Sie sind auf Seite 1von 4

16832 Federal Register / Vol. 72, No.

65 / Thursday, April 5, 2007 / Notices

Agency will summarize the comments All submissions, including copyrighted required to satisfy 10 CFR 50.48(a).
submitted in response to this notice, material, are available for inspection Specific fire protection features deemed
and will include this summary in its and copying at the OSHA Docket Office. necessary to ensure this capability are
request to OMB. Information on using the http:// delineated in Appendix R to 10 CFR
Type of Review: Extension of a www.regulations.gov Web site to submit Part 50. Section III of Appendix R
currently approved collection. comments and access the docket is contains 15 subsections, lettered A
Title: Asbestos in General Industry (29 available at the website’s ‘‘User Tips’’ through O, each of which specifies the
CFR 1910.1001). link. Contact the OSHA Docket Office requirements for a particular aspect of
OMB Number: 1218–0133. for information about materials not fire protection features at nuclear power
Affected Public: Business or other for- available through the website, and for plants. The Browns Ferry units are
profit. assistance in using the Internet to locate required to comply with the provisions
Number of Respondents: 243. docket submissions. of Sections III.G and III.J and III.O.
Frequency: Annually; semi-annually. Section III.G.2 of Appendix R to 10 CFR
Total Responses: 65,048. V. Authority and Signature Part 50 requires that where cables or
Average Time per Response: Varies Edwin G. Foulke, Jr., Assistant equipment of redundant trains of
from 5 minutes to maintain records to Secretary of Labor for Occupational systems necessary to achieve and
1.5 hours for employees to receive Safety and Health, directed the maintain hot shutdown conditions are
training or medical evaluations. preparation of this notice. The authority located within the same fire area outside
Estimated Total for this notice is the Paperwork of primary containment, one of the
Burden Hours: 23,849. Reduction Act of 1995 (44 U.S.C. 3506 following means of ensuring that one of
Estimated Cost (Operation and et seq.) and Secretary of Labor’s Order the redundant trains is free of fire
Maintenance): $1,625,143. No. 5–2002 (67 FR 65008). damage shall be provided:
IV. Public Participation—Submission of a. Separation of cables and equipment
Signed at Washington, DC on April 2,
Comments on This Notice and Internet 2007. and associated non-safety circuits of
Access to Comments and Submissions redundant trains by a fire barrier having
Edwin G. Foulke, Jr.,
a 3-hour rating. Structural steel forming
You may submit comments in Assistant Secretary of Labor. a part of or supporting such fire barriers
response to this document as follows: [FR Doc. E7–6367 Filed 4–4–07; 8:45 am] shall be protected to provide fire
(1) Electronically at http:// BILLING CODE 4510–26–P resistance equivalent to that required of
www.regulations.gov, which is the the barrier;
Federal eRulemaking Portal; (2) by b. Separation of cables and equipment
facsimile; or (3) by hard copy. All NUCLEAR REGULATORY and associated non-safety circuits of
comments, attachments, and other COMMISSION redundant trains by a horizontal
material must identify the Agency name distance of more than 20 feet with no
and the OSHA docket number for this Tennessee Valley Authority Browns intervening combustible or fire hazards.
ICR (OSHA Docket No. OSHA–2007– Ferry Nuclear Plant, Units 1, 2, and 3 In addition, fire detectors and an
0026). You may supplement electronic Docket Nos. 50–259, 50–260, and 50– automatic fire suppression system shall
submissions by uploading document 296 Exemption be installed in the fire area; or
files electronically. If you wish to mail c. Enclosure of cable and equipment
additional materials in reference to an 1.0 Background and associated non-safety circuits of one
electronic or facsimile submission, you The Tennessee Valley Authority redundant train in a fire barrier having
must submit them to the OSHA Docket (TVA, the licensee) is the holder of a 1-hour rating. In addition, fire
Office (see the section of this notice Facility Operating Licenses DPR–33, detectors and an automatic fire
titled ‘‘ADDRESSES’’). The additional DPR–52, and DPR–68, which authorize suppression system shall be installed in
materials must clearly identify your operation of the Browns Ferry Nuclear the fire area;
electronic comments by your full name, Plant, Units 1, 2 and 3. The license By letter dated October 26, 2006, as
date, and docket number so the Agency provides, among other things, that the supplemented by a letter dated January
can attach them to your comments. facility is subject to all rules, 11, 2007, the licensee requested a
Because of security procedures, the regulations, and orders of the Nuclear revision to an exemption from 10 CFR
use of regular mail may cause a Regulatory Commission (NRC, the 50 Appendix R, III.G.2. For the items
significant delay in the receipt of Commission) now or hereafter in effect. specified in this exemption request, the
comments. For information about The facility consists of three boiling- licensee has selected III.G.2.b as the
security procedures concerning the water reactors located in Limestone option for compliance with Appendix R,
delivery of materials by hand, express County in Alabama. Section II.G.2. The exemption involves
delivery, messenger, or courier service, allowing intervening combustible
please contact the OSHA Docket Office 2.0 Request/Action
materials, for example, fire hazards
at (202) 693–2350 (TTY (877) 889– On November 19, 1980, the (480V reactor building (RB) vent boards
5627). Commission published a new Appendix 1B, 2B, and 3B; small panels in Units 1,
Comments and submissions are R to Title 10 to the Code of Federal 2, and 3, and 1-hour rated Thermo-Lag
posted without change at http:// Regulations (10 CFR) Part 50 regarding 330–1 electrical raceway fire barrier
www.regulations.gov. Therefore, OSHA fire protection features of nuclear power (ERFB) material), in the specified 20 feet
cautions commenters about submitting plants (45 FR 76602). Section 50.48(a) of separation protected with fire
personal information such as social requires that each operating nuclear detection and automatic water-based
security numbers and date of birth. power plant have a fire protection plan fire suppression between redundant
jlentini on PROD1PC65 with NOTICES

