Beruflich Dokumente
Kultur Dokumente
Office Tower
Project definition........................................................................................................................................... 3
General definition ..................................................................................................................................... 3
Definition of supplied circuit ................................ ................................ ................................ ....................... 4
General installation design ............................................................................................................................ 6
Power supply ........................................................................................................................................... 6
Main distribution general diagram : 1 Subst- N TransfoNO- N Rising............................................................ 6
Circuit distribution ..................................................................................................................................... 8
Technical specification for material and installation conditions ....................................................................... 10
MV equipment ........................................................................................................................................ 10
Main switchboards and main LV distribution equipment ................................ ................................ ............. 13
LV switchboard and distribution equipment............................................................................................... 15
Technical appendix N1: circuit distribution principle ................................ ................................ ..................... 22
Centralized Layout.................................................................................................................................. 22
Distributed Layout .................................................................................................................................. 22
Technical appendix N2: circuit configuration................................................................................................ 23
Radial Configuration ............................................................................................................................... 23
Technical appendix N3: Backup generator.................................................................................................. 24
LV Back-up Generator ............................................................................................................................ 24
Technical appendix N4: Uninterruptible Power Supply ................................................................................. 26
UPS....................................................................................................................................................... 26
Technical specification for UPS : ................................ ................................ ................................ ............. 27
Detailed Technical specification for MV switchboard ................................ ................................ ..................... 28
Detailed Technical specification for MV/LV transformer................................................................................. 37
Detailed Technical specification for LV switchboard ...................................................................................... 44
Detailed Technical specification for Busbar trunking system .......................................................................... 54
Project definition
General definition
Activity
This project is in the domain of High-end office
Definition:
Building mainly dedicated to for office usage which can integrate some other synergetic activities, such as: fitness centre, cafe/restaurant,
shops.
Description:
Buildings are generally located in high tech tertiary activity park with:
surface from 4000 to 20000 m - surfaces are normally arranged in partitioned areas
According to the need the installed power may vary from 400kVA minimum to 1500kVA.
The needs are:
- Maximize letting space
- Secure construction cost and delay
- Secure building capability to be let:
Proof customers that embedded technology and products are good quality, durable and available
The solutions for electrical distribution are due to the f lexibility need mainly distributed downstream the Main Low Voltage Switchboard:
One or two distributed LV switchboards per floor, for power socket, lighting and HVAC
Busbar trunking systems, downstream the LV switchboards, to meet flexibility for power sockets and lighting circuits
Site Topology
This project is intended for a Single Several Floors Building
The building floor number is more than 10
Power Demand
The Power Demand of the project is more than 2500 kVA
Circuit: Lift
Installation flexibility: No
Load Distribution: Localised
Power interruption sensitivity: No Interruption Acceptable
Disturbance sensitivity: Medium
Environment, atmosphere: Standard
Maintainability: Standard
Circuit: IT server
Installation flexibility: No
Load Distribution: Localised
Power interruption sensitivity: No Interruption Acceptable
Disturbance sensitivity: High
Environment, atmosphere: Standard
Maintainability: Standard
10
10 000
10 000
5 000
2 500
0
0
Inst. power field (kVA)
Project floor N
High
Medium
Basic
Reliability
Technicity
Installed power
The installed power is usually greater than 1250 kVA. But this solution can be used for smaller installed power in case of:
redundancy requirements,
accessibility constraints to the substation (its sometime worthwhile having 2 small transformers instead of a big one).
In practice, this solution will be limited to 5 transformers (3 for typical applications), so the installed power can reach about 10 MVA, and
typically will be from 4 to 10 MVA.
Project size
For implementation reason, from 2500 kVA, this solution is limited to a few floors (10 maxi).
Interruption sensitivity
This solution contains more than one transformer. Consequently, it is possible to use back-up operation modes preventing installation shut
down in case of transformer failure.
In nominal operation mode, each transformer feeds its own main LV switchboard.
In back-up operation mode, in order to limit the short-circuit withstand of downstream equipment:
each transformer should be sized in order to be able to feed its own downstream installation, and part (with load shedding) or all the
downstream installation its neighbor.
As this solution contains at least one rising main per main LV switchboard, in case of rising main failure only one part of the building is
affected.
Disturbance sensitivity
As in this solution, the transformers of the substation are never connected together, they can feed loads with medium sensitivity to
disturbance:
by separating properly sensitive loads and non linear ones on different transformers.
