Beruflich Dokumente
Kultur Dokumente
LogicPro v1.5
User Manual
OMICRON LogicPro
Table of Contents
TABLE OF CONTENTS
About This Guide ......................................................................................................................... 1
Before you start............................................................................................................................ 2
Prerequisites ................................................................................................................................ 2
69
69
71
71
72
72
73
Remote-End-Opened................................................................................................................. 74
Objective....................................................................................................................................
REO logic description ................................................................................................................
Fault locations............................................................................................................................
Test Cases.................................................................................................................................
Hardware Requirements ............................................................................................................
74
74
76
76
76
OMICRON LogicPro
79
79
80
81
81
82
82
Load Encroachment................................................................................................................... 84
Objective ....................................................................................................................................
LE logic description ....................................................................................................................
Fault locations ............................................................................................................................
Test Cases .................................................................................................................................
Hardware Requirements ............................................................................................................
Automatic test sequence............................................................................................................
Test object settings ....................................................................................................................
84
84
85
86
86
87
87
88
88
89
90
90
91
91
93
93
94
95
95
96
96
Power-Swing-Blocking ............................................................................................................... 98
Objective .................................................................................................................................... 98
PSB logic description ................................................................................................................. 98
Fault locations .......................................................................................................................... 100
Test Cases ............................................................................................................................... 100
Hardware Requirements .......................................................................................................... 101
Automatic test sequence.......................................................................................................... 102
Test object settings .................................................................................................................. 102
Table of Contents
Power-Swing-Tripping.............................................................................................................. 103
Objective..................................................................................................................................
PST logic description ...............................................................................................................
Fault locations..........................................................................................................................
Test Cases...............................................................................................................................
Hardware Requirements ..........................................................................................................
Automatic test sequence .........................................................................................................
Test object settings ..................................................................................................................
103
103
104
104
104
105
105
106
106
107
108
108
109
109
111
111
112
113
113
114
115
116
116
117
118
118
119
119
121
121
123
123
123
125
125
OMICRON LogicPro
127
128
128
129
129
131
131
132
133
133
134
134
OMICRON LogicPro
Recommended:
Pentium 166MHz
64 MB RAM
Windows 95, Windows NT4.0 or higher
(32-bit Windows)
OMICRON LogicPro
install and run the software on computers other than those controlling
OMICRON test equipment
Copyright
The software is property of OMICRON and is protected under copyright law.
Warranty
The manufacturer agrees to remove all defects occurring during the first 90 days
free of charge. A defect is defined as follows: The software does not have
significant function, properties or does not meet performance specified in the user
manual.
If any warranty claim is made, the original packing of the device must be used to
return it in order to prevent the warranty claim from becoming void.
The manufacturer is not liable for lost profit, damages to saved data or other
indirect or consequential damages.
10
The electric power utility industry is going through significant changes due to
deregulation, downsizing and free wheeling, etc. Power System Protection and
Control departments face multiple challenges of their own:
Utilities can best insure optimal selection of the protection by benchmarking using
appropriate tools. In addition, proper relay settings and operation for their particular complex
problem need to be guaranteed by use of comprehensive test procedures.
Another improvement is to use data from the field to test protection systems. Modern
microprocessor relays allow the user to collect disturbance data from the field.
This data can be used for evaluation of the protection system performance and for
benchmark testing of new products, by directly comparing their performance under
identical power system and fault conditions.
11
OMICRON LogicPro
Overview
distance relays
current differential relays
directional comparison relays
phase comparison relays
The development of the different packages is prioritized based on the popularity of
a certain protection principle, i.e. the number of protective relays of specific type
manufactured and installed. In Transmission Line Protection without a doubt the
most popular relay is the Distance Relay. Because of that, the distance principle
Transmission Line Protection Testing Software is the first to be developed.
12
Considering the main goal of the Performance Testing to be the evaluation of applicability of
a specific distance type multifunctional protective relay to different transmission line
configurations and realistic power system conditions, the different groups of tests included in
the package are of the Dynamic State Test Type and Transient Simulation Test Type
(depending on the requirements of each particular test).
13
OMICRON LogicPro
14
Substation 1
Zone 1
Forward
Zone 2
Forward
Substation 2
Distance
Relay
Figure 0-1:
The transmission line distance protection relay with two forward looking zones, is
shown in ( Figure 0-1, page -9 )
Different fault conditions and the operations of the breakers after a fault occurs
have also to be considered in the design of the protective relays.
The requirements for improved stability of the power system during fault conditions
result in the use of single pole tripping and reclosing. The performance of different
relay protection elements related to this mode of operation are also covered by
special logic schemes.
There are several different types of conditions that have to be considered:
Abnormal power system conditions include power swings or overloading of the
transmission lines during a power system disturbance.
Failure of voltage or current transformers or the circuits connecting them to the
analog inputs of the relay leads to a difference between the primary currents and
15
OMICRON LogicPro
voltages in the power system and the currents and voltages measured by the
relay.
Breaker failure under fault conditions and non-fault conditions, for example
overvoltage during light loading of long transmission lines, presents a different kind
of problems to the distance relay.
To address all the requirements for speed and selectivity of operation during fault
conditions, as well as to avoid maloperation under abnormal, but non-fault
conditions, modern transmission line protection relays have multiple built-in logic
schemes.
The communications based schemes, such as Permissive Overreaching or
Blocking schemes are covered by the CommPro software.
LogicPro is designed for the testing of the more typical non-communications based
logic schemes that still play a very important part and define the overall
performance of distance transmission line protection relays.
Logic Pro test cases are divided in two groups as a function of the selected mode
of tripping - single pole or three pole.
In both cases the following modules are available for testing of
non-communications based logic schemes in modern distance relays:
Switch-Onto-Fault
Remote-End-Opened (Loss-of-Load)
Zone 1 Extension
Load Encroachment
Breaker Failure Protection
Block Reclosing
Power Swing Blocking
Power Swing Tripping
Loss-of-Potential (Voltage Transformer Supervision)
Current Transformer Supervision
Stub Bus Protection
The inputs and outputs of the CMC are programmed in such a way, that allows the
testing of all the above schemes without any rewiring between the CMC and the
test object.
If a Single Pole Tripping option is selected, three additional test modules become
available:
16
Before running these three tests, the test engineer or technician will have to
change the wiring according to the diagrams in the Hardware Requirements in
order to be able to monitor the trip outputs for each individual phase.
They allow the relay to operate with high speed for conditions that challenge
the operating principle of the main protection element - the distance protection
They ensure the stability of relay operation during abnormal power system
conditions such as power swings or overloading of the transmission lines
They allow the relay to correctly detect the failure of a breaker to trip under
fault or non-fault conditions, as well as to detect the opening of a remote
breaker in order to accelerate the tripping of the local breaker
The relay can selectively trip one or all three phases for simple or evolving fault
conditions
17
OMICRON LogicPro
18
Getting results
GETTING RESULTS
Test task
Modes of operation
The software can be used for different purposes and in different modes as described in detail
later in the document.
The first mode is for benchmarking or complete evaluation purposes. In this case
multiple logic schemes are selected in a point-and-click manner and the
software automatically executes a series of predefined tests, measures the relay
under test response, analyses the results and prepares the test report.
The second mode is for testing of a specific logic scheme, for example a
Loss-of-Potential (Voltage Transformer Supervision) Scheme. In this case the
software automatically executes a series of predefined tests required for the
19
OMICRON LogicPro
selected scheme, measures the relay under test response, analyses the results
and prepares the test report.
The third mode of operation of the software is for training purposes. It includes
multiple animated demonstrations of the sequence of events and the operation of
different relay elements at each step of a test sequence. This tool is designed to
help a protection or test engineer or technician with limited experience to
understand the dynamics of the logic schemes operation and the functioning of the
relay logic for different fault conditions and different substation or power system
equipment performance.
Switch-Onto-Fault scheme
Remote-End-Opened (Loss-of-Load) scheme
Zone 1 Extension scheme
Load Encroachment scheme
Breaker Failure Protection scheme
Block Reclosing scheme
Power Swing Blocking scheme
Power Swing Tripping scheme
Loss-of-Potential (Voltage Transformer Supervision) scheme
Current Transformer Supervision scheme
Stub Bus Protection scheme
Single Pole Tripping scheme
Evolving Fault scheme
Pole Dead Logic scheme
The logic for each of the above listed schemes is based on existing documents
and may be implemented with modifications in specific products.
The testing of logic schemes is intended to evaluate the performance of the Test Object
under different fault, system and substation conditions.
Different tests are designed to monitor the relay operation for the following fault
conditions:
Zone 1 fault
Zone 2 fault on the protected line
Zone 2 fault outside of the protected line
20
Getting results
Single- phase-to-ground faults, three phase faults or evolving faults are applied
depending on the requirements of the tested logic scheme.
Some of the logic schemes apply to the relay under test abnormal system
conditions such as:
power swing
overload
overvoltage
TEST METHODS
The testing of distance relays with built-in logic schemes can be performed in
several different ways
USING FIXED INPUT STATUS
In this mode the testing of relays is performed with their inputs energized
constantly and not synchronized with the test equipment. This approach can be
used for testing of very simple relay functions. It does not adequately represent the
dynamics of real life events and has very limited application for testing of modern
microprocessor based transmission line protection relays.
Using this method the test engineer or technician can test just a simple scheme,
For example:
if a Switch-Onto-Fault scheme is tested,
the breaker status monitoring input of the test object will be continuously
de-energized and when the fault currents and voltages are applied by the test
device, this should result in switch-onto-fault.
It is obvious that this method can not be used for testing of more advanced logic
schemes, such as Evolving Fault or Current Transformer Supervision.
21
OMICRON LogicPro
This approach can be used for testing of very complicated relay functions. It allows
for an adequate representation of the dynamics of real life events and can be used
for advanced testing of modern microprocessor based transmission line protection
relays.
For example:
using this method the test engineer or technician can test not only a simple
Switch-Onto-Fault scheme, but also more advanced logic schemes, such as Permissive
Overreaching Unblocking. In this case in the pre-fault condition a communication status
signal (guard frequency available) will be simulated, which under fault conditions will change
to a trip frequency Carrier Receive.
