Sie sind auf Seite 1von 87

Hng Phm

Phone: 01649397068
Mobile:

Installation calculation report


New_project
Full

Page 2/87

Project information
Name :
Place :
Customer name:
Revision :

Project: New_project

capdienhathekhuvucnhatro
hanoi
-

06/08/2015

Page 3/87

Content

Project description.................................................................................................................. 4
1.1

Project general settings................................................................................................................... 4

1.2

Settings for wiring device calculation............................................................................................ 4

1.3

List of loads...................................................................................................................................... 4

Installation general design.....................................................................................................6


2.1

List of devices.................................................................................................................................. 6

Calculation notes.................................................................................................................. 14
3.1

Source circuits............................................................................................................................... 14

3.2

Generator circuits.......................................................................................................................... 23

3.3

LV Source circuits.......................................................................................................................... 23

3.4

UPS circuits.................................................................................................................................... 24

3.5

Surge Arrester circuits................................................................................................................... 24

3.6

Capacitor bank circuits.................................................................................................................. 24

3.7

Feeder circuits................................................................................................................................ 24

3.8

LV Transformer circuits................................................................................................................. 25

3.9

Couplers circuits............................................................................................................................ 27

3.10

Generic load circuits................................................................................................................. 27

3.11

Lighting load circuits................................................................................................................ 27

3.12

Power socket load circuits....................................................................................................... 28

3.13

Motor starter combination........................................................................................................ 28

3.14

Busbar circuits.......................................................................................................................... 29

3.15

Busbar trunking system circuits............................................................................................. 29

3.16

Busbar trunking system circuits............................................................................................. 29

3.17

Lighting Busbar trunking system circuits..............................................................................29

Project: New_project

06/08/2015

Page 4/87

1 Project description
1.1 Project general settings
Installation standard

IEC60364

Calculation standard
Circuit breaker standard
Frequency

TR50480
IEC 60947-2
50 Hz

1.2 Settings for wiring device calculation


Maximal CSA

300 mm

1.3 List of loads


Name
AA 17
AA 31
AA 17
(1)
AA 17
(1) (1)
Name
AA 13
AA 25

Name
EA 6
EA 7
EA 8
EA 9
EA 10
EA 11
EA 12
EA 18
EA 20
EA 18
(1)
EA 18
(1) (1)

1.3.1 Generic loads


Sr (kVA)
Pr (kW) Ir (A)
1.82
1.82
7.87
1
1
4.33
1.82
1.82
7.87

Cos
1
1
1

Nbr
16
1
16

Polarity
1Ph+N
1Ph+N
1Ph+N

Non linear load


No
No
No

THDi 3 (%)
0
0
0

1.82

16

3Ph+N

No

Cos
1
1

Nbr
1
2

Polarity
1Ph+N
1Ph+N

Non linear load THDi 3 (%)


No
0
No
0

1.82

2.62

1.3.2 Power sockets


Sr (kVA)
Pr (kW) Ir (A)
3.68
3.68
15.9
3.68
3.68
15.9

1.3.3 Lighting distribution


Type of lamp P Lamp (W)
P ballast (W)
Metal iodine
70
4.5
Metal iodine
70
4.5
Metal iodine
70
4.5
Fluorescent
36
4.5
with electronic
ballast
Fluorescent
36
4.5
with electronic
ballast
Fluorescent
18
4.5
with electronic
ballast
Fluorescent
18
4.5
with electronic
ballast
Fluorescent
36
4.5
with electronic
ballast
Metal iodine
70
4.5
Fluorescent
36
4.5
with electronic
ballast
Fluorescent
36
4.5
with electronic
ballast

Project: New_project

Nb of lamp/light
1
1
1
1

Nb of light
9
9
9
5

10

10

1
1

4
6

06/08/2015

Page 5/87

Name
MA 30

1.3.4 Motor loads


Sr (kVA)
Pr (kW) Ir (A)
2.49
2.12
3.6

Project: New_project

Cos
0.85

Nbr
1

Polarity
3Ph

Non linear load THDi 3 (%)


No
0

06/08/2015

Page 6/87

2 Installation general design


2.1 List of devices
Name

2.1.1 MV/LV transformer


Nbr Range
Insulation

TA 0

Trihal

Dry-type

Sr (kVA)

ukrT (%) Connection U2 (V) SEA

160

2.1.2 LV switchboards and busbar


Switchboard name
Range
UC 2
No preference
UC 5
No preference
UC 16
No preference
UC 22
No preference
UC 29
No preference
UC 16 (1)
No preference
UC 16 (1) (1)
No preference
Busbar name

Switchboard
name
UC 2
UC 5
UC 16
UC 22
UC 29
UC 16 (1)
UC 16 (1) (1)

WC 1
WC 4
WC 15
WC 21
WC 28
WC 15 (1)
WC 15 (1) (1)

Name

2.1.3
Nbr

QA 0

QA 3

QA 6

QA 7

QA 8

QA 9

QA 10

QA 11

QA 12

QA 13

QA 14

QA 17

16

Project: New_project

Circuit breaker
Range Rating (A)
Designation
Compact
250
NSX NSX250B
Acti9 iC60 - 16
iC60N
Acti9 iC60 - 4
iC60N
Acti9 iC60 - 4
iC60N
Acti9 iC60 - 4
iC60N
Acti9 iC60 - 1
iC60N
Acti9 iC60 - 1
iC60N
Acti9 iC60 - 1.6
iC60L
Acti9 iC60 - 1.6
iC60L
Acti9 iC60 - 16
iC60N
Acti9 iC60 - 32
iC60N
Acti9 iC60 - 10
iC60N

420

Rating (A)
0.00
0.00
0.00
0.00
0.00
0.00
0.00

TN-S

Rb
(m)
10000

IP
Undefined
Undefined
Undefined
Undefined
Undefined
Undefined
Undefined

Ks

Polarity

SEA

Equipotential bounding

1
1
1
1
1
1
1

3Ph+N
3Ph+N
3Ph+N
3Ph+N
3Ph+N
3Ph+N
3Ph+N

TN-S
TN-S
TN-S
TN-S
TN-S
TN-S
TN-S

With
Without
Without
Without
Without
Without
Without

Poles

Trip unit/Curve

RCD

RCD class

4P4d

Micrologic 5.2 A

RH197P

4P4d

RH99M

2P1d

RH99M

2P1d

RH99M

2P1d

RH99M

2P1d

RH99M

2P1d

RH99M

2P2d

RH99M

2P2d

RH99M

2P1d

RH10M

4P4d

RH99M

2P1d

RH10M

A
06/08/2015

Page 7/87

QA 18

QA 19

QA 20

QA 25

QA 27

QA 30

QA 31

QA 17 (1)

16

QA 18 (1)

QA 14 (1)

QA 17 (1) (1) 16
QA 18 (1) (1) 1
QA 14 (1) (1) 1

Name
WD 3
WD 14
WD 19
WD 14
(1)
WD 14
(1) (1)

Acti9 iC60 iC60L


Acti9 iC60 iC60N
Acti9 iC60 iC60L
Acti9 iC60 iC60N
Acti9 iC60 iC60N
Acti9 P25M P25M
Acti9 iC60 iC60N
Acti9 iC60 iC60N
Acti9 iC60 iC60L
Acti9 iC60 iC60N
Acti9 iC60 iC60N
Acti9 iC60 iC60L
Acti9 iC60 iC60N

1.6

2P2d

RH99M

16

4P4d

RH99M

1.6

2P2d

RH99M

16

2P1d

RH10M

10

4P4d

RH99M

3P3d

RH10M

2P1d

RH10M

10

2P1d

RH10M

1.6

2P2d

RH99M

32

4P4d

RH99M

4P4d

RH10M

1.6

2P2d

RH99M

32

4P4d

RH99M

2.1.4 Transmission busbar trunking system schedule


Nbr Incomer
Feeder
L (m)
Range
1 QA 3
WC 4
3
KTC
1 QA 14
WC 15
4
KTC
1 QA 19
WC 21
4
KTC
1 QA 14 (1) WC 15 (1)
4
KTC

Rating (A)
1000
1000
1000
1000

1000

QA 14 (1)
(1)

WC 15 (1) (1) 4

KTC

2.1.5 Cable schedule


Name Nbr Incomer Feeder Type
WD 0 1
TA 0
QA 0
Multi-core

Insulation L (m)
XLPE
300

WD 12 1

QA 12

EA 12

Multi-core

PVC

20

WD 10 1

QA 10

EA 10

Multi-core

PVC

20

WD 8

QA 8

EA 8

Multi-core

PVC

17

WD 7

QA 7

EA 7

Multi-core

PVC

17

WD 6

QA 6

EA 6

Multi-core

PVC

17

WD 31 1

QA 31

AA 31

Multi-core

XLPE

10

WD 20 1

QA 20

EA 20

Multi-core

PVC

10

WD 13 1

QA 13

AA 13

Multi-core

PVC

10

WD 11 1

QA 11

EA 11

Multi-core

PVC

WD 9

QA 9

EA 9

Multi-core

PVC

Project: New_project

L1/L2/L3
2x185
Copper
1x1.5
Copper
1x1.5
Copper
1x1.5
Copper
1x1.5
Copper
1x1.5
Copper
1x1.5
Copper
1x1.5
Copper
1x2.5
Copper
1x1.5
Copper
1x1.5
Copper

N
2x185
Copper
1x1.5
Copper
1x1.5
Copper
1x1.5
Copper
1x1.5
Copper
1x1.5
Copper
1x1.5
Copper
1x1.5
Copper
1x2.5
Copper
1x1.5
Copper
1x1.5
Copper

PE/PEN
1x185
Copper
1x4 Copper
1x4 Copper
1x4 Copper
1x4 Copper
1x4 Copper
1x4 Copper
1x4 Copper
1x4 Copper
1x4 Copper
1x4 Copper
06/08/2015

