multi-purpose compact unit

ventilators with counterflow


heat recovery core
Indoor compact unit ventilators of DUPLEX-S 1500 to 5600
series are used for comfort ventilation, as well as warm-air
heating and cooling of small office areas, shops, retail
facilities, school buildings, restaurants, small stores, sport
centres, industrial halls and swimming pools.
The units are suitable for all facilities where effective
ventilation or warm air circulation heating/cooling
at minimum operating costs is required; it means highefficient heat recovery, low power consumption of fans
and minimum noise level.
The units are available in two basic versions:
indoor version
rooftop version (with double insulation)
The DUPLEX-S unit is designed as a compact appliance.
In single casing it contains: two independently controlled
centrifugal fans with anti-vibration motor support,
high-efficient counterflow air-to-air heat recovery core
assembled from thin plastic plates, removable supply
and exhaust air filters of the G4 or F7 class, condensation
pans, an optional internal by-pass with a remote-controled
actuator and a mixing damper with an actuator.
The unit casing consists of steel Lprofile frame
and sandwich panels made of aluminum metal sheets filled
with polyurethane insulation (tepeln odpor R = 1,05 m2KW-1,
resp. 2,1 m2KW-1 ). The sandwich panels are fixed to the
frame. A front access door enables comfortable access to all
components and filters. Standard surface finish. Inlet and
outlet ports are round or rectangular with different location
configuration based on an order.
In the rooftop units inlet and outlet ports are standardly
covered by hoods. We recommend that both shutoff
dampers be installed to prevent drafts.

The units may optionally be equipped with efficient EC type


fans with constant airflow control option.
Features of the DUPLEX-S units
high recovery efficiency of counterflow exchanger up to 80 %
highly compact shape enables space reduction up to 60 %
compared to units with modular design
low purchase cost
up to 32 installation configurations
choice of non-standard connection ports (round or
rectangular) on request
very low noise level
low weight
low power input
different types of complete built-in control systems based
on application complexity; fully integrated into the unit
high chemical resistence of the hPS exchanger
optional hygienic design according to the VDI 6022
optional delivery in disassembled state for inaccessible spaces

S-1500 to 5600

DUPLEX-S 1500 to 5600

AVAILABLE MODIFICATIONS (CAN BE COMBINED)

Unit ventilators, heat recovery chapter 2.1. issue 08/2010

Indoor type
B
C
T
CHF
CHW

Rooftop type
N-B
N-C
N-T
N-CHF
N-CHW

with built-in by-pass


with built-in mixing damper
with built-in hot water heating coil
with built-in DX cooling coil
with built-in chilled water cooling coil

with built-in by-pass


with built-in mixing damper
with built-in glycol heating coil
with built-in in DX cooling coil
with built-in glycol chilled water cooling coil

OPERATING MODES OF THE DUPLEXS UNITS


H

e2

i2

e2

i2

e2

i1

e1

i1

e1

i1

Ventilation with heat recovery


with heating (cooling)

i1
i2

e2

i2

i1

e1

Ventilation without recovery


(via bypass)

Circulation heating,
or cooling

Combined ventilation with air


mixing and heating (cooling)

e1 ... Inlet of fresh outdoor air outside air


e2 ... Outlet of fresh filtered air supply air

... Inlet of stale air return air


... Outlet of stale air exhaust air

H ... Heating medium connection


C ... Cooling medium connection

SELECTION SOFTWARE

s a v e

y o u r

e n e r g y

For detailed selection of Duplex units,


accessories and control system we recommend
to use our special selection software.
To select a heat recovery exchanger
you can use our special selection software.
Download it from our webpage www.atrea.cz
or contact us at our mail address.

N I T

V E N T I L A T O R S

&

H E A T

R E C O V E R Y

ATREA s.r.o., V Aleji 20


466 01 Jablonec n. N.
Czech Republic

D I V I S I O N

Phone: +420 483 368 111


Fax: +420 483 368 112
E - m a i l : atr ea@ a t r e a . c z
www.atrea.cz

PERFORMANCE CURVES
INDOOR TYPE

ROOFTOP TYPE

DUPLEX-S
typ 1500 2200 3100 4500 5600
1)
Supply air max.
m3h-1 1 500 2 200 3 200 5 000 6 500
1)
Exhaust air max.
m3h-1 1 450 2 000 3 000 4 900 5 700
2)
Recovery efficiency
%
up to 80
Configurations
see the installation positions table
3)
Weight
kg 125-210 135-235200-340230-420300-520
Max. power input
kW
based on fan type
Power supply
V 230 230 230/400 400 400
Frequency
Hz
50
Speed
min-1
based on fan type
Heating capacity T max. 4) kW 21
24
41
63
80
Cooling capacity CHW -max. 4) kW
9
12
20
30
39
Cooling capacity CHF -max.4) kW 10
13
21
32
41