The fundamental requirement in the LogicPro software is ease of use. The goal is to achieve
maximum results with a minimum effort. That is why, the test configuration and execution
efforts in most cases are limited to a point-and-click action.
For example, if the test is for a Switch-Onto-Fault scheme and the test conditions
are breaker opened with a closing onto a fault, the sequence will include only three
steps:
pre-fault with breaker in a closed position, nominal voltage and normal load
current conditions
22
Getting results
To simplify the testing, the current and voltage levels are limited within the output range of
the basic CMC module (no amplifiers are required). This way there is no need for the user to
define the requirements for the CMC.
OVERVIEW
As mentioned earlier, the goal of the LogicPro software is to allow the testing of logic
schemes and comparing the performance of different relays under identical test conditions.
During the testing of the previously listed schemes all phase and ground distance
zone settings remain the same. The only changes made are in the logic scheme
selected for each individual subgroup of tests and the relay settings specific to the
scheme under test.
The fault currents and voltages are calculated based on a simple network model,
since it is assumed that the basic distance functions have already been tested
using more sophisticated test methods.
The following sections in this chapter describe the network model used for the
calculation of the fault currents and voltages and the settings of the test object
corresponding to this model.
Since the software has test and training modes of operation, the global test data is
entered by the user only if one of the two test mode options has been selected.
NETWORK MODEL
Because only a single end relay is tested, the network model used for calculation
of short circuit currents and voltages for a Zone 1 or Zone 2 fault is a steady state
single source fault analysis model.
23
OMICRON LogicPro
Substation A
50 miles
Type Delta
0.625 omhs/mile
120 kV
Figure 0-1:
A 120 kV, 50 miles long line with delta configuration is used in the default model.
The system is homogenous (i.e. source and line impedances have the same
angle) and the Source to Line Impedance Ratio is SIR = 1.
The line impedance is 0.625 primary ohms per mile. The default line impedance
angle is 75 deg.
The zero sequence impedance is 2.5 primary ohms per mile. The line zero
sequence impedance angle is 75 deg.
The zero sequence to positive sequence impedance ratio is 4 and the zero
sequence compensation factor KL
If the rated current of the distance relay under test is 5 amperes, it is assumed that
the CT ratio setting is
24
Getting results
It is assumed that the rated voltage of the distance relay is 120 V phase-to-phase
and the VT ratio setting is
ZS = 12.5 ohms
The source angle is 75 deg (default homogeneous system) and the K-factor
KS = 1.0
25
OMICRON LogicPro
need for amplifiers. This simplifies the hardware configuration requirements for the
testing.
Three phase voltages and currents are required from the CMC to the relay under
test.
A different number of binary outputs of the CMC are programmed to simulate the
relay environment as a function of the scheme under testing.
A different number of binary inputs of the CMC are programmed to monitor the
relay operation as a function of the scheme under testing.
TEST OBJECT SETTINGS
The expected basic settings of the multifunctional relay under test associated with
the communication based schemes are given below.
26
Getting results
Zone 1:
An 80% reach setting for Zone 1 is expected
In polar coordinates
In rectangular coordinates
Zone 2:
A 120% reach setting for Zone 2 is expected
In polar coordinates
In rectangular coordinates
27
OMICRON LogicPro
If the distance relay settings are entered using the positive and zero
sequence impedance for the different zones, the zero sequence impedance,
resistance or reactance settings should be calculated based on the 50 ohm
zero sequence secondary line impedance.
Switch-Onto-Fault scheme
Remote-End-Opened (Loss-of-Load) scheme
Zone 1 Extension scheme
Load Encroachment scheme
Breaker Failure Protection scheme
Block Reclosing scheme
Power Swing Blocking scheme
Power Swing Tripping scheme
Loss-of-Potential (Voltage Transformer Supervision) scheme
Current Transformer Supervision scheme
Stub Bus Protection scheme
Single Pole Tripping scheme
Evolving Fault scheme
Pole Dead Logic scheme
Steps in testing
Multifunctional transmission line protection relays are very complex devices that
require during testing adequate simulation of their operating environment, to
ensure that they will perform correctly when installed in the field. There is a
sequence of steps related to the testing of electromechanical, solid state or
microprocessor based relays using different logic schemes for improved fault
clearing. They depend on the goals of the test and the level of knowledge of the
relay under test and it's operating principles
28
Getting results
If the user is familiar with the principles of the distance relay under test and the
LogicPro software, he/she can proceed with the actual testing process.
For testing of multiple logic schemes in a new distance relay, the user should
follow the step-by-step procedure described in Multiple Scheme Test Mode.
To test a specific logic scheme, the steps required are described in Single
Logic Scheme Mode.
The user has to select the appropriate settings for each logic scheme.
Analyze the Test Results
If the automatic analyses of the Test results indicates that some tests have failed,
the user should check the required wiring, relay operating times, relay settings,
relay logic diagrams, etc., to determine the reasons for the specific test failure.
29
OMICRON LogicPro
30
Figure 1-1:
31
OMICRON LogicPro
Figure 1-2:
At this stage it is not required to have a CMC test device connected to the
computer for the software to run.
II
32
Figure 2-1:
The individual scheme control window has multiple control buttons that can be
enabled or disabled depending on the actions of the user. Some of the control
buttons used for the graphical user interface can also be visible or invisible at
different times. This reduces the chances for an inappropriate action by the
LogicPro software user.
33
OMICRON LogicPro
Figure 2-2:
1 Ph Failure
Single Ph Fault
1 Ph Failure with Fault
6. On the bottom of the window a LEGEND with the symbols used in the graphics
and animation is displayed ( See Figure 2-3, page - 29 ).
34
Figure 2-3:
IOC
- Instantaneous Overcurrent
Note:
It is recommended
for users that do not have
experience in power system
or transmission line
protection, to start by
selecting the Slow speed
option.
Figure 3-1:
The frame with the animation speed options will be enabled and it's label will turn
red when the animation mode is selected.
It includes three option buttons. Select a slow, medium or fast speed depending
on your knowledge of the specific scheme displayed.
35
OMICRON LogicPro
IV Start Animation
1. Click on one of the available animation control buttons bellow the label saying
Click bellow to start Animations .
For example, to watch the test sequence and relay operation for a single phase
voltage circuit failure, click on the Single Ph. Failure.
During the animation each of the relay elements that are involved in the scheme
logic is displayed with a different color depending on it's status.
When an element picks-up, it's color will change from black to red, and when it
drops-out, the color will change back from red to black.
2. At the start of animation, a few additional changes occur:
A new Pause control button appears in the animation control frame (See
bottom of ( Figure 2-3, page -29 ). It allows the user at any moment to stop
the animation at the current state, so the current status of the simulation
and relay performance can be reviewed in detail. It changes to Continue
when clicked. If you want to proceed with the animation, click on Continue.
The status bar will display the name of the chosen fault scenario (See
bottom of ( Figure 4-1, page -30 ) and ( Figure 2-3, page -29 )
A progress bar ( Figure 2-3, page -29 ) will appear, showing the progress
of the animation
The Animated logic scheme Status Legend - 1.1 ( Figure 4-2, page -31 ),
will appear
The Animated logic scheme Status Legend - 1.2 ( Figure 4-3, page -31 ),
explains different stages of the process
Figure 4-1:
The Animated logic scheme Status Legend ( See Figure 4-2, page - 31 ) and (
Figure 4-3, page -31 ), which changes in accordance with the animation, shows
the details at any moment of the process.
The Name of the state ( Figure 4-2, page -31 ) - the Pre-Fault condition is shown
in red, while the State number (State 1) and the State Time is displayed in white
when it is a non-fault state or in red, when it is a fault state ( Figure 4-3, page -31 )
36
Figure 4-2:
Figure 4-3:
3. A second timer to the right of the progress bar displays the current simulation
time since the fault inception ( See Figure 4-4, page - 31 )
Figure 4-4:
1. To view the objective of the test included in the LogicPro software, click on the
Test Objective command button.
37
OMICRON LogicPro
Figure 5-1:
38
Figure 6-1:
There are several options to print the information related to the communication
scheme under consideration.
To Print:
1. Click on the Print option in the Menu bar on top of the Scheme Control window
2. Select the information to be printed
3. The Print dialog box will appear, allowing the user to specify a printer, if
necessary.
The following options for printing ( See Figure 7-1, page - 34 ) are available:
1. the Scheme Logic as displayed during the animation
2. the Test Objective
3. the Hardware Requirements for the selected scheme
4. the complete Scheme Documentation (all options offered above) for the
selected scheme
39
OMICRON LogicPro
Figure 7-1:
40
GETTING RESULTS
IN
The goal of the test is usually a benchmark test of the logic schemes of a new to the utility
distance relay.
To perform such a test, the user should follow the step-by-step procedure
described below.
Note: It is recommended to set all available setting groups with different logic schemes,
especially the mode of tripping-Single or Three Pole, and then during the test to switch
between the setting groups as required by the test selected.
Check the required time settings for each scheme in the protection users manual.
1. Wire the Test Object (distance relay), DC power supply (if necessary) and the
Test Device (CMC x56) according to the diagrams shown in Hardware
Requirements for each of the individual schemes.
All logic schemes with Three Pole tripping mode can be tested without the
need for changes in the wiring between the Test Device and the Test
Object.
If Single Pole tripping is selected, a change in the wiring is required for the
last three tests.
2. Connect the parallel cable between the Test Device and the Test Computer
with LogicPro installed.
Note: Check if the relay uses 52a or 52b breaker status contacts. LogicPro simulates
52a breaker status.
41
OMICRON LogicPro
The analysis of the distance relay performance during the test is based on the
expected operating times, of tested relay elements under different fault conditions.
The software is loaded using some default settings. However, if the user needs to
change them based on the technical specifications of the distance relay under test,
the default setting can be changed using the following steps:
42
Note: The default times for Zone1 (50 ms) and Zone2 (250 ms) faults, include a margin of
50 ms, i.e. Zone1 is set as instantaneous, while Zone2 is set with time delay of 200 ms.