Page 8/87

WD 18
(1) (1)
WD 17
(1) (1)
WD 18
(1)
WD 17
(1)
WD 30

EA 18
(1) (1)
AA 17
(1) (1)
EA 18
(1)
AA 17
(1)
MA 30

Multi-core

PVC

Multi-core

PVC

Multi-core

PVC

Multi-core

PVC

QA 18
(1) (1)
QA 17
(1) (1)
QA 18
(1)
QA 17
(1)
QA 30

Multi-core

XLPE

WD 27 1

QA 27

WC 28

Multi-core

XLPE

WD 25 2

QA 25

AA 25

Multi-core

PVC

WD 18 1

QA 18

EA 18

Multi-core

PVC

WD 17 16

QA 17

AA 17

Multi-core

PVC

16
1
16

2.1.6 MV Cable
Name Nbr Designation CSA (mm) Icc (A)
MVWD 1
NA
1 x 185 Al 16.4
0

Project: New_project

In (A)
353

1x1.5
Copper
1x1.5
Copper
1x1.5
Copper
1x1.5
Copper
1x1.5
Copper
1x1.5
Copper
1x2.5
Copper
1x1.5
Copper
1x1.5
Copper

1x1.5
Copper
1x1.5
Copper
1x1.5
Copper
1x1.5
Copper

1x4 Copper
1x4 Copper
1x4 Copper
1x4 Copper
1x4 Copper

1x1.5
Copper
1x2.5
Copper
1x1.5
Copper
1x1.5
Copper

1x4 Copper
1x4 Copper
1x4 Copper
1x4 Copper

Un (kV)
24

06/08/2015

Page 9/87

3 Calculation notes
3.1 Source circuits
3.1.1 Circuit Source 0
MV power supply
W0
Max. upstream short circuit power 500 MVA
Min. upstream short circuit power 100 MVA
MV Cable
MVWD 0
Parameters
Length
10 m
Type of cable
Single core
Ib
5A
Nb of conductor per phase
1
Cross section area
1 x 185 Al mm
Core
Aluminium
Short circuit withstand
16.4 kA
Assigned voltage
20 kV
Insulation voltage
24 kV
MV/LV transformer
Range
Technology
Rated power
ukrT
Type of losses
PkrT
System earthing arrangement
MV Connection
LV Connection
No load secondary voltage Ur0
Ur LV
Rb (neutral grounding)
Ra (mass grounding)
Sizing information
Cable
Parameters
Length
Max length
Installation method

TA 0
Trihal
Dry-type
160 kVA
6%
Normal
2.35 kW
TN-S
D
yn
420V
400V
NA
NA
UkrT and PkrT calculated by system
WD 0

300 m
NA
31
E
Multi-core cables on vertical perforated
tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
XLPE
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
231 A
Sizing constraint
Voltage drop
Sizing Information
The CSA of cable WD 0 has been
increased from 35 to 2*185 to comply
with the voltage drop in the circuit.

Project: New_project

06/08/2015

Page 10/87

Sized with Ir
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference

1
B-52-14
1
B-52-16
1
E-52-1
0.88
B-52-20
1
0.88

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

2x185 mm
Copper
803 A
2x185 mm
Copper
803 A
1x185 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 3.82
3.31

3.82

2.17

1.98

2.50 0.00

Synthesis for all operating mode


(kA) 3.82
3.31
3.82

2.17

1.98

2.50 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Circuit breaker
Ib
Distance from origin

QA 0
231 A
NA

Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr

Sized by system
Compact NSX
NSX250B
250 A
25 kA
NA
NA
NA
4P4d
Micrologic 5.2 A
250 A

Project: New_project

231 A
16 s
06/08/2015

Page 11/87

Short delay settings


Isd current
Tsd
Instantaneous tripping
Ii current

1502 A
0s
3000 A

Discrimination Results
UpStream

Discrimination Limit

Operating mode Normal


NA

Discrimination can't be determinated : no


upstream Lv Breaker

RCD designation
Class
In
Break Time
t
Discrimination
Normative required break time
Normative required sensitivity

RH197P
A
30000 mA
4.7 s
4.5 s
NA
[0.00 ; 5.00] s
[0.03 ; 1281.00] mA

Discrimination Results
UpStream

Discrimination Limit

Operating mode Normal


NA

Design current
IL1

Discrimination not analyzed

IL2

Operating mode Normal


(A)
66.629
76.476

IL3
66.340

Synthesis for all operating mode


(A)
66.629
76.476
66.340
Voltage drop
Cumulated from upstream
Operating mode Normal
1.957
U3L (%)
2.259
UL1L2 (%)
2.266
UL2L3 (%)
2.265
UL3L1 (%)
1.956
UL1N (%)
1.957
UL2N (%)
1.968
UL3N (%)

Project: New_project

IN
10

10
Circuit
1.957
2.259
2.266
2.265
1.956
1.957
1.968

06/08/2015

Page 12/87

3.2 Feeder circuits


3.2.1 Circuit Feeder circuit 27
Circuit breaker
QA 27
Ib
7.14 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
10 A
10 kA
NA
NA
NA
4P4d
C
10 A
10 A
NA
80 A
NA
NA
Discrimination Limit

Operating mode Normal


QA 0
NSX250B
Micrologic 5.2 A
250 A / 4P4d

Full Discrimination

RCD designation
Class
In
Break Time
t
Discrimination
Normative required break time
Normative required sensitivity

RH99M
A
10000 mA
1.2 s
1s
NA
[0.00 ; 5.00] s
[0.03 ; 667.87] mA

Discrimination Results
UpStream

Discrimination Limit

Operating mode Normal


RH197P (QA 0)

Project: New_project

Full Discrimination

06/08/2015

Page 13/87

Cable
Parameters
Length
Max length
Installation method

WD 27

5m
NA
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
XLPE
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
7A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
B-52-14
Soil thermal resistivity factor
1
Standard table reference
B-52-16
Loaded neutral factor
1
Standard table reference
E-52-1
Touching conductor factor
1
Standard table reference
B-52-20
User correction factor
1
Overall factor
1
Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x1.5 mm
Copper
23 A
1x1.5 mm
Copper
23 A
1x4 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 3.07
2.66

2.54

1.37

0.95

1.34 0.00

Synthesis for all operating mode


(kA) 3.07
2.66
2.54

1.37

0.95

1.34 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Project: New_project

06/08/2015

Page 14/87

Design current
IL1

IL2

Operating mode Normal


(A)
3.600
3.600

IL3
7.137

Synthesis for all operating mode


(A)
3.600
3.600
7.137
Voltage drop
Cumulated from upstream
Operating mode Normal
2.195
U3L (%)
2.380
UL1L2 (%)
2.464
UL2L3 (%)
2.463
UL3L1 (%)
2.181
UL1N (%)
2.183
UL2N (%)
2.327
UL3N (%)

Project: New_project

IN
3.54

3.54
Circuit
0.238
0.121
0.198
0.198
0.226
0.226
0.359

06/08/2015

Page 15/87

3.2.2 Circuit Feeder circuit 3


Circuit breaker
QA 3
Ib
15.9 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
16 A
10 kA
NA
NA
NA
4P4d
C
16 A
16 A
NA
128 A
NA
NA
Discrimination Limit

Operating mode Normal


QA 0
NSX250B
Micrologic 5.2 A
250 A / 4P4d

Full Discrimination

RCD designation
Class
In
Break Time
t
Discrimination
Normative required break time
Normative required sensitivity

RH99M
A
10000 mA
1.2 s
1s
NA
[0.00 ; 5.00] s
[0.03 ; 1254.29] mA

Discrimination Results
UpStream

Discrimination Limit

Operating mode Normal


RH197P (QA 0)

Project: New_project

Full Discrimination

06/08/2015

Page 16/87

Transmission busway
Parameters
Length
Max length
Installation method
Ambient temperature
Level of third harmonic THDI
Ib
Sizing Information
Correction factors
Temperature factor
Installation method factor
Type of protection factor
User defined factor
Selected busway
Designation
Rating
PE type
IP
IK
Core
Icw
Ip
Reinforced short circuit
withstand

WD 3
3m
NA
Standard
35 C
0%
16 A
Sized with Ir
1
1
1
1
KTC1000
1000
Standard PE
55
08
Copper
50 kA
110 kA
NA

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 3.07
2.66

2.54

2.22

2.08

2.51 0.00

Synthesis for all operating mode


(kA) 3.07
2.66
2.54

2.22

2.08

2.51 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Design current
IL1

IL2

IL3

IN

Operating mode Normal


(A)
3.226
15.935

3.651

12.5

Synthesis for all operating mode


(A)
3.226
15.935

3.651

12.5

Voltage drop
Cumulated from upstream
Operating mode Normal
1.958
U3L (%)
2.259
UL1L2 (%)
2.267
UL2L3 (%)
2.265
UL3L1 (%)
1.956
UL1N (%)
1.959
UL2N (%)
Project: New_project

Circuit
0.001
0.001
0.001
0.000
0.000
0.002
06/08/2015

Page 17/87

UL3N (%)

Project: New_project

1.968

0.001

06/08/2015

Page 18/87

3.2.3 Circuit Feeder circuit 14


Circuit breaker
QA 14
Ib
28.3 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
32 A
10 kA
NA
NA
NA
4P4d
C
32 A
32 A
NA
256 A
NA
NA
Discrimination Limit

Operating mode Normal


QA 0
NSX250B
Micrologic 5.2 A
250 A / 4P4d

Full Discrimination

RCD designation
Class
In
Break Time
t
Discrimination
Normative required break time
Normative required sensitivity

RH99M
A
10000 mA
1.2 s
1s
NA
[0.00 ; 5.00] s
[0.03 ; 1245.60] mA

Discrimination Results
UpStream

Discrimination Limit

Operating mode Normal


RH197P (QA 0)

Full Discrimination

Transmission busway

WD 14

Project: New_project

06/08/2015

Page 19/87

Parameters
Length
Max length
Installation method
Ambient temperature
Level of third harmonic THDI
Ib
Sizing Information
Correction factors
Temperature factor
Installation method factor
Type of protection factor
User defined factor
Selected busway
Designation
Rating
PE type
IP
IK
Core
Icw
Ip
Reinforced short circuit
withstand

