Considerations
Daniel Dettmers (djdettme@wisc.edu)
Industrial Refrigeration Consortium
University of Wisconsin
www.irc.wisc.edu
(866) 635-4721
What is a Refrigerant?
Refrigerant
- the vital working fluid in refrigeration,
air-conditioning, and heat pumping
systems.
- absorbs heat from one area, such as an
air-conditioned space, and rejects it
into another, such as outdoors, usually
through evaporation and condensation
process, respectively.
- ASHRAE Fundamentals Chpt. 16
Dettmers 2/8/07
impacts
Likelihood of future availability
Refrigerant properties
Toxicity
& flammability
Thermodynamic & transport
Other
Economics
Operating
efficiency
Capital costs (refrigerant & equipment)
Staff capabilities
Dettmers 2/8/07
Composition of Fluorocarbons
CFC-12
Cl
Cl
HCFC-22
HFC-32
Dettmers 2/8/07
Cl
C
H
C
C
F
C
hloro
luoro
arbons
H
C
F
C
ydro
hloro
luoro
arbons
H
F
C
ydro
luoro
arbons
100%
65%
All
All other
other
HCFCs
HCFCs
Production
Production
Freeze
Freeze
35% HCFC-141b
HCFC-141b
Production
Production
Ban
Ban
HCFC-22
HCFC-22
HCFC-142b
HCFC-142b
Production
Production
Ban
Ban
All
All other
other
HCFCs
HCFCs
Ban
Ban in
in New
New
Equipment
Equipment
All
All other
other
HCFCs
HCFCs
Production
Production
Ban
Ban
10%
0.5%
2003
Dettmers 2/8/07
2010
2015
2020
2030
1.0
ODP
Same as
CFC-11
or CO2
GWP
Global Warming Potential
Contribution
of substance to the
atmospheres heat retention,
relative to CO2 or CFC-11
0.0
Dettmers 2/8/07
None
HCFCs
HFCs
1.2
11
12
113
0.8
114
0.6
115
0.4
0.2
0 0
0 0
123
0.2
0.4
0.8
0.2
CFCs
0.15
0.1
141b
142b
HCFCs
220
0.05
HFCs
124
0
134a
152a
32
ODP and GWP are relative to CFC-11
Source: World Meteorological Organization
Dettmers 2/8/07
0.6
125 0 143a
Chemical
Formula
CFC-11
CFC-12
CFC-113
CFC-114
CFC-115
CCl3F
CCL2F2
CCl2FCClF2
CClFCClF2
CClF2CF2
45
100
85
300
1700
1.000
1.000
1.000
1.000
0.940
0.440
4680
10720
10720
6030
9880
7250
A1
A1
A1
A1
A1
HCFC-22
HCFC-123
HCFC-124
HCFC-141b
HCFC-142b
CHClF2
CF3CHCl2
CHClFCF3
CH3CCl2F
CH3CClF2
12
1.3
5.8
9.3
17.9
0.050
0.050
1780
1780
A1
B1
A1
HFC-32
HFC-125
HFC-134a
HFC-143a
HFC-152a
CH2F2
CHF2CF3
CF3CH2F
CH3CF3
CH3CHF2
4.9
29
14
52
1.4
0.000
0.000
0.000
0.000
0.000
0.000
R-717
R-718
HC-290
NH3
H 2O
C3H8
Dettmers 2/8/07
Lifetime
Years
ODP
(R11)
GWP
(CO2)
Safety
Classification
0.020
0.020
0.120
0.070
0.000
0.000
0.000
0.000
76
599
713
2270
A2
543
3450
1320
1320
4400
122
A2
A1
A1
A2
A2
00
0
0
B2
A1
A3
Increasing
Flammability
Dettmers 2/8/07
Increasing
Toxicity
A3
Propane, Butane
B3
A2
B2
R-142b, R-152a
Ammonia
A1
B1
R-123, SO2
Lower
Toxicity
Higher
Toxicity
COP
kW/ton
