND DATA - 960rpm


Blade Angle

25o

35o

50o

Ps [Pa]
0
22
42
57
0
26
45
66
0
28
53
71

63
80
79
80
80
81
80
80
81
84
83
82
84

125
76
74
75
81
77
76
76
82
80
79
79
81

Sound Power Level Lw, dB


250
500
1K
2K
69
67
65
62
68
67
65
63
68
68
67
64
78
73
70
65
70
68
66
64
70
68
66
63
69
69
67
64
78
73
70
66
74
72
69
65
73
72
69
66
73
73
70
67
76
74
72
68

4K
55
57
58
58
58
57
58
60
60
61
62
63

8K
45
48
49
50
49
49
50
53
54
55
57
58

LwA dB(A)
70
70
72
76
71
71
72
76
74
75
75
77

The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA International Standard 301. The A-weighted sound
ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D:
ducted inlet, ducted outlet. Ratings include the effects of duct end correction.

13

M.S. AXIAL Model: 630 2P ( 2880RPM, TYPE D )


630/9

Fan Total Efficiency

Fan Absorbed Power, kW

Fan Static Pressure, Pa

2880 rpm

Performance certified is for installation type D- Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (Accessories).

SOUND DATA - 2880rpm


Blade Angle

25o

35o

50o

Ps [Pa]
0
284
564
918
0
324
792
993
0
362
785
997

63
103
102
102
105
105
105
104
106
110
109
109
111

125
106
105
105
108
108
108
107
109
113
112
112
114

Sound Power Level Lw, dB


250
500
1K
2K
100
103
99
96
99
103
98
96
99
102
98
97
109
107
106
104
102
105
101
97
101
105
99
97
102
104
102
99
109
106
107
104
105
110
106
101
104
110
104
101
103
110
104
101
114
110
106
104

4K
94
94
96
100
95
95
98
100
98
99
100
101

8K
94
94
94
94
94
93
94
95
95
95
95
96

LwA dB(A)
105
104
105
111
106
106
107
111
111
110
110
112

The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA International Standard 301. The A-weighted sound
ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D:
ducted inlet, ducted outlet. Ratings include the effects of duct end correction.

14

M.S. AXIAL Model: 630 4P ( 1450RPM, TYPE D )


630/9

Fan Total Efficiency

Fan Absorbed Power, kW

Fan Static Pressure, Pa

1450 rpm

Performance certified is for installation type D- Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (Accessories).

SOUND DATA - 1450rpm


Blade Angle

25o

35o

50o

Ps [Pa]
0
72
143
233
0
82
201
252
0
92
199
252

63
91
90
90
93
93
93
92
94
98
97
97
99

125
85
84
84
94
87
86
87
94
90
89
88
99

Sound Power Level Lw, dB


250
500
1K
2K
88
84
81
79
88
83
81
79
87
83
82
81
92
91
89
85
90
86
82
80
90
84
82
80
89
87
84
83
91
92
89
85
95
91
86
83
95
89
86
84
95
89
86
85
95
91
89
86

4K
79
79
79
79
79
78
79
80
80
80
80
81

8K
69
70
71
71
70
70
72
73
74
74
75
75

LwA dB(A)
87
87
88
93
89
88
90
94
93
92
93
94

The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA International Standard 301. The A-weighted sound
ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D:
ducted inlet, ducted outlet. Ratings include the effects of duct end correction.

15

M.S. AXIAL Model: 630 6P ( 960RPM, TYPE D )


630/9

Fan Total Efficiency

Fan Absorbed Power, kW

Fan Static Pressure, Pa

960 rpm

Performance certified is for installation type D- Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (Accessories).

