Potter, Nebraska
Location/Elevation
Environment
Grassland
-10 to 35
20
Availability Required
Days of Storage
4 - Fiberglass Tank
Source
17
Water Required
Installation
The PV modules are mounted on a passively controlled tracking structure and tilted at
55 for maximum winter performance. Sunlight resistant USE wire is used to
interconnect the modules. A switch box was attached to the pole and the linear current
booster was installed in the box. The pump was attached to 2-inch plastic pipe and
installed in the 3-inch bore hole. A float switch was installed near the top of the
holding tank and the control cables are protected from damage by conduit. The system
was grounded to the well casing using a short length of No. 6 stranded copper wire.
Controller Specifications
This linear current booster was used between the pump and the PV array to provide a
better match between source and load.