SYSTEM DETAILS
kV
33
1.1
kV
36
1.2
1.3
System frequency
INSULATION
site altitude)
2.1
2.2
2.3
2.4
2.5
2.6
LEVEL
solid
Hz
50
(at
kVp
170
kVp
kVp
kV
kV
70
70
kV
mm
/kV
25
3. SWITCHGEAR DETAILS
Item
No
Description
Particulars
kV
TYPE OF SWITCHGEAR
3.1
Type of switchgear
GIS or Open terminal
Open terminal
3.2
Installation
Indoor
SHORT
CAPACITY
4.1
4.2
Maintenance
3 seconds
CIRCUIT BREAKER
5.1
5.2
Fault rating
5.2.1
TIME
36.3
Indoor
CURRENT
kA
25
kA
25
1250
Making current
kA
p
62..5
5.2.2
kA
25
5.2.3
Breaking
(asymmetrical)
current
5.2.4
Breaking current
phase conditions
under
5.2.5
earthing
devices,
% DC/kAp
out
of
IEC 56
kA
6.25
10
5.2.6
50
5.2.7
1 to 10 - 50 - 100 - 200
5.2.8
pu
<2.0
Item
No
Description
Particulars
5.3
Operating sequence
5.3.1
Normal
5.3.2
Auto re-closing
5.3.3
High speed single phase auto reclose cycle adjustable dead time
6.1
2-30
6.2
(2.0
pu)
6.3
6.4
6.5
IEC 56
6.6
IEC 56
6.7
6.8
6.9
6.10
mechanical
1.5
ohm
s
kV
29
pu
Item
No
6.11
6.12
6.13
6.14
6.15
Description
Maximum
total
break
time
throughout complete rating, ie trip
coil initiation to final arc extinction
ms
50
ms
ms
ms
10
ms
kV
36.3
6.6
6.6.1
6.
6.2
Particulars
kVp
kVp
kVp +
kVACp
kVp
kVp
kVp +
kVACp
Item
No
Description
6.6.3
Particulars
Dry/wet
kV
kV
70
80
6.7
Ancillary equipment
6.7.1
6.7.2
Number
required
6.7.3
Degree of protection
of
closing
coils
IP 56
1.1.
13.1 General
Circuit breakers shall be of three pole air break design, horizontal
draw out type in accordance with IEC 947-2. In particular, evidence
shall be provided of the performance when switching currents in the
critical current range. They shall be capable of the ratings specified in
the Schedules, when mounted in the switchboard.
Circuit breakers shall be fitted with trip-free, spring-operated
mechanisms of the independent manually operated type and be
provided with making and over current release facilities. A pushbutton shall be provided to trip the breaker electrically.
The breaker shall be provided with `OPEN'. `CLOSE', `SERVICE',
`TEST' and `SPRING CHARGED' position indicators and shall be
provided with the necessary number of auxiliary contacts for
interlocking, indication and tripping purposes plus two spare.
Each incoming circuit shall be provided with thermal overload relays
and short circuit protection relays; they shall also be provided with an
undervoltage relay to trip breaker in the event of a supply failure.
There shall be `SERVICE', `TEST' and fully withdrawn positions for
the breakers. It shall be possible to close the door in TEST position.
Movement of a circuit breaker between SERVICE and TEST
positions shall not be possible unless it is in OPEN position.
Attempted withdrawal of a closed circuit breaker shall not trip the circuit breaker.
Closing of a circuit breaker shall not be possible unless it is in
SERVICE, TEST or fully withdrawn positions.
A breaker of particular rating shall be prevented from insertion in a
cubicle of a different rating.
Circuit breakers shall be provided with electrical anti-pumping and trip
free feature.
Means shall be provided to slowly close the circuit breaker in
withdrawn position if required for inspection and setting of contacts. In
service position slow closing shall not be possible.
Circuit breakers shall be provided with the following mechanism as
specified in the Bill of Material.
SCOPE
STANDARDS
All circuit breakers and associated equipment shall comply with the
latest editions of the relevant Indian Standards (IS), International
Electro-Technical Commission (IEC) standards and any other standard
mentioned as here under.
STANDARD
TITLE
IEC 815
Bushings
1000 V.
IS 4379
IS 7311
for
alternating
voltages
above
IS 2959 / 337
IS 2629/BS 729
IEC 72
IS 6005
IEC 227
IEC 617
IS 5
4.