Figure 4-1:
Figure 4-2:
43
OMICRON LogicPro
Figure 4-3:
3. Review and change the settings in the Change Settings window accordingly.
to review or edit the Primary Settings - Select the PRIMARY option ( See
Figure 4-4, page - 39 )
to edit CT Ratio and PT Ratio Settings - Select Nominal Values and then
select the PRIMARY option. The window will display CT Ratio and PT Ratio
options. ( See Figure 4-6, page - 41 )
To change the Zone 1 fault location (should be less than 100%) - enter
the new number in the Fault Location field, as a percentage of the line
impedance. This option is available both in Secondary and Primary.
4. To apply the New Setting - press the Apply button.
5. To return the Default Setting - press the Default button.
6. To Cancel and Exit the window with restored Default Settings - Press the
Cancel button.
7. To Exit the window with the new entered Settings - Press the OK button.
44
The Line impedance Settings window ( Figure 4-3, page -38 ) displays the
Secondary settings as Default.
Figure 4-4:
If PRIMARY Settings are displayed - the Secondary Settings will be disabled and
grayed out.
Changes in the Primary Impedance are automatically reflected in the Secondary
Impedance. When the Apply button is pressed - the program will apply the settings
and automatically will recalculate the SECONDARY Settings and display the
changes based on modification in the CT or PT ratio.
Note:
Based on Secondary Line Impedance, the software automatically calculates the
fault voltages and currents to be applied for Zone 1 and Zone 2 faults, when the user clicks
on Apply or OK buttons.
45
OMICRON LogicPro
Figure 4-5:
to review or edit the Primary Settings - Select the PRIMARY option ( See
Figure 4-6, page - 41 )
46
Note: The user has an option to select to enter the voltage values as Phase-to-Neutral
(default) or Phase-to-Phase.
Note: The default frequency setting is 60 Hz. When the user decides to change it for the
first time, the software will ask, whether to leave it as a new default.
Figure 4-6:
If PRIMARY Settings are displayed - the Secondary Settings will be disabled and
grayed out.
Changes in the Primary Currents and Voltages are automatically reflected in the
Secondary. When the Apply button is pressed - the program will apply the settings
and automatically will recalculate the SECONDARY Impedance Settings and
display the changes based on modification in the CT or PT ratio.
47
OMICRON LogicPro
The Nominal Values Settings window ( See Figure 4-5, page - 40 ) displays the
Secondary Settings for the currents and voltages as default.
Figure 4-7:
Breaker/VT Settings
The 3 Pole Trip/Close option is a default, and causes the following modifications
in the Main selection window ( Figure 1-2, page -26 ):
To enable them: Select Single Pole Trip/Close option in the settings window (
Figure 4-7, page -42 ) instead of the default 3 Pole Trip/Close option.
the names of the last 3 logic schemes are displayed in red color
the Check Box controls in front of those schemes are disabled
48
Figure 4-8:
Figure 4-9:
The calculated Fault Currents and Voltages for Zone 2 faults (Single Phase Faults
and 3 Phase Faults), appear at the bottom of the window ( See Figure 4-10,
page - 44 ). The Vnom, Line Impedance and Source Impedance used for the
calculations, are also displayed.
49
OMICRON LogicPro
The Settings are directly accessible from here, and when clicked, the Settings
options window will appear on the top of the current window.
The changes made in the settings will be automatically reflected in the calculations
of the Fault Currents and Voltages.
V Scheme Selection
50
Figure 5-1:
Note: The names of the last three schemes are in red color and the Check
Box controls in front of them are disabled when 3 Pole Trip is selected.
To enable them:
Click OK.
51
OMICRON LogicPro
The color of the names of the last three schemes will change to normal and the
Check Box controls in front of them will be enabled.
As soon as the user clicks on any of the Check Boxes, the Main Selection window
changes as shown in ( Figure 5-2, page -46 ).
Figure 5-2:
Based on the selected logic schemes the software displays Test Boxes with
the test cases associated with each selected scheme on the left side of the
schemess Check Boxes. Each individual test case can be un-selected by
its check box. ( See Figure 5-2, page - 46 ).
When all tests have been completed, the Test Details window will display
the test summary.
52
2. Another option is to click on the Clear control button at the bottom of the
window, that will result in displaying the default.
To exit the software at any time, just click on the Exit button.
VII
1. As soon as the Start Test button is clicked, a Message Box ( See Figure 7-1,
page - 47 ) will appear before the beginning of the test asking the test engineer
or technician to check if the CMC is on.
If the CMC is on, just click Yes. Otherwise turn on the CMC and then click
Yes, so that the tests may be performed.
The second option is to select No, which will disable the Start Test button
and reset the selected test cases.
Figure 7-1:
CMC On - Off
2. After the CMC is turned On, it is initialized and starts the preprogrammed and
selected tests execution.
53
OMICRON LogicPro
1. Before the execution of each group of tests associated with a specific logic
scheme, the user is reminded by the software ( Figure 8-1, page -48 ) to
enable the logic scheme setting of the distance transmission line protection
relay to match the expected by the test scheme.
Figure 8-1:
2. If the scheme has already been enabled or after the change, proceed by
clicking on the OK command button.
IX Tests Execution
1. The running test will display a flashing yellow background. At the same time to
the right of the selected test cases a small screen TEST Status will show a
brief description of each test.
Note: Before the execution of an individual test the background of the Test Box is
white.
2. Immediately after each individual test is completed, the result is analyzed and
the background of the Test Box changes color.
If the relay operated as expected, the test is OK and the background turns
green.
If there is any out of range operation the test fails and the Test Box
background turns red.
54
After the completion of all tests the results are visible as the background color of
the Test Boxes.
If the Multiple Schemes test is successful, the background of all Test Boxes should
be green.
The Test Details window at the same time displays a message All tests are OK.
If even one test has failed, the Test Details window displays a different message. It
advises the user to check the relay logic, settings, etc., and the test objectives, and
results in the Test report.
3. If necessary, the test engineer can preview the Test report, print it and save it
as a file.
4. After all tests have been executed, the Print Report button in the Main
Selection window is enabled so that the test report can be previewed and/or
printed.
5. When the Print Report button is checked the Data Entry form is displayed as
well.
1. Before the test results are previewed or printed, the user is asked to fill in the
generic data for the test report.
Some of the entries are required and are supposed to be entered in the
white fields.
The rest of the fields are optional and have gray background, as shown on
( Figure 10-2, page -50 ).
The software will keep the entered information for a specific field, if the
Check Box in front of the field is checked.
55
OMICRON LogicPro
The software allows the user to save as a file for further use, the most
frequently used information, (as shown in the detail ( Figure 10-1,
page -49 )
2. When the Close button is pushed a message will appear, warning that the
entered data related to the completed tests will be lost.
The measured operating times, the monitored protection functions for each
individual test are stored in the memory of the computer and are available in the
test report.
1. To preview these detailed test results, click on the Preview Report command
button in the Data Entry form.
2. As a result, the Test Report window shown in ( Figure 11-1, page -51 ) and (
Figure 11-2, page -51 ) is displayed. You can scroll through the report as
necessary.
56
Figure 11-1:
57
OMICRON LogicPro
1. Click on Save As File button in the Data Entry window ( See Figure 10-2,
page - 50 )
2. The Save As window will open allowing the user to choose directory and file
format.
3. Unless changed, the File will be saved as Rich Text Format.
To print the results from the Multiple Test, click the Print Report command button
in the Data Entry form ( Figure 10-2, page -50 ). The Print dialog box is displayed,
allowing the user to specify a printer, if necessary.
XV Help
OMICRON Logic Pro software offers brief on-line explanations for the major tasks
to be performed. The Help Topics are accessible only through the Menu in the
Main Selection window. To see the different topics, click on Logic Pro Help
Topics... ( See Figure 15-1, page - 53 )
58
Figure 15-1:
The help window opens with brief overview of the software, displayed in the front
page. ( See Figure 15-2, page - 53 ).
59
OMICRON LogicPro
To view the available Help Topics, click on HelpTopics in the menu of the Help
window. ( See Figure 15-3, page - 54 )
The full topic, or a selection of the content of the topic, can be printed from that
window as well. Some of the Settings provide additional topics with in detail
instructions as follows.
The Animation Mode offers:
Overview
Animation Scheme
Animation Controls
Animation Speed
The Test Mode offers:
Overview
Fault Currents/Voltages
Select Test Cases
Start Selected Tests
The Settings offer:
Breaker/VT
Time Test Settings
Line Impedance Settings
Nominal Values Settings
60
Overview
Data Entry
Print Preview
Print Test Results
When a specific topic is selected and displayed, its name is shown on the top of
the Help window and appears disabled in the HelpTopics menu. ( See Figure
15-4, page - 55 ).
61
OMICRON LogicPro
To perform such a test, the user should follow the step-by-step procedure
described below.
To achieve this task, the following steps should be performed:
.
1. Wire the Test Object (distance relay), DC power supply (if necessary) and the
Test Device (CMC x56) according to the diagrams shown in Hardware
Requirements for the communication aided scheme to be tested.
2. Connect the parallel cable between the Test Device and the Test Computer
with LogicPro installed.
62
Note: Check if the relay uses 52a or 52b breaker status contacts. LogicPro simulates
52a breaker status only.
Since a single scheme is tested, use the Hardware Requirements for the selected
scheme.
The analysis of the distance relay performance during the Single Scheme test is
based on the expected operating times under different fault conditions.
The software is loaded using some default settings. However, if the user needs to
change them based on the technical specifications of the distance relay under test,
the default setting can be changed using the steps described in the Multiple
schemes test chapter ( See Figure 4-2, page - 37 )
( See also Change Time Test Settings.... window , page -37 )
(See also Line Impedance Settings - SECONDARY, page -38.)
