Sie sind auf Seite 1von 1

Min.

6 ACH
2

3 4 5

Constant 6 ACH

LEGEND
1.) Heat recovery wheel (optional)
2.) Mixing section
3.) Cooling/dehumidifying coil
4.) Heating coil
5.) MERV 13 filter
6.) VAV terminal with reheat

PATIENT ROOM
12% cooling reduction before reheat

Space Sensible Ducted Airflow


Sensible
Space Reheat
Cooling Load
Rate
Cooling Delivery Requirement
-1
(BTUH/FT 2)
(ACH )
(BTUH/FT 2)
(BTUH/FT 2)

25 (100%)

6.9

25

20 (80%)

6.0

22

15 (60%)

6.0

22

10 (40%)

6.0

22

12

5 (20%)

6.0

22

17

Figure 1: Patient Room Cooling with All-air System


2 ACH (100% exhaust)
2 ACH (100% OA)
6

3 4 5

LEGEND
1.) Heat recovery wheel (optional)
3.) Cooling/dehumidifying coil
4.) Heating coil
5.) MERV 13 filter
6.) Active chilled beam
Space Sensible
Cooling Load

Ducted Airflow
Rate

25 (100%)

(BTUH/FT 2)

-1

Constant 6 ACH
PATIENT ROOM

71% cooling reduction before reheat

Airside Sensible
Water Side
Cooling
Sensible Cooling

Total Sensible
Cooling

Space Reheat
Requirement

(BTUH/FT 2)

(BTUH/FT 2)

(BTUH/FT 2)

2.0

7.2

17.8

25

20 (80%)

2.0

7.2

12.8

20

15 (60%)

2.0

7.2

7.8

15

10 (40%)

2.0

7.2

2.8

10

5 (20%)

2.0

7.2

22

5.2

(ACH )

(BTUH/FT 2)

Figure 2: Patient Room Cooling with Active Chilled Beam System