Although all submissions are listed in which satisfies General Design Criterion safe-shutdown trains.
the http://www.regulations.gov index, (GDC) 3, ‘‘Fire protection,’’ in Appendix The redundant trains are separated by
some information (e.g., copyrighted A, ‘‘General Design Criteria for Nuclear a horizontal distance of 20 feet with
material) is not publicly available to Power Plants,’’ to 10 CFR Part 50. The intervening combustibles in certain fire
read or download through this website. approved fire protection plan is the plan zones in the Units 1, 2, and 3 RBs.

VerDate Aug<31>2005 17:37 Apr 04, 2007 Jkt 211001 PO 00000 Frm 00071 Fmt 4703 Sfmt 4703 E:\FR\FM\05APN1.SGM 05APN1
Federal Register / Vol. 72, No. 65 / Thursday, April 5, 2007 / Notices 16833

Exemptions are requested from the combustibles. The following is a list of present within a 20-foot spatial
requirements to provide 20 feet of those fire zone locations and separation zone for redundant safe-
separation, free of intervening intervening combustibles/fire hazards shutdown trains:

• Unit 1 Fire Zone 1–1/1–2 ................. 565′ Elevation ....... 480V (RB) Vent Board 1B.
• Unit 1 Fire Zone 1–1/1–2 ................. 565′ Elevation ....... 1-LPLN–925–338 & 338A Process Radiation Monitor and Relay Panel.
• Unit 1 Fire Zone 1–1/1–2 ................. 565′ Elevation ....... Thermo-Lag on Conduits ES2625-II and ES2673–II.
• Unit 1 Fire Zone 1–3/1–4 ................. 593′ Elevation ....... Thermo-Lag on Conduits PP459-IA, PP460-IA, and ES125-I.
• Unit 1 Fire Zone 1–3/1–4 ................. 593′ Elevation ....... 1-LPLN–925–0281A Fire Detection Panel.
• Unit 1 Fire Zone 1–3/1–4 ................. 593′ Elevation ....... 1-LPLN–925–0315 Heat Detection Panel.
• Unit 2 Fire Zone 2–1/2–4 ................. 565′ Elevation ....... 480V (RB) Vent Board 2B.
• Unit 2 Fire Zone 2–1/2–2 ................. 565′ Elevation ....... 2-PWR–276–0007 480V Power Distribution Panel.
• Unit 2 Fire Zone 2–3/2–4 ................. 593′ Elevation ....... 25–281A Fire Detection Panel.
• Unit 2 Fire Zone 2–3/2–4 ................. 593′ Elevation ....... 25–316 Cable Tray Fire Detection Control.
• Unit 3 Fire Zone 3–1/3–2 ................. 565′ Elevation ....... 480 V (RB) Vent Board 3B.
• Unit 3 Fire Zone 3–1/3–2 ................. 565′ Elevation ....... 1-LPLN–925–336 & 336A Raw Cooling Water Effluent Radiation Monitor and
Relay Panel.
• Unit 3 Fire Zone 3–1/3–2 ................. 565′ Elevation ....... 1-LPLN–925–337 & 337A Process Radiation Monitor and Relay Panel.

To justify inclusion of intervening of the cabinet. The fire started from non- provided a revised fire model to address
combustibles in RB fire areas, the qualified Institute of Electronics and the NRC concerns.
licensee performed fire modeling to Electrical Engineering Standard (IEEE)– In the revised fire modeling analysis,
assess potential hazards using 383 cables within the cabinet and was the HRR for multiple-cable bundles was
methodology from NUREG–1805, ‘‘Fire assumed to be limited to one cable assumed due to multiple conduit entries
Dynamics Tools (FDTs) Quantitative bundle. The heat release rate (HRR) 2 in each section of the low voltage
Fire Hazard Analysis Methods for the used to calculate heat fluxes to the vertical cabinet. The HRR associated
U.S. Nuclear Regulatory Commission targets (cable trays located at radial with multiple-cable bundles for a
Fire Protection Inspection Program,’’ distance of approximately 7 feet [17 feet vertical cabinet with non-qualified