DUPLEX-NS
typ 1500 2200 3100 4500
1)
Supply air max..
m3h-1 1 500 2 200 3 200 6 500
1)
Exhaust air max.
m3h-1 1 450 2 000 3 000 4 900
2)
Recovery efficiency
%
up to 80
Configurations
see the installation positions table
3)
Weightt
kg 185-280 230-350 290-450 340-560
Max. power input
kW
based on fan type
Power supply
V
230
230 230/400 400
Frequency
Hz
50
Speed
min-1
based on fan type
Heating capacity T max.4) kW
21
24
41
63
Cooling capacity CHW -max. 4) kW
9
12
20
30
Cooling capacity CHF -max. 4) kW
10
13
21
32

1)

1)

maximum airflow through units at zero external pressure


based on air volume flow
3)
based on accessories
4)
based on coil type, medium, and water flow

maximum airflow through units at zero external pressure


based on air volume flow
based on accessories
4)
based on coil type, medium, and water flow

2)

2)

3)

PERFORMANCE CURVES (INDOOR TYPE)

Available pressure pst (Pa)

800
Supply section (G4)
Exhaust section
Supply section with T.3
Supply section with CHF.4
Supply section with CHF.5
Supply section with T.3+CHF.4
Supply section with T.3+CHW.5
Recommended operation
area with high efficiency

700
600

500

M0 UPL
17 EX
;S
10 -S
58 56
/1 0
03 0
8.A

400

DU

00 .A
22038
-S /1
EX 58
0
PL ; S1
DU014
00 .A
M
15 038
-S 8/1
EX 05
PL ; S1
DU007

01 PL
0; E
S1 X05 S
8/ 31
10 0
38 0
.A

M0 UPL
12 EX
;S
10 -S
58 45
/1 0
03 0
8.A

300

200
100
0
0

1 000

2 000

3 000

4 000

Note: for performance curves of a rooftop version see the respective catalog sheet

5 000
6 000
Volume flow rate (m3/h)

Heat recovery efficiency (%)

HEAT RECOVERY EFFICIENCY

95
90
85
80
75
70
65

At te1 = -15 C, ti1 = +20 C, rhi1 = 55 %, Mi = Me


At te1 = +7 C, ti1 = +20 C, rhi1 = 40 %, Mi = Me

1 000

2 000

3 000

4 000

5 000
6 000
Volume flow rate (m3/h)

Heating / cooling capacity QT/CH (kW)

HEATING AND COOLING CAPACITIES

100
Max. heating capacity T at water temp.
drop of 80/60 C; inlet air (after
recovery) + 3 C, rh 30 %.
Max. cooling capacity CHW at 30%
water/ethylene glycol mixture temp. drop
of 6/12 C; outdoor air at 30 C, rh 50 %.

80
60

T.3 (3-r

40
-row)
CHW.5 (5

20
0

1 000

2 000

ow)
-row)
CHF.4 (4
max. heating capacity T.3
max. cooling capacity CHF.4 and CHW.5

3 000

4 000

6 000
5 000
Volume flow rate (m3/h)

DIMENSIONS
INDOOR TYPE POSITION 10 TO 43

ROOFTOP TYPE
FLAT POSITION ONLY (only DUPLEX-NS 1500 4500)
B

L0 / L1 / L2
B

L0 / L1 / L2

150 OB

OB
M
OH2
A
B Fe

Ke

Ki

min. OH1
150

Fi
K

T CH

Fi

OH1

Ki

Mi
Me
A

Mi

T CH

Door

Me

CH
OH2

Fe

Ke
UT1,2 CH1,2

1500
1 270
435
1 920
2 100

mm 315
mm 220
mm 315x315

2200 3100 4500


1 350 1 500 1 500
565 650 870
2 120 2 300 2 300
2 300 2 500 2 500
(1 2) x 32 mm
315
220

