Sie sind auf Seite 1von 16

January 2006

Labko Oil Separator Systems

Labko Oil Separator Systems

Wavin-Labko in brief
Wavin-Labko Ltd is a Finnish company with over 40 years'
experience in developing, manufacturing and marketing of
measurement devices and various plastic products. In the field
of measurement devices we are specialized in level instruments
and alarm devices, automation and identification, and in webbased solutions of data transfer. In the field of plastic products
we have focused our know-how on wastewater and stormwater
treatment by using various separator systems. These systems
cover the separator solutions in business and services
construction, the wastewater treatment in rural area settlements,
as well as the wastewater treatment of private houses and
summer cottages.
Wavin-Labko Ltd is a part of international Wavin Group, which
is the leader in the European market for plastic pipe systems.
Wavin Group has a presence in 27 European countries.

Wavin-Labko Ltd reserves the rights to alterations without prior notice. Due to policy of continuous
improvement in R&D, technical specifications may change. Installation shall always be made as
documented in manufacturer's instructions.

Pictorino Oy/Kirjapaino Hermes 1/2006 2.000

www.wavin-labko.fi
Wavin-Labko Ltd
Labkotie 1
FI-36240 Kangasala
FINLAND
Tel. int. +358 20 1285 200
Fax int. +358 20 1285 280
E-mail tanks@wavin-labko.fi

FOR STORMWATER TREATMENT


IN INDUSTRIAL, STORAGE AND
TRAFFIC AREAS

Reliable solutions

Separators and tanks

Labko Oil Separator Systems


Labko Bypass System

Labko
Bypass
System for
stormwater
treatment
prevents the washout of
the separator system
during heavy downpour

Labko Bypass System

At this point the flow rate has not reached

and heavy metals, are carried from surfaced

Operation and structure of the


Labko Bypass System

areas into the environment. Up to 80 % of

Within the Labko Bypass System the peak

the Labko Bypass System process all the

heavy metals are combined with solid matter,

flow of the stormwater is directed through the

rainwater. The following peak flow that

such as sand and silt, which are carried

Labko FRW Flow Regulation Well to pass the

contains fewer pollutants is directed past

along with the rainwater.

separator system consisting of the EuroHEK

the separator system. Thus, the washout

to treat the entire downpour, thus requiring

sand and sludge trap and the EuroPEK oil

of the separator is prevented, and oil will

larger separators and causing more

separator. Following the separator system

not be carried from the separator to the

substantial building costs than the Labko

rainwater flowing from surfaced areas should

there is the EuroNOK FRW sampling shaft,

sewer system, which normally leads the

Bypass System.

be cleaned. In general, the areas from which

in which the bypass line is reconnected with

rainwater to the ground.

the rainwater is collected are relatively large,

the rainwater line. In spite of the bypass flow,

for example car parks, industrial areas, traffic

a well dimensioned Labko Bypass System

Considerable savings are obtained by using

areas, terminals, or airfields. Environmentally

treats approximately 95 % of the annual

Labko Bypass System, in comparison with

most delicate areas should be equipped

downfall. Thanks to the Labko Bypass

cleaning systems, which are sized to treat

with a system processing all the downfall.

System, stormwater treatment is not only

the whole nominal flow. Smaller and more

In normal conditions it is possible to reduce

effective, but cost-effective, too.

economical separators can be used in a

Many hazardous substances, such as oil

To save nature from harmful emissions the

Efficient and cost-effective


stormwater treatment

System.

stormwater treatment in

its maximum yet, letting the separators in

Direct
system

areas, which for some other reason require


100 % cleaning of the rainwater, it is
reasonable to use the traditional, so called
direct system. This system is dimensioned

system.
EuroHEK sand
and sludge trap

It is a research observation that most of the

large areas

In environmentally sensitive areas or in

Labko Bypass System than in a direct

the investment costs by using Labko Bypass

economical solution for

Labko Oil Separator Systems

oils and heavy metals carried with the rainwater

treats 95 % of the annual

from surfaced areas are mainly washed away

rainfall

TEGRA 600
inspection well

Wavin
HEK 400 TEL

Wavin
HEK 400 TEL
TEGRA 600
inspection well

EuroNOK FRW
sampling shaft with
a shut-off valve

EuroPEK
oil separator

at the beginning of the downpour.

Labko FRW
Flow Regulation
Well

Wavin
HEK 400 TEL sand
and sludge trap

SandSET-1000
sludge alarm

Wavin
HEK 400 TEL
sand and
sludge trap

Labcom 200
communication unit

OilSET-1000
oil alarm

Designed for use in


parking lots
industrial yards and storage areas
traffic areas

EuroHEK sand
and sludge trap

terminals
airfields

Labko Bypass System

TEL. INT.

FAX INT.

E-MAIL

+358 20 1285 200

+358 20 1285 280

tanks@wavin-labko.fi

EuroNOK FRW
sampling shaft with
a shut-off valve

EuroPEK
oil separator

Labko Oil Separator Systems


www.wavin-labko.fi

Separators and tanks

Labko Oil Separator Systems


Labko Bypass System

Labko
Bypass
System for
stormwater
treatment
prevents the washout of
the separator system
during heavy downpour

Labko Bypass System

At this point the flow rate has not reached

and heavy metals, are carried from surfaced

Operation and structure of the


Labko Bypass System

areas into the environment. Up to 80 % of

Within the Labko Bypass System the peak

the Labko Bypass System process all the

heavy metals are combined with solid matter,

flow of the stormwater is directed through the

rainwater. The following peak flow that

such as sand and silt, which are carried

Labko FRW Flow Regulation Well to pass the

contains fewer pollutants is directed past

along with the rainwater.

separator system consisting of the EuroHEK

the separator system. Thus, the washout

to treat the entire downpour, thus requiring

sand and sludge trap and the EuroPEK oil

of the separator is prevented, and oil will

larger separators and causing more

separator. Following the separator system

not be carried from the separator to the

substantial building costs than the Labko

rainwater flowing from surfaced areas should

there is the EuroNOK FRW sampling shaft,

sewer system, which normally leads the

Bypass System.

be cleaned. In general, the areas from which

in which the bypass line is reconnected with

rainwater to the ground.

the rainwater is collected are relatively large,

the rainwater line. In spite of the bypass flow,

for example car parks, industrial areas, traffic

a well dimensioned Labko Bypass System

Considerable savings are obtained by using

areas, terminals, or airfields. Environmentally

treats approximately 95 % of the annual

Labko Bypass System, in comparison with

most delicate areas should be equipped

downfall. Thanks to the Labko Bypass

cleaning systems, which are sized to treat

with a system processing all the downfall.

System, stormwater treatment is not only

the whole nominal flow. Smaller and more

In normal conditions it is possible to reduce

effective, but cost-effective, too.

economical separators can be used in a

Many hazardous substances, such as oil

To save nature from harmful emissions the

Efficient and cost-effective


stormwater treatment

System.

stormwater treatment in

its maximum yet, letting the separators in

Direct
system

areas, which for some other reason require


100 % cleaning of the rainwater, it is
reasonable to use the traditional, so called
direct system. This system is dimensioned

system.
EuroHEK sand
and sludge trap

It is a research observation that most of the

large areas

In environmentally sensitive areas or in

Labko Bypass System than in a direct

the investment costs by using Labko Bypass

economical solution for

Labko Oil Separator Systems

oils and heavy metals carried with the rainwater

treats 95 % of the annual

from surfaced areas are mainly washed away

rainfall

TEGRA 600
inspection well

Wavin
HEK 400 TEL

Wavin
HEK 400 TEL
TEGRA 600
inspection well

EuroNOK FRW
sampling shaft with
a shut-off valve

EuroPEK
oil separator

at the beginning of the downpour.