December 2004. Enclosure 2 of the above floor], conduits located at the IEEE–383 cables was based on Table E–
exemption request discussed the fire- bottom of the duct approximately 9 feet 5 in Appendix E of NUREG/CR–6850.
risk analysis for the Units 1, 2, and 3 above the top of the cabinet, and The critical incident radiative heat flux 3
RBs. Thermo-Lag 330–1 wrapped conduit for ignition is calculated from the
TVA provided an assessment utilizing located approximately 7 feet from the cabinet fire scenario to see if ignition of
fire modeling to evaluate the fire edge of the cabinet) was based on Table the redundant cables and adjacent
hazards due to intervening combustibles E–4 in Appendix E of NUREG/CR–6850 surrounding targets (intervening
between redundant cable trains in the (EPRI [Electric Power Research Institute] combustibles) is possible. The critical
RBs. In this fire modeling analysis, the TR–1019181), ‘‘EPRI/NRC–RES Fire incident radiative heat flux from the
licensee modeled fire in Unit 1 RB PRA [Probabilistic Risk Analysis] maximum fire HRR, that is, 816
Elevation 565′ in the 20-foot zone of Methodology for Nuclear Power Kilowatt (kW), was estimated at 4.28
separation between fire zones 1–1 and kW/m2.
Facilities,’’ November 2005.
1–2.1 Specifically, 480V (RB) vent The licensee determined that the
boards 1B, 2B, and 3B are located In order to evaluate the licensee’s maximum radiant heat flux is not
within the 20-foot zone of separation. conclusion that a cabinet fire would not sufficient to ignite non-qualified IEEE–
The fire model uses a series of empirical result in fire damage adversely affecting 383 cable or Thermo-Lag 330–1
correlations from NUREG–1805 to show the safe-shutdown capability in Units 1, wrapped on conduits or safety-related
the largest fire from a vertical low 2, and 3 RB located within the 20-foot cables or equipment of redundant trains
voltage electrical cabinet should not separation area, the NRC staff identified of systems for safe-shutdown, nor to
produce enough radiant energy to ignite areas in which additional information adversely impact any surrounding
the closest redundant cable trays or was necessary to complete its equipment. The targets require a large
intervening combustibles within the evaluation. The NRC staff had amount of radiative heat to ignite. The
redundant trains. discussions with the licensee on measured critical heat flux level for
The analysis is used to determine the November 20, 2006, concerning use of representative non-qualified IEEE–383
extent of the potential fire damage the HRR of a single bundle cable (vs. or thermoplastic cable samples typically
associated with a realistic worst case multiple bundles) fire from NUREG/CR– is in the range of 6 kW/m2 (NUREG/CR–
fire scenario between Unit 1 RB fire 6850 in fire modeling. Specifically, the 6850, Appendix H, Table H–1). The
zones 1–1 and 1–2 and the anticipated NRC staff requested TVA to justify how measured critical heat flux for ignition
failure of cables or equipment of the single bundle cable HRR assumption for Thermo-Lag 330–1 ERFB material is
redundant trains of systems required for bounds the worst case cabinet fire 25 kW/m2 based on American Society of
safe-shutdown. A fire scenario was scenario. On January 11, 2007 (ADAMS Testing and Materials (ASTM) E1321,
postulated for the Unit 1 RB, that is, fire Accession Number ML070160050), TVA ‘‘Standard Test Method for Determining
started in a vertical electrical cabinet Material Ignition and Flame Spread
(480V RB vent board 1B). This cabinet 2 HRR is the rate at which heat energy is