400
260

500
310

5600
1 500
1 050
2 300
2 500
2)
2)

315x400 400x400 500x500 500x630

mm 200
mm 215
mm 345

270
230
360

300
285
405

420
320
452

510
335
485

mm 200
mm 215
mm 345

345
230
260

360
285
335

455
320
320

----

DUPLEX-NS
Distance A
Distance B
Length L0 (without coil)
Length L1/L2 (1 2 coil)
Condensate drain K
Port hood length M
Connection ports
Round duct diameter D 1)
Port with a damper LH2
Rectangular duct Y x X 1)
Port axis OB
Port axis OH1 inlet
Port axis OH2 outlet
1)

1)

standard sizes of round and rectangular ports, others as option


(for allowable airflow speed)
2)
only rectangular ports
INDOOR TYPE POSITION 50, 51

mm
mm
mm
mm
mm
mm
mm
mm
mm
mm
mm
mm

1500 2200 3100


1 310 1 390 1 540
475
605
690
1 960 2 160 2 240
2 200 2 340 2 540
(1 2) x 32 mm
360
360
450
315
220

315
220

315x315

220
240
365

4500
1 540
910
2 240
2 540
650

400
260

500
310

315x400 400x400 500x500

335
285
285

375
305
360

480
360
355

standard sizes of round and rectangular ports, others as option


(for allowable airflow speed)
PORT TYPES AND DIMENSIONS

RECTANGULAR
X+20
X

ROUND

OB

Door

mm
mm
mm
mm
mm

Door

DUPLEX-S
Distance A
Distance B
Length L0/L1 (without/1 coil)
Length L2 (2 coils)
Condensate drain K
Connection ports
Round duct diameter D 1)
Port with a damper LH2
Rectangular duct Y x X 1)
Configurations 10 21
Port axis OB
Port axis OH1 inlet
Port axis OH2 outlet
Configurations 30 41
Port axis OB
Port axis OH1 inlet
Port axis OH2 outlet

Basic port
(inlet, outlet)

Mi

Fe
B

80

80

alter.

Port with
a damper
(inlet only)

alter.

LH2

110

220

150

n x 100

OH2

Door

Fi

Ke

Me

Ki

OB

min.
150

CH1,2 UT1,2

B
OH1

Port with
a flexible
connection
(max. Length)
(inlet, outlet)

alter.

DUPLEX-S
distance A height
distance B depth
distance L width
inlet port axis OB
inlet port axis OH1
outlet port axis OH2

mm
mm
mm
mm
mm
mm

1500
1 550
435
2 400
200
810
345

2200
1 600
565
2 400
270
860
360

3100
1 700
650
2 500
300
900
355

4500
1 700
870
2 800
420
1 050
380

5600
1 750
1 050
2 900
510
1 100
420

Port with
a damper
and flexible
connection
(inlet only)

LH2+140

alter.

260
n x 100

OH1
OH2

OH1
OH2

Y
Y+20

OB

DUPLEXS INSTALLATION CONFIGURATION


INSTALLATION POSITIONS AND PORT CONFIGURATIONS

DUPLEX-S 1500 5600 units are available in wide range


of configuration that makes the installation work in a mechanical
room easy. This increases the possibility of installing the unit even
in cramped spaces.
Due to construction reasons and the need for good condensate
drainage, it is not possible to deliver all types and sizes
in all configurations - for details see the installation configurations
table.

The DUPLEX units are characterized by a wide range


of configurations and port sizes. All ports can be either round
or rectangular, optionally equipped with flexible connections,
and the inlet ports can be equipped with shutoff dampers on
request.
All units are available with non-standard port configuration
(dashed line on layouts), with a code according to the summary
table Installation positions & port configurationsl.

