Fieldbus Diagnostics

Agenda

Introduction

Level of Diagnostics

Function Block Diagnostics

Resource Block Diagnostics

Transducer Block Diagnostics

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 2

Fieldbus brings dramatic


savings in installation and
commissioning, but the
real value is seen during
plant operation...

Elimination of Unneeded Trips to


the field: Transmitter Diagnostics
63% of trips to the field can be eliminated
50
40

35%
28%

30

20%

20

6%

10

6%

4%

0
Routine
Check

No
Calibration
Problem
Shift

Source: Dow Chemical


[File Name or Event]
Emerson Confidential
27-Jun-01, Slide 4

Zero
Off

Plugged
Failed
Lines Instrument

Diagnostics Definitions
Level 3

Level 2

Loop

Operations

Boiler
Turbine
Generator

Make Up Water

Pulveration

Drift

Level 1

Device
Communications
Diagnostics

Electronics
Diagnostics

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 5

Plugged
Impulse
Line

Sensor
Drift

Device Maintains Statistics For Communication


Diagnostics

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 6

Diagnostic Examples

Transmitter generates an alert


when

the sensor degenerates

the device has exceeded


factory maximum field
temperature usage
Cycle Counter
Valve Signature
Dynamic Error Band

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 7

O2 Sensor creates alert when the


sensor fouls

Using Device Intelligence


The Device
Detects Process
Conditions

Impulse Lines Plug


PV (V)

1.82
1.819
1.818
1.817
1.816
1.815
1.814
1.813
1.812
1.811
1.810

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 8

10

12

Time (min)

14

16

18

20

Devices Provide Predictive Diagnostics


Provide Information On Life Expectancy and
Performance Degradation
Predictive Alarm
Failure

Device Performance

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 9

Diagnostics are Utilized in Fieldbus


Blocks for Measurement and Control
PV is MarkedUncertain
or Bad if Abnormal

and propagated

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 10

Event is Time Stamped At The Source!

H1

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 11

Conditions of FT-101

Recommended Action: Perform recommended sensor/wiring checks

FT-101
Inlet 3, Cooling Tower 1

Failed

Electrode Signal Fault

Maintenance

Sensor Calibration

Failed Conditions
Sensor

Failed

Process

Electronics

Communications Failure
Failed
Maintenance
Advisory

Enable

Electrode Signal Fault


Enable

Maintenance

Grounding/Wiring Fault

50/60 Hz Noise::

.003401 mV

i
Advisory

Print

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 12

Close

Help

TOWER_1

Process plants can be tough on field


devices!

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 13

Internal Diagnostics

Sensor failure

Sensor malfunction

Sensor disconnected

Electronic Board failure

Bad grounding

Operating conditions out of specifications

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 14

Process Diagnostics

Plugged line
Empty pipe
Statistical Process Monitoring
Vibration
Valve travel integration
Noise
Drift
Flame instability
>>>>>>

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 15

Diagnostic Examples

Transmitter generates an alert


when

the sensor degenerates

the device has exceeded


factory maximum field
temperature usage
Cycle Counter
Valve Signature
Dynamic Error Band

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 16

O2 Sensor creates alert when the


sensor fouls

Variability Index provides additional


insight into Loop Performance
Variability Index Diagnostic
Variable

Performance Change

Variability
Index

Is Detected with
Variability Index

Acceptable
Value

DeltaV Inspect Identifies


Under-performing Loops
VI=

Measured Standard Deviation


Minimum Expected Standard Deviation

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 17

Take Corrective Action

Plugged Impulse Line Diagnostic


1.82
1.819
1.818
1.817

Manifold
P V (V)

1.816

Sensing
Line

1.815
1.814

Both Open

1.813

HP Closed

LP Closed

Both Closed

1.812
1.811

Clog

Flow

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 18

1.81
0

10
12
Time (min)

14

16

18

20

Statistical Process Monitoring

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 19

Proof Using SPM Prevents Plant


Damage
10.00

Statistical
Process
Monitoring data
coming from
3051 ADB
helped predict
catalyst problem
30 min
in advance

PHD Data
23:30
23:00

9.00

23:30

8.00
7.00
6.00
5.00
4.00

23:00

23:00

3.00

SPM Data

2.00
1.00
0.00

6/4

6/6

6/8

Source: ExxonMobil Baytown, Tx Refinery


[File Name or Event]
Emerson Confidential
27-Jun-01, Slide 20

6/10

6/12

Status
All connectable variables have
STATUS.
STATUS

VALUE

Value: 234.5 m3/h


Status: Good, Bad or Uncertain
Sub-Status: (more status details)
Limit : High, Low, Constant or not limited
Diagnostics
AI

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 21

Status can be used in the control


strategy to switch a controller to
Manual when the variable goes to
a Bad status.

