SPECIFICATIONS
Supply Voltage (S-SC)
Average Current
Consumption
Contacts
Contact Rating
Max. Quantity Per Loop
Dimensions
Operating Temperature
Mounting
Relative Humidity
25.3 ~ 39 VDC
390A (Typical)
400A (Alarm)
2 Independently Controlled Form C
1Amp @ 30VDC or
0.5Amp @ 120 VAC
127
4.2W x 4.7H x 1.4D
32F (0C) ~ 120F (49C)
4 square electrical box
90% RH Non-Condensing
DESCRIPTION
STANDARD FEATURES
UL 864 9th Edition Listed
Provides two independently configurable Form C
PRODUCT LISTINGS
CS943
S5694
MEA
284-91-E Vol. IV
3022559
California
State Fire
Marshal
7300-0410:150
Continued on back.
F0058
07/2010
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, the Hochiki DCP-R2M addressable relay
module. The modules shall be UL listed compatible with Hochiki Digital Communications Protocol (DCP) supporting
control panel loops. The relay module must provide two Form C dry contacts rated at 1Amp @ 30 VDC or 0.5Amp
@ 125 VAC. The relay module must be suitable for mounting in a standard 4" square electrical box or double gang.
The relay module must provide a bi-colored LED for indication of status.
WIRING DIAGRAM
WIRING TO BOTH SETS
OF FORM "C" CONTACTS
MUST BE EITHER POWER
LIMITED OR NON-POWER
LIMITED. DO NOT MIX
POWER LIMITED WIRING
WITH NON-POWER
LIMITED WIRING ON TB2.
ALL WIRING SHOWN ON
TB2 IS NOT SUPERVISED.
CONTACTS ARE SHOWN IN
STANDBY MODE - REFER
TO CONTROL PANEL'S
OPERATION MANUAL FOR
PROPER RELAY OPERATION
AND CONFIGURATION.
DCP-R2M
S, SC WIRING
POWER LIMITED
NC1
NON
POWER
LIMITED
S +
HOCHIKI
POWER
LIMITED
SC -
U.L. LISTED
COMPATIBLE
FIRE CONTROL
PANEL
SET 1
COM1
TB1
NO1
S5694
NO2
CROSS OUT
TYPE NOT
USED
SET 2
COM2
NC2
NOTE: