01

Cast Resin Transformers

Trihal - Standard losses


Common electrical characteristics
PM102305

Frequency(1): 50Hz
Maximum ambient temperature: 40C
Secondary voltage at no-load(1):
- 400 to 433V between phases
- 231 to 250V phase to neutral
HV tapping range (off-circuit)(1): 2.5 to 5
Vector group: Dyn (delta, star neutral brought out)
Partial discharges according to IEC 60076-11
standard: 10 pC at 1.3 Um

(*) The rated power is defined by natural air cooling (AN). Should there
be particular constraints, it may be increased by 40 % by forced cooling
addition (AF). Please consult us. (1) Others possibilities upon request,
consult us. (2) Non standard ratings available on request.

Electrical characteristics for insulation level: 7.2 kV and 12kV


Rated power(1)(*) (kVA)

160 (2)

250

400

630

800

1000

1250

1600

2000

2500

3150

Losses (W) - no-load losses

610

820

1150

1370

1700

2000

2500

2800

3500

4300

5500

Losses (W) - load losses at 75C

2300

3100

4300

6700

7700

8800

10500

12300

14900

18300

21800

Losses (W) - load losses at 120C

2700

3500

4900

7600

8800

10000

12000

14000

17000

21000

25000

Rated impedance voltage (%)

No-load current (%)

2.3

1.5

1.3

1.3

1.2

1.2

1.2

1.1

Switching current - Ie/In (peak value)

13.5

13

13

10

10

10

10

9.5

Switching current - time constant

0.13

0.18

0.25

0.3

0.3

0.34

0.35

0.42

0.45

0.5

0.5

Noise level dB(A)- acoustic power LWA

62

65

68

70

72

73

75

76

77

81

81

Noise level dB(A)- acoustic pressure


LPA at 1 m (according to IEC 270)

50

53

55

57

59

59

61

61

61

61

59

Electrical characteristics for insulation level: 17.5 kV and 24 kV


Rated power (kVA) (1)(*)

160 (2)

250

400

630

800

1000

1250

1600

2000

2500

3150

Losses (W) - no-load losses

650

880

1200

1650

2000

2300

2800

3100

4000

5000

6300

Losses (W) - load losses at 75C

2350

3300

4800

6800

8200

9600

11400

14000

17500

20000

21800

Losses (W) - load losses at 120C

2700

3800

5500

7800

9400

11000

13100

16000

20000

23000

25000

Rated impedance voltage (%)

No-load current (%)

2.3

1.5

1.3

1.3

1.2

1.2

1.2

1.1

Switching current - Ie/In (peak value)

10.5

10.5

10

10

10

10

10

10

9.5

9.5

9.5

Switching current - time constant

0.13

0.18

0.25

0.26

0.3

0.3

0.35

0.4

0.4

0.5

0.5

Noise level dB(A)- acoustic power LWA

62

65

68

70

72

73

75

76

78

81

81

Noise level (3) dB(A)- acoustic pressure


LPA at 1 m (according to IEC 270)

50

53

56

57

59

60

61

62

63

66

66

Electrical characteristics for insulation level: 36 kV


Rated power (kVA)(1)(*)

160 (2)

250

400

630

800

1000

1250

1600

2000

2500

3150

Losses (W) - no-load losses

On request

1280

1650

2200

2650

3100

3650

4200

5000

5800

6800

Losses (W) - load losses at 75C

On request

3480

4960

6960

8440

10000

12610

14790

18270

21740

22610

Losses (W) - load losses at 120C

On request

4000

5700

8000

9700

11500

14500

17000

21000

25000

26000

Rated impedance voltage (%)

On request

No-load current (%)

On request

Switching current - Ie/In (peak value)

On request

Switching current - time constant

On request

Noise level dB(A)- acoustic power LWA

On request

67

70

72

73

74

76

77

79

77

77

Noise level dB(A)- acoustic pressure


LPA at 1 m (according to IEC 270)

On request

55

56

57

58

59

61

61

63

61

61

Cast Resin Transformers

E/2
J

13
tapping
links

C
M

H
B

earthing
terminal

different (consult us).

