Power Transmission and Distribution

Differential Protection 7UT6


Presentation

The 7UT6 Family

SIPROTEC 4
7UT6 differential protection relay for transformers,
generators, motors and busbars

7UT612:
7UT613:
7UT633:
7UT635:

for two end protection objects


for three end protection objects
for three end protection objects
for five end protection objects

(1/3 x 19 housing 7XP20)


(1/2 x 19 housing 7XP20)
(1/1 x 19 housing 7XP20)
(1/1 x 19 housing 7XP20)
PTD PA 7UT6 Present 11/04 No. 2

Hardware options

Device

7UT612

7UT613

7UT633

7UT635

Current Inputs (normal)


Current Inputs (sensitive)
Voltage Inputs (Uph / UE)
Binary Inputs
Binary Outputs
Life contact
LC Display

7 (7)*
1
--3
4
1
4 lines

11 (6)*
1**
3/1
5
8
1
4 lines

11 (6)*
1**
3/1
21
24
1
Graphic

14 (12)*
2**
--29
24
1
Graphic

1A, 5A, (1A, 5A, 0.1A) changeable (jumper position)

** changeable normal or sensitive (jumper position)

PTD PA 7UT6 Present 11/04 No. 3

Scope of functions and Protection objects


Function

ANSI No.

Protection Objects

Differential

87T/G/M/L

Three-phase transformer

Restricted Earth fault

87 N

Single-phase transformer

Overcurrent-time, phases

50/51

Auto-transformer

Overcurrent-time, 3I0

50N/51N

Generator / Motor

Overcurrent-time, earth

50G/51G

Busbar, 3-phase (Branch point)

Overcurrent-time, single phase

Busbar, 1-phase

Negative sequence

46

Overload IEC 60255-8

49

Overload IEC 60354 (hot spot)

49

Overexcitation V/Hz

24

Breaker failure

50BF

External temperature monitoring

38

Lockout

86

Measured value supervision


Trip circuit supervision

74TC

Direct coupling
Operational measured values

PTD PA 7UT6 Present 11/04 No. 4

Cross reference - functions and protected objects


Protection functions

ANSI No.

Transf.
3-phase

Transf.
1-phase

Autotransf.

Gen. /
Motor

Busbar
3-phase

Busbar
1-phase

Differential

87T/G/M/L

Restricted Earth Fault

87 N

---

---

---

Overcurrent-time, phases

50/51

---

Overcurrent-time, 3I0

50N/51N

---

---

Overcurrent-time, earth

50G/51G

Overcurrent-time, single phase


Negative sequence

46

---

---

Overload IEC 60255-8

49

---

Overload IEC 60354

49

---

24

Breaker failure

50 BF

---

External temperature monitoring


(thermo-box)

38

Lockout

86

Direct coupling 1

Direct coupling 2

Operational measured values

Overexcitation V/Hz

*)

Measured value supervision


Trip circuit supervision

X Function applicable ;

74TC

--- Function not applicable ;

*) only 7UT613 / 633

PTD PA 7UT6 Present 11/04 No. 5

Communication features
Flexibility due to plug in modules
Compatibility to international standards

RS232/RS485 electrical module

Front interface

System interface

DIGSI4

IEC60870-5-103

WEB Monitor

Profibus FMS
Profibus DP

Service interface (s)


DIGSI4 operation
Fibre-optic module

modem connection
RTD box

DNP3.0
Modbus ASCII/RTU

Time synchronising
IRIG-B (GPS)
DCF77

Optical double-ring module

PTD PA 7UT6 Present 11/04 No. 6

Connection Example
M3
L1
side 3

L2
L3

L1

M2

side 2

side 1

M1
L1

L2

L2

L3

L3

direct connection to the


main Cts
no matching transformers /
no matching connections
numerical vector group
adaptation without zero
sequence current correction
depending of the type of
earthing of the winding.
increased sensitivity by 33%
by measuring of the zero
sequence current (7UT6) for
single-pole faults.

I L1M2

I X1

I L1M1

I L2M2

I L2M1

I L3M2

I L3M1

1A/5A main Cts adaptation


in the relay
permissible ratio Ct nominal
current to transformer nominal
current up to 1 : 4

I L1M3

Surface
mounting
housing
Flush/
cubiclemounting
housing

I X3

I L2M3
I L3M3

7UT613
PTD PA 7UT6 Present 11/04 No. 7

Commissioning and operating aids

(1 of 4)

WEB-Technology
Access to the relay with a WEB Monitor
Help system in
INTRANET / INTERNET
http://www.siprotec.com

1. Serial connection
Direct or via modem with a
standard DIAL-UP Network

The homepage of the relay


is:http://141.141.255.160
IP-address is set with DIGSI 4
on front- or rear service port

WEB server in the relays


firmware
Server sends its HTML-pages
and JAVA-code to the WEB Monitor
after a DIAL-UP connection

2. HTML page view in a WEB Monitor


with the IP-address of the relay
http://141.141.255.160
PTD PA 7UT6 Present 11/04 No. 8

Commissioning and operating aids

(2 of 4)

Transformer YNd11d11, 110/11/11kV, 38.1MVA, IL2S2? wrong polarity


PTD PA 7UT6 Present 11/04 No. 9

Commissioning and operating aids

(3 of 4)

Transformer YNd11d11, 110/11/11kV, 38.1MVA, IL2S2? wrong polarity


PTD PA 7UT6 Present 11/04 No. 10

Commissioning and operating aids

(4 of 4)

PTD PA 7UT6 Present 11/04 No. 11

Benefits for the Customer


Protection relay with flexible adaptation to the transformer/generator/motor
or short line. Programming of the device data in the relay.
Reduced amount of wiring by direct connection to the main Cts.
No matching transformers and therefore no wiring errors.
Zero sequence current can be measured (in the 7UT6).
Sensitivity for single-pole faults in the transformer increased by 33% .
Flexible adaptation of the tripping characteristic to various main Cts,
tapped transformers.
Exact discrimination between the short circuit condition and the inrush
condition by on-line analysis of the harmonics. Fast tripping for
high-current faults. Ct saturation detector for external faults.
Thermal monitoring of one transformer winding (including RTD meas.)
Back-up DMTL/IDMTL with reverse blocking for one winding.
Sensitive short circuit protection for faults winding against earth.
External Trip functions
Various commissioning aids.
Common DIGSI 4 software
PTD PA 7UT6 Present 11/04 No. 12

Comparison of functions/settings
between 7UT51- and 7UT6 relays
7UT51

7UT612

7UT613

7UT633

7UT635

Tripping Characteristic: Base point for slope 1 settable

---

Tripping Characteristic: Increasing of characteristic at start

---

Tripping Characteristic: minimum setting for add-on stabilization I/InO

Tripping Characteristic: cross block for add-on stabilization

---

---

Tripping Characteristic: slope of add-on stabilization / slope 1

Tripping Characteristic: Increasing of characteristic due to DC offset in IDiff

---

---

Transformer inrush: Default setting for cross block 2. harmonic [cycles]

Transformer inrush: Default setting for 5. harmonic [%]

80

30

30

30

30

Negative sequence current protection

---

Over excitation protection [V/Hz]

---

---

---

Overload protection IEC 60354 (hot spot)

---

Single phase busbar differential

---

High impedance Restricted Earth Fault

---

Voltage measurements

---

---

---

Temperature monitoring (via Thermo-box / RS 485)

---

All functions can be enabled at the same time

---

WEB monitor (commissioning aid)

---

PTD PA 7UT6 Present 11/04 No. 13