Fire safety
starts here
David Sugden explains the vital role of passive fire protection in
ensuring the safety of building occupants, firefighters and property
HE STABILITY of a building in a fire depends upon the
performance of all the component parts of the
structure. Buildings are designed to keep products of
combustion away from building occupants, allowing them
time to escape safely. Regulations that govern the design of
buildings also take into consideration the safety of firefighters
who attend an incident. Thus, if a building is adequately
protected, it should withstand a fire for a reasonable time,
without collapse.
Providing guidance
This supplement describes the aims of the PFPFs member
organisations (see p.26) and provides guidance in a series of
product sector pages (see p.5-21). This guidance is designed
to help all users of the products and services that the
industry has to offer, including the building occupier. They
provide information on what to look for, what to avoid,
what to maintain and where more detailed information may
be obtained.
The performance in practice of all construction materials is
dependent upon the way in which the product is installed. For
this reason, the PFPF has always favoured third-party
accreditation of both materials and installers; a principle which
is also endorsed by the Chief Fire Officers Association (CFOA)
(see p.22), whose members have to deal with the situations
that arise from incomplete or badly maintained fire protection.
The article on page 22 explains how these schemes operate.
Approved Document B of the Building Regulations in England
and Wales recommends that certificated products and thirdparty accredited installers of all fire safety products should be
used as a means of ensuring that products achieve the required
level of performance. Building owners and regulators alike
should follow this advice and follow the lead set by CFOA.
The PFPFs objective with this publication is to provide
designers, regulators, building owners and occupiers with a
simple reference document that provides basic guidance on
the many forms of passive fire protection found in buildings.
The trade associations that specialise in these materials and
product sectors also offer their services, should you require
further guidance.
Often, it is not realised how much the individual elements of
construction contribute to the fire performance of the
complete structure, nor how the structural performance is
vital to a successful fire strategy. The PFPF hopes that the
information provided will help all concerned to understand
the ways in which these elements work together to ensure
public safety
October 2004
27/9/04
October 2004
4:29 PM
Page 2
27/9/04
4:30 PM
Page 3
October 2004
the
27/9/04
4:34 PM
Page 4
Burning Question
the
Answer
Leighs Paints
department on
Leighs Paints
LEIGHS
PAINTS
FIRETEX
Product Calculator
27/9/04
4:34 PM
Page 5
PRODUCT RANGE
Proprietary structural steel fire protection systems include boards,
casings, intumescents (thin and thick film) and cementitious
coatings (hand and spray applied).
Fire protection systems for structural steel can provide up to
4 hours fire protection against a cellulosic fire. Products are also
available to protect structural steel against hydrocarbon pool and jet
fires.
AREAS OF APPLICATION
universal columns, beams (plain and perforated) and joists
structural and rolled tees
angles
channels
hollow sections (square, rectangular and circular)
The above sections may or may not support concrete or metal
decking.
Plate steel in the form of bulkheads or vessel supports can also be
protected using structural steel fire protection systems, as can
vessels containing flammable liquids and gases.
NEVER . . .
MAINTENANCE
visual inspection is required and this may prove difficult if the
structural steel fire protection system has been clad
any damage to the structural steel fire protection should be
made good using the same product as that originally installed,
as indicated in the manufacturers instructions for repair
ALWAYS . . .
RELEVANT STANDARDS
BS 476-20: Fire tests on building materials and structures.
Methods of determination of the fire resistance of elements of
construction (General principles)
BS 476-21: Fire tests on building materials and structures.
Methods of determination of the fire resistance of loadbearing
elements of construction
BS EN 1365-3: 2000: Fire resistance tests for loadbearing
elements. Beams
BS EN 1365-4: 1999: Fire resistance tests for loadbearing
elements. Columns
DD ENV 13381-4: 2002: Test methods for ddetermining the
contribution to the fire-resistance of structutal members. Applied
protection to steel members
For further information contact: ASFP (see p.26)
October 2004
27/9/04
4:35 PM
Page 6
Founder member of
AREAS OF APPLICATION
partitions and compartment walls
floors and ceilings
escape and access corridors
stairways, lobbies and enclosures to protected shafts
structural steel protection
Grace Monokote
plasterboard type
number of layers of board used
fixings used and fixing centres
correct detailing of services penetrations
finishing and sealing of construction joints
the quality of installation
October 2004
MAINTENANCE
only visual inspection is required
carry out any necessary refurbishments according to the
original installed system approved specification, following the
manufacturers operating and maintenance manual
27/9/04
4:36 PM
Page 7
EMS
ASFP
ALWAYS . . .