Labko FRW
Flow Regulation
Well

Wavin
HEK 400 TEL sand
and sludge trap

SandSET-1000
sludge alarm

Wavin
HEK 400 TEL
sand and
sludge trap

Labcom 200
communication unit

OilSET-1000
oil alarm

Designed for use in


parking lots
industrial yards and storage areas
traffic areas

EuroHEK sand
and sludge trap

terminals
airfields

Labko Bypass System

TEL. INT.

FAX INT.

E-MAIL

+358 20 1285 200

+358 20 1285 280

tanks@wavin-labko.fi

EuroNOK FRW
sampling shaft with
a shut-off valve

EuroPEK
oil separator

Labko Oil Separator Systems


www.wavin-labko.fi

Separators and tanks

Labko Oil Separator Systems

Labko FRW Flow Regulation Well

Labko
FRW Flow
Regulation
Well

Flow Regulation Well adjusts and restricts


the incoming flow to the separator system.
The Labko FRW Flow Regulation Well
contains a mechanical flow regulator, which
provides an even flow into the separators,
even if the incoming flow should exceed
the dimensioned flow of the separator
system. The excess flow is directed via
system. This prevents the washout of the
gathered sands and oils in the separator
system. Labko FRW Flow Regulation Well
is dimensioned to process approximately
95% of the annual downpour.

EuroHEK sand and sludge trap EuroHEK Omega sand and sludge trap

During a heavy downpour, the Labko FRW

the bypass pipe to pass the separator

Labko Oil Separator Systems

EuroHEK
and
EuroHEK
Omega
Sand and
Sludge
Traps

The larger EuroHEK Omega 20005000

carried by the rainwater is separated. Thus,

and EuroHEK 650050000 are the sand

the sand and sludge trap contributes to the

and sludge traps for e.g. parking lots.

smooth operation of the oil separator and

During normal downfall all the rainwater is


directed through the separator. The figure
presents the early phase of a heavy downpour,
during which the FRW flow regulation
mechanism starts to function. The flow
regulator only allows the maximal rainwater
amount corresponding to the dimensioned
flow into the separator system. The excess
flow is shortly dammed, until let flow via
bypass pipe past the separator system.

In EuroHEK sand and sludge trap the sand

to lower maintenance costs. The rainwater

SandSET-1000 sludge alarm controls the

to be treated flows into the sand and sludge

filling of the sludge storage space and

trap, which separates sand, sludge and

indicates an alarm when the sand and sludge

further solids from the water. The solid-free

trap must be emptied (some 1/3 of the water

rainwater flows from the sand and sludge

capacity is filled with sand). The timely

trap into the oil separator. According to the

emptying of the sand and sludge trap

EN 858 standard, a sand and sludge trap

ensures the proper functioning of the oil

is always a part of the oil separator system.

separator. SandSET-1000 is provided as a


standard in EuroHEK 10000 and larger sand

EuroHEK 6001500 sand and sludge traps

and sludge traps. For smaller sand and

are designed for stormwater treatment in

sludge traps the SandSET-1000 is available

parking areas, petrol station filling areas and

as an accessory.

in yard areas.

The rainwater from surfaced areas carries


sand and finer-grained sludge. Most of the
heavy metals occurring in traffic areas are
bound to these solid particles.

Flow rate
Concentration of
oil and solids
Time
First Flush phenomenon: Most of the oils and heavy metals carried by the rainwater are
flushed from surfaced areas during the first phase of the downpour. At this point, the
rainwater flow has not reached its maximum yet, allowing all the rainwater flow though
the separators of the Labko Bypass System.

Also during the peak flow of the heavy


downpour the separator system functions
normally. The Labko FRW Flow Regulation
Well leads the excess flow exceeding the
dimensioned flow of the oil separator via the
bypass pipe to pass the separator system.
Thus the washout of the separators is
prevented.
SandSET-1000
sludge alarm

Labko FRW
Flow Regulation
Well

SET-2000
oil alarm

EuroHEK Omega
sand and sludge
separator

TEL. INT.

FAX INT.

E-MAIL

+358 20 1285 200

-358 20 1285 280

tanks@wavin-labko.fi

EuroPEK
Omega Filter
oil separator

EuroNOK FRW
sampling shaft with
a shut-off valve

Labko Oil Separator Systems


www.wavin-labko.fi

Separators and tanks

Labko Oil Separator Systems

Labko FRW Flow Regulation Well

Labko
FRW Flow
Regulation
Well

Flow Regulation Well adjusts and restricts


the incoming flow to the separator system.
The Labko FRW Flow Regulation Well
contains a mechanical flow regulator, which
provides an even flow into the separators,
even if the incoming flow should exceed
the dimensioned flow of the separator
system. The excess flow is directed via
system. This prevents the washout of the
gathered sands and oils in the separator
system. Labko FRW Flow Regulation Well
is dimensioned to process approximately
95% of the annual downpour.

EuroHEK sand and sludge trap EuroHEK Omega sand and sludge trap

During a heavy downpour, the Labko FRW

the bypass pipe to pass the separator

Labko Oil Separator Systems

EuroHEK
and
EuroHEK
Omega
Sand and
Sludge
Traps

The larger EuroHEK Omega 20005000

carried by the rainwater is separated. Thus,

and EuroHEK 650050000 are the sand

the sand and sludge trap contributes to the

and sludge traps for e.g. parking lots.

smooth operation of the oil separator and

During normal downfall all the rainwater is


directed through the separator. The figure
presents the early phase of a heavy downpour,
during which the FRW flow regulation
mechanism starts to function. The flow
regulator only allows the maximal rainwater
amount corresponding to the dimensioned
flow into the separator system. The excess
flow is shortly dammed, until let flow via
bypass pipe past the separator system.

In EuroHEK sand and sludge trap the sand

to lower maintenance costs. The rainwater

SandSET-1000 sludge alarm controls the

to be treated flows into the sand and sludge

filling of the sludge storage space and

trap, which separates sand, sludge and

indicates an alarm when the sand and sludge

further solids from the water. The solid-free

trap must be emptied (some 1/3 of the water

rainwater flows from the sand and sludge

capacity is filled with sand). The timely

trap into the oil separator. According to the

emptying of the sand and sludge trap

EN 858 standard, a sand and sludge trap

ensures the proper functioning of the oil

is always a part of the oil separator system.

separator. SandSET-1000 is provided as a


standard in EuroHEK 10000 and larger sand

EuroHEK 6001500 sand and sludge traps

and sludge traps. For smaller sand and

are designed for stormwater treatment in

sludge traps the SandSET-1000 is available

parking areas, petrol station filling areas and

as an accessory.

in yard areas.

The rainwater from surfaced areas carries


sand and finer-grained sludge. Most of the
heavy metals occurring in traffic areas are
bound to these solid particles.

Flow rate
Concentration of
oil and solids
Time
First Flush phenomenon: Most of the oils and heavy metals carried by the rainwater are
flushed from surfaced areas during the first phase of the downpour. At this point, the
rainwater flow has not reached its maximum yet, allowing all the rainwater flow though
the separators of the Labko Bypass System.

Also during the peak flow of the heavy


downpour the separator system functions
normally. The Labko FRW Flow Regulation
Well leads the excess flow exceeding the
dimensioned flow of the oil separator via the
bypass pipe to pass the separator system.
Thus the washout of the separators is
prevented.
SandSET-1000
sludge alarm

Labko FRW
Flow Regulation
Well

SET-2000
oil alarm

EuroHEK Omega
sand and sludge
separator

TEL. INT.

FAX INT.

E-MAIL

+358 20 1285 200

-358 20 1285 280

tanks@wavin-labko.fi

EuroPEK
Omega Filter
oil separator

EuroNOK FRW
sampling shaft with
a shut-off valve

Labko Oil Separator Systems


www.wavin-labko.fi

Separators and tanks

Labko Oil Separator Systems

EuroPEK oil separator

EuroPEK
Oil Separator
EuroPEK oil separator is a class I oil
separator. It is designed and tested

The coalescing plates of the EuroPEK

solids in the rainwater, meaning e.g. waste

separators can be cleaned with pressure

treatment plants or collecting sites, scrap

washer, after which they reach their proper

yards, service and storage sites for earth-

functioning again. The possibility to clean

movers, and areas with peat processing.

the plates significantly reduces the maintenance and service costs of the separator,

EuroPEK oil separators include the OilSET-

for there are no filters, which are classified

1000 oil alarm with ATEX compliance as

as hazardous waste, to be disposed of.

a standard. It indicates an alarm if the oil

according to the requirements of the

storage space is full. Further information

EN 858 standard, and it can be used to


treat all kinds of oily waste and rainwaters.

EuroPEK separators present an extensive

on the alarm device and data transfer can

range of applicability. They are best applied

be found on page 12.

Labko Oil Separator Systems


EuroPEK Omega Filter oil separator

EuroPEK
Omega
Filter
Oil Separator

EuroPEK Omega Filter oil separators are class

in areas, in which there is a high content of


EuroPEK oil separators are equipped with

I separators. They are designed and tested

coalescing plates, which separate oil from

in accordance with the EN 858 standard,

the water. The process is based on the fact

and they are suitable for treating oily rainwater.

that oil drops coalesce when they run onto

EuroPEK Omega Filter separators are

the oleophilic (oil attracting) plates. When

available in size classes NS3-NS15. Their

the size of the oil drop grows, its upward

high cleaning capacity is based on a

velocity grows (Stokes' law) and the oil

coalescent 3-D filter.

drops rise along the angled plates surfaces


and through the holes in the coalescing

The EuroPEK Omega Filter oil separators are

plates. The separated oil is stored as a

made of strong and recyclable PE-plastic.

homogenous layer on the surface of the

The separators are light to transport and easy

water in the separator.

to install. The spherical bottom of the sludge


storage space allows complete emptying.
EuroPEK Omega Filter includes the SET-2000
oil alarm with ATEX compliance as a standard.
It indicates an alarm if the oil storage space
is full or in case of a high water level. Further
information on the alarm device and data
transfer can be found on page 12.

Operating
principle of the
coalescer.

SandSET-1000
sludge alarm

Labko FRW
Flow Regulation
Well

OilSET-1000
oil alarm

EuroHEK sand
and sludge trap

TEL. INT.

FAX INT.

E-MAIL

+358 20 1285 200

+358 20 1285 280

tanks@wavin-labko.fi

The superb cleaning


efficiency of the EuroPEK
Omega Filter oil separators
is verified by flow tests run
in compliance with the
EN 858 standard.

EuroPEK
oil separator

EuroNOK FRW
sampling shaft with
a shut-off valve

Labko Oil Separator Systems


www.wavin-labko.fi

Separators and tanks

Labko Oil Separator Systems

EuroPEK oil separator

EuroPEK
Oil Separator
EuroPEK oil separator is a class I oil
separator. It is designed and tested

The coalescing plates of the EuroPEK

solids in the rainwater, meaning e.g. waste

separators can be cleaned with pressure

treatment plants or collecting sites, scrap

washer, after which they reach their proper

yards, service and storage sites for earth-

functioning again. The possibility to clean

movers, and areas with peat processing.

the plates significantly reduces the maintenance and service costs of the separator,

EuroPEK oil separators include the OilSET-

for there are no filters, which are classified

1000 oil alarm with ATEX compliance as

as hazardous waste, to be disposed of.

a standard. It indicates an alarm if the oil

according to the requirements of the

storage space is full. Further information

EN 858 standard, and it can be used to


treat all kinds of oily waste and rainwaters.

EuroPEK separators present an extensive

on the alarm device and data transfer can

range of applicability. They are best applied

be found on page 12.

Labko Oil Separator Systems


EuroPEK Omega Filter oil separator

EuroPEK
Omega
Filter
Oil Separator

EuroPEK Omega Filter oil separators are class

in areas, in which there is a high content of


EuroPEK oil separators are equipped with

I separators. They are designed and tested

coalescing plates, which separate oil from

in accordance with the EN 858 standard,

the water. The process is based on the fact

and they are suitable for treating oily rainwater.

that oil drops coalesce when they run onto

EuroPEK Omega Filter separators are

the oleophilic (oil attracting) plates. When

available in size classes NS3-NS15. Their

the size of the oil drop grows, its upward

high cleaning capacity is based on a

velocity grows (Stokes' law) and the oil

coalescent 3-D filter.

drops rise along the angled plates surfaces


and through the holes in the coalescing

The EuroPEK Omega Filter oil separators are

plates. The separated oil is stored as a

made of strong and recyclable PE-plastic.

homogenous layer on the surface of the

The separators are light to transport and easy

water in the separator.

to install. The spherical bottom of the sludge


storage space allows complete emptying.
EuroPEK Omega Filter includes the SET-2000
oil alarm with ATEX compliance as a standard.
It indicates an alarm if the oil storage space
is full or in case of a high water level. Further
information on the alarm device and data
transfer can be found on page 12.

Operating
principle of the
coalescer.

SandSET-1000
sludge alarm

Labko FRW
Flow Regulation
Well

OilSET-1000
oil alarm

EuroHEK sand
and sludge trap

TEL. INT.

FAX INT.

E-MAIL

+358 20 1285 200

+358 20 1285 280

tanks@wavin-labko.fi

The superb cleaning


efficiency of the EuroPEK
Omega Filter oil separators
is verified by flow tests run
in compliance with the
EN 858 standard.

EuroPEK
oil separator

EuroNOK FRW
sampling shaft with
a shut-off valve

Labko Oil Separator Systems


www.wavin-labko.fi

Separators and tanks

Labko Oil Separator Systems

EuroPEK Filter oil separator

EuroPEK
Filter Oil
Separator

EuroPEK Filter is a class I oil separator.

EuroPEK Filter separators are designed for

It is designed and tested according to the

areas with only a low quantity of solids and

requirements of the EN 858 standard. The

oils in the rainwater.

cleaning capacity of the EuroPEK Filter is


based on a coalescent 3-D filter. There are
1-4 filters in each separator, depending on
the model. EuroPEK Filter separators are
made of reinforced plastic and they are
available in size classes NS20-NS150.

As a standard, an ATEX-approved SET2000 oil alarm is included in the EuroPEK


Filter oil separator. The oil alarm signals,
not only when emptying is needed, but in
case of blocking, too. Further information
on the alarm device and data transfer can
be found on page 12.