( See also Line Impedance Settings window - PRIMARY Settings , page -39 )
( See also Nominal Values (Voltage/Frequency) Secondary Settings window ,
page -40 )
( See also Nominal Values (Voltage/Frequency) Primary Settings window ,
page -41 )
( See also Breaker/VT Settings , page -42 )
63
OMICRON LogicPro
V Scheme Selection
Figure 5-1:
2. Before a selection is made, the Start Test command button remains disabled.
3. As soon as you click on one of the Scheme Name Box, the Individual Scheme
Control Window will open as shown in ( Figure 5-2, page -59 ).
64
Figure 5-2:
4. If you want to return to the Main Selection window at any time, just click on the
Main button.
.
LogicPro allows the user to select from the available tests before starting the tests
execution.Click on Select Test Case in the Test Options frame to Start Test
Procedures.
65
OMICRON LogicPro
66
Figure 6-1:
Faults Currents and Voltages for the first selected test case
Figure 6-2:
If necessary, unselect a test case to prevent its execution (all Test Cases are
selected as default).
VII
If the CMC is on, just click Yes. Otherwise turn on the CMC and then click
Yes, so that the tests may be performed.
The second option is to select No, which will disable the Start Test button
and reset the selected test cases.
Figure 7-1:
CMC On - Off
67
OMICRON LogicPro
1. Before the execution of the selected test cases associated with the selected
logic scheme, the user is reminded by the software ( Figure 8-1, page -62 ) to
enable the logic scheme, of the distance transmission line protection relay to
match the expected by the test scheme.
Figure 8-1:
IX Tests Execution
Note: Before the execution of an individual test the background of the Test
Box is white.
2. Immediately after each individual test is completed, the result is analyzed and
the background of the Test Box changes color.
If the relay operated as expected, the test is OK and the background turns
green.
If there is any out of range operation the test fails and the Test Box
background turns red.
68
After the completion of all tests the results are visible as the background color of
the Test Boxes. If the scheme test is successful, the background of all Test Boxes
should be green.
The Test Details window at the same time displays a message All test are OK.
If even one test has failed, the Test Details window displays a different message. It
advises the user to check the relay logic, settings, etc., and the test objectives, and
results in the Test report.
3. If necessary, the test engineer can preview the Test report, print it and save it
as a file.
4. After all tests have been executed, the Print Report button in the Main
Selection window is enabled so that the test report can be previewed and/or
printed,
5. When the Print Report button is pushed the General Data Entry form is
displayed as well.
1. Before the test results are previewed or printed, the user is asked to fill in the
generic data for the test report.
Some of the entries are required and are supposed to be entered in the
white fields.
The rest of the fields are optional and have gray background as shown on (
Figure 10-1, page -64 ).
The software will keep the entered information for a specific field, if the
Check Box in front of the field is checked.
69
OMICRON LogicPro
Figure 10-1:
2. If the Close button is pushed a message will appear, warning that the entered
data related to the completed tests will be lost.
The most frequently used data can be saved for future use, by clicking the Save
General Report Data in the Data Entry form.( See Figure 10-1, page - 49 )
The measured operating times of each individual test are stored in the memory of
the computer and are available in the test report.
1. To preview these detailed test results, click on the Preview Report command
button in the Data Entry form.
2. As a result, the Data Entry window shown in ( Figure 11-1, page -65 ) and (
Figure 11-2, page -65 ) is displayed. You can scroll through the report as
necessary.
70
Figure 11-1:
Figure 11-2:
71
OMICRON LogicPro
1. Click on Save As File button in the Data Entry window ( See also Global Data
Entry form , page -64 )
2. The Save As window will open allowing the user to chose directory and file
format.
3. Unless changed the File will be saved as Rich Text Format.
To print the results from the test, click the Print Report command button in the
Data Entry form on ( Figure 10-1, page -64 ). The print dialog box is displayed,
allowing the user to specify a printer, if necessary.
XV Help
OMICRON LogicPro software offers brief on-line explanations for the major tasks
to be performed. The Help Topics are accessible only through the Menu in the
Main Selection window.
72
Figure 15-1: Help Options under the Menu in the Main Selection window
To open the Help window with the available help topics, click on Logic Pro Help
Topics.... ( See Figure 15-1, page - 67 ).
To check the different Help Topics, click on HelpTopics in the menu of the help
window.( See Figure 15-2, page - 67 ).
The full topic, or a selection of the content of the topic, can be printed from that
window as well.
73
OMICRON LogicPro
74
Switch-Onto-Fault
SWITCH-ONTO-FAULT
Objective
75
OMICRON LogicPro
voltage transformers are located on the line side of the breakers, the absence of
voltage in all three phases can be used to detect the line open condition. At the
same time all three phase currents shall be below the level defined by a low
undercurrent setting.
The Switch-On-To-Fault Logic enables the operation typically of non-directional
overcurrent elements. However, many modern microprocessor based relays allow
the user to define which protection functions will be operational during the time that
the Switch-On-To-Fault logic is enabled.
A similar logic is used during the reclosing cycle of a distance relay when the relay
is connected to line-side voltage transformers. This logic is called Trip-On-Reclose
and follows the same ideas as in the SOTF logic.
Since the SOTF logic always operates for a permanent fault condition, it will trip
three phase regardless of the type of fault.
A transmission line can be energized from each end. The grounding switches can
be closed at the remote end of the line when the breaker is closed at the local end.
In this case the line should be trip instantaneously, without any time delay, other
than the operating time of the protection elements enabled by the SOTF logic.
Simplified diagram of the Switch-On-To-Fault logic is shown in ( Figure 0-1,
page -70 ).
0
0
0
tpu
Trip
Manual Close
Breaker Open
Z
IOC
Fault Detect
Figure 0-1:
76
Switch-Onto-Fault
Fault locations
Faults are simulated at 2 locations along the model transmission line:
VA VB VC
R
50%
IA
100%
VA VB VC
2
IB
IC
Relay
Substation 2
Substation 1
Figure 0-2:
Test Cases
The Switch-Onto-Fault (SOTF) scheme is tested for the following fault conditions:
1. For Zone 1 single-phase-to-ground fault: - the relay should trip three phase
without time delay. Switch-On-To-Fault alarm should be detected if available in
the relay under test.
2. For Zone1 three-phase fault: - the relay should trip three phase without time
delay. Switch-On-To-Fault alarm should be detected if available in the relay
under test.
3. For Zone2 three-phase fault: - the relay should trip three phase without time
delay. Switch-On-To-Fault alarm should be detected if available in the relay
under test.
77
OMICRON LogicPro
Hardware requirements
IA
CMC
Analog
Outputs
IA
IB
IB
IC
IC
IN
Digital
Outputs
Out 2
Out 3
Digital
Inputs
Figure 0-3:
Analog
Inputs
IN
VA
VB
VC
VN
Out 1
RELAY
VA
VB
VC
VN
+ DC
- DC
52aA
+ DC
- DC
52aB
+ DC
- DC
52aC
In 1
Trip A
In 2
Trip B
In 3
Trip C
In 4
3Ph Trip
Digital
Inputs
Relay
Outputs
The CMC test device is programmed to simulate the substation and power system
environment through the analog and binary outputs. At the same time the binary
inputs are used to monitor the operation of the test object.
A typical wiring diagram for the SOTF logic test is shown ( Figure 0-3, page -72 )
78
Switch-Onto-Fault
The only setting that has to be changed for this group of test cases is the enabling
of the SOTF logic.
Three relay inputs have to be programmed as single phase normally open (52a)
breaker status monitoring inputs.
Three relay outputs should be programmed to trip phase A, B and C accordingly.
Single Pole Tripping should be enabled. The Phase A Trip and SOTF or 3Phase
Trip signals are monitored by the CMC.
79
OMICRON LogicPro
REMOTE-END-OPENED
Objective
The objective is to perform dynamic test to evaluate the Remote End Opened
(REO) scheme of a distance relay, as a function of the fault location, type of fault,
and healthy phase current conditions.
The Test Object is a multifunctional distance relay with REO scheme at one end of
the line.
80
Remote-End-Opened
relay can recognize this by detecting the loss of load current in the healthy phases.
This, combined with operation of the Zone 2 element at the local end will result in
the tripping of the local circuit breaker.
In order for the logic to function in the case of single-phase-to-ground,
phase-to-phase or two-phase-to-ground faults, the logic must detect the
availability of three phase load current prior to the fault.
The loss of load current opens a window during which time a trip will occur if a
Zone 2 element operates.
The accelerated trip is delayed by a certain time (about one cycle) in order to
prevent initiation of a loss of load trip due to circuit breaker pole discrepancy
occurring for clearance of an external fault. The local fault clearance time is
determined by the maximum Zone 1 trip time, the breakers trip time and the load
current level detector reset time, as well as the Remote-End-Opened logic time
delay
Note that loss of load tripping is only available where 3 pole tripping is
used.
Substation A
Substation B
Ia
Ib
Ic
Trip
3 Ph Load
Current
tpu
tdo
Zone 2
Figure 0-4:
Trip
Zone 1
81
OMICRON LogicPro
Fault locations
Faults are simulated at two location on the substation bus:
1. Internal single-phase-to-ground fault - at 50%
2. External Zone 2 single-phase-to-ground fault
3.
VA VB VC
R
50%
IA
IB
IC
100%
VA VB VC
2
100%
Ext
Relay
Substation 2
Substation 1
Figure 0-5:
The three fault locations are shown on ( Figure 0-5, page -76 ).
Test Cases
The Remote-End-Opened (REO) scheme is tested for the following fault
conditions:
1. For Zone 1 single-phase-to-ground fault: - the relay should trip with Zone 1
2. For External single-phase-to-ground Zone 2 fault: - the relay should not trip
3. For Internal single-phase-to-ground Zone 2 fault: - the relay should trip with
REO time
4. For External single-phase-to-ground Zone 2 fault with zero current in a healthy
phase: - the relay should not trip
Hardware Requirements
The CMC test device is programmed to simulate the substation and power system
environment through the analog and binary outputs. At the same time the binary
inputs are used to monitor the operation of the test object.
A typical wiring diagram for the Remote-End-Opened logic test is shown in:
( Figure 0-6, page -77 ).