install the fire-resisting plasterboard system according to
configuration, design and materials as tested or assessed
ensure all openings and penetrations are correctly built in
accordance with manufacturers guidelines and ensure
following trades are aware that systems should not be altered
structurally in case this affects fire performance
ensure that any manufacturers installation instructions and
guidance are followed
NEVER . . .
approve and use a drywall system that does not have relevant
and applicable evidence of performance
allow the mixing and matching of components between
different fire-resisting drywall systems
RELEVANT STANDARDS
BS 8212: 1995: Code of practice for dry lining and partitioning
using gypsum plasterboard
For further information contact: AIS and GPDA (see p.26)
October 2004
27/9/04
4:37 PM
Page 8
FIRE-RESISTANT DUCTWORK
Fire-resisting ventilation or extraction steel ductwork is designed
using proprietary materials and fixing techniques to contain fire and
the products of combustion in a manner that does not allow passage
to other parts of the building from the compartment of origin for a
stipulated time period. Fire-resistant ductwork can also be
constructed without a steel lining duct using self-supporting board
and casing systems made from calcium silicate and cement based
products.
AREAS OF APPLICATION
smoke extract systems
dual ventilation/smoke systems
pressurisation systems
car park extract systems
kitchen extract systems
MAINTENANCE
visual inspection is required and this may prove difficult if the
fire-resistant ductwork system has been hidden behind
partitions or suspended ceilings
any damage to the fire-resistant ductwork system should be
made good using the same product as that originally installed,
as indicated in the manufacturers instructions for repair
competent contractors should repair structural steel fire
protection systems
ALWAYS . . .
install fire-resistant ductwork systems that have been fully
tested or independently assessed to the requirements of
BS 476-24 (or BS EN 1366-1)
use a competent installer and preferably one that is a member
of a third-party accreditation scheme, such as FIRAS
consult a competent fire engineer for advice where no fire test
evidence or assessments are available due to the size or the
complexity of the ductwork system that requires fire protection
NEVER . . .
specify or install a fire-resistant ductwork system that has no
relevant and applicable evidence of performance
PRODUCT RANGE
October 2004
RELEVANT STANDARDS
BS 476-24: 1987, ISO 6944: 1985: Fire tests on building materials
and structures. Method for determination of the fire resistance of
ventilation ducts
Fire Rated And Smoke Outlet Ductwork the Blue Book and
Ensuring Best Practice for Passive Fire Protection in Buildings, both
published by the Association for Specialist Fire Protection
For further information contact: ASFP, IFSA (see p.26)
28/9/04
2:40 PM
Page 9
FIRE-RESISTING DAMPERS
PRODUCT RANGE
curtain dampers
multi-blade dampers
intumescent, typically either louvred or honeycomb
single-blade circular dampers
AREAS OF APPLICATION
ALWAYS . . .
install dampers in accordance with the manufacturers
instructions
provide access to each mechanical damper, so their ability to
close can be checked
provide sufficient access to allow for the inspection of each
intumescent damper
NEVER . . .
install dampers away from the wall through which the ductwork
passes
RELEVANT STANDARDS
October 2004
27/9/04
4:38 PM
Page 10
AREAS OF APPLICATION
multi-service openings through walls and floors
blank service openings through walls and floors
combustible pipes (plastics)
cavity barriers
construction joints
any imperfection of fit to a fire-rated building element
10 October 2004
27/9/04
4:38 PM
Page 11
ON SEALS
EUROPEAN FIRE TESTING FOR FIRESTRIP 30
MAINTENANCE
inspection of the penetration seal should be made periodically
to ensure services have not been removed/installed, leaving
holes in the system
any damage to the penetration seal system should be made
good using the same product as that originally installed
competent contractors should repair penetration seal systems
ALWAYS . . .
NEVER . . .
specify or install a penetration seal system that has no relevant
and applicable evidence of performance
mix and match products from different manufacturers
use an installation contractor that cannot demonstrate the
appropriate level of competence and experience
apply a coating to the penetration seal without manufacturers
approval
RELEVANT STANDARDS
BS 476-20: Fire tests on building materials and structures.
Methods of determination of the fire resistance of elements of
construction (General principles)
BS EN 1366-3: Fire resistance tests for service installations.
Penetration seals
Full range of proven products for the passive fire protection market
All comprehensively tested and approved to relevant
British Standards
Pyroplex products available worldwide
Pyroplex Limited, The Furlong, Droitwich,Worcestershire WR9 9BG, England.
