Beruflich Dokumente
Kultur Dokumente
Practice
Earthing or Grounding of electrical installation is a common practice. However, some common terms
used in the practice could sometimes be tricky. Here, we have attempted to provide explanations for
some of the more common terms used when earthing or grounding an installation. These terms are the
ones used in the various national and international standards:
Current Transformers
A current transformer transforms line current into values suitable for standard protective relays and
instruments. The primary of a current transformer has a few turns, while the secondary may have a
great many turns which results in the stepping down of current as shown in the schematic below:
Autotransformer Schematic
The primary is always the portion of the winding connected to the AC power source. This transformer
may be used to step voltage up or down. If the primary is the total winding and is connected to a supply,
and the secondary circuit is connected across only a portion of the winding (as shown in schematic (a)
above), the secondary voltage is stepped-down. If only a portion of the winding is the primary and is
connected to the supply voltage and the secondary includes all the winding(as shown above in schematic
(b) above) then the voltage will be stepped-up in proportion to the ratio of the total turns to the
number of connected turns in the primary winding.
The main disadvantage of the autotransformer is that the primary and secondary
circuits are electrically connected and, therefore, could not safely be used for stepping down from high
voltage to a voltage suitable for plant loads.
Uses of the Autotransformer
Autotransformers find wide application in the following situations:
(a) Where the system supplied contains an identified-grounded conductor that is solidly connected to a
similar identified grounded conductor of the system supplying the autotransformer.
(b) Where an induction motor is to be started or controlled
(c) Where a dimming action is required, as in the theatre lighting
(d) Where the autotransformer is to be a part of a ballast for supplying lighting units
Where:
I = Current in Amps
V = Voltage in volts
The unit of power is the Watt(W). Power can also be expressed in volt amps (VA) usually in Alternating
current systems.
In a D.C system, the current and voltage do not vary over time. Hence the product of voltage and current
gives us power in Watt.
In A.C systems, the voltage and current entities are constantly changing in a sinusoidal manner as shown
below:
Where:
P = power in watts
Iphase = phase current
Vphase = phase voltage
Cos = power factor
In a three phase electrical system:
Substituting the values for phase current and phase voltage for both Delta and Wye connected system
into the above formula gives power in watts in a 3-phase A.C circuit connected in either Delta or Wye
connection as:
So knowing the line voltage and line current in any 3-phase A.C circuit and the power factor , the power
delivered into the system can easily be calculated.
NEMA Letter
Designation
105
Ambient
Temperature
Maximum Allowable
Temperature Rise
Maximum Allowable
Operating Temperature
50
122
105
221
130
80
176
130
226
155
105
221
155
311
180
125
257
180
356
220
150
302
220
428
40C
Note that a transformer with a Class 220 insulation system can be designed for a maximum temperature
rise that is lower than the standard 150C . It can be designed for either 125 or 80C rise. Also, a Class
180 insulation transformer can be designed with 80C rise. Class 155 and 105 transformers are not
typically designed for other than their standard temperature rise
The maximum operating temperature is determined by by adding the rated ambient temperature of the
device which is normally 40C, the maximum temperature rise, and a 10C hot-spot allowance:
Maximum operating Temperature
= Ambient Temperature + Maximum Temperature Rise + 10C hot-spot allowance.
Impedance Rating
The impedance of a transformer is the total opposition offered to an alternating current. When referring
to impedance of a transformer, it is the equivalent impedance that is meant. To determine the equivalent
impedance of a transformer, one of the windings, usually the low voltage winding is short circuited
while just enough voltage is applied to the other winding to create full load current in the short circuited
winding. This voltage is known as the impedance voltage.
Impedance rating is a characteristic of large power and distribution transformers. The transformer
impedance value is often given in percent on the nameplate
It means that the voltage drop due to the impedance is expressed as a percent of rated voltage.
For example, suppose the impedance rating of a 2400V/240V transformer with full load current of 90
amps is given as 3%.