SOUND DATA - 960rpm


Blade Angle

25o

35o

50o

Ps [Pa]
0
32
63
102
0
36
88
110
0
40
87
111

63
78
77
77
85
80
80
80
85
84
83
83
90

125
78
78
77
83
80
80
79
82
84
84
84
87

Sound Power Level Lw, dB


250
500
1K
2K
77
73
71
70
76
73
71
70
76
74
72
71
82
81
78
72
79
75
72
70
77
74
72
70
79
76
74
72
83
81
78
73
84
79
75
72
82
78
76
73
82
78
76
73
84
81
78
74

4K
64
65
65
65
65
64
66
67
67
67
68
68

8K
54
56
57
57
56
56
59
60
61
61
63
62

LwA dB(A)
77
77
77
82
78
77
79
83
82
81
82
83

The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA International Standard 301. The A-weighted sound
ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D:
ducted inlet, ducted outlet. Ratings include the effects of duct end correction.

16

M.S. AXIAL Model: 710 2P ( 2880RPM, TYPE D )


710/9

Fan Total Efficiency

Fan Absorbed Power, kW

Fan Static Pressure, Pa

2880 rpm

Performance certified is for installation type D- Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (Accessories).

SOUND DATA - 2880rpm


Blade Angle

25o

35o

50o

Ps [Pa]
0
339
690
974
0
414
955
1152
0
611
1038
1161

63
103
103
103
104
106
105
105
110
111
109
109
109

125
106
106
106
107
109
108
108
113
114
112
112
112

Sound Power Level Lw, dB


250
500
1K
2K
101
102
101
99
100
102
100
99
101
102
103
103
104
107
109
108
102
103
102
100
101
102
101
100
104
107
106
106
113
115
112
109
106
105
106
103
104
105
105
103
104
105
106
105
110
107
108
106

4K
97
97
100
103
97
98
102
104
101
102
104
105

8K
98
98
98
98
98
98
99
98
99
99
99
99

LwA dB(A)
106
106
109
113
107
107
112
117
111
110
111
113

The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA International Standard 301. The A-weighted sound
ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D:
ducted inlet, ducted outlet. Ratings include the effects of duct end correction.

17

M.S. AXIAL Model: 710 4P ( 1450RPM, TYPE D )


710/9

Fan Total Efficiency

Fan Absorbed Power, kW

Fan Static Pressure, Pa

1450 rpm

Performance certified is for installation type D- Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (Accessories).

SOUND DATA - 1450rpm


Blade Angle

25o

35o

50o

Ps [Pa]
0
86
175
247
0
105
242
292
0
155
263
294

63
91
91
91
92
94
93
93
98
99
97
97
97

125
86
85
86
89
87
86
89
98
91
89
89
95

Sound Power Level Lw, dB


250
500
1K
2K
87
86
84
82
87
85
84
82
87
88
88
85
92
94
93
88
88
87
85
82
87
86
85
83
92
91
91
87
100
97
94
89
91
88
86
90
90
88
87
90
91
90
89
90
93
91
90
92

4K
83
83
83
83
83
83
84
83
84
84
84
84

8K
73
74
75
75
74
74
76
75
79
79
79
79

LwA dB(A)
90
90
92
97
91
91
95
99
94
94
95
96

The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA International Standard 301. The A-weighted sound
ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D:
ducted inlet, ducted outlet. Ratings include the effects of duct end correction.

18

M.S. AXIAL Model: 710 6P ( 960RPM, TYPE D )


710/9

Fan Total Efficiency

Fan Absorbed Power, kW

Fan Static Pressure, Pa

960 rpm

Performance certified is for installation type D- Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (Accessories).

SOUND DATA - 960rpm


Blade Angle

25o

35o

50o

Ps [Pa]
0
38
77
108
0
46
106
128
0
68
115
129

63
79
78
79
81
81
80
82
89
85
83
83
87

125
77
77
77
82
78
77
82
90
91
80
80
82

Sound Power Level Lw, dB


250
500
1K
2K
77
76
74
74
77
76
74
74
79
79
77
75
84
85
81
76
78
77
74
74
77
77
75
74
82
82
80
76
89
86
82
76
82
80
78
76
81
80
78
76
82
82
80
77
84
83
81
77

4K
68
69
69
69
69
69
70
69
72
72
72
72

8K
58
60
61
61
60
60
62
61
67
67
67
67

LwA dB(A)
80
80
82
86
80
80
84
88
83
83
85
86

The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA International Standard 301. The A-weighted sound
ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D:
ducted inlet, ducted outlet. Ratings include the effects of duct end correction.