INDOOR TYPE
FLOOR-STANDING
HORIZONTAL POSITION

Configuration 10/0 to 11/10 (DUPLEX-S 1500 5600) door side view (8 configurations in total)
e2

i2

e2

i2

10

11

e1

FLOOR-STANDING
VERTICAL POSITION

i1

e1

i1

Configuration 20/6 to 21/15 (DUPLEX-S 1500 5600) door side view (8 configurations in total)
not in CHF, CHW, CHP modifications
i2
i2
e1
e1

20

i1

CEILING-SUSPENDED
POSITION

21

e2

e2

Configuration 30/0 to 31/15 (DUPLEX-S 1500 4500) top view (32 configurations in total)
e2

i2

31
e1

i1

e1

i1

Configuration 40/0 to 41/15 (DUPLEX-S 1500 4500) top view (32 configurations in total)
e2

i2

e2

e1

i2

41

40

UPRIGHT POSITION

e2

i2

30

FLOOR-STANDING
FLAT POSITION

i1

i1

e1

i1

Configuration 50; 51 (DUPLEX-S 1500 5600) door side view (2 configurations in total)
i2 e1
i1
e2
e2
i1
e1 i2

50

51

ROOFTOP TYPE
ROOFTOP FLAT POSITION

Configuration 3/8, 10, 12, 14 and 4/8, 10, 12, 14 (DUPLEX-NS 1500 4500) top view (8 configurations in total)
i2
i2
e2

e2

3
e1

4
i1

i1

e1

MANIPULATION SPACE
MANIPULATION SPACE

Each individual drawing shows the minimum manipulation distance


when hinged door is used (easier access), and minimum
manipulation space for hingeless door, with quick locks (more
difficult access).
For all units a minimum 600 mm of manipulation space must be
left on side where an electrical control panel is located according.
For units equipped with a heating or cooling hydralic kit a free
space on side of the kit must be left.

Accessory-side manipulation space

Control modules

RMD, RMT, RMCH


SR, SR-T

Hydraulic kits
R-TPO / R-TPO-3 / RS-TPO
R-CHW / RCHF

min. T

min. U

Hinges

floor
Hinges

floor
wall

min. U

min. - see actual


unit size

Floor-standing flat
DUPLEX-S 1500 to 4500

min. 150

min. 150

View with an
installation opening
(also to access
the electric RMD
and a hydraulic kit)

min. 80

min. 150

floor
wall

Ceiling- suspended
DUPLEX-S 1500 to 4500

min. U

Hinges

Hinges

Hinges

Floor-standing vertical
DUPLEX-S 1500 to 5600

min. 600
140

Door-side manipulation space


Floor-standing horizontal
DUPLEX-S 1500 to 5600

min.
600
200

When installing DUPLEX-S units it is necessary to allow


for recommended free manipulation space around the unit.
Minimum space of 150 mm is needed under a unit to install
a DN 32 condensate drain pipe. A trap of minimum height
of 150 mm must be installed before connecting the pipe
to a building sewer. The recommended space is easily ensured
when delivered standard support steel legs are used.
Unit front service space is needed for opening access door, filter
removal and access to all components for maintenance.

T=
DUPLEX-S 1500
DUPLEX-S 2200
DUPLEX-S 3100
DUPLEX-S 4500
DUPLEX-S 5600

without coil
1 coil

2 coils

hingeless

1 150
1 260
1 260
1 260
1 260

1 150
1 260
1 325
1 325
1 325

440
570
650
870
1 050

U=
DUPLEX-S 1500
DUPLEX-S 2200
DUPLEX-S 3100
DUPLEX-S 4500
DUPLEX-S 5600

SOUND POWER LEVEL LW

Type

Fan

Oper. point

M.005

230 V
1 000 m3/h

M.007

230 V
1 300 m3/h

M.014

230 V
1 800 m3/h

M.010

400 V
2 650 m3/h

M.014

230 V
2 100 m3/h

M.011

400 V
3 000 m3/h

M.012

400 V
4 350 m3/h

M.010

400 V
3 750 m3/h

M.017

400 V
5 200 m3/h

DUPLEX
S-1500

DUPLEX
S-2200

DUPLEX
S-3100

DUPLEX
S-4500

DUPLEX
S-5600

without coil /1 and 2 coils


hinged
hingeless
1 300
440
1 350
570
1 520
650
1 520
870
1 520
1 050

S O U N D P R E S S U R E L E V E L L D1

Sound power Lw [dB(A)]


inlet e1,i1
56,6
outlet e2,i2
72,5
unit
62,2
inlet e1,i1
57,0
outlet e2,i2
74,5
unit
63,4
inlet e1,i1
60,6
outlet e2,i2
75,6
unit
61,8
inlet e1,i1
62,8
outlet e2,i2
81,7
unit
67,9
inlet e1,i1
53,4
outlet e2,i2
76,1
unit
61,4
inlet e1,i1
62,7
outlet e2,i2
82,5
unit
67,6
inlet e1,i1
69,3
outlet e2,i2
87,3
unit
73,3
inlet e1,i1
63,1
outlet e2,i2
85,3
unit
68,2
inlet e1,i1
67,9
outlet e2,i2
87,7
unit
72,5