Voltage drop due to impedance with low voltage winding short circuited
= 0.03 X 2400 = 72volts
This means there would be a 72-volt drop in the high-voltage winding at full load due to losses in the
windings and core. Only 1 or 2% of the losses are due to the core; about 98% are due to the winding
impedance.
We can also calculate the actual impedance value on the high voltage side in ohms:
Where:
Z = impedance in ohms
V = impedance voltage drop
I = Rated full load current in the primary of transformer
Now V = 72V, I = 90Amp
Therefore Z = 72/90 = 0.8
Transformer Action
When the primary winding of a transformer is energized from an alternating current (AC) source, an
alternating magnetic field is established in the transformer core. Alternating magnetic lines of force,
called flux, circulate through the core. With a second (secondary) winding around the same core, a
voltage is induced by the alternating flux lines. A load, connected to the terminals of the secondary
winding, results in current flow.
Parts of A Transformer
A transformer is made up of two basic non-moving parts:
(a) A laminated iron core
(b) Windings (primary & secondary)
Laminated Iron core
The iron core of a transformer is made up of sheets of rolled iron. This iron is treated so that it has a high
magnetic conducting quality (high permeability) throughout the length of the core. Permeability is the
term used to express the case with which a material will conduct magnetic lines of force.
The iron also has a high ohmic resistance across the plates (through the thickness of the core). It is
necessary to laminate the iron sheets to reduce heating of the core. There are two common types of
transformer cores:
(a) Core type
(b) Shell type
Transformer Efficiency
The efficiency of a transformer is equal to the ratio of the power output of the secondary winding to the
power input to the primary winding.
An ideal transformer is 100 percent efficient because it delivers all the energy it receives.
However, because of core and copper losses, the efficiency of even the best practical transformer is less
than 100 percent. Expressed as an equation:
Transformer Efficiency
Where:
Eff = efficiency
Ps = power output from secondary = Input power core losses Copper losses
Pp = power input to primary
Efficiencies of well-designed transformers are very high, averaging over 98 percent (%) for power
transformers. The only losses, in a transformer, are due to core losses which go to maintaining the
alternating magnetic field, resistance losses in the coils, and power used for cooling for large
transformers requiring cooling.
The main reason for high efficiencies of transformers, compared to other equipment, is the absence of
moving parts. Transformers are called static AC machines.
Inductance adds when inductors are connected in series. It diminishes when inductors are connected in
parallel:
L(series) = L1 + L2 + .+ Ln
L(parallel) = 1/[1/L1 + L2 + +1/Ln]
Flow of DC Current through an Inductor
When DC source is connected across a pure inductor, the flow of current creates a magnetic field which
acts in such a manner as to oppose the change in current. The relationship between voltage and current
for an inductor is given by:
V = LdI/dt
Inductors oppose changes in current over time by dropping a voltage. This behavior makes inductors
useful for stabilizing current in DC circuits. One way to think of an inductor in a DC circuit is as a
temporary current source, always wanting to maintain current through its coil at the same value.
Energy Stored in an Inductor
When DC current flows through an inductor, it stores energy in the form of a magnetic field. This stored
energy is given by the formula:
E = 1/2LI2
Where:
E = Energy stored
L = Inductance of inductor
I = Current flowing through inductor
Flow of Alternating Current (AC) through an Inductor.
When AC current flows through an inductor, it creates a magnetic field which varies continuously. In
fact, the magnetic field will expand and contract as the current increases and decreases. The changing
magnetic field will induce a voltage and a current in the inductor. This induced voltage is in a direction
so as to oppose the supply voltage and is called a counter-EMF or back-EMF.
The net effect of this back-EMF is to oppose the change of current due to the alternating voltage. This
opposition to current flow causes the voltage to lead the current by 90as indicated in the waveform
below:
Inductive Reactance
Inductive reactance, is the opposition to AC current due to the inductance in the circuit. The unit of
inductive reactance is the ohm. The formula for inductive reactance is given by:
XL = 2fL
Where:
XL = Inductive reactance
f = frequency
L = Inductance
Capacitor Symbols
Capacitance of a Capacitor
Electrically, the capacitance of a capacitor is its ability to store electrical charge. The bigger the
capacitance, the more the electrical charge stored. The capacitance of a parallel plate capacitor is given
by:
C = A/d
Where:
C = capacitance of capacitor in faradays (F). Units could be microfards (F) or picofarads (pF)
= electric permittivity of the dielectric material
A = Area of capacitor plates
d = Separation of the plates
The capacitance output of the capacitor will increase if a higher dielectric material is used or if the area
of the plates is increased or if the distance of separation between the plates is decreased.
