DESIGN MEMORENDUM

FOR
ELEVATOR

DOC. NO.PE-DC-361-502-A001
REV. 00
DATE:10/12/10
Page 1 of 8

CONTENTS
1.0.0 INTENT
2.0.0 SERVICE DESCRIPTION
3.0.0 OPERATIONAL REQUIREMENTS
4.0.0 ELECTRICAL REQUIREMENTS
5.0.0 PERFORMANCE GUARANTEE
6.0.0 PAINTING SCHEDULE
7.0.0 EQUIPMENT DESIGN CRITERIA/ DATA SHEET
8.0.0 SUB VENDOR ITEMS
9.0.0 SCOPE OF WORK
11.1.0 SCOPE OF SUPPLY
11.2.0 SCOPE OF SERVICES

10.0.0 DRAWING/DOC TO BE SUBMITTED DURING DETAIL ENGINEERING


10.0.0 ANNEXURE-I (EQUIPMENT SELECTION & DESIGN CRITERIA/ DATA
SHEET FOR ELEVATOR):

DESIGN MEMORENDUM
FOR
ELEVATOR

DOC. NO.PE-DC-361-502-A001
REV. 00
DATE:10/12/10
Page 2 of 8

1.0.0 INTENT
1.0.1 The purpose of this document is to bring out clarity with regard to the
following:
a) System description and Basic operation & Control Philosophy
b) Major technical requirements of various items covered under this
package
c) Scope, exclusion
1.0.2

Approved copy of this document shall form the basis for subsequent
approval of elevator vendor documents (by Client /their consultant or by
BHEL)

1.0.3

During execution of the package by BHEL through approved vendor the


elevator will be governed by IS code and manufactures standard
practice.

2.0.0 SERVICE DESCRIPTION


Passenger elevator shall be provided for access to various operating
floors / platforms in TG hall, Service Building, Administrative Building and
ESP Control Room to facilitate movement of operating and maintenance
personnel.
3.0.0 OPERATIONAL REQUIREMENTS:
3.1.0 Elevator shall have provision to meet following operational requirements:
3.1.1 Selective simplex collective, automatic operation with or without attendant
through illuminated push button station located inside the lift car.
3.1.2 Door operating shall be automatic and infrared curtain type electronic door
protection system for opening / closing of car and landing doors.
3.1.3 Car operating panel shall be provided with luminous buttons, car position
indication in car (both visual and audio) combined with direction arrows,
overload warning indicator, battery operated alarm bell and emergency
light and fan and hands free speaker telephone set

DESIGN MEMORENDUM
FOR
ELEVATOR

DOC. NO.PE-DC-361-502-A001
REV. 00
DATE:10/12/10
Page 3 of 8

3.1.4 Two (2) push buttons, one for upward movement and the other for
downward movement at each intermediate landing and one (1) push
button at each terminal landing shall be provided in order to call the car.
Digital car position indicator at all floors, tell tale lights at all floors shall
also be provided.
3.1.5 Push buttons shall be fixed in the car for holding the door open for any
length of time required.
3.1.6 Other facilities shall be as per details indicated in data sheet placed under
Annexure-I.
4.0.0 Electrical Requirements
The motors will be squirrel cage type suitable for operation at 415V (+10%
to -15%variation), 3ph, 3 wire, 50 Hz (+3% to -5% variation) supply. The
motors will be with class-F insulation with temperature rise limited to classB. The motors will generally conform to IS-325 and suitable for AC
variable voltage variable frequency (VVVF) application. Other detail shall
be as indicated in data sheet placed under Annexure-I.
5.0.0 Performance and functional Guarantee
The functional guarantee test shall be carried out at site for over speed
test and over load test, travel and hoist speed checks.
6.0.0 Painting Schedule
6.1.0 All items shall be treated with anti corrosive epoxy based paint for the
ferrous metal items except for the items of SS construction, which shall not
be painted.
7.0.0 EQUIPMENTS DESIGN CRITERIA/DATA SHEET
7.1.0 The design criteria / data sheet indicating major parameters/ MOC to be
followed for elevator with different type of switches, push buttons,
Counterweight, Lighting &fan, Control and operation along with other
relevant details of elevator shall be as mentioned under Annexure- I.
7.2.0 For other mechanical items, if any, design criteria / data sheet shall be as
per Elevator vendors standard practice.
7.3.0 Electrical items shall in general be in line with BHEL standard
specifications.