Labko Oil Separator Systems

EuroNOK FRW sampling shaft with a shut-off valve EuroHUK maintenance shaft PP-HUK 600 maintenance shaft

EuroNOK
FRW
Sampling
Shaft with
a shut-off
valve

EuroHUK and
PP-HUK 600
Maintenance
Shaft
The EuroHUK maintenance shaft is a waterproof solution in compliance with the oil

EuroNOK FRW sampling shaft with a


shut-off valve.

separator standard to go with the separators.


The EuroHUK maintenance shaft is selected
according to the installation depth of the

According to the EN 858 standard, a


sampling shaft always builds a part of the
oil separator system. The EuroNOK
sampling shafts make it possible to monitor
the quality of the wastewater or rainwater
that is led into the sewer system.

weight, the installation goes fast. Except for


the smallest model, all the shafts have steps
inside to ease the maintenance. A specialshaped gasket, which is delivered with the
maintenance shaft, guarantees that the sep-

shaft is installed to follow the oil separator.

arator and the shaft are compatible and that

In the Labko Bypass System, the EuroNOK

their junction is tight.

EuroNOK FRW is that the bypass-pipe is


connected back to the rainwater sewer.
Both the EuroNOK and the EuroNOK FRW
contain a shut-off valve that makes it
possible to close the sewer line, should an
accident occur in the area.

PP-HUK 600 maintenance shafts are used

SandSET-1000
sludge alarm

Labko FRW
Flow Regulation
Well

EuroHEK sand
and sludge trap

TEL. INT.

FAX INT.

E-MAIL

+358 20 1285 200

+358 20 1285 280

tanks@wavin-labko.fi

EuroHUK maintenance shafts installed.

with EuroPEK Filter oil separators to ease the


maintenance of their filters. PP-HUK 600 is
a waterproof solution in compliance with the
oil separator standard to go with the separators.
Cast iron covers and frames are available as

SET-2000
oil alarm

10

Since the maintenance shaft is light in its

In a direct system the EuroNOK sampling

FRW is used. The difference in the

The superb cleaning efficiency of the


EuroPEK Filter oil separators is verified
by flow tests run in compliance with the
EN 858 standard.

separator.

accessories for the maintenance shafts. They

A special-shaped
gasket guarantees
the standardcompliant
tightness
of the maintenance
shaft.

are chosen according to the traffic load on


the site.

PP-HUK 600
maintenance
shaft

EuroHUK
maintenance
shaft

EuroPEK Filter
oil separator

EuroNOK FRW
sampling shaft with
a shut-off valve

Labko Oil Separator Systems


www.wavin-labko.fi

Separators and tanks

11

Labko Oil Separator Systems

EuroPEK Filter oil separator

EuroPEK
Filter Oil
Separator

EuroPEK Filter is a class I oil separator.

EuroPEK Filter separators are designed for

It is designed and tested according to the

areas with only a low quantity of solids and

requirements of the EN 858 standard. The

oils in the rainwater.

cleaning capacity of the EuroPEK Filter is


based on a coalescent 3-D filter. There are
1-4 filters in each separator, depending on
the model. EuroPEK Filter separators are
made of reinforced plastic and they are
available in size classes NS20-NS150.

As a standard, an ATEX-approved SET2000 oil alarm is included in the EuroPEK


Filter oil separator. The oil alarm signals,
not only when emptying is needed, but in
case of blocking, too. Further information
on the alarm device and data transfer can
be found on page 12.

Labko Oil Separator Systems

EuroNOK FRW sampling shaft with a shut-off valve EuroHUK maintenance shaft PP-HUK 600 maintenance shaft

EuroNOK
FRW
Sampling
Shaft with
a shut-off
valve

EuroHUK and
PP-HUK 600
Maintenance
Shaft
The EuroHUK maintenance shaft is a waterproof solution in compliance with the oil

EuroNOK FRW sampling shaft with a


shut-off valve.

separator standard to go with the separators.


The EuroHUK maintenance shaft is selected
according to the installation depth of the

According to the EN 858 standard, a


sampling shaft always builds a part of the
oil separator system. The EuroNOK
sampling shafts make it possible to monitor
the quality of the wastewater or rainwater
that is led into the sewer system.

weight, the installation goes fast. Except for


the smallest model, all the shafts have steps
inside to ease the maintenance. A specialshaped gasket, which is delivered with the
maintenance shaft, guarantees that the sep-

shaft is installed to follow the oil separator.

arator and the shaft are compatible and that

In the Labko Bypass System, the EuroNOK

their junction is tight.

EuroNOK FRW is that the bypass-pipe is


connected back to the rainwater sewer.
Both the EuroNOK and the EuroNOK FRW
contain a shut-off valve that makes it
possible to close the sewer line, should an
accident occur in the area.

PP-HUK 600 maintenance shafts are used

SandSET-1000
sludge alarm

Labko FRW
Flow Regulation
Well

EuroHEK sand
and sludge trap

TEL. INT.

FAX INT.

E-MAIL

+358 20 1285 200

+358 20 1285 280

tanks@wavin-labko.fi

EuroHUK maintenance shafts installed.

with EuroPEK Filter oil separators to ease the


maintenance of their filters. PP-HUK 600 is
a waterproof solution in compliance with the
oil separator standard to go with the separators.
Cast iron covers and frames are available as

SET-2000
oil alarm

10

Since the maintenance shaft is light in its

In a direct system the EuroNOK sampling

FRW is used. The difference in the

The superb cleaning efficiency of the


EuroPEK Filter oil separators is verified
by flow tests run in compliance with the
EN 858 standard.

separator.

accessories for the maintenance shafts. They

A special-shaped
gasket guarantees
the standardcompliant
tightness
of the maintenance
shaft.

are chosen according to the traffic load on


the site.

PP-HUK 600
maintenance
shaft

EuroHUK
maintenance
shaft

EuroPEK Filter
oil separator

EuroNOK FRW
sampling shaft with
a shut-off valve

Labko Oil Separator Systems


www.wavin-labko.fi

Separators and tanks

11

Labko Oil Separator Systems

Alarm devices Data transfer LabkoNet

Labko Oil Separator Systems

Labko FRW Flow Regulation Wells EuroHEK sand and sludge traps
Legend
A
Du
Du1/Du2
Dy
Dy1/Dy2
H1/H2/H3/H4

Alarm devices and Data transfer


remote monitoring and LabkoNet

Labko FRW Flow Regulation Wells

Alarm systems monitoring


the functioning of the separators

Labcom 200 communication unit transfers


the alarm directly to the recipient

All the separators of Wavin-Labko can be equipped with alarm

Labcom 200 sends alarms and measurement data as GSM short

units that control the functioning of the separator. Most separators

messages either directly to the user's own mobile phone or via

include the alarm devices as a standard. The alarm can be

LabkoNet system. The LabkoNet system makes sure the information

transmitted directly to the user's house automation system or with

is delivered to the user, for the server also controls the functioning

the Labcom communication unit to a GSM phone. Furthermore,

of the communication unit.

the alarm can be transmitted via LabkoNet server to those who


find the information is essential. When the separators are remotely

LabkoNet system is an easy and reliable way


of transferring and controlling the alarm data

monitored, timely emptying is made possible, and thus the

Introducing and using the LabkoNet system is easy; no separate

environmental risks are minimized and costs are lowered.

software is needed. Only an Internet connection, Labcom 200

Nominal size
10/30...100/300

Nominal size
125/375...150/450

communication unit, gauges and alarm devices are needed. In


addition to the separator alarms, e.g. storage tank level gauging
can be connected with the LabkoNet.

= area of the yard (0.015 l/(s*m2))


= outer diameter
= inner diameter
= outer diameter of the ventilation pipe (accessory)
= outer diameter of the connection pipe
= height

L
h
V
Vo
Vs
Lkm

Labko
FRW

Nominal Total flow


A
Du Du1 Dy Dy1 Dy2
flow into the of the
separator system
l/s
l/s
m2 mm mm mm mm mm
FRW 10/30
10
30
2000 1780 800 110 200 160
FRW 15/45
15
45
3000 1780 800 110 250 200
FRW 20/60
20
60
4000 1780 800 110 250 200
FRW 30/90
30
90
6000 1780 800 110 315 250
FRW 40/120 40
120 8000 1780 800 110 315 315
FRW 50/150 50
150 10000 1780 800 110 400 315
FRW 65/195 65
195 13000 2170 800 110 400 315
FRW 80/240 80
240 16000 2170 800 110 500 315
FRW 100/300 100
300 20000 2250 800 110 500 315
FRW 125/375 125
375 25000 2200 800 110 500 400
FRW 150/450 150
450 30000 2200 800 110
*** 400
*** according to the delivery Dy1 500 or Dy1 600.
EuroHUK 800
FRW 10/30 - 50/150 FRW 65/195 - 100/300
for FRW
h* (mm)
h* (mm)
9-13
1300-1700
1700-2100
13-17
1700-2100
2100-2500
17-21
2100-2500
2500-2900
21-25
2500-2900
2900-3400

= length
= installation depth
= effective volume
= oil storage volume
= sludge storage volume
= number of the coalescent 3-D filters
H1

mm
750
750
750
750
650
650
950
950
950
475
475

H2

H3

H4 h* Weight

mm mm mm
700 900 1660
700 900 1660
700 900 1660
700 940 1660
600 850 1660
600 810 1660
900 1090 2100
900 1150 2100
900 1150 2200
500 475 1785
500 475 1785

kg
187
188
191
211
225
232
321
391
407

FRW 125/375 - 150/450


h* (mm)
2100-2500
2500-2900
2900-3400
3400-3900

For further information on LabkoNet and its possibilities,


visit www.labkonet.com
SandSET-1000 sludge alarm device
Indicates an alarm when the sludge storage space is full.
The timely desludging reduces unnecessary emptying and
guarantees the smooth operation of the oil separator.

EuroHEK 600...1500 sand and


sludge traps

GSM short messages


The alarm can be transmitted to the
user's GSM either directly with
Labcom 200 communication unit or
via LabkoNet server.

OilSET-1000 oil alarm


Indicates an alarm if the oil storage
space is full and it is time for
emptying. This prevents leakages
into the sewer system.

EuroHEK Omega sand and


sludge traps
E-mail
LabkoNet can also send
the alarm as an e-mail
message.
Labcom 200
communication unit
A data transfer unit
designed for transmitting
measurement and
alarm data.

SET-2000
oil alarm
Gives an alarm if
the oil storage space
is full or if the water
surface level rises
indicating the need
for filter maintenance.

LabkoNet server
Collects the alarms and adapts
their information to be sent further
either as a short message or as
an e-mail. The data is displayed
on user's own web page, too.

Dy

EuroHEK

Du Du1
Dy
Dy1 H1
H2
mm mm mm
mm mm mm
600 h 9-13 1000 600 110 110...250 870 850
h 13-17
h 17-21
h 21-25
1000 h 9-13 1400 600 110 110...250 870 850
h 13-17
h 17-21
h 21-25
1500 h 9-13 1400 600 110 110...250 1410 1340
h 13-17
h 17-21
h 21-25
SandSET-1000 sludge alarm as an accessory.

H3
mm
2070
2470
2870
3270
2070
2470
2870
3270
2610
3010
3410
3810

h
mm
900...1300
1300...1700
1700...2100
2100...2500
900...1300
1300...1700
1700...2100
2100...2500
900...1300
1300...1700
1700...2100
2100...2500

V
l
600

1000

1500

Weight
kg
91
106
122
137
151
175
199
223
183
207
231
255

EuroHEK Omega

Du Du1
Dy
Dy1
H1
H2
mm mm mm
mm
mm
mm
2000
1750 600 110 110...200 1280 1200
4000
2170 600 110 110...200 1730 1650
5000
2200 600 110 110...200 1820 1730
* For further information on EuroHUK 600: table on page 15.
SandSET-1000 sludge alarm as an accessory.

H3
mm
1650
2100
2250

h*

V
l
2000
4000
5000

Weight
kg
170
230
280

EuroHEK

L
mm
4000
4900

h*

V
l
6500
8000

Weight
kg
396
513

Look
at live
demo

EuroHEK 6500...8000 sand and


sludge traps

www.labkonet.com
LabkoNet service
LabkoNet server collects and logs data in the Internet and it is
applicable with different user names and passwords to meet
different needs. Among other things, the service provides reports
as printouts.

Du1 Du2
Dy
Dy1
H1
H2
H3
mm mm mm
mm mm mm mm
6500
600 1600 110 110...400 1410 1360 1860
8000
600 1600 110 110...400 1410 1360 1860
* For further information on PP-HUK 600: table on page 15.
SandSET-1000 sludge alarm as an accessory.

12

TEL. INT.

FAX INT.

E-MAIL

+358 20 1285 200

+358 20 1285 280

tanks@wavin-labko.fi

Labko Oil Separator Systems


www.wavin-labko.fi

Separators and tanks

13

Labko Oil Separator Systems

Alarm devices Data transfer LabkoNet

Labko Oil Separator Systems

Labko FRW Flow Regulation Wells EuroHEK sand and sludge traps
Legend
A
Du
Du1/Du2
Dy
Dy1/Dy2
H1/H2/H3/H4

Alarm devices and Data transfer


remote monitoring and LabkoNet

Labko FRW Flow Regulation Wells

Alarm systems monitoring


the functioning of the separators

Labcom 200 communication unit transfers


the alarm directly to the recipient

All the separators of Wavin-Labko can be equipped with alarm

Labcom 200 sends alarms and measurement data as GSM short

units that control the functioning of the separator. Most separators

messages either directly to the user's own mobile phone or via

include the alarm devices as a standard. The alarm can be

LabkoNet system. The LabkoNet system makes sure the information

transmitted directly to the user's house automation system or with

is delivered to the user, for the server also controls the functioning

the Labcom communication unit to a GSM phone. Furthermore,

of the communication unit.

the alarm can be transmitted via LabkoNet server to those who


find the information is essential. When the separators are remotely

LabkoNet system is an easy and reliable way


of transferring and controlling the alarm data

monitored, timely emptying is made possible, and thus the

Introducing and using the LabkoNet system is easy; no separate

environmental risks are minimized and costs are lowered.

software is needed. Only an Internet connection, Labcom 200

Nominal size
10/30...100/300

Nominal size
125/375...150/450

communication unit, gauges and alarm devices are needed. In


addition to the separator alarms, e.g. storage tank level gauging
can be connected with the LabkoNet.