19

M.S. AXIAL Model: 710 8P ( 720RPM, TYPE D )


710/9

Fan Total Efficiency

Fan Absorbed Power, kW

Fan Static Pressure, Pa

720 rpm

Performance certified is for installation type D- Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (Accessories).

SOUND DATA - 720rpm


Blade Angle

25o

35o

50o

Ps [Pa]
0
21
43
61
0
26
60
72
0
38
65
73

63
71
70
71
74
72
71
74
83
76
74
74
80

125
72
72
72
77
73
72
77
85
75
75
75
77

Sound Power Level Lw, dB


250
500
1K
2K
71
69
67
68
70
69
67
68
73
73
70
68
79
78
73
68
72
70
67
68
71
70
68
68
76
76
72
69
82
79
74
68
76
73
71
69
75
73
72
69
76
75
74
69
78
76
75
69

4K
58
59
60
60
59
59
61
60
64
64
64
64

8K
48
50
52
52
50
50
53
52
59
59
59
59

LwA dB(A)
73
73
75
78
73
73
77
80
76
76
78
79

The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA International Standard 301. The A-weighted sound
ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D:
ducted inlet, ducted outlet. Ratings include the effects of duct end correction.

20

M.S. AXIAL Model: 800 4P ( 1450RPM, TYPE D )


800/9

Fan Total Efficiency

Fan Absorbed Power, kW

Fan Static Pressure, Pa

1450 rpm

Performance certified is for installation type D- Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (Accessories).

SOUND DATA - 1450rpm


Blade Angle

25o

35o

50o

Ps [Pa]
0
87
198
353
0
91
210
340
0
186
301
354

63
96
95
95
101
96
96
95
99
101
100
100
102

125
88
88
89
112
88
88
89
101
93
92
96
106

Sound Power Level Lw, dB


250
500
1K
2K
91
89
87
83
92
88
87
84
93
92
92
89
101
97
94
89
93
90
88
84
93
89
88
85
94
91
91
88
106
100
97
92
91
88
98
93
92
90
98
94
94
91
100
97
97
93
103
101

4K
87
87
87
83
89
89
88
85
86
86
87
87

8K
77
78
79
75
79
79
79
78
79
82
83
82

LwA dB(A)
93
93
96
101
94
94
96
103
97
98
100
103

The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA International Standard 301. The A-weighted sound
ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D:
ducted inlet, ducted outlet. Ratings include the effects of duct end correction.

21

M.S. AXIAL Model: 800 6P ( 960RPM, TYPE D )


800/9

Fan Total Efficiency

Fan Absorbed Power, kW

Fan Static Pressure, Pa

960 rpm

Performance certified is for installation type D- Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (Accessories).

SOUND DATA - 960rpm


Blade Angle

25o

35o

50o

Ps [Pa]
0
38
87
155
0
40
92
149
0
82
132
155

63
82
82
82
99
82
82
82
91
87
86
89
85

125
81
82
83
94
82
82
83
95
87
87
90
94

Sound Power Level Lw, dB


250
500
1K
2K
81
79
76
76
81
79
76
77
83
83
81
79
90
86
82
76
82
80
77
78
82
80
77
78
83
82
80
79
93
89
85
79
86
83
80
78
87
84
82
79
89
86
83
80
93
90
86
80

4K
72
73
73
69
74
74
74
72
73
75
76
75

8K
62
64
65
61
64
64
65
65
66
71
72
70

LwA dB(A)
82
83
86
88
84
84
86
91
86
87
89
91

The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA International Standard 301. The A-weighted sound
ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D:
ducted inlet, ducted outlet. Ratings include the effects of duct end correction.