40 (50)

125 (160)

D
E

Insulation level: 7.2 kV and 12 kV- low voltage 400 V to 433 V


Rated power (kVA)

160

250

400

630

800

1000

1250

1600

2000

2500

3150

Dimensions (mm) - Lenght A

1080

1180

1335

1440

1510

1525

1605

1665

1760

1850

2070

- Width B

650

650

795

815

835

945

945

945

1195

1195

1195

- Height C

1250

1260

1350

1550

1670

1675

1860

2035

2180

2360

2550

- Roller pitch D

520

520

670

670

670

820

820

820

1070

1070

1070

- Frame width E

645

645

795

795

795

945

945

945

1195

1195

1195

- Roller diam. F

125

125

125

125

125

125

125

125

160

160

160

- Roller width G

40

40

40

40

40

40

40

40

50

50

50

750

960

1240

1740

2040

2125

2580

3210

3910

4480

6000

Weight without enclosure (kg)

Insulation level: 17.5 kV and 24 kV - low voltage 400 V to 433 V


Rated power (kVA)

160

250

400

630

800

1000

1250

1600

2000

2500

3150

Dimensions (mm) - Lenght A

1300

1330

1410

1480

1555

1645

1645

1735

1860

2025

2200

- Width B

710

715

805

820

830

850

850

955

975

1000

1200

- Height C

1335

1345

1435

1740

1760

1800

2070

2120

2310

2355

2410

- Roller pitch D

520

520

670

670

670

820

820

820

1070

1070

1070

- Frame width E

645

645

795

795

795

945

945

945

1195

1195

1195

- Roller diam. F

125

125

125

125

125

125

125

125

160

160

160

- Roller width G

40

40

40

40

40

40

40

40

50

50

50

860

990

1320

1820

2060

2560

2920

3355

4080

5080

6770

Weight without enclosure (kg)

Insulation level: 36 kV - low voltage 400 V to 433 V


Rated power (kVA)

160

250

400

630

800

1000

1250

1600

2000

2500

3150

Dimensions (mm) - Lenght A

On request

1460

1460

1530

1660

1740

1780

1850

1970

2270

2400

- Width B

On request

790

870

870

870

950

950

950

1200

1200

1200

- Height C

On request

1750

1790

1950

1990

2160

2200

2400

2500

2460

2750

- Roller pitch D

On request

520

670

670

670

820

820

820

1070

1070

1070

- Frame width E

On request

645

795

795

795

945

945

945

1195

1195

1195

- Roller diam. F

On request

125

125

125

125

125

125

125

160

160

160

- Roller width G

On request

40

40

40

40

40

40

40

50

50

50

On request

1460

1600

2000

2400

2910

3280

3920

4900

6580

8280

Weight without enclosure (kg)

SM100016

Dimensions and weights


without enclosure housing
(IP00)
Dimensions and weights
are for guidance only, and
are provided for a singlevoltage transformer with
the following HV insulation
levels and low voltages.
Only the definitive drawings
following from the order will
commit us contractually. For
other voltages, impedance
voltages and dual-voltages,
weights and dimensions are

02

Trihal - Standard losses

Cast Resin Transformers

different (consult us).

SM100017

Dimensions and weights


with IP31 metal
enclosure
Dimensions and weights
are for guidance only, and
are provided for a singlevoltage transformer with
the following HV insulation
levels and low voltages.
Only the definitive drawings
following from the order will
commit us contractually. For
other voltages, impedance
voltages and dual-voltages,
weights and dimensions are

03

Trihal - Standard losses

13

tapping
links

earthing
terminal

40 G
(50)
D
B

125 (160)

Insulation level: 7.2 kV and 12 kV- low voltage 400 V to 433 V


Rated power (kVA)

160

250

400

630

800

1000

1250

1600

2000

2500

3150

Dimensions (mm) - Lenght A

1650

1650

1700

1700

1700

2000

2000

2150

2330

2330

2500

- Width B

950

950

1020

1020

1020

1170

1170

1170

1270

1270

1290

- Height C

1750

1750

1900

1900

1900

2400

2400

2480

2650

2650

2800

- Roller pitch D

520

520

670

670

670

820

820

820

1070

1070

1070

- Frame width E

645

645

795

795

795

945

945

945

1195

1195

1195

- Roller diam. F

125

125

125

125

125

125

125

125

160

160

160

- Roller width G

40

40

40

40

40

40

40

40

50

50

50

910

1130

1430

1930

2230

2390

2845

3535

4280

4850

6400

Total Weight with enclosure IP31 (kg)