4m
NA
Standard
35 C
0%
28 A
Sized with Ir
1
1
1
1
KTC1000
1000
Standard PE
55
08
Copper
50 kA
110 kA
NA

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 3.07
2.66

2.54

2.21

2.08

2.49 0.00

Synthesis for all operating mode


(kA) 3.07
2.66
2.54

2.21

2.08

2.49 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Design current
IL1

IL2

IL3

IN

Operating mode Normal


(A)
23.617
24.295

28.340

4.42

Synthesis for all operating mode


(A)
23.617
24.295

28.340

4.42

Voltage drop
Cumulated from upstream
Operating mode Normal
1.959
U3L (%)
2.261
UL1L2 (%)
2.268
UL2L3 (%)
2.268
UL3L1 (%)
1.959
UL1N (%)
1.961
UL2N (%)
1.973
UL3N (%)
Project: New_project

Circuit
0.002
0.002
0.003
0.003
0.004
0.004
0.005
06/08/2015

Page 20/87

Project: New_project

06/08/2015

Page 21/87

3.2.4 Circuit Feeder circuit 19


Circuit breaker
QA 19
Ib
15.9 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
16 A
10 kA
NA
NA
NA
4P4d
C
16 A
16 A
NA
128 A
NA
NA
Discrimination Limit

Operating mode Normal


QA 0
NSX250B
Micrologic 5.2 A
250 A / 4P4d

Full Discrimination

RCD designation
Class
In
Break Time
t
Discrimination
Normative required break time
Normative required sensitivity

RH99M
A
10000 mA
1.2 s
1s
NA
[0.00 ; 5.00] s
[0.03 ; 1245.60] mA

Discrimination Results
UpStream

Discrimination Limit

Operating mode Normal


RH197P (QA 0)

Full Discrimination

Transmission busway

WD 19

Project: New_project

06/08/2015

Page 22/87

Parameters
Length
Max length
Installation method
Ambient temperature
Level of third harmonic THDI
Ib
Sizing Information
Correction factors
Temperature factor
Installation method factor
Type of protection factor
User defined factor
Selected busway
Designation
Rating
PE type
IP
IK
Core
Icw
Ip
Reinforced short circuit
withstand

4m
NA
Standard
35 C
0%
16 A
Sized with Ir
1
1
1
1
KTC1000
1000
Standard PE
55
08
Copper
50 kA
110 kA
NA

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 3.07
2.66

2.54

2.21

2.08

2.49 0.00

Synthesis for all operating mode


(kA) 3.07
2.66
2.54

2.21

2.08

2.49 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Design current
IL1

IL2

IL3

IN

Operating mode Normal


(A)
15.935
15.935

1.434

14.5

Synthesis for all operating mode


(A)
15.935
15.935

1.434

14.5

Voltage drop
Cumulated from upstream
Operating mode Normal
1.958
U3L (%)
2.260
UL1L2 (%)
2.267
UL2L3 (%)
2.266
UL3L1 (%)
1.958
UL1N (%)
1.959
UL2N (%)
1.968
UL3N (%)
Project: New_project

Circuit
0.001
0.002
0.001
0.001
0.003
0.003
0.000
06/08/2015

Page 23/87

Project: New_project

06/08/2015

Page 24/87

3.2.5 Circuit Feeder circuit 14 (1)


Circuit breaker
QA 14 (1)
Ib
28.3 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
32 A
10 kA
NA
NA
NA
4P4d
C
32 A
32 A
NA
256 A
NA
NA
Discrimination Limit

Operating mode Normal


QA 0
NSX250B
Micrologic 5.2 A
250 A / 4P4d

Full Discrimination

RCD designation
Class
In
Break Time
t
Discrimination
Normative required break time
Normative required sensitivity

RH99M
A
10000 mA
1.2 s
1s
NA
[0.00 ; 5.00] s
[0.03 ; 1245.60] mA

Discrimination Results
UpStream

Discrimination Limit

Operating mode Normal


RH197P (QA 0)

Full Discrimination

Transmission busway

WD 14 (1)

Project: New_project

06/08/2015

Page 25/87

Parameters
Length
Max length
Installation method
Ambient temperature
Level of third harmonic THDI
Ib
Sizing Information
Correction factors
Temperature factor
Installation method factor
Type of protection factor
User defined factor
Selected busway
Designation
Rating
PE type
IP
IK
Core
Icw
Ip
Reinforced short circuit
withstand

4m
NA
Standard
35 C
0%
28 A
Sized with Ir
1
1
1
1
KTC1000
1000
Standard PE
55
08
Copper
50 kA
110 kA
NA

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 3.07
2.66

2.54

2.21

2.08

2.49 0.00

Synthesis for all operating mode


(kA) 3.07
2.66
2.54

2.21

2.08

2.49 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Design current
IL1

IL2

IL3

IN

Operating mode Normal


(A)
23.617
24.295

28.340

4.42

Synthesis for all operating mode


(A)
23.617
24.295

28.340

4.42

Voltage drop
Cumulated from upstream
Operating mode Normal
1.959
U3L (%)
2.261
UL1L2 (%)
2.268
UL2L3 (%)
2.268
UL3L1 (%)
1.959
UL1N (%)
1.961
UL2N (%)
1.973
UL3N (%)
Project: New_project

Circuit
0.002
0.002
0.003
0.003
0.004
0.004
0.005
06/08/2015

Page 26/87

Project: New_project

06/08/2015

Page 27/87

3.2.6 Circuit Feeder circuit 14 (1) (1)


Circuit breaker
QA 14 (1) (1)
Ib
25.9 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
32 A
10 kA
NA
NA
NA
4P4d
C
32 A
32 A
NA
256 A
NA
NA
Discrimination Limit

Operating mode Normal


QA 0
NSX250B
Micrologic 5.2 A
250 A / 4P4d

Full Discrimination

RCD designation
Class
In
Break Time
t
Discrimination
Normative required break time
Normative required sensitivity

RH99M
A
10000 mA
1.2 s
1s
NA
[0.00 ; 5.00] s
[0.03 ; 1245.60] mA

Discrimination Results
UpStream

Discrimination Limit

Operating mode Normal


RH197P (QA 0)

Full Discrimination

Transmission busway

WD 14 (1) (1)

Project: New_project

06/08/2015

Page 28/87

Parameters
Length
Max length
Installation method
Ambient temperature
Level of third harmonic THDI
Ib
Sizing Information
Correction factors
Temperature factor
Installation method factor
Type of protection factor
User defined factor
Selected busway
Designation
Rating
PE type
IP
IK
Core
Icw
Ip
Reinforced short circuit
withstand

4m
NA
Standard
35 C
0%
26 A
Sized with Ir
1
1
1
1
KTC1000
1000
Standard PE
55
08
Copper
50 kA
110 kA
NA

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 3.07
2.66

2.54

2.21

2.08

2.49 0.00

Synthesis for all operating mode


(kA) 3.07
2.66
2.54

2.21

2.08

2.49 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Design current
IL1

IL2

IL3

IN

Operating mode Normal


(A)
25.191
25.191

25.870

0.679

Synthesis for all operating mode


(A)
25.191
25.191

25.870

0.679

Voltage drop
Cumulated from upstream
Operating mode Normal
1.959
U3L (%)
2.261
UL1L2 (%)
2.268
UL2L3 (%)
2.268
UL3L1 (%)
1.960
UL1N (%)
1.961
UL2N (%)
1.972
UL3N (%)
Project: New_project

Circuit
0.002
0.002
0.003
0.003
0.004
0.004
0.004
06/08/2015

Page 29/87

Project: New_project

06/08/2015

Page 30/87

3.3 Generic load circuits


3.3.1 Circuit Load 17
Circuit breaker
QA 17
Ib
7.87 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
10 A
10 kA
NA
NA
NA
2P1d
C
10 A
10 A
NA
80 A
NA
NA
Discrimination Limit

Operating mode Normal


QA 14
iC60N
C
32 A / 4P4d

260 A

RCD designation
Class
In
Break Time
t
Discrimination
Normative required break time
Normative required sensitivity

RH10M
A
300 mA
0.03 s
0s
NA
[0.00 ; 0.40] s
[0.00 ; 681.34] mA

Discrimination Results
UpStream

Discrimination Limit

Operating mode Normal


RH99M (QA 14)

Project: New_project

Full Discrimination

06/08/2015

Page 31/87

Cable
Parameters
Length
Max length
Installation method

WD 17

5m
42.4 m
2
A2
Multi-core cables in conduit in a
thermally insulated wall
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
8A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
B-52-14
Soil thermal resistivity factor
1
Standard table reference
B-52-16
Loaded neutral factor
1
Standard table reference
E-52-1
Touching conductor factor
1
Standard table reference
B-52-17
User correction factor
1
Overall factor
1
Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x1.5 mm
Copper
14 A
1x1.5 mm
Copper
14 A
1x4 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 3.07
2.66

2.53

1.41

0.99

1.36 0.00

Synthesis for all operating mode


(kA) 3.07
2.66
2.53

1.41

0.99

1.36 0.00

Project: New_project

Ief2min

06/08/2015

Page 32/87

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

AA 17
400 V
1.82 kVA
1.82 kW
7.87 A
1
1Ph+N
Auto
16
1
No
0
NA

Operating mode Normal


(A)
0.000
0.000

IL3
0.000

Synthesis for all operating mode


(A)
0.000
0.000
0.000
Voltage drop
Cumulated from upstream
Operating mode Normal
2.212
U3L (%)
2.261
UL1L2 (%)
2.268
UL2L3 (%)
2.268
UL3L1 (%)
2.464
UL1N (%)
2.466
UL2N (%)
2.477
UL3N (%)