Status

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 22

Diagnostics are Utilized in Fieldbus


Blocks for Measurement and Control
PV is MarkedUncertain
or Bad if Abnormal

and propagated

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 23

Event is Time Stamped At The Source!

Classic I/O

Other Buses

Other Buses
H1

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 24

Plantweb alerts
Sensor
Failure

Maintenance
Soon

Installation
Problems
Sensor
Failure

Maintenance
Soon
Installation
Problems

Sensor
Failure

Installation
Problems

Sensor
Failure

Maintenance
Soon

Maintenance
Soon

Failed

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 25

Maintenance

Advisory

Route to appropriate plant organization


Recommended Action
Troubleshooting guide

Installation
Problems

Conditions of FT-101

Recommended Action: Perform recommended sensor/wiring checks

FT-101
Inlet 3, Cooling Tower 1

Failed

Electrode Signal Fault

Maintenance

Sensor Calibration

Failed Conditions
Sensor

Failed

Process

Electronics

Communications Failure
Failed
Maintenance
Advisory

Enable

Electrode Signal Fault


Enable

Maintenance

Grounding/Wiring Fault

50/60 Hz Noise::

.003401 mV

i
Advisory

Print

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 26

Close

Help

TOWER_1

Operation
Devices are identified by Tag
Variables are identified by:

TAG.Desired Parameter
FT
102A

FIC
102A

FCV
102A

FIC102A.OUT

No need to remember the Transmitters Hardware Address .

FT102A, not CTL01C03A01


[File Name or Event]
Emerson Confidential
27-Jun-01, Slide 27

Transducer, Resource and Function Blocks

Every Field device has to have a Resource Block and


one or more Transducer blocks.
Function Blocks are desirable, but not mandatory.
Resource Block contains information about the device
resources: hardware and software.
Transducer blocks control access to Input and Output
interfaces such as sensors, switches, actuators etc.
Transducer decouples the process interface from the
Function Blocks. They can run as fast as they can.
Transducer blocks also allow calibration and access to
diagnostics.

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 28

Resource Block

Hardware and Software resources.

When Mode is Out of Service, all other blocks will


be Out of Service.

Allow Device resetting, including resetting with


Default values.

All Emerson devices have a common Resource


Block, with very small variations.

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 29

Pressure Resource Block - Identification

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 30

Pressure Resource Block - Process

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 31

Pressure Resource Block - Alarms

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 32

Pressure Resource Block - Hardware

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 33

Pressure Resource Block - Options

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 34

Pressure Resource Block Suppressed


Alarms

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 35

Transducer Blocks

Transducer blocks provide the interface to


sensors, switches, actuators, etc.

Transducer blocks also allow access to


calibration and I/O diagnostics.

If the Transducer Block is in Out of Service


Mode, the Function Blocks will have
measurement value with Bad Status.

Transducer communicates the values to the I/O


Function Blocks via Channels.

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 36

Transducer
Free Running

Schedule

Transducer

Sensor 1

Channel 1

Ch. 1

AI 1

Channel 2

Ch. 2

AI 2

Channel 3

Ch. 3

AI 3

Channel 4

Ch. 4

AI 4

Sensor 2

Sensor 3

calc
[File Name or Event]
Emerson Confidential
27-Jun-01, Slide 37

Important to remember

AI or AO block has to have the Channel


configured accordingly. Channel = 0, no
measurement or actuation.

AI or AO block XD_SCALE parameter has to


have the same valid Engineering Unit. Pressure
measurement should be inH2O@68F, mbar,
psi,etc. Temperature should be deg. C, not C.

Transducer should be in Auto.

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 38

Pressure Transducer - Process

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 39

Pressure Transducer - Sensor

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 40

Pressure Transducer - PV

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 41

Pressure Transducer -SV

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 42

Pressure Transducer - Materials

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 43

Pressure Transducer - LCD

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 44

Pressure Transducer - LCD

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 45

Pressure Transducer Advanced


Diagnostic Block

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 46

Pressure Transducer Advanced


Diagnostic Block

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 47

Pressure Transducer - Status

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 48

Pressure Transducer - Status

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 49

Pressure Transducer - Status

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 50

Pressure Transducer - Status

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 51

Das könnte Ihnen auch gefallen