Tel: +44 (0)1905 795432 Fax: +44 (0)1905 791878
E-mail: pyroplex@pyroplex.com Web: www.pyroplex.com
BS EN ISO9001:2000
Cert No. FM10371
October 2004 11
27/9/04
4:39 PM
Page 12
FIRE-RESISTING GLASS
PRODUCT RANGE
A variety of glazed systems for use in vertical, horizontal and
inclined applications, either as (i) integrity only, or (ii) integrity and
insulation fire resistance performance.
Products are available for standard test times of 30, 60, 90, 120
and even 180 minutes when tested to the ISO 834 curve, as well
as special formulations to resist the higher intensity petrochemical
fire test curve.
AREAS OF APPLICATION
internal and external fire doors as vision panels or all-glass
doors
partitions and compartment walls
roofs, floors and ceilings
faade glazing
escape and access corridors
stairways, lobbies and enclosures to protected shafts
12 October 2004
27/9/04
4:39 PM
Page 13
MAINTENANCE
only visual inspection is required
carry out any necessary refurbishments according to the
original installed glazed system approved specification
where components cannot be identified then replace with a
complete new approved glazed system
ALWAYS . . .
install the fire-resisting glazed system according to
configuration, design and materials as tested or assessed
ensure that any manufacturers installation instructions and
guidance are followed
NEVER . . .
use a glazed system that does not have relevant and applicable
evidence of performance
substitute one glass for another
assume that standard impact safety toughened or
safety/security laminated glass is fire rated
use standard, non-fire rated glazing seals
allow the mixing and matching of components between
different fire-resisting glazed systems
allow on-site modifications
allow modifications to the glass after installation
ignore glazing instructions on modified toughened soda lime
concerning edge cover
The
The
Professional
Choice
Pyrocet
non-insulating fire resistant glass
RELEVANT STANDARDS
Smokestream
Contact
C3S Securiglass Ltd.
Canal Mills, Elland Bridge, Elland,
West Yorkshire HX5 0SQ
Fax +44 (0) 1422 310070
Email info@c3ssecuriglass.com
Web www.c3ssecuriglass.com
27/9/04
4:40 PM
Page 14
27/9/04
4:41 PM
Page 15
AREAS OF APPLICATION
In the UK, the use of fire doors is generally controlled by the
Building Regulations. These Regulations mainly cover life safety
issues. It is not unusual for fire doors to be required by insurance
providers or building users, either in additional locations or with fire
resistance periods in excess of those recommended by Building
Regulations for specific property-related purposes.
General areas of application are:
internal doors within dwellings over three storeys
internal doors within flats
entrance doors to flats
doors to protected shafts
doors providing compartmentation in buildings used by the
public, such as offices, hospitals, schools and hotels
overall dimensions
configurations (pairs, singles, single-swing, double-swing, etc)
style of door (raised and fielded panel, flush face, etc)
acceptable finishes and appearance
fitting and type of acceptable hardware, including closers
acceptability of glazed openings
dimensions of glazed openings
types of acceptable glass
October 2004 15
28/9/04
2:27 PM
Page 16
MAINTENANCE
ALWAYS . . .
The best way to ensure the performance of a fire door during its
lifetime is to carry out regular checks and have a regular
maintenance schedule, or to take out a maintenance contract with
the original supplier and/or installer.
NEVER . . .
accept any on-site alteration that has not been approved by the
door manufacturer
use essential components or hardware that cannot be supported
by test or assessment data provided by the door manufacturer
allow a door to be modified before installation without
confirmation from the door manufacturer
RELEVANT STANDARDS
BS 476-22 1987: Fire tests on building materials and structures.
Methods for determination of fire resistance of non-loadbearing
elements of construction
BS EN 1634-1: 2000 Fire resistance tests for door and shutter
assemblies. Fire doors and shutters
For further information contact ASDMA, BWF, DHF and GAI (see p.26)
EW
N
CE marked
Type tested to BS EN 1154: 1997. Power size 3
BS EN 1634-1 fire tested for half-hour fire doors
Certifire approved
Endurance tested to 500,000 closing cycles
10-year guarantee
marked
16 October 2004
27/9/04
4:42 PM
Page 17
AREAS OF APPLICATION
Building hardware may be fitted to timber and metal door
assemblies. Care should be taken to ensure that the chosen product
carries the appropriate successful test report. The requirements for
unlatched timber doors vary from those for metal doors.