If addition of this last point, UPS or active f iltering could be implemented to feed high sensitive loads.
Flexibility
Installation flexibility can be managed by taking into account extra power to size the transformers and by including spare capacity in the main
LV switchboards with appropriate service rating.
Rising distribution has low flexibility due to centralized connection of floor distribution panels to main LV switchboard.
Implementation recommendations
The main objectives for MV/LV substation localization is to:
limit the impact on the building architecture (size and place of the technical room),
in an underground floor.
The utility connection can be either single line or ring main or parallel.
Concerning substation:
it can be realized with prefabricated substation which allows, installation time reduction and reliability improvement (but limited to 2
transformers).
As far as possible the transformer power is lower or equal to 1250 kVA. They are all localized in the same substation.
As they are never connected together, they are not necessarily similar.
Despite the utilization of many transformers, all LV equipment require no short circuit withstand over sizing, because transformers are never
connected together.
The main LV switchboard feeds directly the main loads of the installation (generally up to 100 kW), in particular when they are close from its.
Floor distribution circuits are connected by N busbars trunking system rising in order to limit the size and height of the rising BTS and/or in
order to manage redundancy for floor distribution. Common circuits, like lifts, stairs lighting, etc. are generally fed by separate circuits.
The changeover between normal and back-up operation mode can be implemented with prefabricated changeover systems.
When limited to 2 transformers, the 2 main LV switchboards can be implemented in the same enclosure.
Typical applications
Office tower building.
Shopping centers, malls.
Collectif housing building. /Hospital.
Circuit distribution
Circuit: Office lighting
Distribution principle: Distributed
Circuit configuration: Radial
Genset: LV Generator
UPS: No UPS
Circuit: Lift
Distribution principle: Centralized
Circuit configuration: Radial
Genset: No Generator
UPS: UPS
Circuit: IT server
Distribution principle: Centralized
Circuit configuration: Radial
Genset: No Generator
UPS: UPS
switch-disconnector
Disconnector
For this project, MV substation configuration is as follows :
7.2
12
17.5
24
20
23
60
70
28
32
75*
85
38
45
95
110
50
60
125
145
16
31.5
25
630 1250A
20
630 1250 A
16
630 1250 A
12.5
430 630 1250 A
The making capacity is equal to 2.5 times the short-time withstand current
*60 kV peak for the CRM unit
General Characteristics
Maximum breaking capacity
Rated voltage (kV)
Units
IM, IMC, IMB
NSM-cables, NSM-busbars
PM, QM, QMC, QMB
CRM
CRM with fuses
SF6 circuit breaker range :
DM1-A, DM1 -D, DM1-W, DM1-Z,
DM1-S, DM2
Vacuum circuit breaker range :
DMV-A, DMV -D, DMV -S
* in 800 A consult us
7.2
12
17.5
630A 800A*
25kA
10kA
25kA
20kA
8 kA
25kA
20kA
25kA
20kA
24
Trihal is a three phase dry type transformer, cast under vacuum in epoxy resin with an active filler for indoor installation.
Thanks to the absence of any dielectric liquid and the excellent fire behaviour, it provides an easy and fast installation.
The Trihal cast resin transformer can be protected from any damaging temperature rises by monitoring winding temperature.
Characteristics :
Rated power :
160 kVA to 2500 kVA
Insulation level :
7.2 to 36 kV
Maximum ambient temperature :
40C
Rated frequency :
50Hz
Degree of protection :
IP00 or IP31 with protection cabinet
Losses :
Normal or reduced
Connection components for Canalis Busbar trunking
The Prisma Plus System P can be used for all types of low -voltage distribution switchboards (main, subdistribution and final) up to
3200A in commercial and industrial environnments.The switchboard is made up of frameworks that can be combined widthwise or
dephtwise, a distribution system with horizontal and vertical busbars and a complete functional units designed for the devices.
Characteristics
Rated current In
Withstand current Icw
Degree of protection
Degree of protection against mechanical impact
Service ratings
Cubicles
up to 3200 A
85 kA
IP 30-IP31-IP55
IK07-IK08-IK10
from 211 to 332
Icw
IP
IK
Nbr mod .
Height
Width
Depth
Associability
85KA
rms/1s
30/31/55
07
08
10
36
2 000 mm
300 mm
400 mm
650 mm
800 mm
400 mm
600 mm
Width and
depth
KS
General characteristics
Compliance with standards
100
160
250
400
500
630
800
1000
IEC/EN 60439-2
Degree of protection
Mechanical impacts
IP
IK
55
08
55
08
55
08
55
08
55
08
55
08
55
08
55
08
Inc
100
160
250
400
500
630
800
1000
Ui
690
690
690
690
690
690
690
690
Ue
690
690
690
690
690
690
690
690
Uimp
kV
Rated frequency
Hz
50 /60
50 /60
50 /60
50 /60
50 /60
50 /60
50 /60
50 /60
100
160
250
400
500
630
800
1000
IP
55
55
55
55
55
55
55
55
Mechanical impacts
IK
08
08
08
08
08
08
08
08
Ui
Ue
V
V
Uimp
f
kV
Hz
6.8
50 /60
6.8
50 /60
6.8
50 /60
6.8
50 /60
6.8
50 /60
6.8
50 /60
6.8
50 /60
6.8
50 /60
IS : 111
IP : IP > 20
IK : IK = 07
Equipment : Prisma Plus G
Circuit: Lift
Distribution principle: Centralized
Circuit configuration: Radial
Genset: No Generator
UPS: UPS
Withdrawability : FFF
Form : 1
IS : 211
IP : IP > 20
IK : IK = 07
Equipment : Prisma Plus P
IS : 111
IP : IP > 20
IK : IK = 07
Equipment : Prisma Plus P
Circuit: IT server
Distribution principle: Centralized
Circuit configuration: Radial
Genset: No Generator
UPS: UPS
Withdrawability : FFF
Form : 1
IS : 211
IP : IP > 20
IK : IK = 07
Equipment : Prisma Plus P
Prisma Plus System G includes a wide range of solutions, from the most simple to the most sophisticated, for switchboards in small to midsized commercial, industrial and residential applications up to 630A.
Main characteristics :
Pack wall-mount enclosures
Rated current In
160 A
Withstand current Icw : 10 kA
Degree of protection
IP30
Degree of protection against
mechanical impact
IK07-IK08
A
Pack
160A
Wallmounted
enclosures
A
Wall630A
mounted
enclosures
Floor
630A
standing
enclosures
Wall
630A
mounted
and
Floor
standing
enclosures
IP55
Icw
Ipk
IP
IK
10 kA
ms/1s
32kA
30
7/8
Icw
Ipk
IP
IK
25 kA
ms/1s
52.5kA
30/31/43
7/8
25kA
ms /
1s
28kA
ms :
1s
52.5kA
52.5kA
30/31/43
55
7/8
10
IP55 enclosures
Rated current In
up to 630 A
Withstand current Icw 25 kA
Degree of protection
IP55
Degree of protection against
mechanical impact
IK10
Nbr
Height
Width
Rows
2
5 heights from
555 mm
(48 mod of 9
3
480 mm to
mm or 24
1080 mm
4
modules of
5
18 mm)
6
Nbr
Height
Rows
6
8 heights from
9
330 mm
12
to 1390 mm
15
18
21
24
27
27
30
33
7
11
15
19
23
27
33
3 heights from
1560 mm
to 1830 mm
(including
plinth)
7 heights from
450 mm
to 17500 mm
Depth
Associability
157 mm
(without
door)
196 mm
(with
door)
Height with
Enclosure
extension
Width
Depth
Associability
595 mm
(enclosure)
205 mm
(without
door)
Width and
height
305 mm
(cable duct)
250 mm
(with
door)
595 mm
(basic
enclosure)
205 mm
305 mm
(cable duct)
250 mm
(with
floor)
600 mm
(basic
enclosure)
230 mm
325 mm
or 595 mm
(extensions)
290 mm
(including
30mm
handle)
Width and
height (with
wm. enclosure
above)
Width
Height
square
L shaped
The Prisma Plus System P can be used for all types of low -voltage distribution switchboards (main, subdistribution and final) up to
3200A in commercial and industrial environnments.The switchboard is made up of frameworks that can be combined widthwise or
dephtwise, a distribution system with horizontal and vertical busbars and a complete functional units designed for the devices.
Characteristics
Rated current In
Withstand current Icw
Degree of protection
Degree of protection against mechanical impact
Service ratings
Cubicles
up to 3200 A
85 kA
IP 30-IP31-IP55
IK07-IK08-IK10
from 211 to 332
Icw
IP
IK
Nbr mod .
Height
Width
Depth
Associability
85KA
rms/1s
30/31/55
07
08
10
36
2 000 mm
300 mm
400 mm
650 mm
800 mm
400 mm
600 mm
Width and
depth
KDP
20 A
690V
IP55
1L+N+PE, 3L+N+PE
1.5m - 3m
10 and 16A for power distribution and lighting control
0.33 m
KDP
20
IEC/EN 60439-2
Degree of protection
IP
Mechanical impact
IK
55
Inc
20
Ui
690
Ue
Uimp
V
kV
230 400
4
Rated frequency
Hz
50/60
07
KBC 10
KBC 10
KBC 16CB
KBC 16CF
Lighting
control
General characteristics
Compliance with standards
IEC/EN 60 439-2
Degree of protection
IP
55
55
55
55
Inc
10
10
16
16
Ui
690
400
690
400
Ue
kV
230 400
230 .. 400
230 ..400
230 ..400
Rated frequency
Hz
50/60
50/60
50/60
50/60
IP
Inc
16
16
16
16
Ui
250
250
250
250
Ue
250
250
250
250
Rated frequency
Hz
50
50
50
50
KNA
KN
40
63
100
160
IEC/EN 60 439-2
Degree of protection
IP
55
55
55
55
Mechanical impacts
IK
08
08
08
08
Inc
40
63
100
160
Ui
500
500
500
500
Ue
Ump
V
kV
500
6
500
6
500
6
500
6
Rated frequency
Hz
50 /60
50 /60
50 /60
50 /60
KN
40
63
100
160
55
08
55
08
55
08
55
08
Degree of protection
Mechanical impacts
IP
IK
Ui
Ue
V
V
Ump
f
kV
Hz
4.6
50 /60
4.6
50 /60
4.6
50 /60
4.6
50 /60
Localized
Intermediate
Uniform
No
Design
Centralized
Implementation
Operation
Distributed
Distributed Layout
Description
It consists in connecting consumers to sources via a busway. Busbar Trunking System (BTS) are well suited to
distributed distribution layout, to supply many loads that are spread out, making it easy to change, move or add
connections..
Recommendations
Distributed Layout is recommended when:
Installation flexibility is high (moving of workstation),
Load distribution is uniform: loads evenly distributed of low and homogenous unit power.
The use of BTS allows load power circuits to be combined and saves on conductors by taking advantage of a
clustering coefficient. The choice between cable and BTS, according to the clustering coefficient, allows us to
find an economical optimum between investment costs, implementation costs and operating costs.
Load distribution
Flexibility
Localized
Intermediate
Uniform
No
Design
Centralized
Implementation
Operation
Distributed
No
Sheddable
Yes
Radial
Long interruption
Short interruption
No interruption
Radial
Double
connection
Minimum
Standard
Sheddable
Long interruption
Short interruption
Enhanced
No LV generator
LV
generator
LV generator
No interruption
No LV generator
The source-changeover can be automated to take into account the status of thenormal and back up sources before switching.
The automatic source-changeover system requires no human intervention and switching form the normal to the replacement source takes
place in less than 1 second.
This changeover system is made up of:
- 2 or 3 circuit breakers,
- 1 mechanical and electrical interlocking system,
- 1 controller.
The controller can be of type BA or UA:
BA controller, for a simple source-changeover system (automatic switching between the normal and replacement sources depending on
theirstatus).
UA controller, for a source-changeover system integrating the following automatic functions:
- automatic switching between sources,
- control and management of engine generating sets,
- load shedding for non-priority circuits,
- switching to the replacement source if one of the phases of the normal
source is absent.
A communication option based on the Schneider internal bus is available for the UA controller.
Range
Type of device
Mechanical interlocking
On mounting plate
By rods
By cable
Electrical interlocking
By diagram
With IVE unit
Source changeover controller
BA controller
UA controller
Remote communication via bus
Device status indications
Device remote control
Compact
NS100 to 250
NS100 to 250
NS100 to 250
Masterpact
NT 06 to 16
NW08 to 63
n
n
n
n
n
n
n
n
n
n
n
n
n
n
Only with UA or BA
n
Only with UA or BA
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
Low
Mediu m
High
Sheddable
Long interruption
Short interruption
No interruption
No UPS
UPS
Galaxy 6000 and Galaxy 5000 UPS are ideal for high power data centres and industrial applications.