CIRCUIT BREAKER
INTERUPTING MEDIA
Vacuum
In vacuum circuit breakers, facilities shall be provided for monitoring
the contact erosion and any contact gap. The vacuum bottles shall be
easily replaceable and the mechanism shall be conveniently calibrated
to permit resetting the contact gap when open
The vacuum circuit breakers poles shall be sealed to prevent
contamination of the spaces surrounding the interrupters. The bidders
shall be required to demonstrate how this is achieved by supplying
technical details along with the bid.
6.
6.1.
The mechanism shall fully close the circuit breaker and sustain it in the
closed position against the forces of the rated making current and shall
fully open the circuit breaker without undue contact bounce at a speed
commensurate with that shown by tests to be necessary to achieve the
rated breaking capacity in accordance with IEC 56. The mechanism
shall be capable of being locked in either the open or closed position.
When auto-reclosing is specified, it shall be suitable for multi-shot high
speed duty. The mechanism shall be capable of fully closing and
opening again after the auto-reclose time interval specified. Evidence
shall be submitted to show that the design of the mechanism has
given satisfactory service experience in tropical climatic conditions for
at least three years.
The mechanism and the connected interrupters shall satisfy the
mechanical endurance requirements of IEC 56 and all additional
requirements specified herein.
A positively driven open/closed indication device, clearly visible without
the necessity to open the mechanism door, shall be provided. The
drive for the device shall be positive in both directions.
Means shall be provided to prevent the mechanism from responding to
a close signal when the trip coil is energised, or to reclosing from a
sustained close signal either after opening due to a trip signal or
failure to hold in the closed position. Any relays to accomplish these
provisions shall be continuously rated and mounted at the circuit
breaker.
Duplicate trip coils with independent trip circuits and phase
discrepancy remote indication shall be provided. Trip circuits shall be
suitable for trip circuit supervision in both open and closed positions.
For single phase mechanisms pole discrepancy scheme shall be an
integral feature of circuit breaker control system to detect any
discrepancy of one or more phases during an opening or closing
operation. In the event of occurrence of a pole discrepancy, the
scheme shall apply a trip signal to the circuit breaker with an alarm.
A mechanical open push button shall be provided on the circuit breaker
which shall be shrouded and shall be lockable.
The following facilities shall be provided at each circuit breaker local
control point:
LOCAL/REMOTE selector switch. The selection of local operation
shall inhibit the operation of the breaker from any remote source
including the protection scheme.
Spring mechanism
Provision should be made for remote indication of Spring charged
and Spring charge fail conditions.
The mechanism shall be complete with spring charging motor, closing
and opening springs with limit switches for automatic charging and
with all necessary accessories to make a complete operating unit.
A spare normally open spring-drive limit switch shall be provided.
b).
c).
Mechanism housing
The heaters provided inside the housing to stop condensation, shall be
permanently connected. Where two stage heaters are provided, one
stage shall be permanently connected and the other switched.
Mechanism housings shall have an IP55 rating and means for locking
shall be provided for each door.
Supplier shall provide all necessary inter-pole cables and cabling from
individual poles to the local control cubicle, as well as all cable
accessories necessary to achieve proper installation.
The control cabinet shall be provided with 415 V, 3-phase and 240 V,
1-phase ac (50 Hz) and 220 V dc supplies. Separate terminal blocks
for terminating circuits of different voltages shall be provided. CT loads
shall be terminated on a separate block and shall have provision for
short circuiting the CT secondary terminals. All terminals shall be
adequately screened, insulated and marked with the phase colour.
DANGER notices shall be affixed to the terminal blocks and a danger
notice stating the voltages shall be fixed on the inside and outside of
the cabinet. The conductors of all current circuits shall be annealed
copper of cross sectional area of not less than 4 mm2 and that for
potential and control circuits shall not be less than 2.5 mm2 and shall
be insulated with PVC to IEC 227.
6.5.
6.6.
6.7.
Inductive/reactor switching
In addition to the inductive current switching tests, the circuit breaker
shall also be tested for shunt reactor switching in accordance with
IEC 1233 and 17A/474/CD. Examination of the interrupter after the
tests shall not show any evidence of surface tracking or erosion of
nozzle.
6.8.
Insulation co-ordination
Insulation co-ordination shall be applied in accordance with IEC 71.
The Supplier is free to select appropriate rated levels from IEC 71 but
will need to provide test evidence to the Purchasers Representatives
satisfaction, by means of type tests, to verify that co-ordination of
insulation has been achieved.
Insulation co-ordination shall consider the following site conditions:
Mechanical endurance
In addition to the requirements of IEC 56, extended mechanical
endurance test is required to show that the circuit breaker is capable
of at least 10 000 operations in accordance with IEC 17A/474/CD
Clause 6.101.2.4.