Samer,

Ineedforyoutoprovidemewiththefollowing:
NameofSubContractorandcontactdetailsofyourHydroTestVendor.
AListofallEquipmentthatheintendstobringtosite:
E.g.FillPumps(Name,Brand,TechSheet,DisplacementCapabilityi.e.LitersPerMinute)
ListoftestBlindsandTestCertificationthattheyintendtouseforthejob.

Confirmationthathehasattheleastthefollowingequipment:

FillandDrainage:
50mofEachtypeofFillingHose,1,2(Shallcomewithchangeableconnectionstothepumplocated
onthefillVehicle,orfordischargeofthelinewater)
1xFieldTankforholdingandstoringWater,canbeacombinationoftankstoholdaminimumcapacityof
15,000Literstoactasbufferstoragebetweentruckloads.
1xDischargeTankSamesizerecommended.
2xFillPumpsRecommendedCapacitySizewillfollowbasedonvolumeoftestpacks.Pleaseprovidesizeof
thepumpsavailable.Dischargerateispreferredmeasurement.

BlindingandFitUp:
Accessto40BlindFlangeswithNPT/BSPTConnectionsforFillandVentLocations.(Ratingstofollow)
Accessto36BlindFlangeswithNPT/BSPT(RatingsandQuantitytofollow).
Accessto30BlindFlangeswithNPT/BSPT(RatingsandQuantitytofollow)
Accessto28BlindFlangeswithNPT/BSPT(RatingsandQuantitytofollow)
Accessto28BlindFlangeswithNPT/BSPT(RatingsandQuantitytofollow)
Accessto24BlindFlangeswithNPT/BSPT(RatingsandQuantitytofollow)
Accessto12BlindFlangeswithNPT/BSPT(RatingsandQuantitytofollow)
Accessto6BlindFlangeswithNPT/BSPT(RatingsandQuantitytofollow)
ConfirmationthatallflangestobeusedhaveTestingCertification.
NAFGasketstotheabovesizingandrating.

SpecificTestingEquipment:
1xTestingmanifoldsratedto100Barg(TestCerttobesupplied)
2xTestingManifoldsratedto50Barg(TestCerttobesupplied)
2xTestingpumpstocapableofreachingtestpressuresassetoutinthelinelist(Min3.85BargMax92
Barg)
3x30mPressureratedhosingRatedto1500PSI(CertifiedHose),Testpumptomanifold,Manifoldto
testpipe.
3x20mPressureRatedHosingRatedto750PSI(CertifiedHose),Testpumptomanifold,Manifoldto
testpipe.
6xTestGauges010(barg)
6xTestGauges0100(barg)
6xTestGauges050(barg)
6xTestGauges0150(barg)
Alloftheadaptorsthatyouneedtoconnectintotheflange,i.e.NPTMaletoFemaleadaptororvarious
http://webmail.albilalgroup.com/versions/webmail/11.3.13RC/popup.php?wsid=c586b532c1f84da99f80039a3c3139e28d728f65#1428770223188

1/2

11/04/2015

TestingEquipment

combinationsof.

Drying&shockblowing:
Compressor200CFM
Hoses,WhipChecks.
Dryer.
DewPointAnalyser.

Handtools:
Assortmentofhandtoolsforreinstatementandsetup.

Regards,

Andrew Taylor (B2B Fernando Batista)


ConstructionLead
NRIBC
DubaiConventionTower,Zabeel,Dubai
Mobile:+971(0)508834521
Mobile:+964(0)7814843246
Communicator:+31707997858
Email: andrew.a.taylor@basrahgas.com
Website: www.basrahgas.com

TheregisteredaddressofBasrahGasCompanyisRepublicofIraq,Basrah,KhorAlZubairP.O.Box2705AlAsharPostandtheregistrationnumber
is8134302.Pleaserefertowww.basrahgas.comforfurtherinformationonthecompany.Disclaimer:Thisemailisconfidentialandisintended
onlyfortheaddressee.Ifyouhavereceiveditbymistakepleasenotifythesenderanddeleteit.
.81343022705..
.:.www.basrahgas.com
.

http://webmail.albilalgroup.com/versions/webmail/11.3.13RC/popup.php?wsid=c586b532c1f84da99f80039a3c3139e28d728f65#1428770223188

2/2

Das könnte Ihnen auch gefallen