IN
7.87

7.87
Circuit
0.252
0.000
0.000
0.000
0.505
0.505
0.505

Synthesis for all operating mode


2.212
U3L (%)
2.261
UL1L2 (%)
2.268
UL2L3 (%)
2.268
UL3L1 (%)
2.464
UL1N (%)
2.466
UL2N (%)
2.477
UL3N (%)

Project: New_project

06/08/2015

Page 33/87

3.3.2 Circuit Load 31


Circuit breaker
QA 31
Ib
4.33 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
6A
10 kA
NA
NA
NA
2P1d
C
6A
6A
NA
48 A
NA
NA
Discrimination Limit

Operating mode Normal


QA 27
iC60N
C
10 A / 4P4d

80 A

RCD designation
Class
In
Break Time
t
Discrimination
Normative required break time
Normative required sensitivity

RH10M
A
300 mA
0.03 s
0s
NA
[0.00 ; 0.40] s
[0.00 ; 296.34] mA

Discrimination Results
UpStream

Discrimination Limit

Operating mode Normal


RH99M (QA 27)

Full Discrimination

Cable

WD 31

Project: New_project

06/08/2015

Page 34/87

Parameters
Length
Max length
Installation method

10 m
62.6 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
XLPE
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
4A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
B-52-14
Soil thermal resistivity factor
1
Standard table reference
B-52-16
Loaded neutral factor
1
Standard table reference
E-52-1
Touching conductor factor
1
Standard table reference
B-52-20
User correction factor
1
Overall factor
1
Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x1.5 mm
Copper
26 A
1x1.5 mm
Copper
26 A
1x4 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 2.11
1.82

1.33

0.67

0.41

0.59 0.00

Synthesis for all operating mode


(kA) 2.11
1.82
1.33

0.67

0.41

0.59 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
Project: New_project

AA 31
06/08/2015

Page 35/87

U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

400 V
1 kVA
1 kW
4.33 A
1
1Ph+N
Auto
1
1
No
0
NA

Operating mode Normal


(A)
0.000
0.000

IL3
0.000

Synthesis for all operating mode


(A)
0.000
0.000
0.000
Voltage drop
Cumulated from upstream
Operating mode Normal
2.491
U3L (%)
2.380
UL1L2 (%)
2.464
UL2L3 (%)
2.463
UL3L1 (%)
2.181
UL1N (%)
2.183
UL2N (%)
2.919
UL3N (%)

IN
4.33

4.33
Circuit
0.296
0.000
0.000
0.000
0.000
0.000
0.592

Synthesis for all operating mode


2.491
U3L (%)
2.380
UL1L2 (%)
2.464
UL2L3 (%)
2.463
UL3L1 (%)
2.181
UL1N (%)
2.183
UL2N (%)
2.919
UL3N (%)

Project: New_project

06/08/2015

Page 36/87

3.3.3 Circuit Load 17 (1)


Circuit breaker
QA 17 (1)
Ib
7.87 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
10 A
10 kA
NA
NA
NA
2P1d
C
10 A
10 A
NA
80 A
NA
NA
Discrimination Limit

Operating mode Normal


QA 14 (1)
iC60N
C
32 A / 4P4d

260 A

RCD designation
Class
In
Break Time
t
Discrimination
Normative required break time
Normative required sensitivity

RH10M
A
300 mA
0.03 s
0s
NA
[0.00 ; 0.40] s
[0.00 ; 681.34] mA

Discrimination Results
UpStream

Discrimination Limit

Operating mode Normal


RH99M (QA 14 (1))

Full Discrimination

Cable

WD 17 (1)

Project: New_project

06/08/2015

Page 37/87

Parameters
Length
Max length
Installation method

5m
42.4 m
2
A2
Multi-core cables in conduit in a
thermally insulated wall
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
8A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
B-52-14
Soil thermal resistivity factor
1
Standard table reference
B-52-16
Loaded neutral factor
1
Standard table reference
E-52-1
Touching conductor factor
1
Standard table reference
B-52-17
User correction factor
1
Overall factor
1
Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x1.5 mm
Copper
14 A
1x1.5 mm
Copper
14 A
1x4 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 3.07
2.66

2.53

1.41

0.99

1.36 0.00

Synthesis for all operating mode


(kA) 3.07
2.66
2.53

1.41

0.99

1.36 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
Project: New_project

AA 17 (1)
06/08/2015

Page 38/87

U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

400 V
1.82 kVA
1.82 kW
7.87 A
1
1Ph+N
Auto
16
1
No
0
NA

Operating mode Normal


(A)
0.000
0.000

IL3
0.000

Synthesis for all operating mode


(A)
0.000
0.000
0.000
Voltage drop
Cumulated from upstream
Operating mode Normal
2.212
U3L (%)
2.261
UL1L2 (%)
2.268
UL2L3 (%)
2.268
UL3L1 (%)
2.464
UL1N (%)
2.466
UL2N (%)
2.477
UL3N (%)

IN
7.87

7.87
Circuit
0.252
0.000
0.000
0.000
0.505
0.505
0.505

Synthesis for all operating mode


2.212
U3L (%)
2.261
UL1L2 (%)
2.268
UL2L3 (%)
2.268
UL3L1 (%)
2.464
UL1N (%)
2.466
UL2N (%)
2.477
UL3N (%)

Project: New_project

06/08/2015

Page 39/87

3.3.4 Circuit Load 17 (1) (1)


Circuit breaker
QA 17 (1) (1)
Ib
2.62 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
3A
50 kA
NA
NA
NA
4P4d
C
3A
3A
NA
24 A
NA
NA
Discrimination Limit

Operating mode Normal


QA 14 (1) (1)
iC60N
C
32 A / 4P4d

480 A

RCD designation
Class
In
Break Time
t
Discrimination
Normative required break time
Normative required sensitivity

RH10M
A
300 mA
0.03 s
0s
NA
[0.00 ; 0.20] s
[0.00 ; 681.34] mA

Discrimination Results
UpStream

Discrimination Limit

Operating mode Normal


RH99M (QA 14 (1) (1))

Full Discrimination

Cable

WD 17 (1) (1)

Project: New_project

06/08/2015

Page 40/87

Parameters
Length
Max length
Installation method

5m
256 m
2
A2
Multi-core cables in conduit in a
thermally insulated wall
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
3A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
B-52-14
Soil thermal resistivity factor
1
Standard table reference
B-52-16
Loaded neutral factor
1
Standard table reference
E-52-1
Touching conductor factor
1
Standard table reference
B-52-17
User correction factor
1
Overall factor
1
Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x1.5 mm
Copper
13 A
1x1.5 mm
Copper
13 A
1x4 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 3.07
2.66

2.53

1.41

0.99

1.36 0.00

Synthesis for all operating mode


(kA) 3.07
2.66
2.53

1.41

0.99

1.36 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
Project: New_project

AA 17 (1) (1)
06/08/2015

Page 41/87

U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

400 V
1.82 kVA
1.82 kW
2.62 A
1
3Ph+N
16
1
No
0
NA

Operating mode Normal


(A)
2.624
2.624

IL3
2.624

Synthesis for all operating mode


(A)
2.624
2.624
2.624
Voltage drop
Cumulated from upstream
Operating mode Normal
2.043
U3L (%)
2.358
UL1L2 (%)
2.366
UL2L3 (%)
2.365
UL3L1 (%)
2.044
UL1N (%)
2.045
UL2N (%)
2.056
UL3N (%)

IN
0

0
Circuit
0.084
0.097
0.097
0.097
0.084
0.084
0.084

Synthesis for all operating mode


2.043
U3L (%)
2.358
UL1L2 (%)
2.366
UL2L3 (%)
2.365
UL3L1 (%)
2.044
UL1N (%)
2.045
UL2N (%)
2.056
UL3N (%)

Project: New_project

06/08/2015

Page 42/87

3.4 Lighting load circuits


3.4.1 Circuit Load 6
Circuit breaker
QA 6
Ib
3.23 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
4A
50 kA
NA
NA
NA
2P1d
C
4A
4A
NA
32 A
NA
NA
Discrimination Limit

Operating mode Normal


QA 3
iC60N
C
16 A / 4P4d

130 A

RCD designation
Class
In
Break Time
t
Discrimination
Normative required break time
Normative required sensitivity

RH99M
A
3000 mA
0.65 s
0.5 s
NA
[0.00 ; 5.00] s
[0.03 ; 279.88] mA

Discrimination Results
UpStream

Discrimination Limit

Operating mode Normal


RH99M (QA 3)

Project: New_project

Full Discrimination

06/08/2015

Page 43/87

Cable
Parameters
Length
Max length
Installation method

WD 6

17 m
120 m
2
A2
Multi-core cables in conduit in a
thermally insulated wall
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
3A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
B-52-14
Soil thermal resistivity factor
1
Standard table reference
B-52-16
Loaded neutral factor
1
Standard table reference
E-52-1
Touching conductor factor
1
Standard table reference
B-52-17
User correction factor
1
Overall factor
1
Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x1.5 mm
Copper
14 A
1x1.5 mm
Copper
14 A
1x4 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 3.07
2.66

2.54

0.64

0.39

0.56 0.00

Synthesis for all operating mode


(kA) 3.07
2.66
2.54

0.64

0.39

0.56 0.00

Project: New_project

Ief2min

06/08/2015

Page 44/87

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
U
S
P
I
cos
Ku (Normal)
Number of circuit
Polarity
Phase connection
Type of luminaries
Nb of luminaries
Nb of lights/luminaries
Lights power
Ballast power
Ia
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

EA 6
400 V
0.745 kVA
0.67 kW
3.23 A
0.9
1
1
1Ph+N
Auto
Metal iodine
9
1
70 W
4.5 W
5.81 A
No
0
NA

Operating mode Normal


(A)
0.000
0.000

IL3
0.000

Synthesis for all operating mode


(A)
0.000
0.000
0.000
Voltage drop
Cumulated from upstream
Operating mode Normal
2.275
U3L (%)
2.259
UL1L2 (%)
2.267
UL2L3 (%)
2.265
UL3L1 (%)
1.956
UL1N (%)
1.959
UL2N (%)
2.603
UL3N (%)