= area of the yard (0.015 l/(s*m2))


= outer diameter
= inner diameter
= outer diameter of the ventilation pipe (accessory)
= outer diameter of the connection pipe
= height

L
h
V
Vo
Vs
Lkm

= length
= installation depth
= effective volume
= oil storage volume
= sludge storage volume
= number of the coalescent 3-D filters

Labko
FRW

Nominal Total flow


A
Du Du1 Dy Dy1 Dy2
H1 H2
H3
H4 h* Weight
flow into the of the
separator system
l/s
l/s
m2 mm mm mm mm mm mm mm mm mm
kg
FRW 10/30
10
30
2000 1780 800 110 200 160 750 700 900 1660
187
FRW 15/45
15
45
3000 1780 800 110 250 200 750 700 900 1660
188
FRW 20/60
20
60
4000 1780 800 110 250 200 750 700 900 1660
191
FRW 30/90
30
90
6000 1780 800 110 315 250 750 700 940 1660
211
FRW 40/120 40
120 8000 1780 800 110 315 315 650 600 850 1660
225
FRW 50/150 50
150 10000 1780 800 110 400 315 650 600 810 1660
232
FRW 65/195 65
195 13000 2170 800 110 400 315 950 900 1090 2100
321
FRW 80/240 80
240 16000 2170 800 110 500 315 950 900 1150 2100
391
FRW 100/300 100
300 20000 2250 800 110 500 315 950 900 1150 2200
407
FRW 125/375 125
375 25000 2200 800 110 500 400 475 500 475 1785
FRW 150/450 150
450 30000 2200 800 110
*** 400 475 500 475 1785
* For further information on EuroHUK 800: table below. *** According to the delivery Dy1 500 or Dy1 600.
EuroHUK 800
FRW 10/30 - 50/150 FRW 65/195 - 100/300 FRW 125/375 - 150/450
for FRW
h (mm)
h (mm)
h (mm)
9-13
1300-1700
1700-2100
2100-2500
13-17
1700-2100
2100-2500
2500-2900
17-21
2100-2500
2500-2900
2900-3400
21-25
2500-2900
2900-3400
3400-3900

For further information on LabkoNet and its possibilities,


visit www.labkonet.com
SandSET-1000 sludge alarm device
Indicates an alarm when the sludge storage space is full.
The timely desludging reduces unnecessary emptying and
guarantees the smooth operation of the oil separator.

EuroHEK 600...1500 sand and


sludge traps

GSM short messages


The alarm can be transmitted to the
user's GSM either directly with
Labcom 200 communication unit or
via LabkoNet server.

OilSET-1000 oil alarm


Indicates an alarm if the oil storage
space is full and it is time for
emptying. This prevents leakages
into the sewer system.

EuroHEK Omega sand and


sludge traps
E-mail
LabkoNet can also send
the alarm as an e-mail
message.
Labcom 200
communication unit
A data transfer unit
designed for transmitting
measurement and
alarm data.

SET-2000
oil alarm
Gives an alarm if
the oil storage space
is full or if the water
surface level rises
indicating the need
for filter maintenance.

LabkoNet server
Collects the alarms and adapts
their information to be sent further
either as a short message or as
an e-mail. The data is displayed
on user's own web page, too.

Dy

EuroHEK

Du Du1
Dy
Dy1 H1
H2
mm mm mm
mm mm mm
600 h 9-13 1000 600 110 110...250 870 850
h 13-17
h 17-21
h 21-25
1000 h 9-13 1400 600 110 110...250 870 850
h 13-17
h 17-21
h 21-25
1500 h 9-13 1400 600 110 110...250 1410 1340
h 13-17
h 17-21
h 21-25
SandSET-1000 sludge alarm as an accessory.

H3
mm
2070
2470
2870
3270
2070
2470
2870
3270
2610
3010
3410
3810

h
mm
900...1300
1300...1700
1700...2100
2100...2500
900...1300
1300...1700
1700...2100
2100...2500
900...1300
1300...1700
1700...2100
2100...2500

V
l
600

1000

1500

Weight
kg
91
106
122
137
151
175
199
223
183
207
231
255

EuroHEK Omega

Du Du1
Dy
Dy1
H1
H2
mm mm mm
mm
mm
mm
2000
1750 600 110 110...200 1280 1200
4000
2170 600 110 110...200 1730 1650
5000
2200 600 110 110...200 1820 1730
* For further information on EuroHUK 600: table on page 15.
SandSET-1000 sludge alarm as an accessory.

H3
mm
1650
2100
2250

h*

V
l
2000
4000
5000

Weight
kg
170
230
280

EuroHEK

L
mm
4000
4900

h*

V
l
6500
8000

Weight
kg
396
513

Look
at live
demo

EuroHEK 6500...8000 sand and


sludge traps

www.labkonet.com
LabkoNet service
LabkoNet server collects and logs data in the Internet and it is
applicable with different user names and passwords to meet
different needs. Among other things, the service provides reports
as printouts.

Du1 Du2
Dy
Dy1
H1
H2
H3
mm mm mm
mm mm mm mm
6500
600 1600 110 110...400 1410 1360 1860
8000
600 1600 110 110...400 1410 1360 1860
* For further information on PP-HUK 600: table on page 15.
SandSET-1000 sludge alarm as an accessory.

12

TEL. INT.

FAX INT.

E-MAIL

+358 20 1285 200

+358 20 1285 280

tanks@wavin-labko.fi

Labko Oil Separator Systems


www.wavin-labko.fi

Separators and tanks

13

Labko Oil Separator Systems

EuroHEK sand and sludge traps EuroPEK oil separators

EuroHEK 10000...50000 sand and


sludge traps

Dy

EuroHEK

Du1 Du2 Dy
Dy1
H1
H2
mm mm mm
mm mm mm
10000
600 1600 110 110...400 1410 1360
13000
600 2200 110 110...400 1930 1880
15000
600 2200 110 110...400 1930 1880
16000
600 2200 110 110...400 1930 1880
20000
600 2200 110 110...400 1930 1880
30000
600 3000 110 110...400 2650 2600
40000
600 3000 110 110...400 2650 2600
50000
600 3000 110 110...400 2650 2600
* For further information on EuroHUK 600: table on page 15.
SandSET-1000 sludge alarm as a standard.

H3
mm
1950
2550
2550
2550
2550
3360
3360
3360

L
mm
6100
4400
4900
5200
6400
5400
7000
8500

h*

V
l
10000
13000
15000
16000
20000
30000
40000
50000

Weight
kg
620
703
774
817
997
2000
2340

Labko Oil Separator Systems

EuroNOK FRW sampling shafts with a shut-off valve EuroHUK maintenance shafts PP-HUK 600 maintenance shafts

EuroNOK FRW sampling shafts


with a shut-off valve

Nominal size
10/30...100/300

EuroPEK Omega Filter


oil separators

Dy

EuroPEK Filter oil separators

14

EuroPEK Maximum Du1


Du2 Dy Dy1
H1
H2
H3
L
h*
flow
l/s
mm
mm mm mm mm mm mm
mm
NS3
3
800 1000 110 110 860 790 1380 1950
NS6
6
800 1000 110 160 860 790 1380 2200
NS10
10 800/600 1000 110 160 860 790 1380 4100
NS15
15
800 1400 110 200 1300 1230 1750 2800
NS20
20
800 1600 110 200 1410 1340 1950 3000
NS30
30 800/600 1600 110 250 1410 1340 1950 4000
NS40
40
800 2200 110 315 1940 1870 2550 3600
NS50
50 800/600 2200 110 315 1940 1870 2550 4600
NS65
65 800/600 3000 110 315 2740 2670 3360 5500
NS80
80 800/600 3000 110 315 2740 2670 3360 7300
NS100
100 800/600 3000 110 315 2740 2670 3360 7500
NS125
125 800/600 3000 110 400 2740 2670 3360 8800
NS150
150 800/600 3000 110 400 2740 2670 3360 10000
* For further information on EuroHUK 600 and EuroHUK 800: table on page 15.
OilSET-1000 oil alarm as a standard.

EuroPEK
Omega Filter

Maximum Du Du1
Dy Dy1
H1
H2
flow
l/s
mm mm mm mm
mm
mm
NS3/L
3
1780 600 110 110 1300 1220
NS6/S
6
1780 600 110 160 1300 1220
NS10
10
1780 600 110 160 1300 1220
NS15
15
2170 600 110 200 1730 1650
* For further information on EuroHUK 600: table on page 15.
SET-2000 oil alarm as a standard.

H3

h*

mm
1650
1650
1650
2100

EuroPEK Maximum Du1 Du2 Dy Dy1


H1 H2
H3
L h*
Filter
flow
l/s
mm
mm mm mm mm mm mm
mm
NS20
20
600 1600 110 250 1410 1340 1950 3800
NS30
30
600 1600 110 250 1410 1340 1950 3800
NS40
40
600 1600 110 315 1410 1340 1950 3800
NS50
50
600 1600 110 315 1360 1290 1950 5300
NS65
65
600 2200 110 315 1940 1870 2550 4100
NS80
80
600 2200 110 315 1940 1870 2550 5900
NS100
100
600 2200 110 400 1940 1870 2550 8700
NS125
125
600 2200 110 400 1940 1870 2550 11400
NS150
150
600 2200 110 400 1940 1870 2550 13000
* For further information on EuroHUK 600 and PP-HUK 600: table on page 15.
SET-2000 oil alarm as a standard.

TEL. INT.

FAX INT.

E-MAIL

+358 20 1285 200

+358 20 1285 280

tanks@wavin-labko.fi

Vo

Weight

l
860
1000
1950
2940
3930
5500
10000
13500
32200
41000
42000
52500

l
250
290
550
610
770
900
1000
1500
1500
2000
2000
2200

kg
180
235
355
450
600
810
1100
1705
2500
2900

Vo

l
2100
2100
2100
4200

V
l
6000
6000
6000
8700
13000
19200
28000
37100
42500

EuroNOK sampling shafts


with a shut-off valve

Vs Weight

l
l
280
950
280
650
280 separate
380 separate

kg
170
170
170
240

EuroHUK 600 and 800


maintenance shafts

Vo Lkm Weight
l pcs
640
1
640
2
640
2
1000
3
900
3
1400
4
2100
4
3070
4
3520
4

kg
500
550
560
750
1350
1750
2400
3000
3450

Du Du1
Dy Dy1
Dy2
H1
H2
H3
H4
mm mm
110
mm
mm mm mm
mm mm
10/30
1300 600
110
200
160 440 410
950 540
15/45
1300 600
110
250
200 440 410
950 540
20/60
1300 600
110
250
200 440 410
950 540
30/90
1300 600
110
315
250 440 410
950 540
40/120**
1400 600
110
315
315 440 410 1390 540
50/150**
1400 600
110
400
315 440 410 1390 540
65/195**
1400 600
110
400
315 440 410 1390 540
80/240**
1400 800
110
500
315 440 410 1390 540
100/300**
1400 800
110
500
315 440 410 1390 540
125/375**
1400 800
110
500
400 440 410 1390 540
150/450**
1400 800
110
***
400 440 410 1390 540
* For further information on EuroHUK 600 and EuroHUK 800: table on page 15.
** minimum installation depth h=1300 mm.
*** according to the delivery Dy1 500 or Dy1 600.

h*

Weight
kg

Nominal size
125/375...150/450

PP-HUK 600 maintenance shafts

EuroPEK oil separators

EuroNOK FRW

EuroNOK

Du Du1
Dy
Dy1
H1
H2
H3
mm mm
mm
mm mm
mm mm
DN110
1300 600
110
110 440
410 950
DN160
1300 600
110
160 440
410 950
DN200
1300 600
110
200 440
410 950
DN250
1300 600
110
250 440
410 950
DN315
1300 600
110
315 440
410 950
DN400**
1560 600
110
400 440
410 1310
* For further information on EuroHUK 600: table on page 15.
** minimum installation depth h=1300 mm.

h*

Weight
kg
80
84
101
124
155

EuroHUK 600

Du1 Du2
h
mm mm
mm
9-13
600 1000
900...1300
13-17
600 1000
1300...1700
17-21
600 1000
1700...2100
21-25
600 1000
2100...2500
A suitable cover and frame set is the floating cover and frame set 600.

Weight
kg
22
38
56
80

EuroHUK 800

Du1 Du2
h
mm mm
mm
9-13
800 1000
900...1300
13-17
800 1000
1300...1700
17-21
800 1000
1700...2100
21-25
800 1000
2100...2500
A suitable cover and frame set is the floating cover and frame set 800.

Weight
kg
25
42
60
84

PP-HUK 600

Weight
kg
16
20
25
31

Du Du1
L
h*
mm mm
mm
mm
9-13
670 602 1000
900...1300
13-17
670 602 1400 1300...1700
17-21
670 602 1800 1700...2100
21-25
670 602 2200 2100...2500
* connection depth of the separator from the ground surface to the water flow of the inlet.
A suitable cover and frame set is the floating cover and frame set 600.

Labko Oil Separator Systems


www.wavin-labko.fi

Separators and tanks

15

Labko Oil Separator Systems

EuroHEK sand and sludge traps EuroPEK oil separators

EuroHEK 10000...50000 sand and


sludge traps

Dy

EuroHEK

Du1 Du2 Dy
Dy1
H1
H2
mm mm mm
mm mm mm
10000
600 1600 110 110...400 1410 1360
13000
600 2200 110 110...400 1930 1880
15000
600 2200 110 110...400 1930 1880
16000
600 2200 110 110...400 1930 1880
20000
600 2200 110 110...400 1930 1880
30000
600 3000 110 110...400 2650 2600
40000
600 3000 110 110...400 2650 2600
50000
600 3000 110 110...400 2650 2600
* For further information on EuroHUK 600: table on page 15.
SandSET-1000 sludge alarm as a standard.

H3
mm
1950
2550
2550
2550
2550
3360
3360
3360

L
mm
6100
4400
4900
5200
6400
5400
7000
8500

h*

V
l
10000
13000
15000
16000
20000
30000
40000
50000

Weight
kg
620
703
774
817
997
2000
2340

Labko Oil Separator Systems

EuroNOK FRW sampling shafts with a shut-off valve EuroHUK maintenance shafts PP-HUK 600 maintenance shafts

EuroNOK FRW sampling shafts


with a shut-off valve

Nominal size
10/30...100/300

EuroPEK Omega Filter


oil separators

Dy

EuroPEK Filter oil separators

14

EuroPEK Maximum Du1


Du2 Dy Dy1
H1
H2
H3
L
h*
flow
l/s
mm
mm mm mm mm mm mm
mm
NS3
3
800 1000 110 110 860 790 1380 1950
NS6
6
800 1000 110 160 860 790 1380 2200
NS10
10 800/600 1000 110 160 860 790 1380 4100
NS15
15
800 1400 110 200 1300 1230 1750 2800
NS20
20
800 1600 110 200 1410 1340 1950 3000
NS30
30 800/600 1600 110 250 1410 1340 1950 4000
NS40
40
800 2200 110 315 1940 1870 2550 3600
NS50
50 800/600 2200 110 315 1940 1870 2550 4600
NS65
65 800/600 3000 110 315 2740 2670 3360 5500
NS80
80 800/600 3000 110 315 2740 2670 3360 7300
NS100
100 800/600 3000 110 315 2740 2670 3360 7500
NS125
125 800/600 3000 110 400 2740 2670 3360 8800
NS150
150 800/600 3000 110 400 2740 2670 3360 10000
* For further information on EuroHUK 600 and EuroHUK 800: table on page 15.
OilSET-1000 oil alarm as a standard.

EuroPEK
Omega Filter

Maximum Du Du1
Dy Dy1
H1
H2
flow
l/s
mm mm mm mm
mm
mm
NS3/L
3
1780 600 110 110 1300 1220
NS6/S
6
1780 600 110 160 1300 1220
NS10
10
1780 600 110 160 1300 1220
NS15
15
2170 600 110 200 1730 1650
* For further information on EuroHUK 600: table on page 15.
SET-2000 oil alarm as a standard.

H3

h*

mm
1650
1650
1650
2100

EuroPEK Maximum Du1 Du2 Dy Dy1


H1 H2
H3
L h*
Filter
flow
l/s
mm
mm mm mm mm mm mm
mm
NS20
20
600 1600 110 250 1410 1340 1950 3800
NS30
30
600 1600 110 250 1410 1340 1950 3800
NS40
40
600 1600 110 315 1410 1340 1950 3800
NS50
50
600 1600 110 315 1360 1290 1950 5300
NS65
65
600 2200 110 315 1940 1870 2550 4100
NS80
80
600 2200 110 315 1940 1870 2550 5900
NS100
100
600 2200 110 400 1940 1870 2550 8700
NS125
125
600 2200 110 400 1940 1870 2550 11400
NS150
150
600 2200 110 400 1940 1870 2550 13000
* For further information on EuroHUK 600 and PP-HUK 600: table on page 15.
SET-2000 oil alarm as a standard.

TEL. INT.

FAX INT.

E-MAIL

+358 20 1285 200

+358 20 1285 280

tanks@wavin-labko.fi

Vo

Weight

l
860
1000
1950
2940
3930
5500
10000
13500
32200
41000
42000
52500

l
250
290
550
610
770
900
1000
1500
1500
2000
2000
2200

kg
180
235
355
450
600
810
1100
1705
2500
2900

Vo

l
2100
2100
2100
4200

V
l
6000
6000
6000
8700
13000
19200
28000
37100
42500

EuroNOK sampling shafts


with a shut-off valve

Vs Weight

l
l
280
950
280
650
280 separate
380 separate

kg
170
170
170
240

EuroHUK 600 and 800


maintenance shafts

Vo Lkm Weight
l pcs
640
1
640
2
640
2
1000
3
900
3
1400
4
2100
4
3070
4
3520
4

kg
500
550
560
750
1350
1750
2400
3000
3450

Du Du1
Dy Dy1
Dy2
H1
H2
H3
H4
mm mm
110
mm
mm mm mm
mm mm
10/30
1300 600
110
200
160 440 410
950 540
15/45
1300 600
110
250
200 440 410
950 540
20/60
1300 600
110
250
200 440 410
950 540
30/90
1300 600
110
315
250 440 410
950 540
40/120**
1400 600
110
315
315 440 410 1390 540
50/150**
1400 600
110
400
315 440 410 1390 540
65/195**
1400 600
110
400
315 440 410 1390 540
80/240**
1400 800
110
500
315 440 410 1390 540
100/300**
1400 800
110
500
315 440 410 1390 540
125/375**
1400 800
110
500
400 440 410 1390 540
150/450**
1400 800
110
***
400 440 410 1390 540
* For further information on EuroHUK 600 and EuroHUK 800: table on page 15.
** minimum installation depth h=1300 mm.
*** according to the delivery Dy1 500 or Dy1 600.

h*

Weight
kg

Nominal size
125/375...150/450

PP-HUK 600 maintenance shafts

EuroPEK oil separators

EuroNOK FRW

EuroNOK

Du Du1
Dy
Dy1
H1
H2
H3
mm mm
mm
mm mm
mm mm
DN110
1300 600
110
110 440
410 950
DN160
1300 600
110
160 440
410 950
DN200
1300 600
110
200 440
410 950
DN250
1300 600
110
250 440
410 950
DN315
1300 600
110
315 440
410 950
DN400**
1560 600
110
400 440
410 1310
* For further information on EuroHUK 600: table on page 15.
** minimum installation depth h=1300 mm.

h*

Weight
kg
80
84
101
124
155

EuroHUK 600

Du1 Du2
h
mm mm
mm
9-13
600 1000
900...1300
13-17
600 1000
1300...1700
17-21
600 1000
1700...2100
21-25
600 1000
2100...2500
A suitable cover and frame set is the floating cover and frame set 600.

Weight
kg
22
38
56
80

EuroHUK 800

Du1 Du2
h
mm mm
mm
9-13
800 1000
900...1300
13-17
800 1000
1300...1700
17-21
800 1000
1700...2100
21-25
800 1000
2100...2500
A suitable cover and frame set is the floating cover and frame set 800.

Weight
kg
25
42
60
84

PP-HUK 600

Weight
kg
16
20
25
31

Du Du1
L
h*
mm mm
mm
mm
9-13
670 602 1000
900...1300
13-17
670 602 1400 1300...1700
17-21
670 602 1800 1700...2100
21-25
670 602 2200 2100...2500
* connection depth of the separator from the ground surface to the water flow of the inlet.
A suitable cover and frame set is the floating cover and frame set 600.

Labko Oil Separator Systems


www.wavin-labko.fi

Separators and tanks

15

January 2006

Labko Oil Separator Systems

Labko Oil Separator Systems

Wavin-Labko in brief
Wavin-Labko Ltd is a Finnish company with over 40 years'
experience in developing, manufacturing and marketing of
measurement devices and various plastic products. In the field
of measurement devices we are specialized in level instruments
and alarm devices, automation and identification, and in webbased solutions of data transfer. In the field of plastic products
we have focused our know-how on wastewater and stormwater
treatment by using various separator systems. These systems
cover the separator solutions in business and services
construction, the wastewater treatment in rural area settlements,
as well as the wastewater treatment of private houses and
summer cottages.
Wavin-Labko Ltd is a part of international Wavin Group, which
is the leader in the European market for plastic pipe systems.
Wavin Group has a presence in 27 European countries.

Wavin-Labko Ltd reserves the rights to alterations without prior notice. Due to policy of continuous
improvement in R&D, technical specifications may change. Installation shall always be made as
documented in manufacturer's instructions.

Pictorino Oy/Kirjapaino Hermes 1/2006 2.000

www.wavin-labko.fi
Wavin-Labko Ltd
Labkotie 1
FI-36240 Kangasala
FINLAND
Tel. int. +358 20 1285 200
Fax int. +358 20 1285 280
E-mail tanks@wavin-labko.fi

FOR STORMWATER TREATMENT


IN INDUSTRIAL, STORAGE AND
TRAFFIC AREAS

Reliable solutions

Separators and tanks