SWITCH ON TO FAULT (SOTF) FEATURE:

Settings Of Switch On To Fault (SOTF):


ESOTF
=Y
ENCLO
=Y
CLOEND
= 10.00
EN52A
=N
52AEND
= 10.00
SOTFD
= 500 (This setting for testing should be kept some higher value,
after testing of SOTF function it should be kept as original value)
50H
= 1.20
Z2PD
Z3PD
Z4PD
Z2GD
Z3GD
Z4GD

= 2000
= 2000
= 2000
= 2000
= 2000
= 2000

(Keep the Zone time delays {Z2PD to Z4GD} at maximum value for testing of
SOTF function, after testing of SOTF feature change these settings to original
gvalue)
MTO

Step 1

= M2P + Z2G + 50H

Click OMICRON Test Universe


1.51 Icon in desktop.

OMICRON start page window


opens.

Page 1 of 133

Step 2

Click Distance in OMICRON


start page.

OMICRON Distance {Test


View: Distance1 window opens.

Page 2 of 133

Step 3

OMICRON Distance window


select Parameters > Test Object

Parameters For Protection


Device menu window opens.

Page 3 of 133

Step 4

In Parameters For Protection


Device menu window enter the
parameters in Device Settings,
System Settings.

Page 4 of 133

This will configure the settings


essential for testing.

Page 5 of 133

Procedure For Creating MHO Characteristics Zones:

Step 5

In Parameters For Protection


Device > Zone Setting menu
Click New button
Click Edit button
In Characteristic Editor >
Predefined Shapes menu click
Circle button
Enter impedance reach value, offset
and line angle values in the Element
list window then press OK button

Page 6 of 133

New Zone will be added


Characteristic Editor window
opens.
It will add mho characteristics

Adopt the settings corresponding


to zone 2 for testing the SOTF
function. The same procedure
can be followed for including
any number of Mho
characteristics for testing.

Step 6

In Parameters For Protection


Device menu window enter the
parameters in Test Settings,

This will configure the settings


essential for testing.

Step 7

In OMICRON Distance {Test


View: Distance1 window select
Parameters > Hardware
Configuration

Hardware Configuration menu


window opens.

Page 7 of 133

Step 8

In Hardware Configuration menu


Click General > Test Set(s) >
Details.

Output Configuration Details


menu window opens.

Step 9

Select 3 Voltage and 3 current


sources & Click OK.

Output Configuration Details


menu window closes.

Page 8 of 133

Step 10 In Hardware Configuration menu Click


Analog Outputs select the voltage and
current sources.

Page 9 of 133

Step 11 In Hardware Configuration menu Click


Binary / Analog Inputs and in Binary
Outputs select none of the inputs / outputs.

Page 10 of 133

Step 12 In OMICRON Distance {Test View:


Distance1 window select Vie
w > Test.

Step 13

Step 14

In OMICRON Distance {Test


View: Distance2 window Fault
type menu select
R-Y-B fault.
In OMICRON Distance {Test
View: Distance2 window Shot
menu enter the Test point
impedances at line angle to be tested
and click Add button for testing
test points.

Page 11 of 133

Test View Menu


opens.

Fault type cab be selected according to


the element being tested in the MTO
equation.
Enter the test point zone reaches
corresponding to element, which is
being tested in MTO equation and
keep the corresponding zone element
time delay at maximum value in the
SEL 321 relay.

Step 15

Step 16

In OMICRON Distance {Test View: Distance2


window Settings menu enter the parameters for
testing.
Apply rated DC input to the status input,
which has been assigned to breaker-closing
input.

Page 12 of 133

As soon as the DC input


applied to the status input
which has been assigned
to breaker closing input,
the fault should be
applied to create the
SOTF condition with in
SOTFD set time delay in
the relay.

Step 17

In OMICRON Distance {Test View: Distance2


window click and select Start single Test button.

Page 13 of 133

Fault impedance
selected will be
applied to relay.