IN
3.23

3.23
Circuit
0.317
0.000
0.000
0.000
0.000
0.000
0.635

Synthesis for all operating mode


2.275
U3L (%)
2.259
UL1L2 (%)
2.267
UL2L3 (%)
2.265
UL3L1 (%)
1.956
UL1N (%)
1.959
UL2N (%)
2.603
UL3N (%)

Project: New_project

06/08/2015

Page 45/87

3.4.2 Circuit Load 7


Circuit breaker
QA 7
Ib
3.23 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
4A
50 kA
NA
NA
NA
2P1d
C
4A
4A
NA
32 A
NA
NA
Discrimination Limit

Operating mode Normal


QA 3
iC60N
C
16 A / 4P4d

130 A

RCD designation
Class
In
Break Time
t
Discrimination
Normative required break time
Normative required sensitivity

RH99M
A
3000 mA
0.65 s
0.5 s
NA
[0.00 ; 5.00] s
[0.03 ; 279.88] mA

Discrimination Results
UpStream

Discrimination Limit

Operating mode Normal


RH99M (QA 3)

Full Discrimination

Cable

WD 7

Project: New_project

06/08/2015

Page 46/87

Parameters
Length
Max length
Installation method

17 m
120 m
2
A2
Multi-core cables in conduit in a
thermally insulated wall
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
3A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
B-52-14
Soil thermal resistivity factor
1
Standard table reference
B-52-16
Loaded neutral factor
1
Standard table reference
E-52-1
Touching conductor factor
1
Standard table reference
B-52-17
User correction factor
1
Overall factor
1
Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x1.5 mm
Copper
14 A
1x1.5 mm
Copper
14 A
1x4 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 3.07
2.66

2.54

0.64

0.39

0.56 0.00

Synthesis for all operating mode


(kA) 3.07
2.66
2.54

0.64

0.39

0.56 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
Project: New_project

EA 7
06/08/2015

Page 47/87

U
S
P
I
cos
Ku (Normal)
Number of circuit
Polarity
Phase connection
Type of luminaries
Nb of luminaries
Nb of lights/luminaries
Lights power
Ballast power
Ia
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

400 V
0.745 kVA
0.67 kW
3.23 A
0.9
1
1
1Ph+N
Auto
Metal iodine
9
1
70 W
4.5 W
5.81 A
No
0
NA

Operating mode Normal


(A)
0.000
0.000

IL3
0.000

Synthesis for all operating mode


(A)
0.000
0.000
0.000
Voltage drop
Cumulated from upstream
Operating mode Normal
2.275
U3L (%)
2.259
UL1L2 (%)
2.267
UL2L3 (%)
2.265
UL3L1 (%)
1.956
UL1N (%)
2.593
UL2N (%)
1.968
UL3N (%)

IN
3.23

3.23
Circuit
0.317
0.000
0.000
0.000
0.000
0.635
0.000

Synthesis for all operating mode


2.275
U3L (%)
2.259
UL1L2 (%)
2.267
UL2L3 (%)
2.265
UL3L1 (%)
1.956
UL1N (%)
2.593
UL2N (%)
1.968
UL3N (%)

Project: New_project

06/08/2015

Page 48/87

3.4.3 Circuit Load 8


Circuit breaker
QA 8
Ib
3.23 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
4A
50 kA
NA
NA
NA
2P1d
C
4A
4A
NA
32 A
NA
NA
Discrimination Limit

Operating mode Normal


QA 3
iC60N
C
16 A / 4P4d

130 A

RCD designation
Class
In
Break Time
t
Discrimination
Normative required break time
Normative required sensitivity

RH99M
A
3000 mA
0.65 s
0.5 s
NA
[0.00 ; 5.00] s
[0.03 ; 279.88] mA

Discrimination Results
UpStream

Discrimination Limit

Operating mode Normal


RH99M (QA 3)

Full Discrimination

Cable

WD 8

Project: New_project

06/08/2015

Page 49/87

Parameters
Length
Max length
Installation method

17 m
120 m
2
A2
Multi-core cables in conduit in a
thermally insulated wall
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
3A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
B-52-14
Soil thermal resistivity factor
1
Standard table reference
B-52-16
Loaded neutral factor
1
Standard table reference
E-52-1
Touching conductor factor
1
Standard table reference
B-52-17
User correction factor
1
Overall factor
1
Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x1.5 mm
Copper
14 A
1x1.5 mm
Copper
14 A
1x4 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 3.07
2.66

2.54

0.64

0.39

0.56 0.00

Synthesis for all operating mode


(kA) 3.07
2.66
2.54

0.64

0.39

0.56 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
Project: New_project

EA 8
06/08/2015

Page 50/87

U
S
P
I
cos
Ku (Normal)
Number of circuit
Polarity
Phase connection
Type of luminaries
Nb of luminaries
Nb of lights/luminaries
Lights power
Ballast power
Ia
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

400 V
0.745 kVA
0.67 kW
3.23 A
0.9
1
1
1Ph+N
Auto
Metal iodine
9
1
70 W
4.5 W
5.81 A
No
0
NA

Operating mode Normal


(A)
0.000
0.000

IL3
0.000

Synthesis for all operating mode


(A)
0.000
0.000
0.000
Voltage drop
Cumulated from upstream
Operating mode Normal
2.275
U3L (%)
2.259
UL1L2 (%)
2.267
UL2L3 (%)
2.265
UL3L1 (%)
2.591
UL1N (%)
1.959
UL2N (%)
1.968
UL3N (%)

IN
3.23

3.23
Circuit
0.317
0.000
0.000
0.000
0.635
0.000
0.000

Synthesis for all operating mode


2.275
U3L (%)
2.259
UL1L2 (%)
2.267
UL2L3 (%)
2.265
UL3L1 (%)
2.591
UL1N (%)
1.959
UL2N (%)
1.968
UL3N (%)

Project: New_project

06/08/2015

Page 51/87

3.4.4 Circuit Load 9


Circuit breaker
QA 9
Ib
0.943 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
1A
50 kA
NA
NA
NA
2P1d
C
1A
1A
NA
8A
NA
NA
Discrimination Limit

Operating mode Normal


QA 3
iC60N
C
16 A / 4P4d

370 A

RCD designation
Class
In
Break Time
t
Discrimination
Normative required break time
Normative required sensitivity

RH99M
A
3000 mA
0.65 s
0.5 s
NA
[0.00 ; 5.00] s
[0.03 ; 557.38] mA

Discrimination Results
UpStream

Discrimination Limit

Operating mode Normal


RH99M (QA 3)

Full Discrimination

Cable

WD 9

Project: New_project

06/08/2015

Page 52/87

Parameters
Length
Max length
Installation method

7m
485 m
2
A2
Multi-core cables in conduit in a
thermally insulated wall
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
1A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
B-52-14
Soil thermal resistivity factor
1
Standard table reference
B-52-16
Loaded neutral factor
1
Standard table reference
E-52-1
Touching conductor factor
1
Standard table reference
B-52-17
User correction factor
1
Overall factor
1
Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x1.5 mm
Copper
14 A
1x1.5 mm
Copper
14 A
1x4 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 3.07
2.66

2.54

1.19

0.79

1.11 0.00

Synthesis for all operating mode


(kA) 3.07
2.66
2.54

1.19

0.79

1.11 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
Project: New_project

EA 9
06/08/2015

Page 53/87

U
S
P
I
cos
Ku (Normal)
Number of circuit
Polarity
Phase connection
Type of luminaries
Nb of luminaries
Nb of lights/luminaries
Lights power
Ballast power
Ia
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

400 V
0.218 kVA
0.202 kW
0.943 A
0.93
1
1
1Ph+N
Auto
Fluorescent with electronic ballast
5
1
36 W
4.5 W
0.943 A
No
0
NA

Operating mode Normal


(A)
0.000
0.000

IL3
0.000

Synthesis for all operating mode


(A)
0.000
0.000
0.000
Voltage drop
Cumulated from upstream
Operating mode Normal
1.997
U3L (%)
2.259
UL1L2 (%)
2.267
UL2L3 (%)
2.265
UL3L1 (%)
1.956
UL1N (%)
1.959
UL2N (%)
2.047
UL3N (%)

IN
0.943

0.943
Circuit
0.039
0.000
0.000
0.000
0.000
0.000
0.079

Synthesis for all operating mode


1.997
U3L (%)
2.259
UL1L2 (%)
2.267
UL2L3 (%)
2.265
UL3L1 (%)
1.956
UL1N (%)
1.959
UL2N (%)
2.047
UL3N (%)

Project: New_project

06/08/2015

Page 54/87

3.4.5 Circuit Load 10


Circuit breaker
QA 10
Ib
0.943 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
1A
50 kA
NA
NA
NA
2P1d
C
1A
1A
NA
8A
NA
NA
Discrimination Limit

Operating mode Normal


QA 3
iC60N
C
16 A / 4P4d

370 A

RCD designation
Class
In
Break Time
t
Discrimination
Normative required break time
Normative required sensitivity

RH99M
A
3000 mA
0.65 s
0.5 s
NA
[0.00 ; 5.00] s
[0.03 ; 242.72] mA

Discrimination Results
UpStream

Discrimination Limit

Operating mode Normal


RH99M (QA 3)

Full Discrimination

Cable

WD 10

Project: New_project

06/08/2015

Page 55/87

Parameters
Length
Max length
Installation method

20 m
485 m
2
A2
Multi-core cables in conduit in a
thermally insulated wall
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
1A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
B-52-14
Soil thermal resistivity factor
1
Standard table reference
B-52-16
Loaded neutral factor
1
Standard table reference
E-52-1
Touching conductor factor
1
Standard table reference
B-52-17
User correction factor
1
Overall factor
1
Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x1.5 mm
Copper
14 A
1x1.5 mm
Copper
14 A
1x4 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 3.07
2.66