has 12 vertical sections with no vent generated by burning. The HRR of a fuel is related 3 The incident heat flux (the rate of heat transfer

openings. The penetrations in the to its chemistry, physical form, and availability of per unit area that is normal to the direction of heat
oxidant. When an object burns, it releases a certain flow—it is a total of heat transmitted by radiation,
jlentini on PROD1PC65 with NOTICES

cabinet consist of sealed conduits on top amount of energy per unit of time. For most conduction, and convection) required to raise the
materials, the HRR of a fuel changes with time, in surface of a target to a critical temperature is termed
1 The Units 2 and 3 configuration are very similar relation to its chemistry, physical form, and the critical heat flux. Below this heat flux an object
and the results of this analysis are applicable to availability of oxidant (air), and is ordinarily will typically not ignite while above this heat flux
480V (RB) vent board 2B and 480V (RB) vent board expressed as kW (kJ/sec) or Btu/sec and denoted by the time to ignition will decrease with the
3B. Q̇ (1,000 kW = 1 MW or 1 BTU/sec = 1.055 kW). increasing heat flux.

VerDate Aug<31>2005 17:37 Apr 04, 2007 Jkt 211001 PO 00000 Frm 00072 Fmt 4703 Sfmt 4703 E:\FR\FM\05APN1.SGM 05APN1
16834 Federal Register / Vol. 72, No. 65 / Thursday, April 5, 2007 / Notices