22

M.S. AXIAL Model: 800 8P ( 720RPM, TYPE D )


800/9

Fan Total Efficiency

Fan Absorbed Power, kW

Fan Static Pressure, Pa

720 rpm

Performance certified is for installation type D- Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (Accessories).

SOUND DATA - 720rpm


Blade Angle

25o

35o

50o

Ps [Pa]
0
21
49
87
0
22
52
84
0
46
74
87

63
73
73
74
96
73
73
74
86
78
77
91
91

125
76
77
78
86
78
78
79
91
83
83
85
88

Sound Power Level Lw, dB


250
500
1K
2K
74
72
68
72
73
72
69
72
77
77
74
72
82
79
74
68
75
73
69
74
74
73
70
74
76
76
73
73
85
82
77
70
78
76
73
71
79
77
75
71
82
79
76
72
86
82
78
72

4K
62
63
64
60
64
64
64
63
64
67
68
67

8K
52
54
56
52
54
54
55
56
57
63
64
62

LwA dB(A)
76
76
79
81
77
78
79
83
78
80
81
84

The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA International Standard 301. The A-weighted sound
ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D:
ducted inlet, ducted outlet. Ratings include the effects of duct end correction.

23

M.S. AXIAL Model: 900 4P ( 1450RPM, TYPE D )


900/12

Fan Total Efficiency

Fan Absorbed Power, kW

Fan Static Pressure, Pa

1450 rpm

Performance certified is for installation type D- Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (Accessories).

SOUND DATA - 1450rpm


Blade Angle

25o

35o

50o

Ps [Pa]
0
14 0
272
391
0
147
293
439
0
153
314
460

63
97
97
96
96
99
98
97
98
105
104
105
103

125
88
88
89
93
91
90
89
96
95
94
95
107

Sound Power Level Lw, dB


250
500
1K
2K
98
95
92
87
98
93
93
89
99
100
99
96
103
104
101
96
100
95
93
88
100
94
92
89
102
99
97
93
106
106
101
96
107
92
98
95
106
92
97
95
107
94
99
97
109
97
105
102

4K
94
95
94
90
93
93
92
90
95
91
91
92

8K
87
86
84
81
89
87
85
82
87
85
86
86

LwA dB(A)
99
100
104
105
100
99
102
107
103
102
103
107

The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA International Standard 301. The A-weighted sound
ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D:
ducted inlet, ducted outlet. Ratings include the effects of duct end correction.

24

M.S. AXIAL Model: 900 6P ( 960RPM, TYPE D )


900/12

Fan Total Efficiency

Fan Absorbed Power, kW

Fan Static Pressure, Pa

960 rpm

Performance certified is for installation type D- Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (Accessories).

SOUND DATA - 960rpm


Blade Angle

25o

35o

50o

Ps [Pa]
0
61
119
172
0
64
128
193
0
67
138
202

63
83
83
83
85
85
84
83
88
90
89
90
96

125
85
85
86
90
87
87
88
93
93
92
93
99

Sound Power Level Lw, dB


250
500
1K
2K
88
84
80
82
87
84
82
84
91
91
88
86
95
93
89
83
89
85
81
82
88
84
81
82
92
89
86
83
97
94
89
83
94
87
84
85
93
87
84
82
94
89
86
83
98
94
90
85

4K
81
81
79
76
82
80
79
76
81
78
79
79

8K
74
72
69
67
78
74
72
68
73
72
74
73

LwA dB(A)
89
89
93
94
89
89
91
95
92
91
92
96

The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA International Standard 301. The A-weighted sound
ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D:
ducted inlet, ducted outlet. Ratings include the effects of duct end correction.

25

M.S. AXIAL Model: 900 8P ( 720RPM, TYPE D )


900/12

Fan Total Efficiency

Fan Absorbed Power, kW

Fan Static Pressure, Pa

720 rpm

Performance certified is for installation type D- Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (Accessories).