2.54

0.56

0.34

0.49 0.00

Synthesis for all operating mode


(kA) 3.07
2.66
2.54

0.56

0.34

0.49 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
Project: New_project

EA 10
06/08/2015

Page 56/87

U
S
P
I
cos
Ku (Normal)
Number of circuit
Polarity
Phase connection
Type of luminaries
Nb of luminaries
Nb of lights/luminaries
Lights power
Ballast power
Ia
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

400 V
0.218 kVA
0.202 kW
0.943 A
0.93
1
1
1Ph+N
Auto
Fluorescent with electronic ballast
5
1
36 W
4.5 W
0.943 A
No
0
NA

Operating mode Normal


(A)
0.000
0.000

IL3
0.000

Synthesis for all operating mode


(A)
0.000
0.000
0.000
Voltage drop
Cumulated from upstream
Operating mode Normal
2.070
U3L (%)
2.259
UL1L2 (%)
2.267
UL2L3 (%)
2.265
UL3L1 (%)
1.956
UL1N (%)
2.184
UL2N (%)
1.968
UL3N (%)

IN
0.943

0.943
Circuit
0.113
0.000
0.000
0.000
0.000
0.225
0.000

Synthesis for all operating mode


2.070
U3L (%)
2.259
UL1L2 (%)
2.267
UL2L3 (%)
2.265
UL3L1 (%)
1.956
UL1N (%)
2.184
UL2N (%)
1.968
UL3N (%)

Project: New_project

06/08/2015

Page 57/87

3.4.6 Circuit Load 11


Circuit breaker
QA 11
Ib
1.05 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60L
1.6 A
100 kA
100 kA
NA
NA
2P2d
C
1.6 A
1.6 A
NA
12.8 A
NA
NA
Discrimination Limit

Operating mode Normal


QA 3
iC60N
C
16 A / 4P4d

128 A

RCD designation
Class
In
Break Time
t
Discrimination
Normative required break time
Normative required sensitivity

RH99M
A
3000 mA
0.65 s
0.5 s
NA
[0.00 ; 5.00] s
[0.03 ; 557.38] mA

Discrimination Results
UpStream

Discrimination Limit

Operating mode Normal


RH99M (QA 3)

Full Discrimination

Cable

WD 11

Project: New_project

06/08/2015

Page 58/87

Parameters
Length
Max length
Installation method

7m
302 m
2
A2
Multi-core cables in conduit in a
thermally insulated wall
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
1A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
B-52-14
Soil thermal resistivity factor
1
Standard table reference
B-52-16
Loaded neutral factor
1
Standard table reference
E-52-1
Touching conductor factor
1
Standard table reference
B-52-17
User correction factor
1
Overall factor
1
Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x1.5 mm
Copper
14 A
1x1.5 mm
Copper
14 A
1x4 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 3.07
2.66

2.54

1.19

0.79

1.11 0.00

Synthesis for all operating mode


(kA) 3.07
2.66
2.54

1.19

0.79

1.11 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
Project: New_project

EA 11
06/08/2015

Page 59/87

U
S
P
I
cos
Ku (Normal)
Number of circuit
Polarity
Phase connection
Type of luminaries
Nb of luminaries
Nb of lights/luminaries
Lights power
Ballast power
Ia
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

400 V
0.242 kVA
0.225 kW
1.05 A
0.93
1
1
1Ph+N
Auto
Fluorescent with electronic ballast
10
1
18 W
4.5 W
1.05 A
No
0
NA

Operating mode Normal


(A)
0.000
0.000

IL3
0.000

Synthesis for all operating mode


(A)
0.000
0.000
0.000
Voltage drop
Cumulated from upstream
Operating mode Normal
2.002
U3L (%)
2.259
UL1L2 (%)
2.267
UL2L3 (%)
2.265
UL3L1 (%)
2.044
UL1N (%)
1.959
UL2N (%)
1.968
UL3N (%)

IN
1.05

1.05
Circuit
0.044
0.000
0.000
0.000
0.088
0.000
0.000

Synthesis for all operating mode


2.002
U3L (%)
2.259
UL1L2 (%)
2.267
UL2L3 (%)
2.265
UL3L1 (%)
2.044
UL1N (%)
1.959
UL2N (%)
1.968
UL3N (%)

Project: New_project

06/08/2015

Page 60/87

3.4.7 Circuit Load 12


Circuit breaker
QA 12
Ib
1.05 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60L
1.6 A
100 kA
100 kA
NA
NA
2P2d
C
1.6 A
1.6 A
NA
12.8 A
NA
NA
Discrimination Limit

Operating mode Normal


QA 3
iC60N
C
16 A / 4P4d

128 A

RCD designation
Class
In
Break Time
t
Discrimination
Normative required break time
Normative required sensitivity

RH99M
A
3000 mA
0.65 s
0.5 s
NA
[0.00 ; 5.00] s
[0.03 ; 242.72] mA

Discrimination Results
UpStream

Discrimination Limit

Operating mode Normal


RH99M (QA 3)

Full Discrimination

Cable

WD 12

Project: New_project

06/08/2015

Page 61/87

Parameters
Length
Max length
Installation method

20 m
302 m
2
A2
Multi-core cables in conduit in a
thermally insulated wall
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
1A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
B-52-14
Soil thermal resistivity factor
1
Standard table reference
B-52-16
Loaded neutral factor
1
Standard table reference
E-52-1
Touching conductor factor
1
Standard table reference
B-52-17
User correction factor
1
Overall factor
1
Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x1.5 mm
Copper
14 A
1x1.5 mm
Copper
14 A
1x4 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 3.07
2.66

2.54

0.56

0.34

0.49 0.00

Synthesis for all operating mode


(kA) 3.07
2.66
2.54

0.56

0.34

0.49 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
Project: New_project

EA 12
06/08/2015

Page 62/87

U
S
P
I
cos
Ku (Normal)
Number of circuit
Polarity
Phase connection
Type of luminaries
Nb of luminaries
Nb of lights/luminaries
Lights power
Ballast power
Ia
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

400 V
0.242 kVA
0.225 kW
1.05 A
0.93
1
1
1Ph+N
Auto
Fluorescent with electronic ballast
10
1
18 W
4.5 W
1.05 A
No
0
NA

Operating mode Normal


(A)
0.000
0.000

IL3
0.000

Synthesis for all operating mode


(A)
0.000
0.000
0.000
Voltage drop
Cumulated from upstream
Operating mode Normal
2.083
U3L (%)
2.259
UL1L2 (%)
2.267
UL2L3 (%)
2.265
UL3L1 (%)
1.956
UL1N (%)
1.959
UL2N (%)
2.219
UL3N (%)

IN
1.05

1.05
Circuit
0.125
0.000
0.000
0.000
0.000
0.000
0.250

Synthesis for all operating mode


2.083
U3L (%)
2.259
UL1L2 (%)
2.267
UL2L3 (%)
2.265
UL3L1 (%)
1.956
UL1N (%)
1.959
UL2N (%)
2.219
UL3N (%)

Project: New_project

06/08/2015

Page 63/87

3.4.8 Circuit Load 18


Circuit breaker
QA 18
Ib
1.13 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60L
1.6 A
100 kA
100 kA
NA
NA
2P2d
C
1.6 A
1.6 A
NA
12.8 A
NA
NA
Discrimination Limit

Operating mode Normal


QA 14
iC60N
C
32 A / 4P4d

256 A

RCD designation
Class
In
Break Time
t
Discrimination
Normative required break time
Normative required sensitivity

RH99M
A
3000 mA
0.65 s
0.5 s
NA
[0.00 ; 5.00] s
[0.03 ; 681.34] mA

Discrimination Results
UpStream

Discrimination Limit

Operating mode Normal


RH99M (QA 14)

Full Discrimination

Cable

WD 18

Project: New_project

06/08/2015

Page 64/87

Parameters
Length
Max length
Installation method

5m
302 m
2
A2
Multi-core cables in conduit in a
thermally insulated wall
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
1A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
B-52-14
Soil thermal resistivity factor
1
Standard table reference
B-52-16
Loaded neutral factor
1
Standard table reference
E-52-1
Touching conductor factor
1
Standard table reference
B-52-17
User correction factor
1
Overall factor
1
Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x1.5 mm
Copper
14 A
1x1.5 mm
Copper
14 A
1x4 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 3.07
2.66

2.53

1.41

0.99

1.36 0.00

Synthesis for all operating mode


(kA) 3.07
2.66
2.53

1.41

0.99

1.36 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
Project: New_project

EA 18
06/08/2015

Page 65/87

U
S
P
I
cos
Ku (Normal)
Number of circuit
Polarity
Phase connection
Type of luminaries
Nb of luminaries
Nb of lights/luminaries
Lights power
Ballast power
Ia
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

400 V
0.261 kVA
0.243 kW
1.13 A
0.93
1
1
1Ph+N
Auto
Fluorescent with electronic ballast
6
1
36 W
4.5 W
1.13 A
No
0
NA

Operating mode Normal


(A)
0.000
0.000

IL3
0.000

Synthesis for all operating mode


(A)
0.000
0.000
0.000
Voltage drop
Cumulated from upstream
Operating mode Normal
1.993
U3L (%)
2.261
UL1L2 (%)
2.268
UL2L3 (%)
2.268
UL3L1 (%)
1.959
UL1N (%)
2.028
UL2N (%)
1.973
UL3N (%)

IN
1.13

1.13
Circuit
0.034
0.000
0.000
0.000
0.000
0.068
0.000

Synthesis for all operating mode


1.993
U3L (%)
2.261
UL1L2 (%)
2.268
UL2L3 (%)
2.268
UL3L1 (%)
1.959
UL1N (%)
2.028
UL2N (%)
1.973
UL3N (%)

Project: New_project

06/08/2015

Page 66/87

3.4.9 Circuit Load 20


Circuit breaker
QA 20
Ib
1.43 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60L
1.6 A
100 kA
100 kA
NA
NA
2P2d
C
1.6 A
1.6 A
NA
12.8 A
NA
NA
Discrimination Limit

Operating mode Normal


QA 19
iC60N
C
16 A / 4P4d

128 A

RCD designation
Class
In
Break Time
t
Discrimination
Normative required break time
Normative required sensitivity