Properties’’ (TVA October 26, 2006 cabinets would likely be detected in Authorized by Law
(ADAMS ML063040310)). its incipient stage, and fire-fighting This exemption revision allows the
Based on the above evaluation, the activities initiated (including existence of the specified intervening
NRC staff concludes that the ability of actuation of the automatic water- combustibles in the 20-foot separation
Units 1, 2, and 3 to achieve and based fire suppression system) before zone identified previously. As stated
maintain safe-shutdown conditions in the fire becomes fully developed, above, 10 CFR 50.12 allows the NRC to
accordance with the requirements of thereby limiting its potential to grant exemptions from the requirements
Section III.G.2.b to Appendix R to 10 spread. of 10 CFR 50.48 and Appendix R to 10
CFR 50 is not adversely affected by the CFR 50. The NRC staff has determined
inclusion of intervening combustibles or The NRC staff, therefore, finds the
licensee’s proposed exemption to permit that granting of the licensee’s proposed
fire hazards in certain fire zones within exemption will not result in a violation
Units 1, 2, and 3 RBs for the following intervening combustibles in the 20-foot
separation zone for certain specified fire of the Atomic Energy Act of 1954, as
reasons: amended, or the Commission’s
areas in the Units 1, 2, and 3 RBs
—The fire modeling performed by the acceptable. regulations. Therefore, the exemption is
licensee provides reasonable authorized by law.
assurance that redundant safe- The licensee indicated that all fire
zones discussed previously are No Undue Risk to Public Health and
shutdown trains will be maintained
protected with fire detection and Safety
free of fire damage. This is because
the estimated heat flux from the automatic pre-action sprinkler systems, The underlying purpose of 10 CFR
maximum exposure fire is less than manual fire extinguishers, and hose 50.48 is to limit fire damage to
the critical heat flux for ignition for stations. If a fire were to occur in any structures, systems, and components
non-qualified IEEE–383 cable or of these locations it would be detected (SSCs) important to safety so that the
Thermo-Lag 330–1 ERFB material. before significant flame propagation or capability to shut down the plant safely
—In the event of a postulated fire in the increased temperature, radiative heat is ensured. Compliance with the
Units 1, 2, and 3 RBs, all units can flux, and damaging smoke layering applicable provisions of Appendix R to
safely shut down using the alternate occurred. The fire brigade would then Part 50 ensures that one train of cables
shutdown panel located outside each extinguish the fire using hose stations and equipment necessary to achieve and
RB. The Browns Ferry Nuclear Plant and manual fire fighting equipment. If maintain safe-shutdown are maintained
Appendix R alternate shutdown rapid fire propagation occurred before free of fire damage. Based on the above,
strategy is described in the approved the arrival of the fire brigade, one would no new accident precursors are created
fire protection plan. expect the automatic pre-action by allowing the specified intervening
—A significant fire is unlikely due to sprinkler system to actuate and limit fire combustibles into the 20-foot separation
control of transient combustibles near spread. Pending actuation of automatic zone identified previously, thus, the
the redundant trains. RB volume and pre-action sprinkler system, the probability of postulated accidents is
height would dissipate heat from a physical separation of redundant trains not increased. Also, based on the above,
cabinet fire and not threaten is sufficient to provide reasonable the consequences of postulated
redundant trains. Smoke detectors assurance that one safe-shutdown train accidents are not increased. Therefore,
and portable extinguishers were would remain free of fire damage. there is no undue risk to public health
installed for quick fire detection and Therefore, the NRC staff concludes that and safety.
suppression. All electrical cabinets in the existing level of fire protection for Consistent With Common Defense and
the area of concern are enclosed with the redundant safe-shutdown trains is Security
no ventilation openings and the an acceptable deviation from Section
III.G.2 of Appendix R to 10 CFR Part 50. The proposed exemption revision
bottom of the cable tray stacks have would allow the specified intervening
non-combustible covers. 3.0 Discussion combustibles into the 20-foot separation
—A fire originating in a low voltage zone identified previously. This
cabinet exposing intervening Pursuant to 10 CFR 50.12, the revision to the fire protection plan and
combustibles/targets (cable trays Commission may, upon application by existing exemptions has no relation to
located at radial distance of any interested person or upon its own security issues. Therefore, the common
approximately 7 feet, conduits located initiative, grant exemptions from the defense and security are not impacted
at the bottom of the duct requirements of 10 CFR Part 50 when (1) by this exemption.
approximately 9 feet above the top of The exemptions are authorized by law,
the cabinet (17 feet above floor), and will not present an undue risk to public Special Circumstances
Thermo-Lag 330–1 wrapped conduit health or safety, and are consistent with In accordance with 10 CFR
located approximately 7 feet from the the common defense and security; and 50.12(a)(2), special circumstances are
edge of the cabinet) would be slow to (2) when special circumstances are present whenever application of the
develop. Based on the fire detection present. These include the special regulation in the particular
arrangement in the Units 1, 2, and 3 circumstances that the underlying circumstances is not necessary to
RBs, detection of this type of fire purpose of the rule is satisfied by the achieve the underlying purpose of the
would occur well before the fire had requested revision to the exemption, rule. The underlying purpose of 10 CFR
time to develop into a fully developed since the existing fire protection 50.48 is to limit fire damage to SSCs
cable tray fire scenario. features and analyses demonstrate that important to safety so that the capability
—The NRC staff reviewed the physical the quantity of intervening combustibles to shut down the plant safely is ensured.
configuration of the Units 1, 2, and 3 permitted in the 20-foot separation zone Compliance with the applicable
jlentini on PROD1PC65 with NOTICES