82
Remote-End-Opened
The CMC simulates the status of the normally open auxiliary contacts of the
breaker, and the currents and voltages during the pre-fault, fault and post-fault
stages of the simulation.
The potential free relay output of the CMC has one terminal connected to (+) DC
and the second terminal to the (+) DC terminal of the associated relay input. The
second terminal of the relay input is connected to (-) DC.
The Trip output of the relay is wired to the Trip sense input of the CMC and is used
to change from fault to post-fault state, as well as to measure the operating time
and together with the monitored Remote-End-Opened output evaluate the correct
phase selection and operation of the Remote-End-Opened logic during the
different fault tests.
IA
CMC
Analog
Outputs
IA
IB
IB
IC
IC
IN
Digital
Inputs
Figure 0-6:
Analog
Inputs
IN
VA
VB
VC
VN
Digital
Outputs
RELAY
VA
VB
VC
VN
52a
Digital
Inputs
In 1
Trip
Relay
Outputs
In 2
REO
Out 1
+ DC
- DC
83
OMICRON LogicPro
84
Zone 1 Extension
ZONE 1 EXTENSION
Objective
The objective is to perform dynamic test to evaluate the Zone 1 Extension scheme
of a distance relay, as a function of the fault location, type of fault, and healthy
phase current conditions.
The Test Object is a multifunctional distance relay with Zone 1 Extension scheme
at one end of the line.
Breaker Status and Reclosing Status signals are simulated by the CMC.
85
OMICRON LogicPro
Substation A
Substation B
Zone 1 Ext
Zone 2
Ia
Ib
Ic
Zone 1
Figure 0-7:
Z2t
Z2
Z1 Ext
AR
Fault locations
Faults are simulated at two location on the substation bus:
1. Internal single-phase-to-ground fault - at 50%
2. External Zone 2 single-phase-to-ground fault
Internal Zone 2 single-phase-to-ground fault
The three fault locations are shown on ( Figure 0-8, page -81 )
86
Zone 1 Extension
VA VB VC
R
50%
IA
100%
VA VB VC
2
100%
Ext
IB
IC
Relay
Substation 2
Substation 1
Figure 0-8:
Test Cases
The Zone 1 Extension scheme is tested for the following fault conditions:
1. For Zone1 single-phase-to-ground fault: - the relay should trip with Zone 1
time.
2. For External single-phase-to-ground Zone2 fault with unsuccessful reclosing: the relay should trip with no delay, reclose and does not trip after the second
fault.
3. For Internal single-phase-to-ground Zone2 fault with successful reclosing: - the
relay should trip with no delay and reclose
Hardware Requirements
The CMC test device is programmed to simulate the substation and power system
environment through the analog and binary outputs. At the same time the binary
inputs are used to monitor the operation of the test object.
A typical wiring diagram for the Zone 1 Extension logic test is shown on ( Figure
0-9, page -82 )
The CMC simulates the status of the normally open auxiliary contacts of the
breaker (52a) and the currents and voltages during the pre-fault, fault and
post-fault stages of the simulation. It also simulates the operation of an external
autoreclosing device (AR)
Both potential free relay outputs of the CMC have one terminal connected to (+)
DC and the second terminal to the (+) DC terminal of the associated relay input.
The second terminal of each relay input is connected to (-) DC.
The Trip output of the relay is wired to a Trip sense input of the CMC and is used to
change from fault to post-fault state, as well as to measure the operating time and
87
OMICRON LogicPro
evaluate the correct phase selection and operation of the Zone 1 Extension logic
during the test.
A second input of the CMC monitors the Zone 1 Extension operation indication
from the relay.
IA
CMC
IA
IB
IB
IC
Analog
Outputs
IC
IN
Out 1
Digital
Inputs
Figure 0-9:
Analog
Inputs
IN
VA
VB
VC
VN
Digital
Outputs
RELAY
VA
VB
VC
VN
+ DC
- DC
52a
In 1
Trip
In 3
Z1X
Digital
Inputs
Relay
Outputs
88
Zone 1 Extension
One relay input has to be programmed as a normally open (52a) breaker status
monitoring input. A second relay input should be programmed to monitor external
Auto Reclosing status.
One relay output should be programmed to Trip, while a second one should be
programmed to provide a Zone1 Extension operation.
89
OMICRON LogicPro
LOAD ENCROACHMENT
Objective
The objective is to perform dynamic tests to evaluate the performance of a
distance relay, as a function of the load condition, breaker status, fault location,
type of fault, and selected mode of operation for different system conditions.
The Test Object is a multifunctional distance relay. The performance of the relay at
one end of the line is tested.
Breaker status signals for each of the three phases of the breaker are simulated by
the CMC.
LE logic description
(LE - Load Encroachment)
Distance functions based transmission line protection is required to operate
correctly under very different power system conditions. A very important criteria is
the correct relay operation for very heavy load conditions, since this can result in
sequential tripping during a power system disturbance, leading to further
deterioration of the conditions and total system collapse.
The changes of the load impedance measured by the relay are very slow
compared to the changes during a short circuit or power swing in the system.
Another very important characteristic of this process is that there is no significant
change in voltage.
The characteristics of the distance elements are important from the perspective of
the load impedance entering into the backup protection zones - usually Zone 3.
Quadrilateral characteristics or combinations of mho characteristics with load
blinders are typically used to allow backup protection of long lines, while avoiding
the load impedance entering into the distance zone.
At the same time, the protective relay should be able to trip for fault conditions that
occur simultaneously with the maximum load conditions, or for high impedance
faults that may result in a fault current lower than the maximum load condition.
Coverage for such fault conditions is typically based on the quadrilateral
characteristic for ground distance elements or directional ground overcurrent
protection for very high impedance faults
( Figure 0-10, page -85 ) and ( Figure 0-11, page -85 ) show the apparent load
impedance seen by distance relays with a quadrilateral characteristic or mho
characteristic with a Load Blinder.
90
Load Encroachment
Z3
Z2
Z1
No Operation
Z3
Z2
Z1
Fault locations
Faults are simulated at one location along the model transmission line:
1. Zone 1 single-phase-to-ground fault at 50% of the line length with overload
2. High impedance single-phase-to-ground fault
91
OMICRON LogicPro
VA VB VC
R
IA
50%
VA VB VC
2
IB
IC
Relay
Substation 1
Substation 2
Test Cases
The distance relay is tested for the following system and fault conditions:
1. For a maximum load condition (40% overload) the relay distance elements
should not trip
2. For a maximum load condition (40% overload) followed by Zone1
single-phase-to-ground fault: - the relay should trip single pole with Zone1 time
after the fault inception
3. For high impedance single-phase-to-ground fault: - the relay should trip with
ground overcurrent protection time delay
Hardware Requirements
The CMC test device is programmed to simulate the substation and power system
environment through the analog and binary outputs. At the same time the binary
inputs are used to monitor the operation of the test object.
A typical wiring diagram for the Load Encroachment test is shown in ( Figure 0-13,
page -87 ).
The CMC simulates the status of the normally open auxiliary contact for the
breaker (52a) and the currents and voltages during the pre-fault, fault and
post-fault stages of the simulation.
A potential free relay output of the CMC has one terminal connected to (+) DC and
the second terminal to the (+) DC terminal of the associated relay input. The
second terminal of the relay input is connected to (-) DC.
The Trip output of the relay is wired to a Trip sense input of the CMC and is used to
change from fault to post-fault state, as well as to measure the operating time and
evaluate the correct operation of the relay logic during the load encroachment test.
92
Load Encroachment
IA
CMC
Analog
Outputs
IA
IB
IB
IC
IC
IN
Digital
Inputs
Out 1
Analog
Inputs
IN
VA
VB
VC
VN
Digital
Outputs
RELAY
VA
VB
VC
VN
+ DC
- DC
In 1
52a
Digital
Inputs
Trip
Relay
Outputs
93
OMICRON LogicPro
94
Substation A
Substation B
Ia
Ib
Ic
Prot Trip
TBF
Ext BF Start
BF Trip
52
IUC
BF Trip
Fault locations
Faults are simulated at 3 locations along the model transmission line:
1. Zone 1 single-phase-to-ground fault at 50% of the line length
2. Zone 2 single-phase-to-ground fault at 100% of the line length
3.
Reverse fault
The three fault locations are shown on ( Figure 0-15, page -90 )
95
OMICRON LogicPro
VA VB VC
R
IA
50%
r
IB
IC
100%
VA VB VC
2
Relay
Substation 1
Substation 2
Figure 0-15: Fault location for the testing of the Breaker Failure Protection logic
Test Cases
The Breaker-Failure-Protection is tested for the following fault conditions:
1. For Zone 1 single-phase-to-ground fault: - the relay should trip with Zone 1
time and should initiate Breaker Failure Protection (but should not trip).
2. For Zone 2 single-phase-to-ground fault and Breaker Failure: - the relay should
trip with Zone 2 time and should also trip with Breaker Failure time.
3. For Reverse fault with External Breaker Failure Start: - the relay should trip
with Breaker Failure time.
4. For Over-voltage condition and Breaker Failure: - the relay should trip with
Over-voltage Protection time and should also trip with Breaker Failure time.
Hardware Requirements
The CMC test device is programmed to simulate the substation and power system
environment through the analog and binary outputs. At the same time the binary
inputs are used to monitor the operation of the test object.
A typical wiring diagram for the Breaker Failure Protection logic test is shown in (
Figure 0-16, page -91 ).
The two potential free relay outputs of the CMC have one terminal connected to
(+) DC and the second terminal to the (+) DC terminal of the associated relay
input. The second terminal of each relay input is connected to (-) DC.
The Trip output of the relay and the Breaker Failure Trip output are wired to two of
the sense inputs of the CMC and are used to change from fault to post-fault state,
as well as to measure the operating time and evaluate the correct operation of the
Breaker Failure Protection logic during the test.