RH99M
A
3000 mA
0.65 s
0.5 s
NA
[0.00 ; 5.00] s
[0.03 ; 430.87] mA

Discrimination Results
UpStream

Discrimination Limit

Operating mode Normal


RH99M (QA 19)

Full Discrimination

Cable

WD 20

Project: New_project

06/08/2015

Page 67/87

Parameters
Length
Max length
Installation method

10 m
302 m
21
C
Multi-core cables fixed directly under a
wooden ceiling
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
1A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
B-52-14
Soil thermal resistivity factor
1
Standard table reference
B-52-16
Loaded neutral factor
1
Standard table reference
E-52-1
Touching conductor factor
0.95
Standard table reference
B-52-17
User correction factor
1
Overall factor
0.95
Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper
18.5 A
1x4 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 3.07
2.66

2.53

0.95

0.60

0.86 0.00

Synthesis for all operating mode


(kA) 3.07
2.66
2.53

0.95

0.60

0.86 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
Project: New_project

EA 20
06/08/2015

Page 68/87

U
S
P
I
cos
Ku (Normal)
Number of circuit
Polarity
Phase connection
Type of luminaries
Nb of luminaries
Nb of lights/luminaries
Lights power
Ballast power
Ia
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

400 V
0.331 kVA
0.298 kW
1.43 A
0.9
1
1
1Ph+N
Auto
Metal iodine
4
1
70 W
4.5 W
2.58 A
No
0
NA

Operating mode Normal


(A)
0.000
0.000

IL3
0.000

Synthesis for all operating mode


(A)
0.000
0.000
0.000
Voltage drop
Cumulated from upstream
Operating mode Normal
2.041
U3L (%)
2.260
UL1L2 (%)
2.267
UL2L3 (%)
2.266
UL3L1 (%)
1.958
UL1N (%)
1.959
UL2N (%)
2.134
UL3N (%)

IN
1.43

1.43
Circuit
0.083
0.000
0.000
0.000
0.000
0.000
0.166

Synthesis for all operating mode


2.041
U3L (%)
2.260
UL1L2 (%)
2.267
UL2L3 (%)
2.266
UL3L1 (%)
1.958
UL1N (%)
1.959
UL2N (%)
2.134
UL3N (%)

Project: New_project

06/08/2015

Page 69/87

3.4.10 Circuit Load 18 (1)


Circuit breaker
QA 18 (1)
Ib
1.13 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60L
1.6 A
100 kA
100 kA
NA
NA
2P2d
C
1.6 A
1.6 A
NA
12.8 A
NA
NA
Discrimination Limit

Operating mode Normal


QA 14 (1)
iC60N
C
32 A / 4P4d

256 A

RCD designation
Class
In
Break Time
t
Discrimination
Normative required break time
Normative required sensitivity

RH99M
A
3000 mA
0.65 s
0.5 s
NA
[0.00 ; 5.00] s
[0.03 ; 681.34] mA

Discrimination Results
UpStream

Discrimination Limit

Operating mode Normal


RH99M (QA 14 (1))

Full Discrimination

Cable

WD 18 (1)

Project: New_project

06/08/2015

Page 70/87

Parameters
Length
Max length
Installation method

5m
302 m
2
A2
Multi-core cables in conduit in a
thermally insulated wall
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
1A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
B-52-14
Soil thermal resistivity factor
1
Standard table reference
B-52-16
Loaded neutral factor
1
Standard table reference
E-52-1
Touching conductor factor
1
Standard table reference
B-52-17
User correction factor
1
Overall factor
1
Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x1.5 mm
Copper
14 A
1x1.5 mm
Copper
14 A
1x4 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 3.07
2.66

2.53

1.41

0.99

1.36 0.00

Synthesis for all operating mode


(kA) 3.07
2.66
2.53

1.41

0.99

1.36 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
Project: New_project

EA 18 (1)
06/08/2015

Page 71/87

U
S
P
I
cos
Ku (Normal)
Number of circuit
Polarity
Phase connection
Type of luminaries
Nb of luminaries
Nb of lights/luminaries
Lights power
Ballast power
Ia
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

400 V
0.261 kVA
0.243 kW
1.13 A
0.93
1
1
1Ph+N
Auto
Fluorescent with electronic ballast
6
1
36 W
4.5 W
1.13 A
No
0
NA

Operating mode Normal


(A)
0.000
0.000

IL3
0.000

Synthesis for all operating mode


(A)
0.000
0.000
0.000
Voltage drop
Cumulated from upstream
Operating mode Normal
1.993
U3L (%)
2.261
UL1L2 (%)
2.268
UL2L3 (%)
2.268
UL3L1 (%)
1.959
UL1N (%)
2.028
UL2N (%)
1.973
UL3N (%)

IN
1.13

1.13
Circuit
0.034
0.000
0.000
0.000
0.000
0.068
0.000

Synthesis for all operating mode


1.993
U3L (%)
2.261
UL1L2 (%)
2.268
UL2L3 (%)
2.268
UL3L1 (%)
1.959
UL1N (%)
2.028
UL2N (%)
1.973
UL3N (%)

Project: New_project

06/08/2015

Page 72/87

3.4.11 Circuit Load 18 (1) (1)


Circuit breaker
QA 18 (1) (1)
Ib
1.13 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60L
1.6 A
100 kA
100 kA
NA
NA
2P2d
C
1.6 A
1.6 A
NA
12.8 A
NA
NA
Discrimination Limit

Operating mode Normal


QA 14 (1) (1)
iC60N
C
32 A / 4P4d

256 A

RCD designation
Class
In
Break Time
t
Discrimination
Normative required break time
Normative required sensitivity

RH99M
A
3000 mA
0.65 s
0.5 s
NA
[0.00 ; 5.00] s
[0.03 ; 681.34] mA

Discrimination Results
UpStream

Discrimination Limit

Operating mode Normal


RH99M (QA 14 (1) (1))

Full Discrimination

Cable

WD 18 (1) (1)

Project: New_project

06/08/2015

Page 73/87

Parameters
Length
Max length
Installation method

5m
302 m
2
A2
Multi-core cables in conduit in a
thermally insulated wall
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
1A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
B-52-14
Soil thermal resistivity factor
1
Standard table reference
B-52-16
Loaded neutral factor
1
Standard table reference
E-52-1
Touching conductor factor
1
Standard table reference
B-52-17
User correction factor
1
Overall factor
1
Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x1.5 mm
Copper
14 A
1x1.5 mm
Copper
14 A
1x4 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 3.07
2.66

2.53

1.41

0.99

1.36 0.00

Synthesis for all operating mode


(kA) 3.07
2.66
2.53

1.41

0.99

1.36 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
Project: New_project

EA 18 (1) (1)
06/08/2015

Page 74/87

U
S
P
I
cos
Ku (Normal)
Number of circuit
Polarity
Phase connection
Type of luminaries
Nb of luminaries
Nb of lights/luminaries
Lights power
Ballast power
Ia
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

400 V
0.261 kVA
0.243 kW
1.13 A
0.93
1
1
1Ph+N
Auto
Fluorescent with electronic ballast
6
1
36 W
4.5 W
1.13 A
No
0
NA

Operating mode Normal


(A)
0.000
0.000

IL3
0.000

Synthesis for all operating mode


(A)
0.000
0.000
0.000
Voltage drop
Cumulated from upstream
Operating mode Normal
1.993
U3L (%)
2.261
UL1L2 (%)
2.268
UL2L3 (%)
2.268
UL3L1 (%)
1.960
UL1N (%)
1.961
UL2N (%)
2.040
UL3N (%)

IN
1.13

1.13
Circuit
0.034
0.000
0.000
0.000
0.000
0.000
0.068

Synthesis for all operating mode


1.993
U3L (%)
2.261
UL1L2 (%)
2.268
UL2L3 (%)
2.268
UL3L1 (%)
1.960
UL1N (%)
1.961
UL2N (%)
2.040
UL3N (%)

Project: New_project

06/08/2015

Page 75/87

3.5 Power socket load circuits


3.5.1 Circuit Load 13
Circuit breaker
QA 13
Ib
15.9 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
16 A
10 kA
NA
NA
NA
2P1d
C
16 A
16 A
NA
128 A
NA
NA
Discrimination Limit

Operating mode Normal


QA 3
iC60N
C
16 A / 4P4d

No Discrimination

RCD designation
Class
In
Break Time
t
Discrimination
Normative required break time
Normative required sensitivity

RH10M
A
30 mA
0.03 s
0s
NA
[0.00 ; 0.40] s
[0.01 ; 0.03] mA

Discrimination Results
UpStream

Discrimination Limit

Operating mode Normal


RH99M (QA 3)

Project: New_project

Full Discrimination

06/08/2015

Page 76/87

Cable
Parameters
Length
Max length
Installation method

WD 13

10 m
43 m
2
A2
Multi-core cables in conduit in a
thermally insulated wall
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
16 A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
B-52-14
Soil thermal resistivity factor
1
Standard table reference
B-52-16
Loaded neutral factor
1
Standard table reference
E-52-1
Touching conductor factor
1
Standard table reference
B-52-17
User correction factor
1
Overall factor
1
Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x2.5 mm
Copper
18.5 A
1x2.5 mm
Copper
18.5 A
1x4 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 3.07
2.66

2.54

1.29

0.88

1.10 0.00

Synthesis for all operating mode


(kA) 3.07
2.66
2.54

1.29

0.88

1.10 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


Project: New_project

06/08/2015

Page 77/87

All assumptions and device choices are the user's responsibility.


Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

AA 13
400 V
3.68 kVA
3.68 kW
15.9 A
1
1Ph+N
Auto
1
1
No
0
NA

Operating mode Normal


(A)
0.000
0.000

IL3
0.000

Synthesis for all operating mode


(A)
0.000
0.000
0.000
Voltage drop
Cumulated from upstream
Operating mode Normal
2.571
U3L (%)
2.259
UL1L2 (%)
2.267
UL2L3 (%)
2.265
UL3L1 (%)
1.956
UL1N (%)
3.185
UL2N (%)
1.968
UL3N (%)

IN
15.9

15.9
Circuit
0.613
0.000
0.000
0.000
0.000
1.226
0.000

Synthesis for all operating mode


2.571
U3L (%)
2.259
UL1L2 (%)
2.267
UL2L3 (%)
2.265
UL3L1 (%)
1.956
UL1N (%)
3.185
UL2N (%)
1.968
UL3N (%)

Project: New_project

06/08/2015

Page 78/87

3.5.2 Circuit Load 25


Circuit breaker
QA 25
Ib
15.9 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
16 A
10 kA
NA
NA
NA
2P1d
C
16 A
16 A
NA
128 A
NA
NA
Discrimination Limit

Operating mode Normal


QA 19
iC60N
C
16 A / 4P4d

No Discrimination

RCD designation
Class
In
Break Time
t
Discrimination
Normative required break time
Normative required sensitivity

RH10M
A
30 mA
0.03 s
0s
NA
[0.00 ; 0.40] s
[0.01 ; 0.03] mA

Discrimination Results
UpStream

Discrimination Limit

Operating mode Normal


RH99M (QA 19)

Full Discrimination

Cable

WD 25

Project: New_project

06/08/2015

Page 79/87

Parameters
Length
Max length
Installation method

5m
43 m
2
A2
Multi-core cables in conduit in a
thermally insulated wall
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
16 A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
B-52-14
Soil thermal resistivity factor
1
Standard table reference
B-52-16
Loaded neutral factor
1
Standard table reference
E-52-1
Touching conductor factor
1
Standard table reference
B-52-17
User correction factor
1
Overall factor
1
Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x2.5 mm
Copper
18.5 A
1x2.5 mm
Copper
18.5 A
1x4 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 3.07
2.66

2.53

1.69

1.29

1.61 0.00

Synthesis for all operating mode


(kA) 3.07
2.66
2.53

1.69

1.29

1.61 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
Project: New_project

AA 25
06/08/2015

Page 80/87

U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

400 V
3.68 kVA
3.68 kW
15.9 A
1
1Ph+N
Auto
2
1
No
0
NA

Operating mode Normal


(A)
0.000
0.000

IL3
0.000

Synthesis for all operating mode


(A)
0.000
0.000
0.000
Voltage drop
Cumulated from upstream
Operating mode Normal
2.265
U3L (%)
2.260
UL1L2 (%)
2.267
UL2L3 (%)
2.266
UL3L1 (%)
2.571
UL1N (%)
2.572
UL2N (%)
1.968
UL3N (%)

IN
15.9

15.9
Circuit
0.307
0.000
0.000
0.000
0.613
0.613
0.000

Synthesis for all operating mode


2.265
U3L (%)
2.260
UL1L2 (%)
2.267
UL2L3 (%)
2.266
UL3L1 (%)
2.571
UL1N (%)
2.572
UL2N (%)
1.968
UL3N (%)

Project: New_project

06/08/2015

Page 81/87

3.6 Motor starter combination


3.6.1 Circuit Motor Load 30
Circuit breaker
QA 30
Ib
NA
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 P25M
P25M
4A
150 kA
NA
NA
NA
3P3d
M
4A
4A
NA
51 A
NA
NA
Discrimination Limit

Operating mode Normal


QA 27
iC60N
C
10 A / 4P4d

17 A

RCD designation
Class
In
Break Time
t
Discrimination
Normative required break time
Normative required sensitivity

RH10M
A
300 mA
0.03 s
0s
NA
[0.00 ; 0.20] s
[0.00 ; 414.00] mA

Discrimination Results
UpStream

Discrimination Limit

Operating mode Normal


RH99M (QA 27)

Project: New_project

Full Discrimination

06/08/2015

Page 82/87

Contactor
Designation
Type of coordination

LC1K06
LC1K06
T1

Cable
Parameters
Length
Max length
Installation method

WD 30

5m
189 m
20
C
multi-core cables fixed on or spaced less
than 03 x cable diameter from a wooden
wall
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
XLPE
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
4A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
B-52-14
Soil thermal resistivity factor
1
Standard table reference
B-52-16
Loaded neutral factor
1
Standard table reference
E-52-1
Touching conductor factor
1
Standard table reference
B-52-17
User correction factor
1
Overall factor
1
Selected phase
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x1.5 mm
Copper
22 A
1x4 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 2.11
1.82

0.00

0.91

0.00

0.83 0.00

Synthesis for all operating mode


(kA) 2.11
1.82
0.00

0.91

0.00

0.83 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


Project: New_project

06/08/2015

Page 83/87

All assumptions and device choices are the user's responsibility.


Asynchronous LV Motor
Startup type
U
Mechanical power
Startup current Id/Ir
Transient current Id/Ir
Ir for sizing
Sr for sizing
Pr for sizing
cos
Polarity
Number of circuit
Ku (mode Normal)
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

MA 30
Direct
400 V
1.5 kW
6
<=19
3.6 A
2.49 kVA
2.12 kW
0.85
3Ph
1
0.85
No
0%
NA
IL3

Operating mode Normal


(A)
3.600
3.600

3.600

Synthesis for all operating mode


(A)
3.600
3.600
3.600
Voltage drop
Cumulated from upstream
Operating mode Normal
2.300
U3L (%)
2.501
UL1L2 (%)
2.585
UL2L3 (%)
2.584
UL3L1 (%)
2.181
UL1N (%)
2.183
UL2N (%)
2.327
UL3N (%)
Startup Voltage drop
UStartUp

IN
0

0
Circuit
0.105
0.121
0.121
0.121
0.000
0.000
0.000

2.460

3.7 Busbar circuits


3.7.1
Busbar
Parameters
Switchboard Name
Switchboard Range
Rating (A)
IP
Feeder
Circuit name

Circuit WC 1
WC 1
UC 2
No preference
0
Undefined
Protection name

Protection type

Feeder circuit 3

QA 3

iC60N

Feeder circuit 14 (1)

QA 14 (1)

iC60N

Project: New_project

06/08/2015

Page 84/87

Feeder circuit 14

QA 14

iC60N

Feeder circuit 14 (1) (1) QA 14 (1) (1)

iC60N

Feeder circuit 19

QA 19

iC60N

Feeder circuit 27

QA 27

iC60N

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 3.07
2.66

2.54

2.22

2.08

2.56 0.00

Synthesis for all operating mode


(kA) 3.07
2.66
2.54

2.22

2.08

2.56 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
3.7.2
Busbar
Parameters
Switchboard Name
Switchboard Range
Rating (A)
IP
Feeder
Circuit name

Circuit WC 4
WC 4
UC 5
No preference
0
Undefined
Protection name

Protection type

Load 6

QA 6

iC60N

Load 7

QA 7

iC60N

Load 8

QA 8

iC60N

Load 9

QA 9

iC60N

Load 10

QA 10

iC60N

Load 11

QA 11

iC60L

Load 12

QA 12

iC60L

Load 13

QA 13

iC60N

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 3.07
2.66

2.54

2.22

2.08

2.51 0.00

Project: New_project

Ief2min

06/08/2015

Page 85/87

Synthesis for all operating mode


(kA) 3.07
2.66
2.54

2.22

2.08

2.51 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
3.7.3 Circuit WC 15
Busbar
WC 15
Parameters
Switchboard Name
UC 16
Switchboard Range
No preference
Rating (A)
0
IP
Undefined
Feeder
Circuit name
Protection name

Protection type

Load 17

QA 17

iC60N

Load 18

QA 18

iC60L

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 3.07
2.66

2.53

2.21

2.08

2.49 0.00

Synthesis for all operating mode


(kA) 3.07
2.66
2.53

2.21

2.08

2.49 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
3.7.4
Busbar
Parameters
Switchboard Name
Switchboard Range
Rating (A)
IP
Feeder
Circuit name

Circuit WC 21
WC 21
UC 22
No preference
0
Undefined
Protection name

Protection type

Load 20

QA 20

iC60L

Load 25

QA 25

iC60N

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 3.07
2.66

2.53

2.21

2.08

2.49 0.00

Project: New_project

Ief2min

06/08/2015

Page 86/87

Synthesis for all operating mode


(kA) 3.07
2.66
2.53

2.21

2.08

2.49 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
3.7.5 Circuit WC 28
Busbar
WC 28
Parameters
Switchboard Name
UC 29
Switchboard Range
No preference
Rating (A)
0
IP
Undefined
Feeder
Circuit name
Protection name

Protection type

Motor Load 30

QA 30

P25M

Load 31

QA 31

iC60N

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 2.11
1.82

1.33

1.37

0.95

1.34 0.00

Synthesis for all operating mode


(kA) 2.11
1.82
1.33

1.37

0.95

1.34 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
3.7.6
Busbar
Parameters
Switchboard Name
Switchboard Range
Rating (A)
IP
Feeder
Circuit name

Circuit WC 15 (1)
WC 15 (1)
UC 16 (1)
No preference
0
Undefined
Protection name

Protection type

Load 17 (1)

QA 17 (1)

iC60N

Load 18 (1)

QA 18 (1)

iC60L

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 3.07
2.66

2.53

2.21

2.08

2.49 0.00

Project: New_project

Ief2min

06/08/2015

Page 87/87

Synthesis for all operating mode


(kA) 3.07
2.66
2.53

2.21

2.08

2.49 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
3.7.7
Busbar
Parameters
Switchboard Name
Switchboard Range
Rating (A)
IP
Feeder
Circuit name

Circuit WC 15 (1) (1)


WC 15 (1) (1)
UC 16 (1) (1)
No preference
0
Undefined
Protection name

Protection type

Load 17 (1) (1)

QA 17 (1) (1)

iC60N

Load 18 (1) (1)

QA 18 (1) (1)

iC60L

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 3.07
2.66

2.53

2.21

2.08

2.49 0.00

Synthesis for all operating mode


(kA) 3.07
2.66
2.53

2.21

2.08

2.49 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Project: New_project