Sie sind auf Seite 1von 2

EPO-PTC

Direct electric
air heaters

As standard EPO-PTC heaters include:


electronics to allow starting the electric heater via
a 1024 V DC signal (RME-PTC)
A power switching feature with so-called "zero" switching
(SSR)
An operation sensor programmable in a range of 040 C,
connected in the control circuit
A programmable operation sensor to control the use of the
electric heater (pre-heating / reheating), connected in the
control circuit
Two safety control thermostats with manual reset at 70C
in the power circuit; they are located at the beginning and
end of the electric heater (backflow protection)
A filter made of expanded metal, which can be cleaned from
the outside, to filter out coarse contaminants when the
EPO-PTC is used as a pre-heater

EPO-PTC

EPO-PTC (Positive Temperature Coefficient) direct electric air


heaters and re-heaters are generally used to heat air in ducts
in ventilation systems or to protect heat-recovery exchangers
from freezing by pre-heating supply air.
The heaters are installed only when linked to DUPLEX Easy
and EC4 / ECV4 series heat recovery ventilation units.
EPO-PTC heaters are round, with diameters of 125, 160, 200
and 250 and capacity levels between 0.4 kW and 1.75kW.

Control

Warning:
EPO-PTC series direct electric air heaters are intended for
normal environments only. The heaters have a protection
rating of IP 40. The operating temperature of air downstream
of the heater is up to 40 C (dust particles inside the heater
do not get burnt).
When the unit's air flow rate is decreased, the power input of
the PTC heater is lowered. The heater can be thermally
insulated to a thickness of 3050 mm, with the cover to
remain permanently accessible. Insulating material used must

comply with fire response class of building materials A1, A2


(as per CSN 73 0810), or must be self-extinguishing with
thermal resistance up to 170 C.
The electric heaters must be installed and located strictly in
compliance with CSN 33 2000-4-42 (IEC 364-4-42) which
stipulate conditions for heat protection, fire protection,
protection against burning and protection against
overheating, including relevant protective and safety circuits.
The heaters comply with CSN EN 60335-1 A11, A1
and CSN EN 60335-2-30 A1.
The air being drawn in cannot contain dust, contaminants or
corrosive substances. The air flow direction must follow the
arrow on the heater.
Connection to mains electric must be done according to
regulations and standards in force and is subject to approval
inspection.
The heater can only be run provided that:
The supply fan is running (the fan's run-down time is not
required after stopping)
3
A minimum flow rate of 30 m /h is provided

Residential ventilation and heating issue 12/2013

T E C H N I C a L D ATA

EPO-PTC 125 / 0.7


EPO-PTC 160 / 0.4
EPO-PTC 160 / 0.7
EPO-PTC 160 / 1.7
EPO-PTC 200 / 0.7
EPO-PTC 200 / 1.7
EPO-PTC 250 / 1.7

Size

Voltage
(V)

Max. capacity
(kW)

Recommended
protection rating
(A)

CYKY supply
cable size

Min. flow rate


(m3/h)

Min. fan
run-down time
(s)

125
160
160
160
200
200
250

1x 230 V~
1x 230 V~
1x 230 V~
1x 230 V~
1x 230 V~
1x 230 V~
1x 230 V~

0.7
0.4
0.7
1.7
0.7
1.7
1.7

10
10
10
10
10
10
10

3J x 1.5
3J x 1.5
3J x 1.5
3J x 1.5
3J x 1.5
3J x 1.5
3J x 1.5

30
30
30
30
30
30
30

0
0
0
0
0
0
0

Notes: The heaters are designed for TN-C-S networks.


The recommended sizes of supply lines are stated for the standard manner of laying, arrangement and number of cables
(anindependent and horizontal arrangement, quiet air, ambient temperature 30 C). The sizing of cables must be adapted to reflect
the manner of laying, arrangement and number of cables.

SELECTION SOFTWARE

s a v e

y o u r

e n e r g y

To configure EPO-PTC series electric heaters


you can also use the advantages of our
specialized selection software. You can find it
on our website www.atrea.cz or request it at
our address.

E S I D E N T I A L

V E N T I L A T I O N

ATREA s.r.o., V Aleji 20


466 01 Jablonec n. N.
Czech Republic

&

H E A T I N G

Phone: +420 608 644 689


Fax: +420 483 368 112
E-mail: expor t@atrea.cz
www.atrea.cz

EPO-PTC
DIMENSIONAL DRAWING

190

115

60

Expanded metal filter

Safety and control


thermostat 0 to +40 C

30

Inspection opening

EPO-PTC 125 / 0.7


EPO-PTC 160 / 0.4
EPO-PTC 160 / 0.7
EPO-PTC 160 / 1.7
EPO-PTC 200 / 0.7
EPO-PTC 200 / 1.7
EPO-PTC 250 / 1.7

D
(mm)

Weight

125
160
160
160
200
200
250

360
360
360
360
360
360
360

225
260
260
260
300
300
350

2.5
3.0
3.5
4.5
5.0
6.0
7.5

CONDITION OF INSTALLATION AND ELECTRICAL CONNECTION

PERMITTED POSITIONS OF TERMINAL BOARD


EPO-PTC
PE
N
L1

Heater power supply: ~ 230 V / 50 Hz

LS
Y1
G0

Supply lines to humid or corrosive environments must have


areturn damper fitted and no return air flow through the
heater must take place.

Heater switching: digital signal (OFF / ON) 1024 V DC


(Y1 = positive voltage, G0 = earth)

When an EPO-PTC electric heater is used together with


aDUPLEX unit with integrated control system, this control
system ensures all conditions for the safety operation of the
heater are met.
EPO-PTC heaters must not be used on their own or with
different HVAC appliances.

Das könnte Ihnen auch gefallen