Sie sind auf Seite 1von 20

4/1/2014

Overcurrent Protective Device (OCPD) Basics


Dan Neeser
Field Application Engineer
Eatons Bussmann Business
Cell: 314-753-2514
email: dan.neeser@cooperindustries.com

2013 Eaton. All rights reserved.

Agenda

Overcurrent Considerations

Overcurrent Protective Basics

Overcurrents
Overloads
Short-circuits & ground faults
Component protection
Arc Flash

Basics Construction, Operation and Ratings (V, A, IR)


Time Current Curves
Let-through Curves

Overcurrent Protective Device Types

Circuit Breakers (MCCB, ICCB, LVPCB, AFCIs, GFCIs)


Fuses (Class L, H, R, J, T, CC)
High Speed Fuses
Supplemental Protectors

2013 Eaton. All rights reserved.

Overcurrent Protective Devices Protect From


Overcurrent (NEC Definition)
Any current in excess of the rated current of
equipment or the Ampacity of a conductor. It may
result from overload, short circuit, or ground fault.
FPN: A current in excess of rating may be accommodated by certain
equipment and conductors for a given set of conditions. Therefore, the rules for
overcurrent protection are specific for particular situations.

An Overcurrent Results From


Overload, Short Circuit, or Ground Faults
2013 Eaton. All rights reserved.

4/1/2014

Effects Of Overcurrents
Conductor insulation
damage
Fires
Equipment damage
Arc Flash Energy

2013 Eaton. All rights reserved.

Overcurrent Protective Devices Protect From


Overload. (NEC Definition)
Operation of equipment in excess of normal,
full-load rating, or of a conductor in excess of rated
ampacity that, when it persists for a sufficient length
of time, would cause damage or dangerous
overheating. A fault, such as a short circuit or ground
fault, is not an overload.

An Overload Is NOT A
Short Circuit, or Ground Faults
2013 Eaton. All rights reserved.

Overload - Example

VS

Source

Load

Load

IOL= VS / RT

Within the normal path

Voltage (V) = 480


Load Resistance (R) = 2 X 12 = 24 ohms
Wire Resistance (R) = 0.01 ohms

Iload = (480) / (0.01 + 24) = 20 Amps


2013 Eaton. All rights reserved.

4/1/2014

Overcurrent Protective Devices Protect From


Short Circuit Current.
Not Defined In NFPA, IEEE or other similar
organization documents
An overcurrent, typically many times larger than
normal operating current
Can be an arcing fault or bolted fault
Can be between phase(s) and/or phase(s) and
ground (ground fault)
A Short Circuit Is An Overcurrent But Not An Overload
2013 Eaton. All rights reserved.

Short-Circuit - Example
ISC= VS / RT

VS

Source

Load

R
R

Out of the circuit

Outside the normal path

Voltage (V) = 480


Load Resistance (R) = 12 ohms
Wire Resistance (R) = 0.01 ohms
Iload = (480) / (0.01) = 48,000 Amps

2013 Eaton. All rights reserved.

Typical Short-Circuit Currents


Home Receptacle - 200 to 500 amps
Home Service - 2,000 to 10,000 amps
Bussmann Headquarters - 70,000 amps
New York City - 202,000 amps
St. Louis, MO - 210,000
Chicago, IL - 215,000
Dallas, TX - 220,000
Tulsa, Oklahoma - 260,000 amps
2013 Eaton. All rights reserved.

4/1/2014

Short-Circuit Currents
Sources of short-Circuits
Utility
Generator
Motors

Decreases due to
impedance
Conductors, bus, etc.
Transformers (size &
impedance)

Must be calculated
2013 Eaton. All rights reserved.

10

Eaton Bussmann Short-Circuit Calculator


NEW version
Apple or Android Apps
Web (run from homepage
after entering contact info)

2013 Eaton. All rights reserved.

11

OCPD - Voltage & Ampere Rating


Voltage Rating
Circuit Breakers - 120, 120/240, 240, 277, 480,
480/277, 600V.
Fuses - Typically 250 or 600V (Class J & L 600V)

Ampere rating
80% (MCCB-UL 489 and standard fused switch-UL 98)
100% - if CB or fused switch is 100% rated in
enclosure
Few MCCB & Most ICCB - UL489
LVPCB - UL 1066
Bolted pressure switch - UL 977.
2013 Eaton. All rights reserved.

