Beruflich Dokumente
Kultur Dokumente
transient. This is a high-voltage test that is applied to all devices for a specific time in order to
ensure that the insulation is not marginal. Another reason for conducting the hipot test is that it
also detects possible defects such as inadequate creepage and clearance distances introduced
during the manufacturing process.
During type testing, the hipot test is applied after tests such as fault condition, humidity,
and vibration to determine whether any degradation has taken place. The production-line hipot
test, however, is a test of the manufacturing process to determine whether the construction of a
production unit is about the same as the construction of the unit that was subjected to type
testing. Some of the process failures that can be detected by a production-line hipot test
include, for example, a transformer wound in such a way that creepage and clearance have
been reduced. Such a failure could result from a new operator in the winding department. Other
examples include identifying a pinhole defect in insulation or finding an enlarged solder footprint.
Most safety standards use the 2U + 1000 V formula as the basis for testing basic
insulation, where U is the operating rms voltage. Although this formula is a guideline, each
standard— in particular IEC 60950—refers the user to a specific table in the standard showing
the exact test voltage based on the working voltage measurements. The reason for using 1000
V as part of the basic formula is that the insulation in any product can be subjected to normal
day-to-day transient overvoltages. Experiments and research have shown that these
overvoltages can be as high as 1000 V.
Test method. Normally the high voltage is applied between the two parts across the
insulation being tested, such as the primary circuit and metal enclosure of the equipment under
test (EUT). If the insulation between the two is adequate, then the application of a large voltage
difference between the two conductors separated by the insulator would result in the flow of a
very small current. Although this small current is acceptable, no breakdown of either the air
insulation or the solid insulation should take place. Therefore, the current of interest is the
current that is the result of a partial discharge or break down, rather than the current due to
capacitive coupling.
experiments and the manufacturers’ data sheets indicate that each insulating material has its
own specific voltage-time characteristics.
Current Setting. Most modern hipot testers allow the user to set the current limit.
However, if the actual leakage current of the product is known, then the hipot test current can be
predicted. Choosing the trip level really depends on the product being tested. The best way to
identify the trip level is to test some product samples and establish an average hipot current.
Once this has been achieved, then the leakage current trip level should be set to a slightly
higher value than the average figure.
Another method of establishing the current
trip level would be to use the following
mathematical formula:
E (hipot) I (hipot)
=
E (leakage) 2 x I (leakage)
A minor
disadvantage of the ac
hipot tester is that if the
circuit under test has
large values of Y
capacitors, then, de
pending on the current
trip setting of the hipot
tester, the ac tester
could indicate a failure.
Most safety standards
allow the user to
disconnect the
capacitors prior to
testing or, alternatively,
to use a dc hipot tester.
The dc hipot tester
would not indicate the
failure of a unit even
with high Y capacitors
because the capacitors
see the voltage but don’t
pass any current.
Insulation
Resistance
The insulation resistance test is also known as a Megger test. Its objective is to measure
the total resistance between any two points separated by insulation. The test, therefore,
determines how effective the insulation is in resisting the flow of electrical current. The voltage is
typically around 500—1000 V dc; hence, the current is very low. Because the current is so low,
this test is useful for checking the quality of the insulation not only when a product is first
manufactured, but also over time as the product is used.
Test Procedure. The EUT is connected to the measuring instrument, and the voltage is
ramped up from zero to the final value, which in most cases is 500 V dc. Once the voltage
reaches the selected value, it is kept .at that value for a brief period (typically up to 5 seconds)
before the resistance test is measured. The measured value should be very high (typically in the
megohm region). The insulation resistance test is mandatory in some product safety standards,
including IEC 60065 and UL 6500.2,3
Ground Bond Test
Also known as the ground bond continuity test, the ground bond test must be conducted
on all Class I products. The purpose of the test is to ensure that all accessible conductive parts
of the product that could become live in the event of a single insulation fault are connected
securely to the final earth point of the supply input. In other words, a ground bond test verifies
integrity of the ground path by applying a high-current, low- voltage source to the ground-path
circuit.
Compliance is checked by measuring the resistance of the connection between the
protective earthing terminal or earthing contact and the parts to be earthed to ensure that
resistance does not exceed certain values when subjected to a high cur rent as specified in
various product safety standards. It is important to bear in mind that from the constructional and
de sign points of view, the protective earthing conductors should not contain switches or fuses.
Test Requirements. Most safety standards require the following parameters for
conducting the ground bond test:
• The EUT must be subjected to a
high ac or dc current with a low
test voltage for a certain period.
• The voltage drop between the
protective earthing terminal or
earthing contact and the part to
be earthed must be measured.
• The resistance must be
calculated from the current and
the resulting voltage drop using
Ohm’s law.
• The resistance should not
exceed certain values as stated
in various safety standards. For
example, IEC 60950 requires
that the test voltage not exceed
12 V.
• The current can be either ac or dc at 1.5 times the current consumption of the product or
25 A, whichever is greatest.
• The test duration must be 1 minute, and the resistance of the connection between the
protective earthing terminal or earthing contact and parts required to be earthed must
not exceed 0.1 I. This value does not include the resistance of the power cable. Some
standards, such as CAN/CSA-C22.2 No. 60950-00 or UL 60950 with Canadian
deviation, require the test to be conducted at 30 A and for 2 minutes if the current rating
of the circuit under test is 16 A or lower.