Type

Fan

Oper. point
Sound pressure level LD1 [dB(A)]
230 V
unit
51,2
M.005
DUPLEX
1000 m3/h
S-1500
230 V
unit
52,4
M.007
1300 m3/h
DUPLEX
230 V
unit
50,8
M.014
S-2200
1800 m3/h
400 V
unit
56,9
M.010
DUPLEX
2650 m3/h
S-3100
230 V
unit
50,4
M.014
2100 m3/h
400 V
unit
56,6
M.011
DUPLEX
3000 m3/h
S-4500
400 V
unit
62,3
M.012
4350 m3/h
400 V
unit
57,2
M.010
DUPLEX
3750 m3/h
S-5600
400 V
unit
61,5
M.017
5200 m3/h
The sound pressure level is measured at 1 m distance from a unit.

MODIFICATIONS
DUPLEXS BASIC UNIT

DUPLEXS xxxx
Basic configuration
The compact unit consists of supply and exhaust centrifugal fans with electric motors in anti-vibration mounting,
removable counterflow air-to-air heat recovery core assembled from thin plastic plates, removable G4 (or F7)
supply and exhaust air filters, and a condensate pan with DN 32 flexible hose. The unit casing consists of steel
frame and sandwich side panels made of painted aluminum sheets and filled with 22 mm of polyurethane insulation
with thermal resistance R = 1,05 m2KW-1, (rooftop units with insulation of 45 mm). The sandwich panels are fixed
to the frame. A front door enables easy access to all built-in components and filters.
Me.xxx; Mi.xxx
Fans
Variety of fan types of different manufacturers can be used for each DUPLEX unit size. Fans differ in volume flow
rate, available pressure, speed, sound level and power consumption. Single-phase, three-phase or special EC (DC)
energy-saving fans are available. All fans are direct-driven.
S.1058/1038.A
Heat recovery core
The only heat recovery core type made of plastic in counterflow arrangement with high efficiency.

DUPLEXS MODIFICATION DESCRIPTION

B.x
By-pass (B)
By-pass of the plate heat recovery core on supply air side. By-pass consists of an opposed-blade damper
and an actuator.
It is fitted next to the recovery core inside the unit; it does not increase size of the unit.
The standard actuator is BELIMO 230 V; other types are available upon request.

C.x
Mixing damper (C)
Built-in opposed-blade damper including BELIMO 230 V actuator. It enables to mix fresh and stale (internal)
air in 0 to 100 % range. Along with a mixing damper the e1 shutoff damper without spring-return function must always
be installed. Should the unit be equipped with a heating coil (DUPLEX--S-TC) and draft could occur in the duct system
during power failure with the damper stuck open, it is necessary to install separate shutoff damper with spring-return
function into the duct close to an air intake. The damper is controlled by the unit control.
T.x
Hot water heating coil (T)
Built-in water-to-air three-row (possibly five-row) heating coil; made of copper pipes and aluminum fins. Designed
for systems up to 110 C and 1,0 MPa. The coil is standardly equipped with flexible connection and a steam-gas
capillary thermostat for freeze protection. Units in modification T (with heating coil) must be equipped with e1 supply
air shutoff damper; an actuator with spring-return function (BELIMO LF 230 V) is reccommended. A coil hydraulic
kit for heating capacity control of R-TPO, R-TPO-3 or RS-TPO type can be supplied with the coil upon request.
Attention the coil of rooftop units must always be protected against freezing by a water-glycol mixture.
Provision for cooling (CHP)