Flow of DC Current through a capacitor:
As we have already seen in the basics of power factor in electrical distribution system, most Industrial
loads require both Real power and Reactive power to produce useful work. Typically, inductive loads
(motors, transformers etc) require two kinds of power to operate:
(1) Active Power (KW) This actually performs the useful work
(2) Reactive Power(KVAR) This helps to maintain the electromagnetic field.
The vector sum of the active power and the reactive power gives total power often referred to as
apparent
power
in
KVA:
KVA
=
KW +
KVA (vector
sum)
Low power factor in an electrical system often occur when inductive loads are operated below their full
load capacity especially motors. Consistently operating electrical loads at low power factor will result in
higher utility bills because of the poor utilization of electrical energy. In fact, a higher power factor
means less KVA and KVAR components and a more efficient utilization of electrical energy while a low
power factor implies the presence of more KVA and reactive (KVAR) power components and less
efficient electrical energy utilization:
The various types of electrical loads and the type of power they consume are summarized in the table
below:
Types of Power
Common Names
Typical Load
Active power
Kilowatt/Watt power
Real power
Resistive power
Resistors
Incandescent lights
Toasters
Reactive power
Imaginary power
KVAR/VAR power
Inductive/Capacitive
power
Reactors/Inductors
Capacitors
Apparent power
Complex power
Total power
KVA/VA power
Billing Concept
KVA
Connect the BLACK test lead from the multimeter to the diode cathode (This is a white or black band
on one side of one of the diode terminals). Connect the RED test lead of the multimeter to the anode.
If the diode is good, the readout should show between 0.400 to 0.600 along with a single audible beep
(beeping is a basic attribute of most multimeters).
Bad Diode:
If a diode is bad, you will hear a continuous beep tone from the multimeter with any of the following
observed:
(a) A readout of 0.00
(b) The readout will indicate any number value other than 0.400 to 0.600
(c) The readout will indicate OL
Reverse Bias Test:
Good Diode
To test in reverse bias with the knob still in the diode selection, connect the BLACK test lead of the
multimeter to the anode of the diode and the RED test lead to the cathode of the diode as shown below.
If the diode is good, the display should show OL
Ampacity of a Conductor
Ampacity is the current carry capacity of a conductor. Ampacity calculation should take into account
natural variables such as solar warming, wind and air density, viscosity, and thermal conductivity.
Ampacity is a temperature rating. In order words, as temperature changes, the ampacity of a conductor
changes.
Increase in ambient/surrounding/medium temperature can significantly limit the current carrying
capacities of cables. As cable temperature increases, its resistance increases thereby reducing the amount
of current that can be carried.
According to the National Electrical Code, article 310.15(C), the ampacities of conductors can be
calculated by the following general formula:
Where:
TC = Conductor temperature in degree Celsius
TA = Ambient temperature in degree Celsius
TD = Dielectric loss temperature rise
RDC = DC resistance of conductor at temperature TC
YC = Component AC resistance resulting from skin effect and proximity effect
RCA = Effective thermal resistance between conductor and surrounding ambient.
The NEC specifies that the above formula can only be applied under engineering supervision.
The table below gives the ampacities for portable power cables at 90 degree Celsius insulation and under
an ambient temperature of 40 degrees Celsius.
AC Resistance of a Conductor
A conductor offers a greater resistance to the flow of alternating current(AC) than it does to direct
current(DC). The magnitude of the increase is usually expressed as an AC/DC ratio. The reasons for
the increase include:
1.
Skin effect,
2.
Proximity effect,
3.
4.