Fittings should be carefully selected in accordance with the
following classification:
light duty: doors in housing or living areas in other buildings
where there is low frequency of use by those who exercise care
and where there is a small chance of misuse for example,
domestic, offices and areas where there is no access by the
public
medium duty: doors in housing or other living areas, offices
and other commercial buildings where there is a medium
frequency of use by those with some incentive to exercise care
but where there is some chance of misuse for example,
domestic, offices and areas where there may be limited access
by the public
October 2004 17
27/9/04
4:43 PM
Page 18
MAINTENANCE
Building hardware requires regular maintenance to ensure the
correct and efficient operation of all fire-resisting doors. Regular
inspections are essential to ensure that any defective components
are replaced with the minimum of delay:
worn or loose-fitting hinges will allow a door to drop, resulting
in the door binding in the frame or dragging on the floor. This
will also prevent the door from closing correctly
worn latch bolts will obstruct the door from attaining the fully
closed position
faulty door-closing devices will no longer close the door correctly
any intumescent or smoke seals should be inspected for
damage and replaced, where necessary
ALWAYS . . .
select products certificated to the appropriate British Standard
and which are CE marked, if appropriate
ensure that the components are fitted correctly
insist on validation of the product claims
NEVER . . .
accept low grade alternatives on account of price
RELEVANT STANDARDS
Harmonised European standards for which products should carry a
CE mark include:
BS EN 179: 1998: Building hardware. Emergency exit devices
operated by a lever handle or push pad. Requirements and test
methods
British Plywood
Manufacturers
A division of Brooks Bros (UK) Limited
INVICTUS
18 October 2004
27/9/04
4:45 PM
Page 19
27/9/04
4:46 PM
Page 20
EMERGENCY LIGHTING
PRODUCT RANGE
self-contained dedicated luminaires
emergency variant of normal lighting
central power systems
AREAS OF APPLICATION
The aim of emergency lighting is to enable people to exit quickly,
from a building in the event of an emergency involving failure of the
normal lighting supply. This is done by providing at least 1 lux
illumination, to enable the occupants to use the most direct path
and to avoid obstacles and, where necessary, by installing
illuminated safety signs.
In addition, safety equipment, such as fire alarm call points and
extinguishers, must be adequately illuminated so they can be
located and used if needed. Specific areas of high risk and any
relevant control rooms need a higher level of illumination to enable
the processes in these areas to be shut down safely in an
emergency.
Systems cater for an appropriate duration, normally 3 hours for
premises that are not to be evacuated immediately following a
supply failure, such as hotels or hospitals. Systems used in
premises that will be evacuated immediately may only require
1 hour of duration, but most operators still use the standard
3-hour units
Some applications, such as theatres, where the normal lighting may
be dimmed, require the lamp to be illuminated at all times that the
building is occupied. This is called maintained operation.
MAINTENANCE
When initially commissioned, the full operating regime of the
system should be checked. BS 5266 provides a list of the items that
should be covered at this stage:
monthly functional checks to ensure that the luminaires operate
annual full-rated battery discharge test
regular physical inspection for instances of damage to the
equipment
20 October 2004
27/9/04
4:58 PM
Page 21
RELEVANT STANDARDS
BS 5266-1: 1999: Emergency lighting. Code of practice for the
emergency lighting of premises other than cinemas and certain
other specified premises used for entertainment
BS EN 1838/BS 5266-7: 1999: Lighting applications. Emergency
lighting
BS EN 60598-2-22: Luminaires. Particular requirements.
Luminaires for emergency lighting
BS EN 60924/5: Product standard for luminaire circuits
BS EN 50171: Central power supply systems
pr EN 50172: Emergency lighting application standard
ICEL 1004: The modification of normal luminaires for emergency
use
For further information contact ICEL (see p.26)
October 2004 21
27/9/04
4:59 PM
Page 22
28/9/04
2:28 PM
Page 23
Peace of mind
Voluntary third-party certification gives confidence to the
manufacturer, customer and enforcement authorities that the
goods supplied and installed are fit for purpose, argues the
Passive Fire Protection Federation
HY CHOOSE a passive fire protection
product such as a fire door from a
manufacturer whose products are certified by
a third party, rather than from a manufacturer that is not
third-party approved? And why specify that a passive fire
protection product be installed by a certified installer?
October 2004 23
27/9/04
5:01 PM
Page 24
testassured
representing the fire safety
testing community
authorities that the goods supplied and installed are fit for
purpose and will perform their intended function when
called upon to do so.