DESIGN MEMORENDUM
FOR
ELEVATOR

DOC. NO.PE-DC-361-502-A001
REV. 00
DATE:10/12/10
Page 4 of 8

8.0.0 SUB VENDOR ITEMS


All sub- vendor items shall be as per BHEL internal approved subvendor/Elevator suppliers internal vendor list. Customer approval on the
same will not be sought.
9.0.0 MANDATORY SPARES
Order for Mandatory Spares has not been received from Customer.
Accordingly, no mandatory spares have been considered for this package.
10.0.0 SCOPE OF WORK
10.1.0 Scope of Supply
Scope of supply shall be as per Annexure-I.
10.2.0 Scope of Services
Scope of services shall comprise of the following:
a) Erection & Commissioning of Elevator.
b) Assistance for obtaining statutory approval
11.0.0 DRAWING/DOC TO BE SUBMITTED DURING DETAIL ENGINEERING
Following are the list of vendor drawing/doc to be submitted to customer
during detail engineering for approval :
a) GA and civil input for Elevator
b) Data sheet of elevator
c) QAP

DESIGN MEMORENDUM
FOR
ELEVATOR

DOC. NO.PE-DC-361-502-A001
REV. 00
DATE:10/12/10
Page 5 of 8

12.0.0 ANNEXURE-I
EQUIPMENT SELECTION & DESIGN CRITERIA/ DATA SHEET
FOR ELEVATOR

TABLE A

S.No

Building

1.

TG Hall

2.

Service
building

2 Nos.

884 Kg

3.

Administrative
building

2 No.

884 Kg

4.

ESP Control 2 Nos.


room

Sl.No.
A
1.
2.
3.
4.
5.
6.
7.
8.

9.
9.1
9.2

No of Capacity
Lifts
1 Nos. 1088 Kg

680 Kg

No of landing

Total
Rise
0.0m,
8.5m 36 M
,17.0m ,27.5m,
31.75m, 36.0m.
0.0m,
4.25m, 17M
8.5m, 12.75m,
and 17.0m.
0.0m,
4.5m, 16.5M
8.5m,
12.5m,
and 16.5m
0.0m,
3.7m, 17M
8.5m.
12.5m,
17.0m

Type
Conventional

Rated
Speed
1.00 M/s

Conventional

1.00 M/s

Conventional

1.00 M/s

Conventional

1.00 M/s

DESCRIPTION
VALUES
LIFT PARTICULARS
Elevator Location
Type of Service
Type of Elevator
Rated Load on Elevator
AS per TABLE A above
Quantity
Rated Speed of Lift
Total Travel
Nos. of floors to be served
Deisgn,construction,installation,co As per IS:14665
des including car size, door size,
shaft size, size of platform and car
entrance
CAR
Size
As indicated above under Sl.no.8
Car frame
Structural Steel and bolted construction

DESIGN MEMORENDUM
FOR
ELEVATOR

9.3
9.3.1
9.3.1.1
9.3.1.2
9.3.1.3

Car enclosure
Other facilities in car enclosure
Isolating cushion between car and
car frame
Handrails on three sides
Lighting & fan

9.3.1.4

Ventilation fan in the car

9.3.1.5

Telephone facility in the lift car

9.3.1.6
9.4
9.5

Automatic rescue device with


battery drive
Car platform
Car roof

9.6
9.6.1

Car operating panel


Type of construction

9.6.2
9.6.3

Push button
Other accessories of car operating
panel

9.6.4
9.6.4.1
9.6.4.2
9.6.5
9.6.5.1
9.6.5.2
10.
10.1

Push button and call registered


tell tale lights at each landing
Type of construction
Push Buttons
Car position indicator
Type of construction
Type of display
Car, Landing door
Type of door

10.2

Method of operation

DOC. NO.PE-DC-361-502-A001
REV. 00
DATE:10/12/10
Page 6 of 8

SS-304, 1.5mm thick sheet.