HP/ton
CFC-11
4.895
0.718
0.963
CFC-12
4.497
0.782
1.048
HCFC-123
4.717
0.745
0.999
HFC-134a
4.376
0.803
1.077
HCFC-22
4.444
0.791
1.061
R-717
4.643
0.757
1.015
R-290
4.293
0.819
1.098
R-410A
4.137
0.850
1.140
R-407C
4.248
0.828
1.110
R-404A
3.853
0.913
1.224
Dettmers 2/8/07
Mixtures
400
Others
600
Mixtures
400
Others
600
Refrigerant Mixtures
series
Tend to average properties
Segregate (Easy to separate)
Offer greatest flexibility
Azeotropes
R-500
series
Behave like pure fluid
Higher or lower B.P. than components
Non segregating (Difficult to separate)
Some
SomeZeotropes
Zeotropesare
arevery
veryclose
closeto
toAzeotropes
Azeotropes
Dettmers 2/8/07
Evaporation Characteristics-Blends
Boiling Point
Dew
GLIDE
Bubble
Boiling Point
FLUID A
Low-Boiler
Dettmers 2/8/07
Point
RANGE
Point
BLEND
Non-Azeotropic
(400 Series)
FLUID B
High-Boiler
Pressure [psia]
R-407c
Dew Point
200
Bubble Point
150
T~11F
100
50
0
-25
25
50
75
Temperature [F]
Dettmers 2/8/07
100
125
Phaseout Refrigerants
Refrigerant
Application
Alternative
CFC 11
HCFC 123
CFC 12
Refrigerators, MVAC,
Commercial Refrigeration Units
HFC 134a
CFC 502
R-404A (HFC)
R-507A (HFC)
CFC 13/R-503
HCFC 22
Everywhere
R-717, R-410A
HCFC 123
R-245ca*
Large Glide
Dettmers 2/8/07
Option 1
125 / 143a
50% / 50%
R-507A
AZ-50
Allied-Signal
0.1F
359 psig
up 10%
up 0-5%
Option 2
125 / 143a / 134a
44% / 52% / 4%
R-404A
HP62 / Forane-404A
DuPont / Elf Atochem
1.6F
354 psig
same
up 5%
Trade Name
ASHRAE
Number
Several
134A
100%
407C
Large 23%
Glide 25%
52%
KLEA 407C,
AC9000
AZ-20, Puron,
Suva 9100
HFC-32
HFC-125
410A
50%
50%
AC9100
410B
45%
55%
Nu-22,
ISCEON 59
417
Dettmers 2/8/07
46.6%
HFC-134a
50%
R-600
3.4%
Option 2
Option 3
32 / 125
32 / 125 / 134a
50% / 50% 23% / 25% / 52%
R-410A
R-407C
AZ-20/Puron AC9000/KLEA66
Allied-Signal
DuPont/ICI
0.2F
8-10F
479 psig
310 psig
up 40-50%
up 10%
down 5-13%
down 5%
R-417a (Nu-22)
125/134a/600
(46.6%/50%/3.4%)
Drop-in, uses butane for MO miscibility
Reported oil return problems, reduced capacity @ low
temp
Copeland voids warranty if R-417a is used
Many other refrigerants like it (R-422A, R-427A)
Dettmers 2/8/07
Alternatives to R-13/R-503
NH3-CO2 Cascade
Finding
Dettmers 2/8/07
High
Pressure
Receiver
Low
Temperature
Evaporator(s)
Low
Temperature
Recirculator
CO2
Compressor(s)
Dettmers 2/8/07
Cascade
Heat Exchanger
Ammonia
Compressor(s)
No direct environmental
impacts
GWP, ODP
Dettmers 2/8/07
Efficiency [hp/ton]
3.8
3.6
3.4
3.2
CO2/NH 3 Cascade
2.8
-70
-65
-60
-55
-50
-45
2.
3.
Check cost
Dettmers 2/8/07
4.
800-296-1996
www.epa.gov/air/ozonedep.html