Skin Effect
Skin Effect describes the phenomena of alternating current flowing more densely near the surface of a
conductor. The net effect is a reduction in effective area and an increase in the resistance. To calculate
skin effect in tubular conductors made of solid wire to an infinitely thin tube, the curves of Ewan are
used.
The parameter is:
The table below gives the factors for skin effect ratio R/R0 as a function of X, where R is the AC
resistance and R0 is the DC resistance. Note that from the table, R/R0 is the resistance ratio due to skin
effect. L/L0 is the inductance ratio due to skin effect. X is as defined by the formula above.
For conductors larger than 1,500,000 circular mils,other calculation formulas must be used for accuracy.
The non-uniform cross-sectional distribution of current also affects the inductance, the value of which is
less than if the current density were uniform. The table of skin effect ratios above, therefore, lists the
inductance ratio L/L0 where L is the inductance due to a non-uniform current density and L0 is the
inductance assuming uniform current density.
Proximity Effect:
Proximity effect is the distortion of the cross-sectional current distribution of the conductor due to
nearby currents. To calculate approximately the proximity effect, use the following formula:
Where:
fp
= The factor to account for proximity effect
GMR = The geometric mean radius of the equal conductors
GMD = Geometric mean spacing of the conductors
R/R0 = Skin effect ratio
After determining skin and proximity effect, the effective resistance of a conductor taking these two
factors into effect is then given by:
Where:
R/R0 = Skin effect ratio
fp = Factor accounting for proximity effect
DC Resistance of a Conductor
The DC resistance of a conductor or cable is that defined by ohms law. It is a function of many factors
including temperature which greatly affects the resistance of a given material. Copper and Aluminium
are the most widely used conductors. Their resistance (DC) increases with increasing temperature.
The DC resistance of copper wire at 20 degree Celsius(68 degree Fahrenheit) is given below:
The copper wire resistance in the above table are at 20 degree Celsius. To get the resistance at any other
temperature above this, we use the equation:
Actual values of depends on the composition of the material in addition to temperature. For copper
and aluminium, taking, = 0.0039 will give reasonable accuracy for most conductor calculations
Wire size is expressed in circular mils(CM). A mil is one-thousandth of an inch. In the United
States, the American Wire Gauge is used. It is a scale of even numbers that start with the
number 40 and descend. The cross-sectional area becomes larger as the numbers on this
scale get smaller.
For wires larger than No.2 wire, a scale of 1/0, 2/0, 3/0 and 4/0 is used. For even larger
wires, thousands of circular mils is used MCM or Kcmil
AWG Conversions
Copper conductor size conversions are determined using;
Circular mils = sq in. x 1,273,240 = sq mm x 1,973.5
For conductor cross-sectional forms other than circular, where S is the cross-sectional area in
square inches, the conversions are:
Electrical Conductors
Electrical
The
most
Conductors:
popular
electrical
conductors
are
Copper
and
Aluminum.
Copper is the popular choice for power distribution and control circuits because of its excellent
ability to conduct electric current as well as other electrical and mechanical properties. Copper may
be coated with Tin, Nickel or Silver to ensure easier soldering and to retard corrosion
Aluminium is also used in power applications. Its principal advantages are its weight and lower
material
The
cost
main
when
disadvantages
compared
of
with
Aluminium
copper.
are
(a) It has a lower conductivity than Copper hence it will require larger wire and cable sizes than
Copper
(b) Aluminium oxidizes quickly when exposed to air. This oxidation acts as an insulator. This creates
additional
cost
with
regard
to
maintenance
and
testing
when
compared
to
Copper
Aluminium is widely used by the electric utilities in overhead lines primarily because of its light
weight
and
cost
Common
when
Terms
(a)
A wire is
compared
Used
a
to
copper.
with
single
length
Conductors:
of
metal
(b) A stranded wire is a group of small wires that are braided or twisted together to produce a single
conductor. The wires are not insulated from each other. A heavily insulated stranded wire is often
called a cord. The outer jacket of a cord protects the wiring from physical damage.