Type of cushion shall be rubber pad or
spring as per manufacturers standard.
Mirror stainless steel
One cabin fan, two recessed fluorescent
lamp fittings of lux level : 100
Shall be provided for adequate
ventilation of the car by elevator
supplier.
Internal telephone wiring and telephone
hand set shall be provided
Provided
MS plates with PVC tiles
Shall be provided with a three pin plug
5/15A, socket with switch on top of lift
car.
Partial Height car operating panel
(COP), Removable type from Car with
SS face plate
Luminous push buttons with IP 54
Car operating panel with luminous
buttons, car position indication (both
visual and audio), direction arrows,
overload warning indicator, battery
operated alarm bell, emergency light
with suitable battery-battery charger and
controls, emergency stop switch.

Box type with SS face plate


Luminous push buttons with IP 54
As per manufacturers standard
7 segment LED display
Centre opening, horizontal sliding type.
Landing door shall be fire rated for 1hr.
Power operated with automatic door
opening and closing devices.

DESIGN MEMORENDUM
FOR
ELEVATOR

10.3
10.4
11.
12.

Door Hangers and Tracks


MOC for Car, landing door
Buffers
Load Plate

13.

17.

Counter weight and counter weight


frame
Counter weights frame
Counter weight fillers
Guide
rails
complete
with
supporting brackets for the car and
counter weights.
Limit switches
Location
Apron / Facia Plate provided as
per IS 14665
Method of control

18.
19.

Position of Machine Room


Operation

20.

Car Safety & Governor


a) Stopping distance
b) Type and mode of operation of
Over speed Governor device
c) Tripping speed and design code
conforming to
d) Location
Power supply :
a) Power
b) Lighting & fan

13.1
13.2
14.

15.
15.1
16.

21.

22.

Motor details
(a) Type
(b) Type of Duty
(c) Motor Duty

DOC. NO.PE-DC-361-502-A001
REV. 00
DATE:10/12/10
Page 7 of 8

Infrared light curtain shall be provided


for safety operation of door
Provided
SS 304
Spring type for car and counterweight
As per manufacturers standard/as
applicable

Fabricated Steel Construction


Cast Iron
Provided

4 No
Bottom & top terminal
Yes
ACVVVF Control with automatic level
adjustment.
Directly above the lift Shaft.
Selective simplex collective, automatic
operation with and without attendant
with provision for locking control in
auto or Attendant position. Key type
lock switch shall be provided.
As per IS:14665
Centrifugal action
As per IS 14665
At machine room
415 Volts, 3 Phase, 50 c/s, 3 wire
system
240 Volts, 1 Phase, 50 c/s
3 phase AC squirrel Cage Induction
motor
Lift Duty
S4

DESIGN MEMORENDUM
FOR
ELEVATOR

(d) Duty Cycle of Motor


(e) Applicable standard
f) No. Of Starts Per Hour
g)Direction of rotation
h)Class of Insulation
i)Method of Starting

25.
26.
27.

j) Type of enclosures
Door Motor
a) Equipment driven by Motor
b) Direction of rotation
c) Type of enclosures
Metallic Wire Mesh between Car &
Counter Weight
Fire Man Switch
Automatic Rescue Device
Trailing cables

28.

Protection class

29.

AC for Machine room

23.

24.

DOC. NO.PE-DC-361-502-A001
REV. 00
DATE:10/12/10
Page 8 of 8

60%
IS:325
Elevator Motor shall be suitable for
minimum of 150 Starts per hour
Both Clockwise & Anticlockwise
F
AC
Variable
Voltage
Variable
Frequency
IP54
Door
(car and landing)
Bidirectional
IP54
Yes, by package supplier
Yes, by package supplier
Provided
FRLS type/as per manufacture standard
Protection class for main control panel
shall be IP 21, motor IP-54.
Windows air conditioner of 2T capacity
shall be provided by elevator supplier.