Technical Characteristics
Normal AC supply input
Input voltage range
Input Mains 1 and Mains 2
Frequency
Input current total harmonic distorsion (THDI)
Input power factor
Bypass system input
Nominal input voltage
Frequency
Output
Output voltages
Voltage regulation
Frequency
Over load
Output voltage total harmonic distorsion
Max load crest factor
Variation of voltage with 100% load step
Batteries
Backup time
Type
Over all efficiency
Double conversion mode
Economy mode
Environmental conditions and noise
Storage temperature
Operating temperature
Noise level (dBA)
Operating altitude
Standards and approvals
Performance and safety
Performance and design
Design and manufacturing
EMC immunity
EMC emission
Approvals
Galaxy 6000
Galaxy 5000
up to 95%
NA
up to 94%
up to 97%
-25C to +45C
up to 40C for 8 hours, 35C continuously
Less or equal to 72
1000 m
-25C to +45C
up to 40C
1000 m
open-ended design,
easy to install,
safe and easy to operate,
compact design,
low maintenance.
The supplier must be able to prove its extensive possess experience in the field of MV switchgear, and has
already supplied equipment of the same type & production process, in which has been in operation for at least
three years.
2. Standards
The switchgear shall comply with the latest issues of the following IEC recommendations:
- IEC 62 271-200
-
IEC 60265
IEC 62271-102
IEC 60694
IEC 62271-105
IEC 62271-100
IEC 60282-1
IEC 60185
IEC 60186
IEC 60801
- IEC60529
4. System parameters
The insulation level of the switchgear shall comply with IEC recommendations and the values indicated in the
following table.
5.14 LV auxiliaries
Auxiliary equipment shall satisfy section 5.4 of IEC 60298 and section 5.4
of IEC 62 271-200 recommendations.
The LV cables shall be class 2 type with a 2000 V insulation level.
They shall be marked at each end for easy verification during maintenance or servicing work.
The cable cross-sections shall not be less than 2.5 sqmm for circuits carrying high currents, or 1 sqmm for other
circuits.
5.15 Control and monitoring
All the relays, instruments and meters shall be incorporated in the LV box located at the top of the cubicle.
The relays shall be of the integrated unit type, meeting all protection and automatic control needs.
They shall comply with IEC 60801.4 and 50263 recommendations concerning electromagnetic compatibility.
If necessary, they shall be able to communicate:
- using standardised protocols,
- adapting to a wide range of power supply voltages,
- with the possibility of being disconnected while live without any danger to installation,
- storing the information in memory in the event of an auxiliary power failure.
The manufacturer shall provide proof that he has already supplied equipment of the same type and same make
and that this equipment has been in operation for at least three years.
an environmental management system in conformity with ISO 14001, both certified by an official
independent organisation.
3. Description
3.1 Magnetic core
This will be made from laminations of grain oriented silicon steel, insulated with mineral oxide and will be
protected against corrosion with a coat of varnish.
In order to reduced the power consumption due to transformer no-load losses, the magnetic core is stacked
using overlapping-interlocking technology, with at least 6 overlaps.
In order to reduce the noise produced by the magnetic core, it is equipped with noise-damping devices.
3.2 LV windings
The LV winding is produced using al uminium or copper foils (according to the manufacturers preference) in
order to cancel out axial stress during short circuit ; this foil will be insulated between each layer using a heatreactivated class F pre-impregnated epoxy resin film
The ends of the winding are protected and insulated using a class F insulating material, covered with heat
reactivated epoxy resin
The whole winding assembly will be polymerised throughout by being autoclaved for 2 hours at 130C, which will
ensure :
High level of resistance to industrial environments
Excellent dielectric withstand
Very good resistance to radial stress in the instance of a bolted short circuit.
3.3 HV windings
They will be separated from the LV windings to give an air gap between the MV and LV circuits in order to avoid
depositing of dust on the spacers placed in the radical electrical field and to make maintenance easier.
These will be independent of the LV windings and will be made of aluminium or copper wire or foil (according to
the manufacturer's preference) with class F insulation.
The HV windings will be vacuum cast in a class F fireproof epoxy resin casting system composed of :
an epoxy resin
an anhydride hardener with a flexibilising additive
a flame-retardant filler.
6. Metal enclosure
On request, these transformers will be equipped with a metal enclosure for indoor installation comprising an
integral IP 31 (except the base which may be IP 21) metal enclosure, that can be dismantle on request, with :
an anti-corrosion protection in the manufacturer's standard colour
lifting lugs enabling the transformer and enclosure assembly to be handled.
a bolted access panel on the enclosure front to allow access to the HV connections and to the tapping. This
will be fitted with handles, it will have one "Danger Electricity" warning label (T 10 warning), a rating plate
and a visible braid for earthling.
blanked off holes for fitting Ronis ELP 1 or alternatively Profalux P1 type key locks on the bolted access
panel to enable it to be locked.
2 undrilled gland plates on the roof : one on the HV side, one on the LV side (drilling and cable gland not
supplied).
1 plate at the right HV side on the bottom of the enclosure for the HV cables for connections from the bottom
as an option, a HV cables clamping system shall be provided when the cables are coming from the bottom
7. Electrical protection
7.1 Protection relay
The installation must have a protection relay to protect the transformer from:
overload,
short circuits (internal or external),
earth faults,
overflow.
7.2 MV surge arresters
It is advisable to check that the installation will not be subjected to overvoltage of any kind (atmospheric or
switching overvoltage).
If there is a risk, the transformer should be protected by phase-earth surge arresters installed directly on the MV
connection terminals (top or bottom).
Phase-earth surge arresters are absolutely essential in the following cases:
If the lightning impact level Nk is greater than 25. The risk of direct or induced atmospheric overvoltage is
directly proportional to Nk.
During the occasional switching (less than 10 operations a year) of a transformer with a weak load, or during
a magnetisation period.
8. Electrical tests
8.1 Routine tests
These tests will be carried out on all the transformers after the manufacturing, enabling an official test certificate
to be produced for each one :
measurement of windings resistance
measurement of the transformation ratio and vector group
measurement of impedance voltage and load loss
measurement of no load loss and no load current
applied voltage dielectric test
induced voltage dielectric test
measurement of partial discharges.
For measurement of the partial discharges, the acceptance criterion will be :
partial discharges less than or equal to 10 pC at 1.30 Un.
(All these tests are defined in the Harmonisation Document HD 464 S1: 1988, the IEC 60076-11 and IEC
60076-1 to 60076-3 standards).
8.2 Type tests or special tests
These tests can be requested as option, but are subject to prior agreement of the supplier :
temperature rise test carried out in accordance with the simulated loading method as defined by the IEC
60076-11 standard
lightning impulse test in accordance with IEC 60076-3
short circuit test in accordance with IEC 60076-5
noise level measurements in accordance with IEC 60076-10.
(all the tests are defined by the HD 464 S1 Harmonisation Document : 1988, the IEC 60076-11 and IEC 600761 to 60076-5 standards).
9. Climatic and Environmental classifications
These transformers will be of climatic class C2 and of environmental class E2 as defined in appendix B of HD
464 S1: 1988 / A2 : 1991. C2 and E2 classes will be indicated on the rating plate.
The manufacturer must produce a test report from an official laboratory for a transformer of the same design as
those produced.
C
C
C
m
C2
E2
F1
Enclosure..
Protection degree.
YES
IP 31
Length.
Width..
Height.