(c) A cable can either be a solid, stranded conductor or a combination of conductors insulated from
each other. This latter arrangement is called a multiconductor cable. In this cable, the wires may be
stranded,
may
or
may
not
have
common
insulation
covering
(d) A conductor carries electricity from generation equipment to utilization equipment. A conductor
may be solid or stranded. A solid conductor is usually reserved for smaller wire sizes and provides the
benefit of low weight and small diameter. A stranded conductor configuration is usually used for
larger-sized
wires
as
this
configuration
makes
the
cable
lighter
and
more
flexible.
(e) Insulators are non-conductors of electricity. However at a certain voltage known as the
breakdown voltage, an insulator breaks down and becomes a conductor. Hence insulators are rated
for
specific
voltage
which
should
not
be
exceeded.
(f) Insulation is the covering conductors are enclosed in. This insulation protects the wiring and
prevents the electrical energy being carried from leaking into other materials to possibly cause
damage
and
hazards
There are several insulating materials. The most commonly used are tabulated below along with
their
mechanical
and
electrical
properties:
Series of letters are popularly used to identify cable insulation types. Some of the letters used are:
(i)
MI
Mineral
Insulation
(ii)
Rubber
Insulation
(iii)
(iv)
(v)
This
X
lettering
Thermoplastic
system
Varnished
Cross-linked
is
Insulation
specified
by
Insulation
polymer
NEC
National
Insulation
Electrical
Code
The most popular amongst the above are thermoplastic and cross-linked polymer insulation
The ability of the insulation of the conductor material to withstand ambient conditions can be also
be
used
HH
to
Heat
resistant
Heat
W
UF
classify
resistant
-
For
use
cable
insulation
up
up
for
to
75
deg
to
90
deg
Moisture
in
underground
example:
direct
resistant
burial
applications
There are popular cable types in use today that we should know of. Some of them are tabulated
below:
In most industrial environment you are likely to see THHN/THWN and XHHW. They stand for:
CABLE
DESIGNATION
THHN
metallic
sheathed
THWN
XHHW
cable
Non-metallic
sheathed
cable
What is a Diode?
The diode is fabricated of a semiconductor material, usually silicon, which is doped with two
impurities. One side is doped with a donor or n-type impurity which releases electrons into
the semiconductor lattice. These electrons are not bound and are free to move about.
Because there is no net charge in the donor impurity, the n-type semiconductor is
electrically neutral. The other side is doped with an acceptor or p-type impurity which
imparts free holes into the lattice. A hole is the absence of an electron which acts as a
positive charge. The p-type semiconductor is also electrically neutral because the acceptor
material adds no net charge. When a P-type semiconductor material is combined with an ntype semiconductor material, a p-n junction is formed. This p-n junction is called a diode.
Thus the diode has two terminals or electrodes (di-ode),that act like an on-off switch. When
the diode is on, it acts as a short circuit and passes all current. When it is off, it
behaves like an open circuit and passes no current. The two terminals are different and are
marked as plus(+) and minus(-) in the schematic below:
The positive electrode is called the Anode and the negative electrode is called the Cathode.
If the polarity of the applied voltage matches that of the diode (forward bias), then the
diode turns on. When the applied voltage polarity is opposite (reverse bias), it turns off.
This is just the theoretical behaviour of an ideal diode, but it can be seen as a good
approximation for a real diode which will have some reverse current when reverse biased.
Basic
Characteristics
of
the
Semiconductor
Diode
A
diode
has
the
following
basic
characteristics:
(1) When forward bias, the diode needs a small voltage to conduct electricity. This voltage is
maintained
across
the
diode
during
conduction
(2) The maximum forward current a diode can carry is limited by the heat dissipation
capacity
of
the
diode.
(3) There is a small reverse current flowing even when the diode is reversed bias
(4) Every diode has a maximum reverse voltage, called the breakdown voltage, which cannot
be
exceeded
without
damage
to
the
diode.
Technical
Specifications
of
a
Diode
There are four diode ratings that apply to one or other diodes used in various applications.
These
include:
Forward
Voltage
Drop
This is the forward-conducting junction voltage drop (0.7 V for Silicon diodes
and
0.3
V
for
Germanium
diodes).
