Sie sind auf Seite 1von 4

CHAPTER 14

PROCESS PIPING

1401.0 General. SERVICE CORRIDOR – A fully enclosed passage


The regulations of this chapter shall govern the used for transporting hazardous production mate-
installation of process piping in or in conjunction rials and purposes other than required exiting.
with a building or structure or located upon the USE (MATERIAL) – The placing in action or making
premises. available for service by opening or connecting any
container utilized for confinement of material,
whether a solid, liquid, or gas.
1402.0 Definitions.
For the purposes of this chapter, certain terms,
phrases, words, and their derivatives shall be inter- 1403.0 Permit.
preted as set forth in this section. It shall be unlawful to install, alter, or repair or cause
APPROVED. See Section 203.0. to be installed, altered, or repaired any process mate-
rial piping without first obtaining a permit.
EMERGENCY ALARM SYSTEM – A system
Permits for process piping shall show the total
intended to provide the indication and warning of
number of outlets to be provided for on each system
abnormal conditions and summon appropriate aid.
and such other information as may be required by
EMERGENCY CONTROL STATION – An approved the Authority Having Jurisdiction.
location on the premises where signals from emer-
Fees for process piping permits are included in
gency equipment are received.
Table 1-1.
FABRICATION AREA (FAB AREA) – An area
within a Group H Occupancy semiconductor fabrica-
tion facility and related research and development 1404.0 Plans Required.
areas in that there are processes involving hazardous Plans, engineering calculations, diagrams, and other
production materials. Such areas are allowed to data shall be submitted in one or more sets with each
include ancillary rooms or areas such as dressing application for a permit. The Authority Having Juris-
rooms and offices that are directly related to the fab diction may require plans, computations, and speci-
area processes. fications to be prepared and designed by an engineer
HAZARDOUS PROCESS PIPING (HPP) – A process licensed by the state to practice as such.
material piping or tubing conveying a liquid or gas When plans or other data are submitted for
that has a degree-of-hazard rating in health, flamma- review, a plan review fee shall be paid, as provided
bility, or reactivity of Class 3 or 4, as ranked by the in Section 115.3.
Fire Code.
HIGH PURITY PIPING – A form of process piping 1405.0 Workmanship.
but is usually specified for critical clean applications Process piping shall not be strained or bent, nor shall
in the semiconductor, pharmaceutical, biotech- tanks, vessels, vats, appliances, or cabinets be
nology, chemical, fiber optics, food, and dairy indus- supported by or develop strain or stress on the
tries. piping.
HPM STORAGE ROOM – A room used for the
storage or dispensing of hazardous production mate- 1406.0 Inspections.
rial (HPM) and that is classified as a Group H, Divi-
1406.1 General. Upon completion of the installation,
sion 1 or Division 2 Occupancy.
alteration, or repair of process piping, and prior to the
NONHAZARDOUS PROCESS PIPING (NPP) – use thereof, the Authority Having Jurisdiction shall be
Production material piping or tubing conveying a notified that such piping is ready for inspection.
liquid or gas that is not classified as hazardous
Excavations required for the installation of
production material piping. underground piping shall be kept open until such
PROCESS PIPING – Piping or tubing that conveys time as the piping has been inspected and approved.
liquid or gas, which is used directly in research, labo- If any such piping is covered or concealed before
ratory or production processes, and that is not regu- such approval, it shall be exposed upon the direction
lated under the mechanical or plumbing code. of the Authority Having Jurisdiction.

