ATRT-01

S3/ATRT-01B
S3
transformer turns ratio testers

Vanguard Instruments Company, Inc.


www.vanguard-instruments.com

ATRT-01 S3
transformer turns ratio testers

The ATRT-01 S3 is Vanguards fourth generation, micro-processor based, single phase,


automatic transformer turns-ratio tester. This portable test unit is available in two
models, the ATRT-01 S3 (line power only), and the ATRT-01B S3 (rechargeable-battery
powered).
The ATRT-01 S3 uses the IEEE C57.12.90 measuring method to determine the transformer turns-ratio. The transformer turns-ratio is determined by precisely measuring
the voltages across the unloaded transformer windings. The ATRT-01 S3s measuring
circuitry self adjusts before each measurement to ensure turns-ratio accuracy. Two selectable test voltages, 4Vac and 40Vac, offer flexibility in testing different types of
transformers.

The ATR-01 S3 can measure transformer turns-ratios


ranging from 0.8 to 15,000 and can be used to test voltage regulators, power transformers, current transformers (CT), and potential transformers (PT). The ATRT-01
S3 also measures and displays transformer- winding
excitation current, winding polarity, and winding phase
angle. Test results are displayed on a back-lit LCD screen
(128 x 64 pixels) that is viewable in bright sunlight and
low-light conditions.
In addition to measuring a transformers turns-ratio, the
transformers name plate voltages can also be entered,
and the ATRT-01 S3 will then display the turns-ratio
percentage error. This convenient feature eliminates any
user calculation errors when testing transformers.
When testing a 3-phase transformer, the ATRT-01 S3
provides connection information (H and X test leads to
the transformer bushings) for phase A, B and C tests.
The three phase test results (turns-ratio, excitation current, winding polarity, phaseangle, and percentage error) are displayed on the LCD screen.

User Interface
The ATRT-01 S3 features a back-lit LCD screen
(128 x 64 pixels) that is viewable in direct sunlight and low-light levels. A rugged 16-key membrane keypad is used to enter test information
and to operate the unit.

Test Record Storage


The ATRT-01 S3 can store 128 records of 33 readings internally, and up to 999 test records on an
external USB Flash drive. Test records can be
recalled using the included Transformer Analysis
PC software.

Computer Interface
A Windows-based Transformer Analysis application is provided with each unit and can be
used to remotely control the ATRT-01 S3 via the
RS-232C port. Using the Transformer Analysis
software, the user can retrieve test records
(from the ATRT-01 S3s memory or a USB Flash
drive), analyze test results, and print test results
on a desktop printer. Test results are automatically exported to Excel, PDF and XML formats.

Battery Power for


Exceptional Portability
The ATRT-01B S3 is powered by a 6-volt, 7
ampere-hour, lead acid battery. This high capacity battery, coupled with the ATRT-01B S3s low
power consuming circuitry, allows the unit to be
used continuously for up to 4 hours per charge.
A built-in charger allows the unit to be used during charging.

outstanding features
Standalone or computer-controlled
Inexpensive
Displays turns-ratio from 0.8 15,000
Calculates turns-ratio percentage error
Displays winding polarity and phase
angle
Displays excitation current
Battery or AC-powered (ATRT-01B S3
only)

ordering information
Part number ATRT-01 S3

ATRT-01 S3 turns ratio tester, cables, and PC software

Part number ATRT-01B S3

ATRT-01B S3 turns ratio tester, cables, and PC software

Part number ATRT-01 S3-CABLE ATRT-01/01B S3 cables


Part number ATRT-01 S3-CASE

ATRT-01/01B S3 shipping case

Sample Test Results


Single Phase Test Results
Measured Turns
Ratio

Excitation Current Percentage


Reading
Error

Phase Angle

Three Phase Test Results


Measured Ratio for
Phase A, B, and C

Phase A, B, and C Angles

Excitation Current Percentage


Reading
Error

Transformer Type

ATRT-01/01B S3 specifications
type transformer turns ratio tester
physical specifications dimensions: 12W x 10H x 8 D (30.4 cm x 25.4 cm x 20.3 cm);
ATRT-01 S3 weight: 8 lbs. (3.6 Kg), ATRT-01B S3 weight: 9 lbs. (4.3 Kg)
input power ATRT-01 S3: 120 or 240 Vac (selectable), 50/60 Hz
ATRT-01B S3: 90 240 Vac, 50/60 Hz
battery (ATRT-01B S3 only) SLA battery delivering up to 4 hours of continuous operation per charge
measuring method ANSI/IEEE C57.12.90
turns ratio accuracy 40 Vac: 0.8 1,999 (0.1%), 2,000 3,999 (0.25%), 4,000 15,000 (1%)
4 Vac: 0.8 1,999 (0.1%), 2,000 3,999 (0.25%), 4,000 15,000 (2%)
test voltages ATRT-01 S3: 4 Vac @ 1.0A, 40 Vac @ 0.6A
ATRT-01B S3: 4 Vac @ 500mA, 40 Vac @ 70mA
phase angle measurement 0 360 degrees, Accuracy 0.2 degree (1 digit)
polarity reading In-Phase or Out of Phase indication
current reading range 0 2 Amperes, Accuracy: 2% of reading (1 mA)
display Back-lit LCD (128 x 64 pixels), viewable in direct sunlight and low light levels
computer interface RS-232C
pc software Windows-based Transformer Analysis Software (included with purchase)
internal test record storage 128 records of 33 readings
external test record storage Up to 999 test records on external USB Flash drive
safety Designed to meet IEC 61010 (1995), UL 61010A-1, and CSA-C22.2 standards
environment Operating: -10C to +50C (+15F to +122F); Storage: -30C to +70C (-22F to +158F)
humidity 90% RH @ 40C (104F) non-condensing
altitude 2,000 m (6,562 ft) to full safety specifications
cables one 15 ft (4.6m) single phase cable, one power cord, one cable bag
options transportation case (can hold unit and cables)
warranty one year on parts and labor

NOTE : the above specifications are valid at nominal voltage and ambient temperature of +25C (+77F). Specifications are subject to change without notice.

Instruments designed and developed


by the hearts and minds of utility
electricians around the world
Vanguard Instruments Company, (VIC), was founded in 1991.
Currently, our 28,000 square-foot facility houses Administration,
Design & Engineering, and Manufacturing operations. From its
inception, VICs vision was, and is to develop and manufacture
innovative test equipment for use in testing substation EHV circuit
breakers and other electrical apparatus.
The first VIC product was a computerized circuitbreaker analyzer,
which was a resounding success. It became the forerunner of an entire
series of circuitbreaker test equipment. Since its beginning, VICs
product line has expanded to include microcomputer-based, precision
micro-ohmmeters, single and three phase transformer winding turnsratio testers, transformer winding-resistance meters, mega-ohm
resistance meters, and a variety of other electrical utility maintenance
support products.
VICs performance-oriented products are well suited for the utility
industry. They are rugged, reliable, accurate, user friendly, and
most are computer controlled. Computer control, with innovative
programming, provides many automated testing functions. VICs
instruments eliminate tedious and time-consuming operations, while
providing fast, complex, test-result calculations. Errors are reduced
and the need to memorize long sequences of procedural steps is
eliminated. Every VIC instrument is competitively priced and is
covered by a liberal warranty.

Vanguard Instruments Company, Inc.


1520 S. Hellman Avenue Ontario, California 91761, USA
Phone 909-923-9390 Fax 909-923-9391
www.vanguard-instruments.com