Average
Forward
Current
This is the maximum amount of forward current that the diode can carry for an indefinite
period. If the average current exceeds this value, the diode will overheat and, eventually,
will
be
destroyed.
Peak
Reverse
Voltage
or
Reverse
Breakdown
Voltage
This is the largest amount of reverse-bias voltage the diodes junction can withstand for an
indefinite period of time. If a reverse voltage exceeds this level, the voltage will punch
through the depletion layer and allow current to flow backwards through the diode, which is
a
destructive
operation
(except
for
the
case
of
a
Zener
diode).
Maximum
Power
Dissipation
The actual diode power dissipation is determined by multiplying the forward voltage drop
and the forward current. Exceeding the maximum power dissipation will result in thermal
breakdown
of
the
diode.
In practical diode applications, excessive forward current and reverse breakdown voltage are
the most common causes of diode failure. In both cases the diode gets very hot, resulting in
the destruction of the p-n junction. Occasional peaks of voltage or current exceeding these
rates for very short times (few milliseconds) may not overheat the junction, but repeated
peaks
may
fatigue
the
junction.
When used in most applications, diodes are selected with ratings that exceed two or three
times the expected peaks in the circuit where they operate.
One of the most effect ways to improve the power factor of the electrical
distribution system is to install equipment that have the ability to decrease the
reactive component of the power supplied by the utility company. One of such
equipment is the Capacitor. Other equipment with the same ability to decrease
reactive power includes:
Capacitors
Synchronous motors
Synchronous generators
We can reduce reactive power and increase power factor in an electrical
distribution system by the following method:
Installing Capacitors
Installing capacitors decreases the magnitude of reactive power (KVAR), thus
increasing your power factor. A capacitor freely supplies the distribution system
with what is called a Leading reactive power compared to the Lagging
reactive power supplied by the utility company. With capacitors in the
electrical distribution system, the reactive powers cancel each other out
depending on the size of capacitor (in micro-farad) in use or at best reduces the
level of reactive power in the distribution system.
The presence of both a capacitor and inductor in the same circuit results in the
continuous alternating transfer of energy between the two. Thus, when the circuit
is balanced, all the energy released by the inductor is absorbed by the capacitor.
In effect, a capacitor cancels out the effect of an inductive load.
Minimizing Operation of Idling or Lightly Loaded Motors
We have already established the fact that a major cause of low power factor in
most industrial premises is the prevalence of a large number of induction motors.
The problem of low power factor will be compounded if most of theses electric
motors are lightly loaded or left to idle away without any load. To prevent this
from happening, induction motors should be appropriately loaded and idling of
the motors should be discouraged.
Replacing Standard Motors as they Burn out with Energy-Efficient Motors
The rising cost of energy is leading us into an era where every device that
consumes energy need to be energy efficient. With energy-efficient motors, power
factor can be significantly improved but even with these kinds of electric motors,
power factor can be adversely affected by variations in load. A motor must
therefore be operated near its rated load in order to realize the benefits of a high
power factor design.
oil, increased facility efficiency is very desirable. And with lower system losses,
you are also able to add additional load to your system.
Increased Voltage Level and Cooler and More Efficient Motors
Uncorrected power factor causes power system losses in the distribution system.
As power losses increase, voltage drops. Excessive voltage drops can cause
overheating and premature failure of motors and other inductive equipment.
By improving the power factor of your plant, you will minimize these voltage
drops along feeder cables and avoid related problems. Your motors will run
cooler and be more efficient, with a slight increase in capacity and starting
torque. Also note that Severe over-correction (P.F. greater than 1) will cause a
voltage rise that can damage insulation & equipment; or result in utility
surcharges!
The lower the ratio of KW to KVA, the lower the power factor
The higher the ratio of KW to KVA, the larger the power factor.
Power factor has a maximum value of 1.