Installation
A manufacturer can spend a lot of time and money
developing a product, putting together the evidence of
performance and getting it certificated but, if a product is
installed by cowboys, this money is wasted. Over the last
few years, a number of installer schemes have been
developed. These schemes issue a certificate to the installer
of passive fire protection to provide assurance they are
competent. Elements of the schemes, which are developed
in association with the relevant trade association, include:
24 October 2004
CE marking
It is often suggested that CE marking, required under the
European Union Construction Product Directive (CPD),
will make such schemes redundant. However, the fact is
that CE marking is not aimed at the end-user; the
philosophy of the CPD is to allow products to be placed on
the European market without prejudice and that those
products will be safe to use. The CPD thus sets the lowest
common performance denominator for safe use:
27/9/04
5:01 PM
Page 25
October 2004 25
27/9/04
5:02 PM
Page 26
26 October 2004
27/9/04
5:02 PM
Page 27
October 2004 27
27/9/04
5:03 PM
Page 28
Passive guidance
HE PASSIVE Fire Protection Federation (PFPF) has
produced a series of guidance documents to aid designers,
regulators, building owners and occupiers in specifying
and installing passive protection products.
IFC
party
CE M
of co
impa
Prod
IFC
(Inte
qual
spec
user
Prod
safet
cove
radia
If yo
any
IFC
20 P
Tel:
28 October 2004
Inte
staff
know
in pr
of de
Fire
IFC
Inter
in th
Desi
In ad
prod
to yo
Engi
IFC
cont
main
Inte
20 P
Tel:
27/9/04
5:04 PM
Page 29
IFC Certification Ltd is a UKAS approved and internationally recognised provider of high quality and customer focused third
party Certification for fire safety related products. IFC Certification Ltd has now established Notified Body credentials for the
CE Marking of products under the Construction Products Directive. The company is a member of the long established IFC Group
of companies including International Fire Consultants Ltd. who have established an enviable independent position offering clients
impartial advice across the world.
Product Certification Schemes
IFC Certification Ltd staff will assess your products for compliance to both, our scheme documents and any relevant Standards
(International, European, British or Industry etc.) followed by an evaluation of your companys compliance with your documented
quality control systems. This is carried out against the requirements of a Factory Production Control (FPC) system, including
specific requirements contained in each scheme. The purpose of our evaluation, is to assure ourselves, our clients and the end
user of the applicant companys ability to maintain quality and traceability of their outputs.
Product Certification not only includes prime manufacturers of fire safety products but also those companies who install fire
safety products, such as fire doors and vision panels. The already established Fire Resistant Timber Door Scheme, for example,
covers approvals for door leaves or doorsets which satisfy the criteria of integrity, integrity and insulation or integrity and
radiation, as outlined in more detail in the technical guidance documents.
If you would like to know how IFC Certification Ltd can help your company we will be pleased to help you and will welcome
any enquiries to;
IFC Certification Ltd
20 Park Street, Princes Risborough, Buckinghamshire, HP27 9AH, UK
Tel: +44(0)1844 275500, Fax: +44(0)1844 274002, E-mail: info@ifccertification.com
INTERNATIONAL FIRE
CONSULTANTS LTD
International Fire Consultants Ltd (IFC) are an independent professional fire safety engineering practice, now of 30 full time
staff offering advice to designers, contractors, developers, manufacturers and Regulators allowing cost effective solutions. Our
knowledge and experience allow you to eliminate any unnecessary expenditure, time and effort on proposals that will never work
in practice. We offer you our technical support and expertise, allowing you to make full use of engineering principles in the form
of designs, engineering reports, evaluations and assessments.
Fire Safety Design, Strategies & Interpretation of Regulations & Standards
IFC offer you a wide experience and understanding of the various Codes, Regulations and Standards, (both UK and
Internationally) allowing us to advise you of robust fire safety strategies adopting efficient specifications, using proven products
in the correct environments.
Design support & advice, rationalisation of fire testing requirements
In advising manufacturers our role is one of trying to maximise the technical marketing and sales claims that can be made for a
product for the minimum Research and Development costs. This is achieved by giving you detailed technical and design support
to your in house team and offering project management of any fire tests that may be deemed necessary.
Engineering Assessments and Field of Application Reports
IFC also produce engineering assessments and Field of Application reports based upon your test evidence. Such documents
contain full technical justifications to substantiate the fire performance claims for the products being offered for sale. IFC are
main contributors and authors leading the new European extrapolation and interpolation rules and protocols.
International Fire Consultants Ltd (IFC)
20 Park Street, Princes Risborough, Buckinghamshire, HP27 9AH, UK
Tel: +44(0)1844 275500, Fax: +44(0)1844 274002, E-mail: info@intfire.com
27/9/04
5:04 PM
Page 30
www.fireprotectivecoatings.com
Copon E Wood Ltd, Standard Way, Northallerton, N. Yorks, DL6 2XA Tel: 01609 780170 Fax: 01609 780438
www.copon.co.uk