SOUND DATA - 720rpm


Blade Angle

25o

35o

50o

Ps [Pa]
0
35
67
97
0
36
72
108
0
38
78
113

63
73
73
74
78
76
75
74
81
80
79
80
92

125
83
83
84
88
85
85
87
91
92
91
92
94

Sound Power Level Lw, dB


250
500
1K
2K
80
77
72
79
78
78
74
80
85
84
81
79
89
86
81
75
80
78
73
78
79
77
74
78
84
82
78
77
91
86
81
75
83
80
77
80
82
80
77
76
84
82
79
76
90
87
82
77

4K
72
71
69
66
74
72
70
67
72
70
71
71

8K
65
62
59
57
70
66
63
59
64
64
66
65

LwA dB(A)
82
83
86
87
83
82
84
87
85
83
85
88

The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA International Standard 301. The A-weighted sound
ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D:
ducted inlet, ducted outlet. Ratings include the effects of duct end correction.

26

M.S. AXIAL Model: 1000 4P ( 1450RPM, TYPE D )


1000/12

Fan Total Efficiency

Fan Absorbed Power, kW

Fan Static Pressure, Pa

1450 rpm

Performance certified is for installation type D- Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (Accessories).

SOUND DATA - 1450rpm


Blade Angle

25o

35o

50o

Ps [Pa]
0
153
330
549
0
279
416
562
0
158
372
556

63
100
98
96
97
100
97
96
100
105
104
102
102

125
91
89
88
93
94
92
92
98
95
95
94
106

Sound Power Level Lw, dB


250
500
1K
2K
100
97
95
91
100
95
95
91
102
100
100
96
107
107
102
96
101
97
95
91
101
99
99
95
103
105
103
98
112
106
102
97
107
100
93
98
107
93
99
98
109
95
102
100
112
99
108
105

4K
93
93
93
90
94
95
94
91
93
90
91
93

8K
93
93
91
84
95
93
89
83
92
87
87
87

LwA dB(A)
101
101
104
107
102
104
107
108
104
103
105
110

The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA International Standard 301. The A-weighted sound
ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D:
ducted inlet, ducted outlet. Ratings include the effects of duct end correction.

27

M.S. AXIAL Model: 1000 6P ( 960RPM, TYPE D )


1000/12

Fan Total Efficiency

Fan Absorbed Power, kW

Fan Static Pressure, Pa

960 rpm

Performance certified is for installation type D- Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (Accessories).

SOUND DATA - 960rpm


Blade Angle

25o

35o

50o

Ps [Pa]
0
67
145
241
0
122
183
247
0
69
163
244

63
86
84
82
86
87
85
85
90
91
90
88
95

125
87
87
87
92
89
88
90
97
94
93
94
101

Sound Power Level Lw, dB


250
500
1K
2K
90
87
84
83
89
86
84
83
92
91
89
85
98
95
89
83
90
87
84
84
91
90
88
86
95
95
91
87
100
95
90
84
90
86
84
95
90
86
82
94
92
88
84
97
97
92
86
101

4K
84
84
83
77
86
85
82
77
83
79
80
80

8K
84
84
81
71
87
83
77
69
82
76
76
74

LwA dB(A)
92
91
94
96
93
94
96
97
93
92
94
99

The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA International Standard 301. The A-weighted sound
ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D:
ducted inlet, ducted outlet. Ratings include the effects of duct end correction.

28

M.S. AXIAL Model: 1000 8P ( 720RPM, TYPE D )


1000/12

Fan Total Efficiency

Fan Absorbed Power, kW

Fan Static Pressure, Pa

720 rpm

Performance certified is for installation type D- Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (Accessories).