The Power Triangle illustrates this relationship between KW, KVA, KVAR,
and Power Factor:
From this power triangle, we can deduce that a system with good power factor
will possess the following characteristics:
KVAR would be very small (approaching zero)
KW and KVA would be almost equal
The angle (formed between KW and KVA) would approach zero
Cosine would then approach one
Power Factor would approach one
In order to have an efficient system, we want power factor to be as close to
1.0 as possible. In practice however, our electrical distribution sometimes has a
power factor much less than 1.0. What then causes low power factor in the
electrical distribution system?
Causes of Low Power Factor
The cause of low power factor in the electrical distribution system especially in
Any accessible metal parts of electrical equipment item other than the live parts
and which can accidentally become live.
Electrical fault
Accidental connection between two points at different potentials, such as
insulation fault.
Fault voltage
Voltage, in case of an insulation fault, across an exposed conductive part and
an earthing reference.
Direct contact
Contact of persons with the normally live parts of electrical equipment
Non direct contact
Contact of persons with exposed conductive parts accidentally live due to an
insulation fault.
Double insulation
Insulation including both:
Basic insulation required for protection against direct contact, and
Supplementary insulation required for protection against indirect contact in case of a
fault of the basic insulation.
Discrimination
Coordination of the automatic switching devices such that only opening of the
device cuts off the faulty part of the installation located immediately upstream
of the fault.
Protective conductor PE
Conductor used for protection against indirect contact and for interconnecting
exposed conductive parts to one another; to extraneous conductive parts and to earthing
electrodes or earthed parts.
Service voltage
The rated operating voltage of a system, which together with the rated current of the
system determines the load. For three-phase systems, it is the voltage between phases.
Residual current
In case of an insulation fault, the residual current is the leakage current returned to the
source through the earth and the protective conductor.
Residual operating current
Value of the residual current, which causes a residual current device to operate.
Shock protection device
This device must automatically separate from the source any part of the installation on
which there is a fault hazardous to life. Depending on the system earthing arrangement of
the installation, this device is either a residual current device, or an over-current device
(fuse or circuit breaker)
Conductors:
most
popular
electrical
conductors
are
Copper
and
Aluminum.
Copper is the popular choice for power distribution and control circuits because of its excellent
ability to conduct electric current as well as other electrical and mechanical properties. Copper may
be coated with Tin, Nickel or Silver to ensure easier soldering and to retard corrosion
Aluminium is also used in power applications. Its principal advantages are its weight and lower
material
The
cost
when
main
compared
disadvantages
of
with
copper.
Aluminium
are
(a) It has a lower conductivity than Copper hence it will require larger wire and cable sizes than
Copper
(b) Aluminium oxidizes quickly when exposed to air. This oxidation acts as an insulator. This creates
additional
cost
with
regard
to
maintenance
and
testing
when
compared
to
Copper
Aluminium is widely used by the electric utilities in overhead lines primarily because of its light
weight
and
Common
(a)
cost
when
Terms
A wire is
compared
Used
a
to
with
single
length
copper.
Conductors:
of
metal
(b) A stranded wire is a group of small wires that are braided or twisted together to produce a single
conductor. The wires are not insulated from each other. A heavily insulated stranded wire is often
called a cord. The outer jacket of a cord protects the wiring from physical damage.
(c) A cable can either be a solid, stranded conductor or a combination of conductors insulated from
each other. This latter arrangement is called a multiconductor cable. In this cable, the wires may be
stranded,
may
or
may
not
have
common
insulation
covering
(d) A conductor carries electricity from generation equipment to utilization equipment. A conductor
may be solid or stranded. A solid conductor is usually reserved for smaller wire sizes and provides the
benefit of low weight and small diameter. A stranded conductor configuration is usually used for
larger-sized
wires
as
this
configuration
makes
the
cable
lighter
and
more
flexible.
(e) Insulators are non-conductors of electricity. However at a certain voltage known as the
breakdown voltage, an insulator breaks down and becomes a conductor. Hence insulators are rated
for
specific
voltage
which
should
not
be
exceeded.