CHP

Provision for additional installation of cooling coil. This provision comprises space for the cooling coil and the condensate pan.
Attention in case of additional cooling coil installation it is necessary to ensure safe access and a sufficient manipulation
space. A ceiling-suspended unit must be taken down to install the coil. Additional coil installation is only possible for floor-

standing horizontal and flat, ceiling-suspended, and rooftop configurations. Units in configuration CHP without a heating
coil in position 30 to 43 and all rooftop units must be equiped with a droplet eliminator; dimension L2 applies to the
units.
CHF.x
Direct expansion (DX) coil (CHF)
A built-in coil made of copper pipes and aluminum fins, including a condensate pan with individual condensate drainage
and a pressure switch for freeze alarm. Three- or five-row coils are chosen depending on capacity required,
refrigerant type and air parameters. The DX coil can be equipped with accessories on request.
Attention units with the DX coil are only made in floor-standing horizontal and flat, ceiling-suspended, and rooftop
configurations. Units in configuration CHF without a heating coil in position 30 to 43 and all rooftop units must be
equiped with a droplet eliminator; dimension L2 applies to the units.
Chilled water cooling coil (CHW)

CHW.x

A built-in coil made of copper pipes and aluminum fins, including a condensate pan with individual condensate drainage.
Three- or five-row coils are chosen depending on capacity required, cooling medium type and air parameters.
The cooling coil can be equipped with the R-CHW hydraulic kit on request.
Attention units with the cooling coil are only made in floor-standing horizontal and flat, ceiling-suspended, and rooftop
configurations. Units in configuration CHP without a heating coil in position 30 to 43 and all rooftop units must be

equiped with a droplet eliminator; dimension L2 applies to the units.


Individual modifications can be freely combined
DUPLEX-S-TC (unit with a hot-water heating coil and a mixing damper)
Example:
DUPLEX-S-T-CHF (unit with a hot-water heating coil and a DX coil)
DUPLEX-S-TC-CHP (unit with a hot-water heating coil, mixing damper, and provision for cooling) etc.

ACCESSORIES
OTHER OPTIONAL ACCESSORIES (BASIC OVERVIEW)

Ke.xxx; Ki.xxx
S h u t o f f d a m p e r e 1; i 1
Shutoff dampers standardly fitted with BELIMO
actuators are located in the air inlet port.
The following damper types are available:
-- fresh air damper e1 - mandatory for C
modification (with mixing damper)
-- fresh damper e1 LF - mandatory for T
modification (with heating coil)
-- exhaust air damper i1

Fe.xxx; Fi.xxx
Air filtration
All DUPLEX units can be equipped with supply air
filtration of F7 class instead of standard G4
class. Pressure drop of the filter is then 50
to 100 Pa (clean filter) depending on air flow
rate, unit type and dirt accumulated.
Prefilters made of multilayer expanded metal
can be supplied.

R-TPO.x; RS-TPO.x
Heating coil
hydraulic kit
Its function is to control heating capacity
of a heating coil. It consists of a three-speed
pump, two globe shutoff valves and connection
pipes. Further equipment depends on the type:
- R-TPO-4 - four-way mixing valve with
an actuator for digital control system
- R-TPO-3 - three-way mixing valve with
an actuator for digital control system
- RS-TPO - three-way diverting valve with
a thermostatic valve for electric control
system

R-CHW.x
Cooling coil
hydraulic kit
Its function is to control cooling capacity of
a chilled-water cooling coil. It always consists
of two globe shutoff valves and connection pipes.
Further equipment depends on the type:
- R-CHW-3 - three-way mixing valve with an
actuator and a three-speed pump for digital
control system
- R-CHW-2 - throttling valve with an actuator for
digital control system
Available in several sizes based on required
capacity.

Double insulation
It is possible to increase polyurethane insulation
to 45 mm thickness (U = 0,52 W/m2K).
Then outer dimensions of the unit are 40 mm
larger in all directions compared to catalog
dimensional data.

CHF
A
B,C

H.P
Flexible
connections
Round and rectangular ports can be equipped
with flexible connections upon request.

Delivery of diassembled unit


All units can be delivered dismantled on request.
The unit is to be assembled by rivets and bolts
directly on site, therefore the unit can be
installed in inaccessible location.

Hingeless door
When needed it is possible to deliver door
without standard hinges, only with quick lockes
or spring fasteners - than necessary
manipulation space is reduced.

RCHF.x
Accessories
for DX coil
It is possible to equip the DX coils with
refrigeration circle components: expansion valve
with an orifice (A), solenoid valve (B, C),
sight glass (D), filter-drier (E), eventually
with an evaporator pressure regulator.

NFT.x
Spare filtration
textiles
Spare filter textiles in sizes depending on unit
type. They are available in the filtration
of G4 and F7 class.