249
1406.2 – 1407.2 UNIFORM MECHANICAL CODE

1406.2 Required Inspections. The Authority HPP piping shall be identified in accordance
Having Jurisdiction shall make the following inspec- with nationally recognized standards to indicate
tions and shall either approve that portion of the the material being transported. All liquid HPP
work as completed or shall notify the permit holder piping shall have an approved means for
wherein the same fails to comply with this code. directing any spilled materials to an approved
1406.2.1 Rough Piping Inspection. This containment or drainage system.
inspection shall be made after all process piping All liquid HPP waste or drainage systems
authorized by the permit has been installed and shall be installed in accordance with the
before any such piping has been covered or Plumbing Code.
concealed. This inspection shall include a deter- 1407.2.2 Installation in Exit Corridors and
mination that the piping size, material, and Above Other Occupancies. Hazardous process
installation meet the requirements of this code. supply pipe shall not be located within exit
1406.2.2 Final Piping Inspection. This inspec- corridors, within any portion of a means of
tion shall be made after all piping authorized by egress required to be enclosed in fire-resistive
the permit has been installed and after all construction, or in concealed spaces in or above
portions thereof that are to be covered or areas not classified as Group H Occupancies,
concealed are so concealed. This inspection shall except as permitted by this subsection.
include a pressure test, at which time the piping Hazardous production material piping and
shall stand a pressure of not less than 1.5 times tubing may be installed within the space defined
the maximum designed operating pressure by the walls of exit corridors and the floor or
when hydraulic testing is conducted or 110 roof above, or in concealed spaces above other
percent when testing is conducted pneumati- occupancies under the following conditions:
cally. Test pressures shall be held for a length of
1407.2.2.1 Automatic sprinklers shall be
time satisfactory to the Authority Having Juris-
installed within the space, unless the space
diction, but in no case for less than thirty (30)
is less than six (6) inches (152 mm) in least
minutes with no perceptible drop in pressure.
dimension.
HPM drain, waste, and vent piping shall be
tested in accordance with the Plumbing Code. 1407.2.2.2 Ventilation at not less than six (6)
Tests shall be made in the presence of the air changes per hour shall be provided. The
Authority Having Jurisdiction. Necessary appa- space shall not be used to convey air from
ratus for conducting tests shall be furnished by any other area.
the permit holder. 1407.2.2.3 When the piping or tubing is
1406.3 Other Inspections. In addition to the inspec- used to transport HPP liquids, a receptor
tions required by this section, the Authority Having shall be installed below such piping or
Jurisdiction may require a special inspector, as speci- tubing. The receptor shall be designed to
fied in the Building Code, during installation of collect any discharge or leakage and drain it
piping systems. In cases where the work authorized to an approved location. The one (1) hour
was installed in accordance with plans and specifica- enclosure shall not be used as part of the
tions prepared by an engineer, the Authority Having receptor.
Jurisdiction may require a final signed report stating 1407.2.2.4 All HPP supply piping and
that the work was installed in accordance with the tubing and HPP nonmetallic waste lines
approved plans and specifications and the applicable shall be separated from the exit corridor and
provisions of this chapter. from any occupancy other than a semi-
conductor fabrication facility classified as a
Group H Occupancy by construction, as
1407.0 Piping and Tubing. required for walls or partitions that have a
1407.1 General. Process piping and tubing shall fire-protection rating of not less than one (1)
comply with this subsection and shall be installed in hour. When gypsum wallboard is used,
accordance with nationally recognized standards. joints on the piping side of the enclosure
Piping and tubing systems shall be metallic unless need not be taped, provided the joints occur
the material being transported is incompatible with over framing members. Access openings
such system. into the enclosure shall be protected by
1407.2 Hazardous Process Piping (HPP). approved fire assemblies.
1407.2.1 General. HPP supply piping or tubing 1407.2.2.5 Readily accessible manual or
in service corridors shall be exposed to view. automatic remotely activated fail-safe emer-

250
PROCESS PIPING 1407.2 – 1407.3

gency shutoff valves shall be installed on limit, a continuous gas-monitoring system


piping and tubing other than waste lines at shall be provided. The monitoring system
the following locations: shall be connected to the emergency control
1407.2.2.5.1 At branch connections into station.
the fabrication area.
1407.2.2.5.2 At entries into exit corri-
dors. Excess flow valves shall be
installed as required by the Fire Code.
1407.2.2.6 Electrical wiring and equipment
located in the piping space shall be
approved for Class I, Division 2, Hazardous
Locations.
Exception: Occasional transverse
crossing of the corridors by supply
piping that is enclosed within a ferrous
pipe or tube for the width of the
corridor need not comply with Sections
1407.2.2.1 through 1407.2.2.6.
1407.3 Special Requirements for HPP Gases.
1407.3.1 General. In addition to other require-
ments of this section, HPP gases shall comply
with this subsection and the Fire Code.
1407.3.2 Special Provisions.
1407.3.2.1 Excess Flow Control. Where
HPP supply gas is carried in pressurized
piping, a fail-safe system shall shut off flow
due to a rupture in the piping. Where the
piping originates from outside the building,
the valve shall be located outside the
building as close to the bulk source as prac-
tical.
1407.3.2.2 Piping and Tubing Installation.
Piping and tubing shall be installed in accor-
dance with approved standards. Supply
piping for hazardous production materials
having a health hazard ranking of 3 or 4
shall have welded connections throughout,
unless an exhausted enclosure is provided.
Exception: Material that is incompatible
with ferrous piping may be installed in
nonmetallic piping with approved
connections.
1407.3.2.3 Gas-Detection System. When
hazardous production material gas is used
or dispensed and the physiological warning
properties for the gas are at a higher level
than the accepted permissible exposure limit
for the gas, a continuous gas-monitoring
system shall be provided to detect the pres-
ence of a short-term hazard condition. When
dispensing occurs and flammable gases or
vapors may be present in quantities in
excess of 20 percent of the lower explosive

251