96
IA
CMC
Analog
Outputs
IA
IB
IB
IC
IC
IN
Out 1
Out 2
Digital
Inputs
Analog
Inputs
IN
VA
VB
VC
VN
Digital
Outputs
RELAY
VA
VB
VC
VN
+ DC
- DC
52a
+ DC
- DC
Start BF
In 1
Trip
In 5
BF Trip
Digital
Inputs
Relay
Outputs
Figure 0-16: Hardware wiring diagram for testing of the Breaker Failure Protection logic
97
OMICRON LogicPro
One relay output should be programmed to provide Trip, while a second output
should give the indication for detected Breaker Failure Protection trip.
98
Block Reclosing
BLOCK RECLOSING
Objective
The objective is to perform dynamic test to evaluate the Block Reclosing function
of a distance relay, as a function of the type of fault, and the breaker status.
The Test Object is a multifunctional distance relay with built-in Block Reclosing at
one end of the line.
BR logic description
(BR - Block Reclosing)
Most faults on overhead transmission lines are caused by lightning, clashing
conductors and other transient phenomena. Electric power stability and reduction
of outages can be achieved through automatic reclosing of faulted transmission
lines. The success rate of auto reclosing is in the range of 80-90%. After the initial
trip, the relay recloses the circuit breaker after a set time delay in order to allow the
de-ionization of the air in the fault location.
The remaining percentage of faults is permanent in nature and requires immediate
tripping of the line breakers and blocking of the reclosing function. There are
different criteria or events that can be used to determine the need to block
reclosing:
If the fault detected by the relay is multiphase with high currents, there is higher
probability that it is a permanent fault. At the same time exposing the electric
power system to such conditions repeatedly during the reclosing sequence can be
dangerous for the stability of the system.
If the relay clears a fault with one of it's backup zones - Zone 2 or Zone 3 - there is
a possibility that there is some problem with the protection or the breaker at the
remote substation that requires block of reclosing.
If the breaker controlled by the transmission line protection relay is not capable of
reclosing because of low pressure, or something else, obviously the reclosing
should be blocked. This condition is typically detected through a relay input
assigned to detect any external Block Reclosing command.
Usually a Switch-Onto-Fault condition is a result of ground-switches not being
opened before closing the line breaker after maintenance. This condition is
detected based on the monitored by the relay breaker status and with result in
reclosing block. A Block Reclose input is typically assigned and will block
autoreclose and cause a lockout if autoreclose is in progress. If a single pole cycle
is in progress a three pole trip and lockout will result.
It can be used when protection operation without autoreclose is required. A typical
example is on a transformer feeder, where autoreclosing may be initiated from the
feeder protection but blocked from the transformer protection. Similarly, where a
99
OMICRON LogicPro
circuit breaker low gas pressure or loss of vacuum alarm occurring anywhere
during the dead time must block autoreclosure, this input can be used.
Choice of Protection Elements to Initiate Autoreclosure
In most applications, there will be a requirement to reclose for certain types of
faults but not for others. The logic is partly fixed so that autoreclosure is always
blocked for any Switch on to Fault, Stub Bus Protection, Broken Conductor or
Zone 4 trip.
Simplified logic for the Block reclosing scheme is shown in ( Figure 0-17,
page -94 ).
Substation A
Substation B
Ia
Ib
Ic
Back Up Trip
(Zone 3)
Multi Phase Flt
(3 Phase)
Zone 1
SOTF
Block Reclosing
Fault locations
Faults are simulated at two location on the substation bus:
1. Internal Zone 1 single-phase-to-ground fault
2. External Zone 2 single-phase-to-ground fault (on the outside of one of the
breakers)
3. Switch-Onto-Fault (three phase fault)
100
Block Reclosing
VA VB VC
R
IA
50%
100%
IB
IC
VA VB VC
2
100%
Ext
Relay
Substation 1
Substation 2
Figure 0-18: Fault locations for the testing of Block Reclosing logic
The three fault locations are shown on ( Figure 0-18, page -95 )
Test Cases
The Block Reclosing function is tested for the following fault conditions:
1. For Zone 1 single-phase-to-phase fault: - the relay should trip with Zone 1 time
and should Block Reclosing.
2. For External single-phase-to-ground Zone3 fault: - the relay should trip with
Zone 3 time and should Block Reclosing.
3. For Switch-Onto-Fault (3 Phase): - the relay should trip with Zone 1 time and
should Block Reclosing.
Hardware Requirements
The CMC test device is programmed to simulate the substation and power system
environment through the analog and binary outputs. At the same time the binary
inputs are used to monitor the operation of the test object.
A typical wiring diagram for the Block Reclosing logic test is shown in ( Figure
0-19, page -96 ).
The CMC simulates the status of the normally open auxiliary contacts of the
breaker, and the currents and voltages during the pre-fault, fault and post-fault
stages of the simulation.
The potential free relay output of the CMC has one terminal connected to (+) DC
and the second terminal to the (+) DC terminal of the associated relay input. The
second terminal of the relay input is connected to (-) DC.
The Trip output of the relay is wired to the Trip sense input of the CMC and is used
to change from fault to post-fault state, as well as to measure the operating time
101
OMICRON LogicPro
and together with the monitored Block Reclosing output evaluate the correct phase
selection and operation of the Block Reclosing logic during the different fault tests.
IA
CMC
Analog
Outputs
IA
IB
IB
IC
IC
IN
Out 1
Out 3
Digital
Inputs
Analog
Inputs
IN
VA
VB
VC
VN
Digital
Outputs
RELAY
VA
VB
VC
VN
Digital
Inputs
+ DC
- DC
52a
+ DC
- DC
Block Reclosing
Relay
Outputs
In 1
Trip
In 10
Reclose Blocked
Figure 0-19: Hardware wiring for testing of the Block Reclosing logic
102
Block Reclosing
One relay input has to be programmed as a normally open (52a) breaker status
monitoring input.
One relay output is programmed as Trip, while a second one is set to indicate the
operation of the Block Reclosing logic
103
OMICRON LogicPro
POWER-SWING-BLOCKING
Objective
The objective is to perform dynamic test to evaluate the Power-Swing-Blocking
feature of a distance relay, as a function of the system conditions, presence of a
fault, and selected mode of operation.
The Test Object is a multifunctional distance relay with Power-Swing-Blocking
option available at one end of the line.
Breaker Status signals are simulated by the CMC.
104
Power-Swing-Blocking
PwrSwg X
PwrSwg R
Figure 0-20: Power Swing band for a distance relay with quadrilateral characteristic
PwrSwg
Rch
Figure 0-21: Power Swing band for a distance relay with mho characteristic
Unblocking of the relay for faults during power swings should allow the relay to
operate normally for any unbalanced fault occurring during a power swing, as
there are two conditions which can be used to unblock the relay:
105
OMICRON LogicPro
A residual current threshold is exceeded - this allows tripping for ground faults
occurring during a power swing.
A negative sequence current threshold is exceeded - this allows tripping for
phase-to-phase faults occurring during a power swing.
Simplified logic diagram of the Power Swing Block is shown in ( Figure 0-22,
page -100 ).
Substation A
Substation B
Ia
Ib
Ic
Trip
Zpsb
Tpsb
Zs
Block
PS Block
Z2t
Block
Fault Detected
(enabled)
Fault locations
A Zone1 single-phase-to-ground fault is applied following the initial power swing
condition.
Test Cases
The Power Swing Blocking scheme is tested for the following system and fault
conditions:
1. For power swing inside and out of Zone 3: the relay should not trip and should
give Power Swing Alarm
2. For power swing inside of Zone 3 followed by a Zone 1 single-phase-to-ground
fault: the relay should trip and should give Power Swing Alarm
106
Power-Swing-Blocking
Hardware Requirements
The CMC test device is programmed to simulate the substation and power system
environment through the analog and binary outputs. At the same time the binary
inputs are used to monitor the operation of the test object.
A typical wiring diagram for the Power Swing Blocking logic test is shown in:
( Figure 0-23, page -101 ).
The CMC simulates the status of the normally open auxiliary contacts of the
breaker, and the currents and voltages during the pre-fault, power swing, fault and
post-fault stages of the simulation.
The potential free relay output of the CMC has one terminal connected to (+) DC
and the second terminal to the (+) DC terminal of the associated relay input. The
second terminal of the relay input is connected to (-) DC.
The Trip output of the relay is wired to the Trip sense input of the CMC and is used
to change from fault to post-fault state, as well as to measure the operating time
and together with the monitored Power Swing output evaluate the correct
operation of the Power Swing Blocking logic during the different tests.
IA
CMC
Analog
Outputs
IA
IB
IB
IC
IC
IN
RELAY
Analog
Inputs
IN
VA
VB
VC
VN
VA
VB
VC
VN
Digital
Inputs
Digital
Outputs
Out 1
Digital
Inputs
In 1
Trip
In 4
Power Swing
+ DC
- DC
52a
Relay
Outputs
Figure 0-23: Hardware wiring diagram for testing of the Power Swing Blocking logic
107
OMICRON LogicPro
108
Power-Swing-Tripping
POWER-SWING-TRIPPING
Objective
The objective is to perform dynamic test to evaluate the Power-Swing-Tripping
feature of a distance relay, as a function of the system conditions, presence of a
fault, and selected mode of operation.
The Test Object is a multifunctional distance relay with Power-Swing-Tripping
option available at one end of the line.
Breaker Status signals are simulated by the CMC.
Ia
Ib
Ic
Trip
Zps
Tps
Zs
(enabled)
PS Trip
Trip
Z3
Figure 0-24: Simplified logic diagram for Power Swing Trip scheme
109
OMICRON LogicPro
Fault locations
There are no faults applied in the tests for Power Swing Tripping.
Test Cases
The Power Swing Tripping scheme is tested for the following system and fault
conditions:
1. For power swing inside and out of Zone 3: the relay should not trip and should
give Power Swing Alarm
2. For power swing inside of Zone 3: the relay should trip and should give Power
Swing Alarm
Hardware Requirements
IA
CMC
Analog
Outputs
IA
IB
IB
IC
IC
IN
RELAY
Analog
Inputs
IN
VA
VB
VC
VN
VA
VB
VC
VN
Digital
Inputs
Digital
Outputs
Out 1
Digital
Inputs
In 1
Trip
In 4
Power Swing
Figure 0-25:
+ DC
- DC
52a
Relay
Outputs
The CMC test device is programmed to simulate the substation and power system
environment through the analog and binary inputs. At the same time the binary
inputs are used to monitor the operation of the test object.