SOUND DATA - 720rpm


Blade Angle

25o

35o

50o

Ps [Pa]
0
38
81
136
0
69
103
139
0
39
92
137

63
76
74
73
78
79
77
77
83
81
80
79
91

125
85
85
87
92
86
86
88
97
92
92
94
97

Sound Power Level Lw, dB


250
500
1K
2K
82
80
76
78
80
80
76
78
85
85
81
78
92
87
81
75
82
80
76
79
84
84
80
80
90
88
83
79
91
87
82
76
85
83
78
78
84
83
78
75
87
85
80
76
93
90
84
78

4K
78
78
76
69
80
78
74
68
77
72
72
72

8K
78
78
74
63
81
76
69
60
76
69
68
66

LwA dB(A)
85
85
87
88
86
87
89
89
86
85
87
91

The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA International Standard 301. The A-weighted sound
ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D:
ducted inlet, ducted outlet. Ratings include the effects of duct end correction.

29

M.S. AXIAL Model: 1120 4P ( 1450RPM, TYPE D )


1120/16

Fan Total Efficiency

Fan Absorbed Power, kW

Fan Static Pressure, Pa

1450 rpm

Performance certified is for installation type D- Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (Accessories).

SOUND DATA - 1450rpm


Blade Angle

25o

35o

50o

Ps [Pa]
0
294
669
779
0
278
508
760
0
263
600
696

63
103
100
98
101
104
102
100
103
109
107
105
104

125
102
99
101
104
102
100
100
107
104
106
105
108

Sound Power Level Lw, dB


250
500
1K
2K
101
104
100
97
98
103
101
101
105
109
106
101
109
111
104
99
101
104
101
98
99
104
101
100
100
107
107
103
112
111
104
100
104
106
103
100
103
106
102
99
105
108
106
102
110
110
108
104

4K
96
99
95
94
96
98
98
94
95
95
98
99

8K
93
92
87
86
93
92
91
87
91
90
92
92

LwA dB(A)
106
107
110
111
106
107
110
111
108
107
110
112

The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA International Standard 301. The A-weighted sound
ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D:
ducted inlet, ducted outlet. Ratings include the effects of duct end correction.

30

M.S. AXIAL Model: 1120 6P ( 960RPM, TYPE D )


1120/16

Fan Total Efficiency

Fan Absorbed Power, kW

Fan Static Pressure, Pa

960 rpm

Performance certified is for installation type D- Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (Accessories).

SOUND DATA - 960rpm


Blade Angle

25o

35o

50o

Ps [Pa]
0
129
267
342
0
122
223
334
0
115
264
305

63
96
93
91
94
97
95
93
96
102
100
98
97

125
88
85
93
97
88
86
87
101
93
92
94
101

Sound Power Level Lw, dB


250
500
1K
2K
97
92
90
86
95
92
93
91
100
100
94
88
105
97
92
87
97
93
91
86
96
92
92
89
97
99
96
91
105
97
93
88
95
93
87
98
94
92
87
98
98
95
91
100
97
92
100
101

4K
89
88
82
81
89
88
86
81
85
84
85
86

8K
78
77
72
72
78
77
76
73
77
77
79
78

LwA dB(A)
96
98
100
100
97
97
100
100
98
97
100
102

The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA International Standard 301. The A-weighted sound
ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D:
ducted inlet, ducted outlet. Ratings include the effects of duct end correction.

31

M.S. AXIAL Model: 1120 8P ( 720RPM, TYPE D )


1120/16

Fan Total Efficiency

Fan Absorbed Power, kW

Fan Static Pressure, Pa

720 rpm

Performance certified is for installation type D- Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (Accessories).

SOUND DATA - 720rpm


Blade Angle

25o

35o

50o

Ps [Pa]
0
73
165
192
0
69
125
188
0
65
148
172

63
86
83
86
89
87
85
84
92
92
90
90
92

125
86
83
90
94
86
84
85
96
89
88
90
94

Sound Power Level Lw, dB


250
500
1K
2K
89
85
82
81
88
86
86
84
94
91
85
79
96
89
84
78
89
86
83
81
88
86
84
82
92
92
88
83
96
89
85
79
91
88
84
80
90
87
84
80
93
91
87
82
94
93
89
83

4K
78
77
72
71
78
77
76
71
75
75
76
76

8K
67
66
62
62
67
66
66
63
67
68
70
68

LwA dB(A)
88
90
92
91
89
89
93
92
90
89
92
94

The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA International Standard 301. The A-weighted sound
ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D:
ducted inlet, ducted outlet. Ratings include the effects of duct end correction.