RBs, the associated fire hazards does not affect the ability of the existing provisions of Appendix R to Part 50
(intervening combustibles) and fire fire protection features to provide an ensures that one train of cables and
protection features, and fire response equivalent level of protection as equipment necessary to achieve and
procedures. This review found that a required by 10 CFR 50, Appendix R, maintain safe-shutdown are maintained
fire that initiated in one of the Section III.G. free of fire damage. As the existence of

VerDate Aug<31>2005 17:37 Apr 04, 2007 Jkt 211001 PO 00000 Frm 00073 Fmt 4703 Sfmt 4703 E:\FR\FM\05APN1.SGM 05APN1
Federal Register / Vol. 72, No. 65 / Thursday, April 5, 2007 / Notices 16835

the intervening combustibles should not CONTACT PERSON FOR MORE INFORMATION: Price Capital Appreciation Fund, T.
affect the capability of the installed Wendy A. Hocking, Secretary of the Rowe Price International Funds, Inc., T.
suppression and detection system to Board, U.S. Postal Service, 475 L’Enfant Rowe Price Short-Term Bond Fund,
detect and mitigate a fire, the Plaza, SW., Washington, DC 20260– Inc., T. Rowe Price New Income Fund,
underlying purpose of 10 CFR 50.48 and 1000. Inc. and T. Rowe Price Summit Funds,
Appendix R is achieved. Therefore, the Inc. Expenses of approximately
Wendy A. Hocking,
special circumstances required by 10 $490,000 incurred in connection with
Secretary.
CFR 50.12(a)(2) for the granting of an the reorganization were paid by
exemption from 10 CFR 50.48 and [FR Doc. 07–1717 Filed 4–3–07; 3:13 pm] Caterpillar Investment Management
Appendix R to 10 CFR 50 exist. BILLING CODE 7710–12–M Ltd., applicant’s investment adviser.
Filing Dates: The application was
4.0 Conclusion filed on July 20, 2006, and amended on
Accordingly, the Commission has SECURITIES AND EXCHANGE October 30, 2006, January 12, 2007 and
determined that, pursuant to 10 CFR COMMISSION March 23, 2007.
50.12, the revision to the exemption is Applicant’s Address: 411 Hamilton
[Release No. IC–27771]
authorized by law, will not present an Blvd., Suite 1200, Peroria, IL 61602.
undue risk to the public health and Notice of Applications for AIM Floating Rate Fund [File No. 811–
safety, and is consistent with the Deregistration Under Section 8(f) of the 9797]
common defense and security. Also, Investment Company Act of 1940
special circumstances are present. Summary: Applicant, a closed-end
Therefore, the Commission hereby March 30, 2007. investment company, seeks an order
grants the TVA a revision to the The following is a notice of declaring that it has ceased to be an
exemption from the requirements of applications for deregistration under investment company. On April 13,
Section III.G.2 of Appendix R to 10 CFR section 8(f) of the Investment Company 2006, applicant transferred its assets to
50 for the Browns Ferry Nuclear Plant, Act of 1940 for the month of March AIM Counselor Series Trust, based on
Units 1, 2 and 3. 2007. A copy of each application may be net asset value. Expenses of $238,190
Pursuant to 10 CFR 51.32, the obtained for a fee at the SEC’s Public incurred in connection with the
Commission has determined that the Reference Branch (tel. 202–551–5850). reorganization were paid by A I M
granting of this exemption will not have An order granting each application will Advisors, Inc., applicant’s investment
a significant effect on the quality of the be issued unless the SEC orders a adviser.
human environment (22 FR 9036). hearing. Interested persons may request Filing Date: The application was filed
This exemption is effective upon a hearing on any application by writing on February 23, 2007.