110
Power-Swing-Tripping
A typical wiring diagram for the Power Swing tripping logic test is shown in ( Fig.
0-25, page - 104).
The CMC simulates the status of the normally open auxiliary contacts of the
breaker, and the currents and voltages during the pre-fault, power swing, fault and
post-fault stages of the simulation.
The potential free relay output of the CMC has one terminal connected to (+) DC
and the second terminal to the (+) DC terminal of the associated relay input. The
second terminal of the relay input is connected to (-) DC.
The Trip output of the relay is wired to the Trip sense input of the CMC and is used
to change from fault to post-fault state, as well as to measure the operating time
and together with the monitored Power Swing output evaluate the correct
operation of the Power Swing Tripping logic during the different tests.
111
OMICRON LogicPro
LOSS-OF-POTENTIAL
Objective
The objective is to perform dynamic test to evaluate the Loss-of-Potential (LOP)
scheme of a distance relay, as a function of the voltage failure, fault condition or
combination of the two.
The Test Object is a multifunctional distance relay with LOP scheme at one end of
the line. The single phase or three phase micro-breaker status signals are
generated by the CMC.
112
Loss-Of-Potential
Substation A
0
0
0
I0 or I2
V0 or V2
Distance
IOC
Direction
(disabled)
Fault locations
Faults are simulated at one location along the model transmission line:
1. Zone 1 single-phase-to-ground fault at 50% of the line length
The fault location is shown on ( Figure 0-27, page -108 )
113
OMICRON LogicPro
VA VB VC
R
50%
IA
VA VB VC
2
IB
IC
Relay
Substation 1
Substation 2
Figure 0-27: Fault location for the testing of the Loss-of-Potential logic
Test Cases
The Loss-of-Potential (LOP) scheme is tested for the following fault conditions:
1. For Single-phase voltage failure: - the relay should not trip and should give a
LOP alarm.
2. For Single-phase-to-ground Zone 1 fault: - the relay should trip and should not
give a LOP alarm.
3. For Single-phase voltage failure followed by Single-phase-to-ground Zone 1
fault: - the relay should give a LOP alarm and then trip.
Hardware Requirements
The CMC test device is programmed to simulate the substation and power system
environment through the analog and binary outputs. At the same time the binary
inputs are used to monitor the operation of the test object.
A typical wiring diagram for the Loss-of-Potential logic test is shown on ( Figure
0-28, page -109 ).
The CMC simulates the status of the normally open auxiliary contact for the
breaker (52-A), the status of the micro-breaker in the voltage circuit (if required by
the relay logic) and the currents and voltages during the pre-fault, fault and
post-fault stages of the simulation.
114
Loss-Of-Potential
IA
CMC
Analog
Outputs
IA
IB
IB
IC
IC
IN
Digital
Inputs
Analog
Inputs
IN
VA
VB
VC
VN
Digital
Outputs
RELAY
VA
VB
VC
VN
Out 1
+ DC
- DC
52a
Out 2
+ DC
- DC
52bkr
In 1
Trip
In 6
LOP
Digital
Inputs
Relay
Outputs
Figure 0-28: Hardware wiring diagram for testing of the Loss-of Potential logic
The two potential free relay outputs of the CMC have one terminal connected to
(+) DC and the second terminal to the (+) DC terminal of the associated relay
input. The second terminal of each relay input is connected to (-) DC.
The Trip output of the relay is wired to a Trip sense input of the CMC and is used to
change from fault to post-fault state, as well as to measure the operating time and
evaluate the correct operation of the Loss-of-Potential logic during the test.
115
OMICRON LogicPro
The only setting that has to be changed for this group of test cases is the enabling
of the Loss-of-Potential logic and the associated with it relay settings based on the
recommendations in the relay service manual.
One relay input has to be programmed as normally open (52a) breaker status
monitoring input. A second input should be configured to monitor the status of a
Micro-breaker used to protect the voltage circuit.
One relay output should be programmed to provide Distance Trip while a second
output should give the indication for detected Loss-of-Potential.
116
117
OMICRON LogicPro
available to provide some form of backup protection in the case that a fault occurs
before the problem with the current circuits or transformers is detected and fixed.
The above requirements are taken into consideration in the design of the module
for testing of the Current-Transformer-Supervision logic in modern transmission
line protection relays.
Simplified diagram of the Current-Transformer-Supervision logic is shown in:
( Figure 0-29, page -112 ).
Substation A
Ia
Ib
Ic
I0 or I2
V0 or V2
Distance
Ground OC
Negative Seq. OC
Fault locations
Faults are simulated at one location along the model transmission line:
1. Zone 1 single-phase-to-ground fault at 50% of the line length
The fault location is shown on ( Figure 0-30, page -113 )
118
VA VB VC
R
IA
50%
r
IB
IC
VA VB VC
2
Relay
Substation 1
Substation 2
Figure 0-30: Fault location for the testing of the Current-Transformer Supervision logic
Test Cases
The Current Transformer Supervision scheme is tested for the following fault
conditions:
1. For Single-phase CT circuit failure: - the relay should not trip and should give a
CT alarm.
2. For Single-phase-to-ground Zone1 fault: - the relay should trip and should not
give a CT alarm.
3. For Single-phase CT circuit failure followed by Single-phase-to-ground Zone1
fault: - the relay should give a CT failure alarm and then trip with distance
element.
Hardware Requirements
The CMC test device is programmed to simulate the substation and power system
environment through the analog and binary outputs. At the same time the binary
inputs are used to monitor the operation of the test object.
A typical wiring diagram for the Current-Transformer Supervision logic test is
shown in ( Figure 0-31, page -114 )
The CMC simulates the status of the normally open auxiliary contact for the
breaker (52-A), and the currents and voltages during the pre-fault, fault and
post-fault stages of the simulation.
119
OMICRON LogicPro
IA
CMC
Analog
Outputs
IA
IB
IB
IC
IC
IN
RELAY
Analog
Inputs
IN
VA
VB
VC
VN
VA
VB
VC
VN
52a
Digital
Inputs
In 1
Trip
Relay
Outputs
In 7
CT Fail
Digital
Outputs
Out 1
Digital
Inputs
+ DC
- DC
Figure 0-31: Hardware wiring diagram for testing of the Current-TransformerSupervision logic
The potential free relay output of the CMC has one terminal connected to (+) DC
and the second terminal to the (+) DC terminal of the associated relay input. The
second terminal of the relay input is connected to (-) DC.
The Trip output of the relay is wired to a Trip sense input of the CMC and is used to
change from fault to post-fault state, as well as to measure the operating time and
evaluate the correct operation of the Current-Transformer Supervision logic during
the test.
A second output from the relay is wired to input 2 in order to provide indication of
the detection of CT Failure.
120
121
OMICRON LogicPro
122
Simplified diagram of the Stub Bus Protection logic, that should be enabled when
testing the relay under evolving fault conditions is shown in ( Figure 0-32,
page -117 ).
Substation A
CT
CT
CT
Trip
CT
LS Open
CT
CT
Instant OC
Fault locations
Faults are simulated at two locations on the substation bus:
1. Internal single-phase-to-ground fault (between the breakers and the line
switch)
2. External single-phase-to-ground fault (on the outside of one of the breakers)
123
OMICRON LogicPro
Substation A
CT
CT
CT
CT
CT
CT
Relay
Figure 0-33: Fault locations for the testing of the Stub-Bus-Protection logic
Test Cases
The Stub-Bus-Protection scheme is tested for the following fault conditions:
1. For Single-phase-to-ground fault inside the zone of protection: - the relay
should trip without time delay.
2. For Single-phase-to-ground fault outside the zone of protection: - the relay
should not trip.
Hardware Requirements
The CMC test device is programmed to simulate the substation and power system
environment through the analog and binary outputs. At the same time the binary
inputs are used to monitor the operation of the test object.
A typical wiring diagram for the Stub Bus Protection logic test is shown in ( Figure
0-34, page -119 )
The CMC simulates the status of the normally open auxiliary contacts of the
breakers, the state of the line switch and the currents and voltages during the
pre-fault, fault and post-fault stages of the simulation.
124
All three potential free relay outputs of the CMC have one terminal connected to
(+) DC and the second terminal to the (+) DC terminal of the associated relay
input. The second terminal of each relay input is connected to (-) DC.
The Trip output of the relay is wired to the Trip sense input of the CMC and is used
to change from fault to post-fault state, as well as to measure the operating time
and evaluate the correct operation of the Stub Bus Protection logic during the
different fault tests.
A Stub Bus Protection output from the relay is wired to output 2.
IA
CM C
A nalog
O utp uts
IA
IB
IB
IC
IC
IN
VA
VB
VC
VN
+ DC
Digital
O utp uts
O ut 4
Digital
Inp uts
Analog
Inputs
IN
VA
VB
VC
VN
O ut 1
RELA Y
+ DC
- DC
52a1
- DC
52a2
- DC
D igital
Inputs
Line Sw itch
In 1
Trip
In 8
Stub B us
R elay
O utputs
Figure 0-34: Hardware wiring diagram for testing of the Stub-Bus-Protection logic
125
OMICRON LogicPro
The only setting that has to be changed for this group of test cases is the enabling
of Stub-Bus Protection logic. Different relays may have different protection
functions used to make the decision to trip.
One relay input has to be programmed as a normally open (52a) breaker status
monitoring input for Breaker 1.
A second relay input has to be programmed as a normally open (52a) breaker
status monitoring input for Breaker 2.
A third relay input should be programmed as a normally closed (52b) line switch
position monitoring input.
One relay output should be programmed to Trip phase and a second relay output
should provide indication of the operation of the Stub-Bus Protection logic.