Hot water heating coil (TPO)


Separately supplied coil for installation into
round duct.
It is suitable for cramped locations, where
it is impossible to put the coil inside the unit,
as well as for rooftop units.
The coil is standardly equipment with the steamgas capillary thermostat.

Electric heating coil (EPO-V)


Separately supplied heating coil to be fitted into
round or rectangular duct. Capacities and
diameters can be found in respective catalogue
sheets.

Fe.D
Polarisation filter
Additional supply air filter (DYNAMIC), including
24 V transformer and spare filter textile.
For pressure drop data see respective graphs.

CONTROLS
DUPLEX-S units are delivered with basic control components
or with complete control systems.
There are two types of control systems available (electric,
digital) according to customer needs and application.
The systems also include variety of sensors (temperature,
humidity, air quality, CO2) for effective operation control.

Features of the control systems


selection of the most suitable and efficient control system
at the lowest cost, depending on the particular application
control system is integrated with the unit, most components
are already wired and checked in factory, thus reducing the
risk of incorect wiring
no control system project documentation is necessary
for standard cases, standardized solutions can be used
simple wiring, system simplicity, error indication
qualified technical support and consulting

SUMMARY OF DUPLEX CONTROL SYSTEMS

Use

Type

Characteristics

A basic

all electrical components are wired


to a junction box terminal strip
inside or outside the unit
standard components are fans,
damper actuators, capillary freeze
protection thermostat of hot water
heating coil
more components is included upon
customer's request (exact
actuator type, sensors,
thermostats, pressure switches
etc.)

suitable for applications


with separate delivery of
control system; e.g. large
buildings with central
control system etc.

simple system
two-speed fan control (MIN, MAX)
(exact volume flow rate can
individually be set for each fan
during commissioning)
on/off control of by-pass and
mixing damper
on/off remote control of heating
coil: temperature is set on the
thermostatic valve of hot water coil
or directly on the electric coil

electric system is suitable


for simple applications
(e.g. ventilation of locker
rooms, gyms, restaurants
etc.)
it cannot be used for units
with cooling coil
it is recommended for
applications with air reheat
only (not for warm-air
heating)

control system designed specially

suitable for kitchens of all


types and sizes equipped
with kitchen hoods of all
types (e.g. DiNER,
VARIANT, STANDARD)
or by ventilation ceilings
(SKV)
hot water or electric
heating coil control
according to supply air
temperature (OP-T)
by-pass control
summer / winter
operation (OP-T-BP)

RG

OP

SM

E DC-series
digital control

for effective control of kitchens


consist of SM microprocessor
module fitted into kitchen hood
or ventilation ceiling, OP control
panel and RG junction board
control principle consists
of automatic setting of volume flow
rate depending on heat production
of kitchen appliances (i.e. difference
of temperatures under the kitchen
hood and in the space)

A comfort control system for


DUPLEX units
A programmable module software
designed especially for DUPLEX
units
Supply and exhaust fan speed
control
Controlling supply or room
temperatures
Optional control of a water and
electric heating coil
Optional water and direct cooling
Heat pump performance control
Automatic control of by-pass and

Suitable for comfort


applications
Optional fully automatic
operation of the unit via a daily
or weekly programme
Possibility to connect air
quality, Co2 concentration and
relative humidity sensors etc.
Optional performance control
via a 0-10 V signal from a
higher-ranking system
Connectable to central
control systems using
expansion cards (KNX,
Modbus, ...)
Settings can be done using
the connected graphic
controller

basic function
+
elect. heater control
(SR module)
Electric heater
(basic modification)

DUPLEX-T
basic function
+
water heating coil
(SR-T module)

HYG, QPA, PS
(humidity sensors,
air quality, movement)

DUPLEX

230 V
50 Hz

DUPLEX
basic control

kitchen hood /
ventilation ceiling SKV

OP controller
(OP-T, OP-T-BP
options)

D for kitchens

Supervisory control system

OPS 1series control panel


basic series

OPS

basic version
(fans, actuators, thermostats,
pressure switches
and others on request)

RG junction box

B electric

Simplified diagrams of electrical wiring

control module
SM

Controllers
DC-p1, DC-p2

DUPLEX
DC control
(module DC-XS)
(module DC EXPc)

Communication
protocols
KNX, Modbus,
TCP/IP
External
components