Insulation level: 17.5 kV and 24 kV - low voltage 400 V to 433 V


Rated power (kVA)

160

250

400

630

800

1000

1250

1600

2000

2500

3150

Dimensions (mm) - Lenght A

1650

1650

1700

1800

1800

1900

1900

2150

2330

2330

2500

- Width B

950

950

1020

1020

1020

1025

1100

1170

1240

1240

1290

- Height C

1750

1750

1900

2050

2050

2050

2300

2480

2650

2650

2650

- Roller pitch D

520

520

670

670

670

820

820

820

1070

1070

1070

- Frame width E

645

645

795

795

795

945

945

945

1195

1195

1195

- Roller diam. F

125

125

125

125

125

125

125

125

160

160

160

- Roller width G

40

40

40

40

40

40

40

40

50

50

50

1040

1170

1510

2030

2270

2800

3160

3675

4455

5455

7170

Total weight (kg)

Insulation level: 36kV - low voltage 400 V to 433 V


Rated power (kVA)

160

250

400

630

800

1000

1250

1600

2000

2500

3150

Dimensions (mm) - Lenght A

On request

2060

2060

2130

2260

2340

2380

2450

2570

2870

3000

- Width B

On request

1210

1210

1230

1280

1300

1320

1340

1380

1480

1530

- Height C

On request

2050

2090

2250

2290

2460

2500

2700

2800

2860

3150

- Roller pitch D

On request

520

670

670

670

820

820

820

1070

1070

1070

- Frame width E

On request

645

795

795

795

945

945

945

1195

1195

1195

- Roller diam. F

On request

125

125

125

125

125

125

125

160

160

160

- Roller width G

On request

40

40

40

40

40

40

40

50

50

50

On request

1660

1800

2300

2700

3210

3600

4320

5300

6930

8730

Total weight (kg)

Cast Resin Transformers

04

Trihal - Standard losses

Connections - Trihal transformers without enclosure housing (IP 00)


The winding resin coating and the plug-in connectors dont ensure any protection against touch when the
transformer is energized. The contrator must ensure that cables and busbars are adequately supported to
prevent mechanical stresses from being imposed on the transformer terminals, busbars or bushings.

HV and LV standard connection

LV

Insulation
(kV)

Dimension X (mm)
Full wall

Grid wall

7.5

90

300

12

120

300

17.5-24

220

300

HV

SM100019

SM100018

Minimum clearances required

cable support

LV

120
mini

HV

120
mini

According to HD 637-1. Dont take into


account the access to tapping on the
UV side.

Connections -Trihal transformers with IP 31 metal enclosure

HV and LV connection
SM100021

200 mm

LV

HV

cable support

200 mm

200 mm

LV

HV
cable support

SM100020

Minimum clearances required

500 mm*

500 to 800 kVA*

thickness 5

thickness 6

thickness 10

160
80

thickness 12

13

40
35

25
50

1600 kVA*

SM100023

1000 to 1250 kVA*

100
50

4 x 14

23.5
33

4 x 14

4 x 16

2000 kVA* thickness 10


2500 kVA* thickness 2u10

*Valid for aluminium terminations.

The contrator must ensure that cables and busbars are adequately supported to prevent mechanical stresses from being
imposed on the transformer terminals, busbars or bushings.

Schneider Electric Industries SAS


35, rue Joseph Monier
CS 30323
F - 92506 Rueil Malmaison Cedex (France)
Tl. : +33 (0)1 41 29 70 00
RCS Nanterre 954 503 439
Capital social 896 313 776
www.schneider-electric.com
NRJED311119EN

As standards, specifications and designs change from time


to time, please ask for confirmation of the information given
in this publication.
Design: Schneider Electric Industries SAS
Photos: Schneider Electric Industries SAS

This document has been


printed on recycled paper

09-2011

2011 Schneider Electric. All rights reserved. ART. 17813

160 to 400 kVA*

50

50

4 x 14

80
33

23.5
33

14

70
33

15

40

HV terminations

33

SM100022

LV terminations