12

4/1/2014

OCPD - Interrupting Rating


NEC 110.9: Device interrupting rating MUST
be equal to or greater than the maximum
available fault current.
Chapter 1 Video Clips - Interrupting Rating

2013 Eaton. All rights reserved.

13

OCPD Interrupting Rating


Circuit Breakers
Interrupting rating varies - 10, 14, 18, 22, 25, 30,
35, 42, 50, 65, 100, 125, 200 kA. Dependent
upon voltage and manufacturer.
No rejection feature for proper application of
voltage or interrupting rating

Fuses
Minimum interrupting rating of 200,000A (except
for Class H & K - 10,000A) at rated voltage.
Interrupting rating does not vary with voltage.
Many at 300kA.
Unique dimensions or rejection features to prevent
interchangeability
2013 Eaton. All rights reserved.

14

OCPD - Current Limitation


A current limiting
fuse will clear a
fault within one half
of a cycle.
Thermal energy is
proportionate to the
square of RMS current
multiplied by the time
(Irms2t)
Mechanical stresses are
proportionate to the
square of peak current
multiplied by the time
(Ip2t)
2013 Eaton. All rights reserved.

15

4/1/2014

OCPD - Current Limitation


Conductor protection for fault of 45kA/480V (26kA
with conductor) with non-current-limiting device (1
cycle) vs. current-limiting device (>1/2 cycle)

2013 Eaton. All rights reserved.

16

Equipment Protection
NEC 110.10: Equipment short-circuit current ratings must be
adequate for maximum available fault current.
Must Assure Protection

Conductors/Busway
Panelboards/Switchboards
Motor Controllers/MCCs
Switches/Transfer Switches
Industrial Control Panels
HVAC Equipment
Etc.

Current-limiting overcurrent devices can provide increased


short-circuit protection of components and high short-circuit
current ratings for equipment.
2013 Eaton. All rights reserved.

17

17

18

18

Arc Flash Energy People Protection


Arc flash Energy Is Dependent On:
Distance from arcing fault
Arcing fault duration or time to clear
Speed of the overcurrent protective device

Arcing fault current magnitude


Available fault current
Current-limitation can reduce

2013 Eaton. All rights reserved.

4/1/2014

Arc Flash Testing - Test 4


480V, 22.6kA Short-Circuit Current
640A NCL OCPD: 6 cycle Clearing Time

2013 Eaton. All rights reserved.

19

19

Arc Flash Testing - Test 3


480V, 22.6kA Short-Circuit Current
601A CL Fuse: Less Than 1/2 Cycle Clearing Time

2013 Eaton. All rights reserved.

20

20

Circuit Breaker Components


Major Components
Molded Case Frame
Operating Mechanism
Contacts
Arc Extinguishers
Trip Units

Tripping Conditions
Overload
Short-Circuit
Ground Fault
Arcing Fault
2013 Eaton. All rights reserved.

21

4/1/2014

Circuit Breaker Components

2013 Eaton. All rights reserved.

22

Circuit Breaker Components


Contact Assemblies

2013 Eaton. All rights reserved.

23

Circuit Breaker Components


Arc Extinguisher
Contacts Separate
Magnetic Field Drives Arc Into
Steel Plates
Arc Is
Confined
Divided
Extinguished

2013 Eaton. All rights reserved.

24

4/1/2014

Thermal Protection
Bimetal In Series With Connected Cable
Bimetallic Element Is Heated By The Load Current
Sustained Overload Will Cause Bimetal To Deflect
Deflection Trips The Breaker

2013 Eaton. All rights reserved.

25

Magnetic Protection
Electromagnet Winding Is In Series With Load Current

Magnetic
Field
Coil
N

2013 Eaton. All rights reserved.

26

Thermal Magnetic
Time Current Characteristic Curve

2013 Eaton. All rights reserved.

27

4/1/2014

Different Types And Sizes


Molded Case Circuit Breaker (MCCB)
A circuit breaker that is assembled as an integral unit in a supporting and
enclosing housing of insulating material.

Insulated Case Circuit Breaker (ICCB)


A circuit breaker that is assembled as an integral unit in a supporting and enclosing housing
of insulating material and with a stored energy mechanism.