issuance. to the SEC’s Secretary at the address Applicant’s Address: 11 Greenway
below and serving the relevant Plaza, Suite 100, Houston, TX 77046–
Dated at Rockville, Maryland, this 29th day 1173.
applicant with a copy of the request,
of March 2007.
For the Nuclear Regulatory Commission. personally or by mail. Hearing requests Pioneer Balanced Fund [File No. 811–
should be received by the SEC by 5:30 1605]
Catherine Haney,
p.m. on April 25, 2007, and should be
Director, Division of Operating Reactor Pioneer America Income Trust [File No.
accompanied by proof of service on the
Licensing, Office of Nuclear Reactor 811–5516]
Regulation. applicant, in the form of an affidavit or,
for lawyers, a certificate of service. Summary: Each applicant seeks an
[FR Doc. 07–1696 Filed 4–4–07; 8:45 am]
Hearing requests should state the nature order declaring that it has ceased to be
BILLING CODE 7590–01–P
of the writer’s interest, the reason for the an investment company. On November
request, and the issues contested. 10, 2006, each applicant transferred its
Persons who wish to be notified of a assets to corresponding series of Pioneer
UNITED STATES POSTAL SERVICE hearing may request notification by Series Trust IV, based on net asset
BOARD OF GOVERNORS writing to the Secretary, U.S. Securities values. Expenses of $80,698 and
and Exchange Commission, 100 F $81,259, respectively, incurred in
Sunshine Act Meeting; Notification of
Street, NE., Washington, DC 20549– connection with the reorganizations
Item Added to Meeting Agenda
1090. were paid by each applicant, the
DATE OF MEETING: March 28, 2007. For Further Information Contact: acquiring fund, and Pioneer Investment
Diane L. Titus at (202) 551–6810, SEC, Management, Inc., investment adviser to
STATUS: Closed.
Division of Investment Management, both applicants and the acquiring fund.
PREVIOUS ANNOUNCEMENT: 72 FR 14312, Office of Investment Company Filing Date: The applications were
March 27, 2007. Regulation, 100 F Street, NE., filed on March 5, 2007.
ADDITION: Proposed Filing with the Washington, DC 20549–4041. Applicants’ Address: 60 State St.,
Postal Regulatory Commission for an Boston, MA 02109.
Extension of the Market Test for The Preferred Group of Mutual Funds
Repositionable Notes. At its closed [File No. 811–6602] Pioneer Europe Select Fund [File No.
meeting on March 28, 2007, the Board Summary: Applicant seeks an order 811–10111]
of Governors of the United States Postal declaring that it has ceased to be an Summary: Applicant seeks an order
Service voted unanimously to add this investment company. On June 19, 2006, declaring that it has ceased to be an
item to the agenda of its closed meeting each of applicant’s series transferred its investment company. On June 24, 2005,
and that no earlier announcement was assets to the following corresponding applicant transferred its assets to
jlentini on PROD1PC65 with NOTICES

possible. The General Counsel of the funds, based on net asset value: T. Rowe Pioneer Europe Select Equity Fund,
United States Postal Service certified Price Value Fund, Inc., T. Rowe Price based on net asset value. Expenses of
that in her opinion discussion of this Growth Stock Fund, Inc., T. Rowe Price $23,688 incurred in connection with the
item could be properly closed to public Mid-Cap Growth Fund, Inc., T. Rowe reorganization were paid by Pioneer
observation. Price New Horizons Fund, Inc., T. Rowe Investment Management, Inc.,

VerDate Aug<31>2005 17:37 Apr 04, 2007 Jkt 211001 PO 00000 Frm 00074 Fmt 4703 Sfmt 4703 E:\FR\FM\05APN1.SGM 05APN1

Das könnte Ihnen auch gefallen