Total weight
mm
mm
mm
kg
NO*
Altitude
< 2000 m
Other
Value =
Ambient temperature
25 C
35 C
Relative humidity
80% (35C)
Other
Value =
Climatic ambience
T2
Other
Value=
45 C
55 C
Mechanical
Protection degree extern
IP30
IP31
IP43
IP55
IK07
IK08
IK10
Level of partitioning
Form1
Form2a
Form2b
Form3a
Form3b
Door locking
Without
With
N of Key
Colour of Envelop
RAL 9001
Other
Value=
RAL
Colour of Framework
RAL 9001
Other
Value=
RAL
RAL 9001
Other
Value=
RAL
RAL 7032
Other
Value=
RAL
ype of Voltage
AC
DC
Frequency
50Hz
60Hz
Other
Value=
Nominal Voltage
400V
690V
Other
Value=
Value=
Value=
Value=
Earthing Schematics
T.T
Form4a
Form4b
Electrical
I.T
T.N.C
T.N.S
Specifications of devices
-----------------------------------------------------------------------------------------------------------------------------Number
Feeders > 1600 A
1000 A < Feeders < 1600 A
630 A < Feeders < 1000 A
400 A Feeders 630 A
100 A Feeders 250 A
Feeders < 100 A
Percentage of spares space
List below the specifications
of all incoming and outgoers devices
l Number of incoming devices : Value =
Incoming by cables :
Incoming by busways :
T.N. C-S
Yes
Value =
l Number of feeders :
Total =
l Control circuit :
Yes
No
No
AC
DC
Environment
Altitude
< 2000 m
Other
Value =
Ambient temperature
25 C
35 C
Relative humidity
80% (35C)
Other
Value =
Climatic ambience
T2
Other
Value=
45 C
55 C
IP30
IP31
IP43
IP55
IK07
IK08
IK10
Door locking
Without
With
N of Key
Colour of Envelop
RAL 9001
Other
Value=
RAL
Colour of Framework
RAL 9001
Other
Value=
RAL
RAL 9001
Other
Value=
RAL
RAL 7032
Other
Value=
RAL
Type of Voltage
AC
DC
Frequency
50Hz
60Hz
Other
Value=
Nominal Voltage
400V
690V
Other
Value=
Value=
Value=
Value=
Earthing Schematics
T.T
Electrical
I.T
T.N.C
T.N.S
Specifications of devices
-----------------------------------------------------------------------------------------------------------------------------Number
400 A Feeders 630 A
100 A Feeders 250 A
Feeders < 100 A
Percentage of spares space
List below the specifications
of all incoming and outgoers devices
l Number of incoming devices : Value =
Incoming by cables :
l Coupling devices
Yes
Value =
l Number of feeders :
Total =
l Control circuit :
Yes
No
No
T.N.C-S
AC
DC
End cover
Tap-off outlet
Fixing bracket
Straight length
Elbow
2. Standards
Busbar trunking systems must meet all rules stated in IEC 439-2. This defines the manufacturing arrangements
to be complied with in the design of busbar trunking systems (e.g.: temperature rise characteristics, short-circuit
withstand, mechanical strength, etc.) as well as test methods to check them. Standard IEC 439-2 defines 13
compulsory type-tests on configurations or system components. By assembling the system components on the
site according to the assembly instructions, the contractor benefits from conformity with the standard.
3. Introduction to KS range
3.2 Canalis KS
Canalis KS is designed for medium-power distribution with high tap-off densities in industrial and commercial
buildings (factories, exhibition
halls, supermarkets, etc.).
Canalis KS suits as well in multi-storeys buildings (office buildings, hotels, hospitals, car parks and ships).. Its
used as risers to distribute power to each floor.
The range is available in eight ratings: 100, 160, 250, 400, 500, 630, 800 et 1000 A.
4.2 Characteristics
Degree of protection: IP55
Number of live conductors: 4.
Rated insulation voltage: 690 V.
Rated current (Inc): 100 A, 160 A, 250 A, 400 A, 500 A, 630 A, 800 A and 1000 A.
The cross-sectional area of the protective conductor is at least 50% that of the phases.
4.3
Fire resistance
Fire barriers as per standard ISO 834 (DIN 4102-part 9) for passages through partitions.
Resistant to flame propagation in compliance with standard IEC 60332 - part 3.
Materials resistant to abnormal heat (glow-wire test as per IEC 60695-2-1).
The enclosure, made of sheet steel, galvanised and pre-lacquered RAL 9001 white.
The four aluminium conductors are mounted on fibreglass reinforced polyester insulators. All electrical
contacts are made of silver -plated copper.
The straight lengths have a tap-off unit every 0.5 metre on one side. There are four tap-off units per floor for
floor heights between 3.5 and 4.8 metres, or three tap -off outlets per floor for floor heights less than 3.5
metres. The tap-off outlets are equipped with automatic shutters that avoid accidental contact with live parts.
The protective conductor is electrically connected to the enclosure at each jointing unit.
Electrical contact between two components is ensured by flexible contacts designed to adapt to the
difference in expansion between the conductors and the enclosure. It is possible to check visually that the
electrical contact is effective.
- The mechanical junction between two components is ensured by four captive screws. The jointing unit (3)
is maintenance free.
Special components are available to change direction or avoid obstacles.
Technical specifications
Canalis KDP
Cable with prefabricated tap-offs for lighting distribution
End cover
Tap-off outlet
Fixing bracket
Straight length
Elbow
2. Standards
Busbar trunking systems must meet all rules stated in IEC 439-2. This defines the manufacturing arrangements
to be complied with in the design of busbar trunking systems (e.g.: temperature rise characteristics, short-circuit
withstand, mechanical strength, etc.) as well as test methods to check them. Standard IEC 439-2 defines 13
compulsory type-tests on configurations or system components. By assembling the system components on the
site according to the assembly instructions, the contractor benefits from conformity with the standard.