Low Voltage Power Circuit Breaker (LVPCB)


A mechanical switching device, capable of making, carrying, and breaking currents under
normal circuit conditions and making and carrying for a specified time and breaking currents
under specified abnormal circuit conditions such as those of short circuit. Rated 1000 V ac or
below, or 300 V dc and below, but not including molded-case circuit breakers.

2013 Eaton. All rights reserved.

28

Molded Case Circuit Breakers

Miniature G Frame

E Frame

F Frame

J Frame

K Frame

L Frame

M Frame

N Frame

R Frame

15 100A 15 100A

15 125A

10 225A

70 250A

70 400A

70 600A

300 800A

320 1200A

800 2500A

Continuous Ampere Ratings from 15A to 2500A Frame


Interrupting Capabilities of 22KA to 100KA
Found In enclosures, panelboards, switchboards, MCCs and Control
Panels
Industrial AND Residential Applications

2013 Eaton. All rights reserved.

29

Insulated Case Circuit Breakers


Typically 800A 6000A
Frame Range
Interrupting Duty 35
150kA
Found In Enclosures,
Switchboards and
Switchgear

2013 Eaton. All rights reserved.

30

10

4/1/2014

Low Voltage Power Circuit Breakers

Interrupting Duty from 42kA to 100kA and


Current-Limiting Up To 200kA
800A to 6000A Frame
Found in Enclosures, Switchboards, and Switchgear
Draw-out & maintenance capabilities
2013 Eaton. All rights reserved.

31

Electronic Trip Units

Trip Unit
Circuit Board

Flux
Transfer
Shunt Trip
Current Transformer

2013 Eaton. All rights reserved.

32

Time-Current Characteristic

Long Time
Delay

100

Time In Seconds

Depicts the time required for an


overcurrent protective device to open
automatically

Long Time
Pickup

1000

Three Regions

Short Time
Pickup

10

Long-time: Opening in minutes

Short Time Delay


(I2t)

1.0

Short-time: Opening in seconds or


tenths of seconds.

0.1
Instantaneous Pickup

0.01
0.5

10

Instantaneous: Opening with no


intentional delay - milliseconds

100

Multiples of Rated Current

2013 Eaton. All rights reserved.

33

11

4/1/2014

Communications
Remote Data Collection
Energy / Voltage / Current
Cause Of Trip And Other Alarm Information
Control
HTTP
WEB
URL
Internet

2013 Eaton. All rights reserved.

34

Zone Selective Interlocking


Communication Between Breakers
Reduces Trip Time When Possible

Isc

Helps With Arc Flash Energy Reduction

Case 1:
Both Breakers See Fault
Upstream Breaker Waits As Designed
Case 2:
Only Upstream Breaker Sees Fault
No Input From Downstream
Breaker
Trip As Fast As Possible
2013 Eaton. All rights reserved.

35

Arc Flash Reduction Switch


ALWAYS WORK
DE-ENERGIZED
Manually or Automatically
enables analog
instantaneous pickup
Protects all downstream
equipment / personnel
Limits energy available
during maintenance
2013 Eaton. All rights reserved.

36

12

4/1/2014

Arc Flash Reduction Switch


Clearing times are much
faster than ZSI
Clearing times are faster
than standard INST

Ref: Incident energy calculated using IEEE STD 1584TM-2002 method for a 480 Vac system, working distance of 24 inches,
2013 Eaton. All rights reserved.
37
Grounding type = solid grounded
and Equipment type = Switchgear.

Arc Detection / Fire Prevention

Technology Has Progressed To Enable Enhancement


Of The Residential MCCB
Residential And Commercial Applications
2013 Eaton. All rights reserved.