Understanding Resistance Values. With the exception of the Canadian standard, most
standards require 25 A for 1 minute. The value of 25 A for 1 minute represents the worst current
and the longest operation time of a mains overcurrent device. The maximum 25 A is
approximately 1.5 times the mains circuit breaker value installed for most pluggable type A cord-
connected equipment rated up to 16 A. The Canadian National Wiring Code requirements are
very similar to these in the sense that they assume that fuses are expected to operate no more
than 1 minute at twice their rated current. Because most mains circuits are protected with a
15—16 A fuse, the fault current would be 30 A for no more than 2 minutes.
Earth Leakage Current
Some standards, including IEC 60950, 3rd ed., have named the leakage current test
“touch current”. This refers to the electric current through a human body or through an animal
body when it touches one or more accessible parts of installation or equipment. There is also
another concept known as “protective conductor current:’ and this refers to the current that flows
in a protective conductor. A protective conductor current, there fore, can never be the source of
an electric shock because, by definition, the protective conductor is connected to earth.
If touch current is excessive, an operator could receive an electric shock, which could
result in a serious injury, depending on a person’s body weight. Typically, currents of more than
1.0 mA can cause an electric shock to an operator. The shock may or may not be serious,
depending on the amount of the current and the body weight.
Like the other tests, the leakage current test is also a very important safety test, and
most safety standards require the test to be conducted under various conditions such as normal
operating condition, switches open as well as closed, reversed line polarity, and so on. The
measured earth leakage current must not exceed specified limits during any of the tested
conditions. Table I shows some typical limits.
One of the biggest contributors to leakage is the capacitance between ac lines and
earth, i.e., the capacitors. These capacitors are normally placed in the circuit to control
electromagnetic interference. It should be noted that some standards, such as IEC 60950, allow
higher earth leakage current
• Train operators in the basic theory of electrical circuits and explain the object of each
test.
• Review and update all safety test procedures regularly.
• Locate the testing area away from walkways and crowded areas on the shop floor.
• Guard the testing area with nonconductive barrier.
• Mark the testing area with a clear and visible sign such as “Danger” or “High Voltage
Present.”
• Mark the testing area with a clear sign indicating “Qualified Personnel Access Only’
• Ensure that all test equipment is properly connected to a re liable earth.
• Reconfigure all testers (where possible) with push-button switches so that operators
must use both hands to activate the test equipment or, alternatively, provide the
equipment with a safety interlock that automatically shuts down the high voltage when a
safety switch on the EUT is opened.
• Connect the complete test setup to a palm-type switch that can shut off the power to the
test bench in case of an emergency
Record Keeping and Identification
CENELEC has released a standard, EN 50116, which essentially defines the routine
electrical safety tests and their procedures to be applied during or after the manufacturing
process of IT equipment certified or declared as complying with EN 60950.6,7
It is extremely important for manufacturers of electrical products to ensure that all test
results, including routine production tests, are clearly and adequately documented and kept on
file for possible inspection. Although this may not be required by all agencies, keeping accurate
test records is not only good engineering practice, but could also be vital in de fending a legal
action should such a case arise. Most modern test equipment can produce test results in an
electronic format that can be stored or printed when needed.
It is also necessary for manufacturers to ensure that all test equipment is calibrated
regularly and that such records are kept on file. In fact, most test houses expect to see a log for
daily calibration of the hipot tester on the production line. This log confirms that the hipot tester
has indeed been applying high voltage to the EUT. It is also vital to ensure that all electrical
safety tests are carried out on units that have been returned for repair or service.
On the production line, there are generally three product states: not tested, tested-
passed, and tested-failed. The status
Electrical safety testing at the design and development stages as well as at the
production stage is vital to ensure that all products are safe before reaching the end-user. The
four tests described in this article are among the most fundamental tests that manufacturers of
electrical and electronic products should conduct routinely. It is important to use correct test
equipment and adequate and accurate test procedures so that sufficient testing is conducted
and operator safety is considered.
Acknowledgement
The author wishes to thank Rich Nute of Hewlett-Packard for his valuable help.
References:
1. IEC 60950,3rd ed., “Safety of Information Technology Equipment:’ International
Electrotechnical Commission (IEC), Brussels, 1999.
2. IEC 60065, “Audi Video and Similar Electronic Apparatus—Safety Requirements,” IEC,
Brussels, 1998.
3. UL 6500, “Audio/Video and Musical Instrumental Apparatus for Household, Commercial,
and Similar General Use,” Underwriters Laboratories Inc. (UL), Northbrook, IL.
4. CAN/CSA-C22.2 No.60950-00, “Safety of International Information Technology
Equipment,” GSA International, Toronto, ON, Canada.
5. UL 60950, “Safety of Information Technology Equipment,” UL, Northbrook, IL, 2000.
6. EN 50116, “Information Technology Equipment—Routine Electrical Safety Testing in
Production:’ European Committee for Electrotechnical Standardization (CENELEC),
Brussels, 1996.
7. EN 60950, 2nd ed., “Safety of Information Technology Equipment, including Electrical
Business Equipment,” CENELEC, Brussels, 1992.
Homi Ahmadi is the approvals manager for Celetron Inc. (Simi Valley, CA). He can be
reached at Hahmadi@celetron.com.