1.0.0 INTENT
2.0.0 SERVICE DESCRIPTION
3.0.0 OPERATIONAL REQUIREMENTS
4.0.0 ELECTRICAL REQUIREMENTS
5.0.0 PERFORMANCE GUARANTEE
6.0.0 PAINTING SCHEDULE
7.0.0 EQUIPMENT DESIGN CRITERIA/ DATA SHEET
8.0.0 SUB VENDOR ITEMS
9.0.0 SCOPE OF WORK
11.1.0 SCOPE OF SUPPLY
11.2.0 SCOPE OF SERVICES
DESIGN MEMORENDUM
FOR
ELEVATOR
DOC. NO.PE-DC-361-502-A001
REV. 00
DATE:10/12/10
Page 2 of 8
1.0.0 INTENT
1.0.1 The purpose of this document is to bring out clarity with regard to the
following:
a) System description and Basic operation & Control Philosophy
b) Major technical requirements of various items covered under this
package
c) Scope, exclusion
1.0.2
Approved copy of this document shall form the basis for subsequent
approval of elevator vendor documents (by Client /their consultant or by
BHEL)
1.0.3
DESIGN MEMORENDUM
FOR
ELEVATOR
DOC. NO.PE-DC-361-502-A001
REV. 00
DATE:10/12/10
Page 3 of 8
3.1.4 Two (2) push buttons, one for upward movement and the other for
downward movement at each intermediate landing and one (1) push
button at each terminal landing shall be provided in order to call the car.
Digital car position indicator at all floors, tell tale lights at all floors shall
also be provided.
3.1.5 Push buttons shall be fixed in the car for holding the door open for any
length of time required.
3.1.6 Other facilities shall be as per details indicated in data sheet placed under
Annexure-I.
4.0.0 Electrical Requirements
The motors will be squirrel cage type suitable for operation at 415V (+10%
to -15%variation), 3ph, 3 wire, 50 Hz (+3% to -5% variation) supply. The
motors will be with class-F insulation with temperature rise limited to classB. The motors will generally conform to IS-325 and suitable for AC
variable voltage variable frequency (VVVF) application. Other detail shall
be as indicated in data sheet placed under Annexure-I.
5.0.0 Performance and functional Guarantee
The functional guarantee test shall be carried out at site for over speed
test and over load test, travel and hoist speed checks.
6.0.0 Painting Schedule
6.1.0 All items shall be treated with anti corrosive epoxy based paint for the
ferrous metal items except for the items of SS construction, which shall not
be painted.
7.0.0 EQUIPMENTS DESIGN CRITERIA/DATA SHEET
7.1.0 The design criteria / data sheet indicating major parameters/ MOC to be
followed for elevator with different type of switches, push buttons,
Counterweight, Lighting &fan, Control and operation along with other
relevant details of elevator shall be as mentioned under Annexure- I.
7.2.0 For other mechanical items, if any, design criteria / data sheet shall be as
per Elevator vendors standard practice.
7.3.0 Electrical items shall in general be in line with BHEL standard
specifications.
DESIGN MEMORENDUM
FOR
ELEVATOR
DOC. NO.PE-DC-361-502-A001
REV. 00
DATE:10/12/10
Page 4 of 8
DESIGN MEMORENDUM
FOR
ELEVATOR
DOC. NO.PE-DC-361-502-A001
REV. 00
DATE:10/12/10
Page 5 of 8
12.0.0 ANNEXURE-I
EQUIPMENT SELECTION & DESIGN CRITERIA/ DATA SHEET
FOR ELEVATOR
TABLE A
S.No
Building
1.
TG Hall
2.
Service
building
2 Nos.
884 Kg
3.
Administrative
building
2 No.
884 Kg
4.
Sl.No.
A
1.
2.
3.
4.
5.
6.
7.
8.
9.
9.1
9.2
No of Capacity
Lifts
1 Nos. 1088 Kg
680 Kg
No of landing
Total
Rise
0.0m,
8.5m 36 M
,17.0m ,27.5m,
31.75m, 36.0m.
0.0m,
4.25m, 17M
8.5m, 12.75m,
and 17.0m.
0.0m,
4.5m, 16.5M
8.5m,
12.5m,
and 16.5m
0.0m,
3.7m, 17M
8.5m.
12.5m,
17.0m
Type
Conventional
Rated
Speed
1.00 M/s
Conventional
1.00 M/s
Conventional
1.00 M/s
Conventional
1.00 M/s
DESCRIPTION
VALUES
LIFT PARTICULARS
Elevator Location
Type of Service
Type of Elevator
Rated Load on Elevator
AS per TABLE A above
Quantity
Rated Speed of Lift
Total Travel
Nos. of floors to be served
Deisgn,construction,installation,co As per IS:14665
des including car size, door size,
shaft size, size of platform and car
entrance
CAR
Size
As indicated above under Sl.no.8
Car frame
Structural Steel and bolted construction
DESIGN MEMORENDUM
FOR
ELEVATOR
9.3
9.3.1
9.3.1.1
9.3.1.2
9.3.1.3
Car enclosure
Other facilities in car enclosure
Isolating cushion between car and
car frame
Handrails on three sides
Lighting & fan
9.3.1.4
9.3.1.5
9.3.1.6
9.4
9.5
9.6
9.6.1
9.6.2
9.6.3
Push button
Other accessories of car operating
panel
9.6.4
9.6.4.1
9.6.4.2
9.6.5
9.6.5.1
9.6.5.2
10.
10.1
10.2
Method of operation
DOC. NO.PE-DC-361-502-A001
REV. 00
DATE:10/12/10
Page 6 of 8
DESIGN MEMORENDUM
FOR
ELEVATOR
10.3
10.4
11.
12.
13.
17.
18.
19.
20.
13.1
13.2
14.
15.
15.1
16.
21.
22.
Motor details
(a) Type
(b) Type of Duty
(c) Motor Duty
DOC. NO.PE-DC-361-502-A001
REV. 00
DATE:10/12/10
Page 7 of 8
4 No
Bottom & top terminal
Yes
ACVVVF Control with automatic level
adjustment.
Directly above the lift Shaft.
Selective simplex collective, automatic
operation with and without attendant
with provision for locking control in
auto or Attendant position. Key type
lock switch shall be provided.
As per IS:14665
Centrifugal action
As per IS 14665
At machine room
415 Volts, 3 Phase, 50 c/s, 3 wire
system
240 Volts, 1 Phase, 50 c/s
3 phase AC squirrel Cage Induction
motor
Lift Duty
S4
DESIGN MEMORENDUM
FOR
ELEVATOR
25.
26.
27.
j) Type of enclosures
Door Motor
a) Equipment driven by Motor
b) Direction of rotation
c) Type of enclosures
Metallic Wire Mesh between Car &
Counter Weight
Fire Man Switch
Automatic Rescue Device
Trailing cables
28.
Protection class
29.
23.
24.
DOC. NO.PE-DC-361-502-A001
REV. 00
DATE:10/12/10
Page 8 of 8
60%
IS:325
Elevator Motor shall be suitable for
minimum of 150 Starts per hour
Both Clockwise & Anticlockwise
F
AC
Variable
Voltage
Variable
Frequency
IP54
Door
(car and landing)
Bidirectional
IP54
Yes, by package supplier
Yes, by package supplier
Provided
FRLS type/as per manufacture standard
Protection class for main control panel
shall be IP 21, motor IP-54.
Windows air conditioner of 2T capacity
shall be provided by elevator supplier.