38

Arc Detection / Fire Prevention


Push To Trip Test Button
Arc Fault Sensing Circuitry
Operating Handle

Load Terminal

Latch Piece

Panel Neutral Wire


Mechanism Spring

Moving Contact Member

Load Neutral Terminal

Electromagnet

Instantaneous Trip Element


( Armature )
Stationary Contact Member
Long Delay Trip Element
( Bimetal )

2013 Eaton. All rights reserved.

39

13

4/1/2014

Dual Element Time Delay Fuses


Dual Element Time-Delay
MODERN CL FUSES
Designed to be sized close to load and accommodate
motor and transformer inrush which could not be
accomplished by single-element non-time-delay or fastacting fuses.
Overload (time delay) Element
Short Circuit (current limitation) Element

Shortcircuit element

Overload Element

2013 Eaton. All rights reserved.

40

Dual Element Time Delay Fuse - Overload


Before

Dual Element Time-Delay


Under sustained overload condition,
spring operated trigger assembly
separates the connector from the
short-circuit element, opening the
circuit.

After
2013 Eaton. All rights reserved.

41

Dual Element Time Delay Fuses Short Circuit

Dual Element Time-Delay


Under a short-circuit
condition, restricted
portions of the short-circuit
element melt (vaporize)
and arc to burn back the
resulting gaps until the
arcs are suppressed by
the arc quenching material
and increased arc
resistance.
2013 Eaton. All rights reserved.

42

14

4/1/2014

Fuse Classes

High Speed Fuses


Permitted to provide short-circuit, ground-fault
protection for motor branch circuits utilizing
power electronic drives
2013 Eaton. All rights reserved.

43

Fuse Class Dimensions

2013 Eaton. All rights reserved.

44

44

Time Current Characteristic (TCC) Curves


The Trip Curve

Average
1000

A Trip Curve Is Plotted Time Vs.


Current

The Curve Tells The Trip Times


For Various Levels Of Current

Minimum melt, average melt


total clear

Fast acting fuses faster in


overload region than time-delay
fuses. Similar in short-circuit
region.

Melt

100

Time (Seconds)

Total
Clear

10
A Fuse Opens

Overload

At Some Time
1.0

Between These Bands


Minimum

0.1

Melt

Current Limiting
Threshold

Short Circuit

0.01
20

200

Current (Amps)

Understanding How An Overcurrent Protective Device


Operates Is Important
2013 Eaton. All rights reserved.

1000

0.5

45

15

4/1/2014

Fuse Class Current Limitation


All manufacturers must comply with maximum letthrough values (Peak/I2t) for each fuse class
(at fault currents of 50, 100, 200, 300kA)

2013 Eaton. All rights reserved.

46

Current Limiting Effect Charts


Manufacturer (fuse or circuit breaker)
published data provides actual Ip and Irms letthrough

2013 Eaton. All rights reserved.

47

Class L
Large
Class L Low-Peak
KRP-C-(AMP)SP
600V, 601A 6000A, 300kA

Characteristics
Time Delay
Current limiting

Applications
Mains and feeders in electrical distribution
equipment
Large motors
2013 Eaton. All rights reserved.

48

16

4/1/2014

Class T
Tiny

Fast-acting
300V AC or 600V AC
Up to 1200A
Amperage case sizes include:

200kA Interrupting rating


Current limiting
Rejection feature class or size rejecting
Best space saving design of any power
fuse

30, 60, 100, 200, 400, 600, 800, 1200

Applications:
Heating and lighting circuits
Single phase lighting circuits (277V)
Residential and multi-metering

2013 Eaton. All rights reserved.

49

Class H
Hazardous
Class H One-Time
NON-(AMP)/NOS-(AMP)
250V/600V, 1/8A-600A
60A or Less 50kA, above 60A - 10kA

Characteristics
Non-Time Delay
Non-current-limiting & non-rejecting
Recommend REPLACE with RK5/RK1

Applications
General purpose
HVAC, light commercial

2013 Eaton. All rights reserved.

50

Class RK5
Rejection
Class RK5 Fusetron
FRN-R-(AMP) / FRS-R-(AMP)
250V/600V, 1/10A 600A, 200kA

Characteristics
Dual Element Time Delay
Good current limitation
Optional Open Fuse Indication

Applications
Feeders and branch circuits in electrical
distribution and OEM equipment
Time delay good for across the line start motor
applications and transformer primaries

2013 Eaton. All rights reserved.

51

17

4/1/2014

Class RK1
Rejection
Class RK1 Low-Peak
LPN-RK-(AMP)SP/LPS-RK-(AMP)SP
250V/600V, 1/10A 600A, 300kA

Characteristics
Dual Element Time Delay
Better current limitation
(better Type2 and Arc Flash protection)
Less time delay than RK5
Optional open fuse indication

Applications
Feeders and branch circuits
Primarily Building Systems
Electrical Safety Upgrade
2013 Eaton. All rights reserved.