32

M.S. AXIAL Model: 1250 4P ( 1450RPM, TYPE D )


1250/16

Fan Total Efficiency

Fan Absorbed Power, kW

Fan Static Pressure, Pa

1450 rpm

Performance certified is for installation type D- Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (Accessories).

SOUND DATA - 1450rpm


Blade Angle

25o

35o

50o

Ps [Pa]
0
233
493
662
0
266
464
681
0
350
625
733

63
104
103
99
98
105
102
100
100
113
110
108
107

125
102
101
99
99
103
101
100
101
111
108
109
111

Sound Power Level Lw, dB


250
500
1K
2K
101
108
104
103
101
107
106
106
100
109
110
106
103
111
110
105
102
107
105
103
100
107
106
106
101
109
109
107
103
111
110
105
107
110
106
104
105
110
109
105
110
113
112
108
115
113
111
107

4K
101
103
100
100
101
103
101
100
100
101
102
100

8K
99
97
94
92
99
97
95
92
96
95
95
93

LwA dB(A)
110
112
113
113
110
112
113
113
112
113
116
115

The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA International Standard 301. The A-weighted sound
ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D:
ducted inlet, ducted outlet. Ratings include the effects of duct end correction.

33

M.S. AXIAL Model: 1250 6P ( 960RPM, TYPE D )


1250/16

Fan Total Efficiency

Fan Absorbed Power, kW

Fan Static Pressure, Pa

960 rpm

Performance certified is for installation type D- Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (Accessories).

SOUND DATA - 960rpm


Blade Angle

25o

35o

50o

Ps [Pa]
0
102
216
290
0
117
204
299
0
153
275
340

63
97
95
92
91
98
95
93
93
106
103
101
100

125
87
87
86
89
88
87
87
90
95
93
99
106

Sound Power Level Lw, dB


250
500
1K
2K
100
96
95
92
99
97
98
95
98
102
100
93
101
103
98
93
100
96
96
92
98
97
98
95
99
101
100
94
101
103
98
93
102
97
92
98
101
98
94
101
104
96
101
104
105
94
100
103

4K
93
92
89
87
93
92
90
87
89
89
89
87

8K
85
82
79
77
85
83
80
77
84
82
81
80

LwA dB(A)
101
102
104
103
101
102
103
103
101
103
105
105

The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA International Standard 301. The A-weighted sound
ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D:
ducted inlet, ducted outlet. Ratings include the effects of duct end correction.

34

M.S. AXIAL Model: 1250 8P ( 720RPM, TYPE D )


1250/16

Fan Total Efficiency

Fan Absorbed Power, kW

Fan Static Pressure, Pa

720 rpm

Performance certified is for installation type D- Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (Accessories).

SOUND DATA - 720rpm


Blade Angle

25o

35o

50o

Ps [Pa]
0
57
122
163
0
66
115
168
0
86
154
191

63
87
85
83
84
88
85
84
85
98
93
94
96

125
86
86
85
88
87
85
86
88
92
90
95
99

Sound Power Level Lw, dB


250
500
1K
2K
92
89
97
86
92
91
91
88
93
95
91
85
96
95
90
84
92
90
88
86
91
91
90
87
94
94
91
86
96
95
90
84
94
91
89
85
95
94
90
86
98
97
93
87
98
96
91
85

4K
83
82
79
77
83
82
80
77
81
80
79
78

8K
75
72
69
67
75
73
70
67
76
73
71
71

LwA dB(A)
93
95
96
95
93
95
96
95
94
95
98
97

The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA International Standard 301. The A-weighted sound
ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D:
ducted inlet, ducted outlet. Ratings include the effects of duct end correction.