126
127
OMICRON LogicPro
Substation A
Substation B
0
0
0
Trip A
Trip B
Trip 3 Ph
Trip C
Z1 A
Z1 B
Z1 C
3Ph Only
Z1 AB
Z1 BC
Z1 CA
Z1 ABC
The most typical cases when single pole trip and reclosing is selected is to trip
single phase for single-phase to ground faults and trip three phase for any other
fault. Also to trip single-phase for faults in Zone 1 of the protected line and three
phase for any other Zone. The latter is due to the fact, that Zone 2 and Zone 3
provide backup protection, and in this case a three phase trip is required.
Under specific conditions the application may require the relay to convert a single
pole trip decision to a three phase trip. This is typically based on the status of an
opto input that if energized will force the relay to trip three phase even when it has
detected a single-phase to ground fault.
The above requirements are taken into consideration in the design of the module
for testing of the Single-Pole Trip and Reclosing logic in modern transmission line
protection relays.
128
Fault locations
VA VB VC
R
50%
IA
VA VB VC
2
IB
IC
Relay
Substation 2
Substation 1
Figure 0-36:
2.
The three fault locations are shown on ( Figure 0-36, page -123 ).
Test cases
The Single Pole Tripping scheme is tested for the following fault conditions:
1. For Zone1 single-phase-to-ground fault: - the relay should trip single pole with
Zone1 time.
2. For Zone1 phase-to-phase fault: - the relay should trip 3 pole with Zone1 time.
3.
For Zone1 single-phase-to-ground fault with 3 Pole Trip Only energized: - the
relay should trip 3 pole with Zone1 time.
Hardware requirements
The CMC test device is programmed to simulate the substation and power system
environment through the analog and binary inputs. At the same time the binary
inputs are used to monitor the operation of the test object.
A typical wiring diagram for the Single-Pole Tripping logic test is shown in ( Figure
0-37, page -124 )
The CMC simulates the status of the normally open auxiliary contacts for the three
phases of the breaker (52a-A, 52a-B and 52a-C) and the currents and voltages
during the pre-fault, fault and post-fault stages of the simulation
129
OMICRON LogicPro
Another potential free relay output of the CMC is programmed to simulate the 3
Phase Trip Only signal sent from an external relay or another control signal and is
wired to the appropriate input of the relay under test.
All four potential free relay outputs of the CMC have one terminal connected to (+)
DC and the second terminal to the (+) DC terminal of the associated relay input.
The second terminal of each relay input is connected to (-) DC.
IA
CMC
Analog
Outputs
IA
IB
IB
IC
IC
IN
Digital
Outputs
Out 2
Out 3
Out 4
Digital
Inputs
Analog
Inputs
IN
VA
VB
VC
VN
Out 1
RELAY
VA
VB
VC
VN
+ DC
- DC
52aA
+ DC
- DC
52aB
+ DC
- DC
52aC
+ DC
- DC
In 1
Trip A
In 2
Trip B
In 3
Trip C
Digital
Inputs
Relay
Outputs
Figure 0-37: Hardware wiring diagram for testing of the Single-Pole Tripping logic
The three Trip outputs of the relay (one for each phase) are wired to three Trip
sense inputs of the CMC and are used to change from fault to post-fault state, as
well as to measure the operating time and evaluate the correct phase selection
and operation of the Single-Pole Trip logic.
A 3 Phase Trip output of the relay is wired to a fourth sense input of the CMC and
is used as an additional criteria from the relay under test.
130
131
OMICRON LogicPro
132
Substation A
Substation B
0
0
0
Trip A
Trip B
Trip 3 Ph
Trip C
Z1 A
Z1 B
Z1 C
3Ph Only
Z1 AB
Z1 BC
Z1 CA
Z1 ABC
Figure 0-38: Simplified diagram for testing of the Evolving Fault logic
Fault locations
Faults are simulated at one location along the model transmission line:
1. Zone 1 single-phase-to-ground fault at 50% of the line length
2. Zone 1 single-phase-to-ground fault evolving to three-phase-to-ground fault at
50% of the line length
The fault location is shown on ( Figure 0-39, page -127 ).
VA VB VC
R
IA
50%
VA VB VC
2
IB
IC
Relay
Substation 1
Substation 2
Figure 0-39: Fault location for the testing of the Evolving Fault function of Single-Pole
Tripping logic
133
OMICRON LogicPro
Test cases
The distance relay is tested for the following fault conditions:
1. For Zone1 single-phase-to-ground fault: - the relay should trip single pole with
Zone1 time.
2. For Zone1 single-phase-to-ground fault evolving to three-phase-to-ground
fault: - the relay should trip first single-pole with Zone1 time and then trip 3
pole.
Hardware requirements
The CMC test device is programmed to simulate the substation and power system
environment through the analog and binary outputs. At the same time the binary
inputs are used to monitor the operation of the test object.
A typical wiring diagram for the Single-Pole Tripping logic test is shown in ( Figure
0-40, page -129 )
The CMC simulates the status of the normally open auxiliary contacts for the three
phases of the breaker (52a-A, 52a-B and 52a-C) and the currents and voltages
during the pre-fault, fault and post-fault stages of the simulation.
All four potential free relay outputs of the CMC have one terminal connected to (+)
DC and the second terminal to the (+) DC terminal of the associated relay input.
The second terminal of each relay input is connected to (-) DC.
The three Trip outputs of the relay (one for each phase) are wired to three Trip
sense inputs of the CMC and are used to change from fault to post-fault state, as
well as to measure the operating time and evaluate the correct phase selection
and operation of the Single-Pole Trip logic during the evolving fault test.
134
IA
CMC
Analog
Outputs
IA
IB
IB
IC
IC
IN
Digital
Outputs
Out 2
Out 3
Out 4
Digital
Inputs
Analog
Inputs
IN
VA
VB
VC
VN
Out 1
RELAY
VA
VB
VC
VN
+ DC
- DC
52aA
+ DC
- DC
52aB
+ DC
- DC
52aC
+ DC
- DC
In 1
Trip A
In 2
Trip B
In 3
Trip C
Digital
Inputs
Relay
Outputs
Figure 0-40: Hardware wiring diagram for testing of the Evolving Fault logic
135
OMICRON LogicPro
A fourth input of the relay is programmed for 3Phase Trip Only control.
Three relay outputs should be programmed to trip A,B and C accordingly. A fourth
output indicates that the relay issued a 3Phase Trip signal.
136
Pole-Dead Logic
POLE-DEAD LOGIC
Objective
The objective is to perform dynamic tests to evaluate the performance of a
distance relay, as a function of the breaker status, fault location, type of fault, and
selected mode of operation for different fault conditions.
The Test Object is a multifunctional distance relay with Single-Pole-Tripping option
available and enabled. The performance of the relay at one end of the line is
tested.
Breaker status signals for each of the three phases of the breaker are simulated by
the CMC.
137
OMICRON LogicPro
Substation A
Ia
Ib
Ic
CBa
Pole Dead A
CBb
Pole Dead B
CBc
Pole Dead C
Ia
Va
Ib
Vb
Ic
Any Pole Dead
Vc
All Pole Dead
Fault locations
Faults are simulated at one location along the model transmission line:
1. Zone 1 single-phase-to-ground fault at 50% of the line length
2. Zone 1 three-phase fault at 50% of the line length
VA VB VC
R
IA
50%
VA VB VC
2
IB
IC
Relay
Substation 1
Figure 0-42: Fault locations for the testing of the Pole Dead logic
138
Substation 2
Pole-Dead Logic
Test Cases
The Pole-Dead-Logic scheme is tested for the following conditions:
1. Zone 1 single-phase-to-ground fault with Line side VT with single-pole trip: the relay should trip and detect single pole dead condition.
2. Zone 1 single-phase-to-ground fault with Bus side VT with single-pole trip: - the
relay should trip and detect single pole dead condition.
3. Zone 1 three-phase fault with Line side VT with single-pole trip: - the relay
should trip and detect three pole dead condition.
4. Zone 1 three-phase fault with Bus side VT with single-pole trip: - the relay
should trip and detect three pole dead condition.
Hardware Requirements
The CMC test device is programmed to simulate the substation and power system
environment through the analog and binary outputs. At the same time the binary
inputs are used to monitor the operation of the test object.
A typical wiring diagram for the Pole Dead logic test is shown in ( Figure 0-43,
page -134 ).
The CMC simulates the status of the normally open auxiliary contacts for the three
phases of the breaker (52a-A, 52a-B and 52a-C) and the currents and voltages
during the pre-fault, fault and post-fault stages of the simulation.
All three potential free relay outputs of the CMC have one terminal connected to
(+) DC and the second terminal to the (+) DC terminal of the associated relay
input. The second terminal of each relay input is connected to (-) DC.
One Trip output of the relay is wired to a Trip sense input of the CMC and are used
to change from fault to post-fault state, as well as to measure the operating time
and evaluate the operation of the relay. Two other outputs of the relay are
designated as Single-Pole-Dead and All Pole Dead indicators and are wired to two
other inputs of the CMC. They are used to monitor the correct Pole Dead logic
decision during each test.
139
OMICRON LogicPro
IA
CMC
Analog
Outputs
IA
IB
IB
IC
IC
IN
Digital
Outputs
Out 2
Out 3
Digital
Inputs
Analog
Inputs
IN
VA
VB
VC
VN
Out 1
RELAY
VA
VB
VC
VN
+ DC
- DC
52aA
+ DC
- DC
52aB
+ DC
- DC
52aC
Digital
Inputs
Relay
Outputs
In 1
Trip
In 5
Pole-Dead
In 6
3 Pole-Dead
Figure 0-43: Hardware wiring diagram for testing of the Pole-Dead logic
140
Pole-Dead Logic
Three relay inputs have to be programmed as single phase normally open (52a)
breaker status monitoring inputs.
Three relay outputs should be programmed to indicate Trip, Single Pole Dead or
All Poles Dead.
141
OMICRON LogicPro
142
Support
Support
When you are working with our products we want to provide you with the
greatest possible benefits. If you need any support, we are here to assist you!
OMICRON electronics GmbH, Oberes Ried 1, 6833 Klaus, Austria, +43 59495
143
Support
144