52

Class J
Junior
Class J Low-Peak
LPJ-(AMP)SP
600V, 1A 600A, 300kA

Characteristics
Dual Element Time Delay
Better time delay than CC
Less time delay than RK1/RK5

Very current limiting


Smaller than RK1/RK5
Open fuse indication Optional

Applications
Feeder and branch circuits
OEM & Building Systems
Type 2 Protection

2013 Eaton. All rights reserved.

53

Class J
Junior
Class J DFJ High Speed Fuse
DFJ-(AMP)
600V, 1A 600A, 200kA
450Vdc, 100kA

Characteristics
High speed performance: extremely current limiting
(similar to high speed fuses)

Applications
Drive branch circuits
Heater circuits with solid state relays (SSRs)
Protect power electronics and provide branch circuit
protection
Fit HSF performance into standard, off the shelf,
switches, holders and blocks
2013 Eaton. All rights reserved.

54

18

4/1/2014

Class CF

CUBE FUSE

Class CF - TCF(amp), TCF(amp)RN or FCF(amp)RN

TCF - 600Vac/300Vdc, 1-100A, 300kA/100kA


FCF - 600Vac/dc, 1-100A 200kA/50kA

Characteristics

DE Time Delay or Fast Acting


Class J Performance
Very Current Limiting
Small physical Size
Finger safe IP20
Optional Indicating version time-delay only

Applications

General purpose; e.g. motor circuits (Type 2 Protection,


transformers, heaters, feeders and branch circuit protection
WCF_RN CUBEFuse for 690Vac wind turbine systems
(UL 248 Recognized) .

2013 Eaton. All rights reserved.

55

Class CC
Control Circuit or Charlie Chaplin (little hat)
Class CC - General Features

600V, up to 30A
200kA Interrupting rating
Very Current Limiting
Space Saving Design - 13/32 X 1

Grooved ferrule provides rejection feature from


supplementary fuses with same dimensions
(midget fuses) when Class CC fuseholders are
used
Offer 3 different fuse types
Time delay (for motor circuit: LP-CC)
Time delay (for control transformer primary: FNQ-R)
Non-time delay (Non-inductive loads: KTK-R)
2013 Eaton. All rights reserved.

56

Class G Fuses
Growing

Time-delay
600V AC, up to 20A
480V AC, 25-60A
Amperage case sizes include:

100kA Interrupting rating


Current limiting
Rejecting feature
Length of fuse varies with the amperage
Applications:

15, 20, 30, 60

Small Motors
Small Transformers
General applications with inrush current

2013 Eaton. All rights reserved.

57

19

4/1/2014

Edison-Base Fuses and Fuseholders


NEC 240.51(B) permits the use of plug fuses
of the Edison-base type to be used only for
replacements in existing installations where
there is no evidence of overfusing
NEC 240.53(A) Classifies Type S fuses as:
Not over 125V
0-15A, 16-20A, and 21-30A

NEC 240.53(B)
Type S fuses cannot be interchangeable with a
lower ampere classification
Type S fuses are required to be designed for use in
only a Type S fuseholder or an Edison-based
fuseholder with a Type S adapter inserted.
2013 Eaton. All rights reserved.

58

Circuit Breaker versus Fuse


Circuit Breakers

Fuses

Size & Flexibility (IR)


Resettability (OL)
Shunt/Common Trip
Integral Ground Fault
Protection (multi-level)
Adjustable Trip Settings
Advanced Protection &
Monitoring Features
Arc Flash (above 800A and
lower fault currents)
Switching Operations and
Drawout Capability for
Maintenance

Reliability limited
maintenance
Ease of application (V&IR),
rejection features
Current-limitation
Component Protection (motor
circuits, high SCCR and
protection of solid-state
equipment)
Arc Flash Protection (typically
800A and less and higher fault
currents)
Ease of Selective Coordination
(use of fuse ampacity ratios)

2013 Eaton. All rights reserved.

59

Questions And Comments


Thank You

2013 Eaton. All rights reserved.

20

Das könnte Ihnen auch gefallen