(f) Insulation is the covering conductors are enclosed in. This insulation protects the wiring and
prevents the electrical energy being carried from leaking into other materials to possibly cause
damage
and
hazards
There are several insulating materials. The most commonly used are tabulated below along with
their
mechanical
and
electrical
properties:
Series of letters are popularly used to identify cable insulation types. Some of the letters used are:
(i)
MI
Mineral
Insulation
(ii)
Rubber
Insulation
(iii)
(iv)
(v)
This
X
lettering
Thermoplastic
-
system
Varnished
Cross-linked
is
Insulation
specified
by
Insulation
polymer
NEC
National
Insulation
Electrical
Code
The most popular amongst the above are thermoplastic and cross-linked polymer insulation
The ability of the insulation of the conductor material to withstand ambient conditions can be also
be
used
to
Heat
classify
resistant
cable
up
insulation
to
for
75
example:
deg
HH
Heat
W
UF
resistant
up
For
use
to
90
deg
Moisture
in
underground
direct
C
resistant
burial
applications
There are popular cable types in use today that we should know of. Some of them are tabulated
below:
In most industrial environment you are likely to see THHN/THWN and XHHW. They stand for:
CABLE
DESIGNATION
THHN
metallic
sheathed
THWN
cable
XHHW
Non-metallic
sheathed
cable
an
example
using
the
reistance
formula:-
A copper conductor of length 500 meters is used to supply electrical energy to a lighting load of
1,000W. If the cross sectional area of the conductor is 10mmsq, calculate the resistance of the
conductor. If the copper conductor were replaced with an Aluminium conductor of the same length,
calculate
the
resistance
of
the
Aluminium
conductor.
Solution:
The
resistance
per
km
Length
of
22.5/10
conductor
resistance
of
copper
resistance
per
2.25
Ohms
500m
conductor
=500/1000
2.25
0.5
per
km
for
0.5km
=1.125
Ohms
Aluminium,
Aluminium
is
given
of
36/10
by:
36/S(c.s.a)
km
Again
by:
10mmsq
for
Length
given
Similarly
Hence
is
22.5/S(c.s.a)
Hence
The
copper
Here
Therefore
for
3.6
conductor
ELECTRICAL RESISTANCE
10mmsq
Ohms
per
km
0.5km
ELECTRICAL
RESISTANCE:
Electrical resistance is the opposition of a given material to the flow of electricity. The resistance of
a
an
electric
conductor
is
given
by
the
formula:
Where
L
A
Resistance
=
eL/A
Length
Cross
sectional
Resistivity
Resistivity
in
of
in
area
the
ohms
of
conductor
conductor
meters
in
(c.s.a)
ohms
meter
RA/L
If A = 1msq, then: resistivity is defined as the resistance per meter for a unit c.s.a
The two most popular conductors encountered in the electrical engineering field are Copper and
Aluminium
The
electrical
resistance
of
conductor
is
dependent
on
the
following
(a)
factors:
temperature
(b)
length
(c)
of
cross
conductor
sectional
area
material
(c.s.a) of
conductor
OHM'S
LAW:
Ohm's law states that the voltage applied across a conductor is directly proportional to the current
passing through the conductor provided the temperature and physical condition of the conductor
remains
constant.
This
implies
that:
Where
Voltage
Current
IR
applied
passing
across
through
Resistance
conductor
the
conductor
of
conductor
For direct current systems, resistance is the appropriate term to use. For alternating current
systems, impedance is the right term to use. Impedance is the opposition to the flow of alternating
current through a conductor. Impedance is as a result of resistive, capacitive and inductive effect of
alternating current on the conductor. For small sizes of conductor, the capacitive and inductive
effects due to alternating current is usually negligible and the term resistance could be used
Often in electrical works, there is the need to determine approximately the resistance of a
conductor.
Resistance
R
in
(22.5
ohms
Ohms
per
mmsq)/S(c.s.a)
km
is
per
given
km
for
by:
Copper
R
Inductive
(36
reactance is
Ohms
negligible
mmsq)/S(c.s.a)
for
conductors
of
for
c.s.a
less
Aluminium
than
This formula works pretty well for most design calculations of resistance less than 50mmsq
http://www.electricalengineeringtoolbox.com/
50mmsq