3. Introduction to KN ranges
Canalis KN is designed for low-power distribution.
There are two versions:
Canalis KNA: busbar trunking with four live conductors (3L + N + PE), for distribution up to 160 A,
Canalis KNT: identical to KNA, but equipped with a transmission bus with three 2.5 mm conductors (except
160 A). This bus can be used to set up simple control/monitoring systems (lighting or otherloads).
4. KN Conception
4.1 General
Canalis KN Complies with standards IEC 60439 -2 and EN 60439-2
Glossary
Service reliability
Definition: the ability of a power system to meet its supply function under stated conditions for a specified period
of time.
Different categories:
Minimum: this level of service reliability implies risk of interruptions related to constraints that are
geographical (separate network, area distant from power production centers), technical (overhead line,
poorly meshed system), or economic (insufficient maintenance, under-dimensioned generation).
Standard
Enhanced: this level of service reliability can be obtained by special measures taken to reduce the
probability of interruption (underground network, strong meshing, etc.)
Installation flexibility
Definition: possibility of easily moving electricity delivery points within the installation, or to easily increase the
power supplied at certain points. Flexibility is a criterion which also appears due to the uncertainty of the building
during the pre-project summary stage (APS).
Different categories:
No flexibility: the position of loads is fixed throughout the lifecycle, due to the high constraints related to the
building construction or the high weight of the supplied process. E.g.: smelting works.
Flexibility of design: the number of delivery points, the power of loads or their location are not precisely
known.
Implementation flexibility: the loads can be installed after the installation is commissioned.
Operating flexibility: the position of loads will fluctuate, according to process reorganization.
Examples:
industrial building: extension, splitting and changing usage
office building: splitting
Load distribution
Definition: a characteristic related to the uniformity of load distribution (in kVA / m) over an area, or throughout
the building.
Different categories:
uniform distribution: the loads are generally of an average or low unit power and spread throughout the
surface area or over a large area of the building (uniform density). E.g.: lighting, individual workstations
intermediate distribution: the loads are generally of medium power, placed in groups over the whole building
surface area. E.g.: machines for assembly, conveying, workstations, modular logistics sites
localized loads: the loads are generally high power and localized in several areas of the building (nonuniform density). E.g.: HVAC
Disturbance sensitivity
Definition: the ability of a circuit to work correctly in presence of an electrical power disturbance.
A disturbance can lead to varying degrees of malfunctioning. E.g.: stopping working,
incorrect working, accelerated ageing, increase of losses, etc
Types of disturbances with an impact on circuit operations:
brown -outs,
overvoltages
voltage distortion,
voltage fluctuation,
voltage imbalance.
Different categories:
low sensitivity: disturbances in supply voltages have very little effect on operations. E.g.: heating device.
medium sensitivity: voltage disturbances cause a notable deterioration in operations. E.g.: motors, lighting.
high sensitivity: voltage disturbances can cause operation stoppages or even the deterioration of the
supplied equipment. E.g.: IT equipment.
The sensitivity of circuits to disturbances determines the design of shared or dedicated power circuits. Indeed it
is better to separate sensitive loads from disturbing loads. E.g.: separating lighting circuits from motor supply
circuits.
This choice also depends on operating features. E.g.: separate power supply of lighting circuits to enable
measurement of power consumption.
Environment, atmosphere
Definition: a notion taking account of all of the environmental constraints (average ambient temperature, altitude,
humidity, corrosion, dust, impact, etc.) and bringing together protection indexes IP and IK.
Different categories:
Standard: no particular environmental constraints
Enhanced: severe environment, several environmental parameters generate important constraints for the
installed equipment
Specific: atypical environment, requiring special enhancements
Maintainability
Definition: level of features input during design to limit the impact of maintenance actions on the operation of the
whole or part of the installation.
Different categories:
Minimum: the installation must be stopped to carry out maintenance operations.
Standard: maintenance operations can be carried out during installation operations, but with deteriorated
performance. These operations must be preferably scheduled during periods of low activity. Example:
several transformers with partial redundancy and load shedding.
Enhanced: special measures are taken to allow maintainance operations without disturbing the installation
operations. Example: double-ended configuration.